First English printing, October 2002
Information in this document has been carefully checked for accuracy; however, no guarantee is given to the correctness
of the contents. The information in this document is subject to change without notice. We are not liable for any injury or
loss that results from the use of this equipment.
Safety Instructions
Please read all of these instructions carefully before you use the device. Save this manual for
future reference.
■ Unplug equipment before cleaning. Don’t use liquid or spray detergent; use a moist cloth.
■ Keep equipment away from excessive humidity and heat. Preferably, keep it in an air-conditioned environment with
temperatures not exceeding 40º Celsius (104º Fahrenheit).
■ When installing, place the equipment on a sturdy, level surface to prevent it from accidentally falling and causing dam
age to other equipment or injury to persons nearby.
■ When the equipment is in an open position, do not cover, block or in any way obstruct the gap between it and the
power supply. Proper air convection is necessary to keep it from overheating.
■ Arrange the equipment’s power cord in such a way that others won’t trip or fall over it.
■ If you are using a power cord that didn’t ship with the equipment, ensure that it is rated for the voltage and current
labelled on the equipment’s electrical ratings label. The voltage rating on the cord should be higher than the one listed
on the equipment’s ratings label.
■ Observe all precautions and warnings attached to the equipment.
■ If you don’t intend on using the equipment for a long time, disconnect it from the power outlet to prevent being dam
aged by transient over-voltage.
■ Keep all liquids away from the equipment to minimize the risk of accidental spillage. Liquid spilled on to the power
supply or on other hardware may cause damage, fi re or electrical shock.
■ Only qualifi ed service personnel should open the chassis. Opening it yourself could damage the equipment and invali
date its warranty.
■ If any part of the equipment becomes damaged or stops functioning, have it checked by qualifi ed service personnel.
What the warranty does not cover
■ Any product, on which the serial number has been defaced, modifi ed or removed.
■ Damage, deterioration or malfunction resulting from:
□ Accident, misuse, neglect, fi re, water, lightning, or other acts of nature, unauthorized product modifi cation, or failure to follow instructions supplied with the product.
□ Repair or attempted repair by anyone not authorized by us.
□ Any damage of the product due to shipment.
□ Removal or installation of the product.
□ Causes external to the product, such as electric power fl uctuation or failure.□ Use of supplies or parts not meeting our specifi cations.□ Normal wear and tear.
□ Any other causes which does not relate to a product defect.
■ Removal, installation, and set-up service charges.
Regulatory Notices Federal Communications Commission (FCC)
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the
FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
Any changes or modifi cations made to this equipment may void the user’s authority to operate this equipment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the following measures:
■ Re-position or relocate the receiving antenna.
■ Increase the separation between the equipment and receiver.
■ Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
The equipment comes with the standard parts shown in package content. Check and make sure they are
included and in good condition. If anything is missing, or damaged, contact the supplier immediately.
Part I. ATS Installation & Connection
< 1.1 > Package Content
■ Rackmount ATS unit x 1
■ Mounting Bracket ( set of 3 ) x 1
■ M3.2*4.5 mm screw x 12
UM-IP-ATS-Q215V1
P. 1
www.austin-hughes.com
< 1.2 > Product Overview
InfraPower Rackmount Auomatic Transfer Switch ( ATS ) with dual power input provides reliable and
redundant power for single-corded equipment. By the input preference switch, users can defi ne the
preferred power source. If the primary source is unavailable, the ATS will seamlessly source power
from the secondary source without power interruption and downtime. The entire ATS series are designed with a local current meter to easily observe power status and device load.
123
Current ( A )
< Input Preference >
PrimarySecondary
Automatic
Transfer Switch
546
Power
8
Secondary
Input
9
1
Local Current Meter
2
Input Preference Switch
3
Circuit Breaker
4
Power LED - primary input
5
Power LED - secondary input
6
Power LED - outlets
7
Primary Input attached with 3M cord & inlet plug
8
Secondary Input attached with 3M cord & inlet plug
9
Outlets
Primary
Input
7
UM-IP-ATS-Q215V1
P. 2
www.austin-hughes.com
< 1.3 > Installation
Before Installation
■ It is very important to mount the equipment in a suitable cabinet or on a stable surface.
■ Make sure the place has a good ventilation, is out of direct sunlight, away from sources of excessive
dust, dirt, heat, water, moisture and vibration.
All electrical power and power control wiring must be installed by a qualifi ed electrician
and comply with local and national regulations.
Don’t exceed the outlet, branch or phase limitations
Step 1
1
Use the provided screws to attach the mounting bracket set
( set of 3 ).
Step 2
2
M6
screw
Use the M6 screw set to secure the ATS to your rack
( M6 screws not provided ).
Step 3
3
Use the cable ties to fasten each power cord to the
cord retention tray ( cable ties not provided ).
UM-IP-ATS-Q215V1
Cable
tie
P. 3
www.austin-hughes.com
< 1.4 > Power Sources Connection
Step 1 : Before Power Source Connection
This Transfer Switch requires that the applied AC waveforms from
both power sources be in phase with respect to each other. Failure to
do so can potentially damage the unit and create an unexpected
HIGH VOLTAGE
to be present on the pins of either the Primary Source or Secondary
Source plug when disconnected, or on the Primary Source or Secondary Source output receptacles.
For questions concerning this requirement please contact
Austin Hughes Technical Support.
E-mail : support@infra-power.com
All electrical power and power control wiring
must be installed by a qualifi ed electrician and
comply with local and national regulations.
Don’t exceed the outlet, branch or phase
limitations
Step 2 : Power Source Connection
Plug the male end of the power cord into the AC power source.
Power Source Association
After the power source connection, the ATS input power LEDs ( primary & secondary input ) will indicate the
power ON / OFF status. Then slide the input preference switch to the primary input.
Primary
Input / LED
ONONPrimary
OFFONSecondary
ONOFFPrimary
OFFOFFOFF
Secondary
Input / LED
Output
Power Source
< 1.5 > Devices Connection
Step 1 : Before connect the devices to the ATS outlet, please keep the device's on / off
switch in the off position.
Step 2 : After connect the devices to the ATS outlet, please power on the device.
Step 3 : Fasten device's power cord to the cord retention tray with cable ties.
Do not exceed the ATS maximum current loads.
UM-IP-ATS-Q215V1
P. 4
www.austin-hughes.com
Part II. Model & Specifi cation
< 2.1 > 230V ATS Models
Model List - 10 Amp
HeightOutlet
ATS-H8C13-10A_C141UC13 x 8
ATS-H10C13-10A_C141UC13 x 10
ATS-H12C13-10A_C142UC13 x 12
ATS-H16C13-10A_C142U C13 x 16
Model List - 16 Amp
HeightOutlet
ATS-H8C13-16A_EN1UC13 x 8
ATS-H10C13-16A_EN1UC13 x 10
ATS-H12C13-16A_EN2UC13 x 12
Inlet x 2
( 3M cord attached )
C14
input plug
Inlet x 2
( 3M cord attached )
EN16 60309
input plug
ATS-H16C13-16A_EN2UC13 x 16
ATS-H20C13-16A_EN2UC13 x 20
ATS-H8C13 / 1C19-16A_EN1UC13 x 8 + C19 x 1
ATS-H16C13 / 2C19-16A_EN2U C13 x 16 + C19 x 2
Model List - 16 Amp
HeightOutlet
ATS-H8C13-16A_C201UC13 x 8
ATS-H10C13-16A_C201UC13 x 10
ATS-H12C13-16A_C202UC13 x 12
ATS-H16C13-16A_C202UC13 x 16
ATS-H20C13-16A_C202UC13 x 20
Inlet x 2
( 3M cord attached )
C20
input plug
ATS-H8C13 / 1C19-16A_C201UC13 x 8 + C19 x 1
ATS-H16C13 / 2C19-16A_C202U C13 x 16 + C19 x 2
UM-IP-ATS-Q215V1
P. 5
www.austin-hughes.com
< 2.1 > 230V ATS Specifi cation
Nominal input voltage230V
Electrical
Acceptable input voltage±10% nominal
Input frequency50 / 60Hz
Inlet plug & cord2 x C14 / C20 / EN16 60309 plug with 3-meter cord
Outlet connectorsMultiple C13 / C19 outlets
Local meter3-digital LED current meter
Physical
Overload protection
Transfer time25ms maximum
Electrical endurance1 x 10
Power consumptionApprox. 8VA
Product dimensions ( 1U )442 x 270 x 43.5 mm ( W x D x H )
Packing dimensions ( 1U )530 x 380 x 80 mm ( W x D x H )
Net weight4.6 kg / 10.1 lb
Gross weight 5.1 kg / 11.2 lb
Product dimensions ( 2U )442 x 270 x 87.5 mm ( W x D x H )
Packing dimensions ( 2U )530 x 380 x 140 mm ( W x D x H )
Net weight6.5 kg / 14.3 lb
Gross weight 7 kg / 15.4 lb
1 x 16-amp circuit breaker for C20 / EN16 60309 inlet
1 x 10-amp circuit breaker for C14 inlet
5
operations
Environmental
Compliance
UM-IP-ATS-Q215V1
Chassis color / materials Dark / Steel
Operating temperature-5 to 45°C degree ( 23 to 113°F )
Storage temperature-25 to 65°C degree ( 13 to 149°F )
Operating humidity0~95%, non-condensing
Storage humidity0~95%, non-condensing
EMCFCC & CE certifi ed
SafetyLVD certified
EnvironmentRoHS2 & REACH compliant
P. 6
www.austin-hughes.com
< 2.2 > 208V ATS Models
Model List - 20 Amp
HeightOutlet
ATS-H8C13-20A_L6-20P1UC13 x 8
ATS-H10C13-20A_L6-20P1UC13 x 10
ATS-H12C13-20A_L6-20P2UC13 x 12
ATS-H16C13-20A_L6-20P2UC13 x 16
ATS-H20C13-20A_L6-20P2UC13 x 20
ATS-H8C13 / 1C19-20A_L6-20P1UC13 x 8 + C19 x 1
ATS-H16C13 / 2C19-20A_L6-20P2U C13 x 16 + C19 x 2
Inlet x 2
( 3M cord attached )
L6-20P
input plug
UM-IP-ATS-Q215V1
P. 7
www.austin-hughes.com
< 2.2 > 208V ATS Specifi cation
Nominal input voltage208V
Electrical
Acceptable input voltage±10% nominal
Input frequency50 / 60Hz
Inlet plug & cord2 x L6-20P plug with 3-meter cord
Outlet connectorsMultiple C13 / C19 outlets
Local meter3-digital LED current meter
Overload protection 1 x 20-amp circuit breaker
Transfer time25ms maximum
Electrical endurance1 x 10
Power consumptionApprox. 8VA
Product dimensions ( 1U )442 x 270 x 43.5 mm ( W x D x H )
Physical
Packing dimensions ( 1U )530 x 380 x 80 mm ( W x D x H )
5
operations
Environmental
Compliance
Net weight4.6 kg / 10.1 lb
Gross weight 5.1 kg / 11.2 lb
Product dimensions ( 2U )442 x 270 x 87.5 mm ( W x D x H )
Packing dimensions ( 2U )530 x 380 x 140 mm ( W x D x H )
Net weight6.5 kg / 14.3 lb
Gross weight 7 kg / 15.4 lb
Chassis color / materials Dark / Steel
Operating temperature-5 to 45°C degree ( 23 to 113°F )
Storage temperature-25 to 65°C degree ( 13 to 149°F )
Operating humidity0~95%, non-condensing
Storage humidity0~95%, non-condensing
EMCFCC & CE certifi ed
SafetyLVD certified
UM-IP-ATS-Q215V1
EnvironmentRoHS2 & REACH compliant
P. 8
www.austin-hughes.com
< 2.3 > 110V ATS Models
Model List - 15 Amp
HeightOutlet
ATS-H8US-15A_5-15P1UNEMA x 8
ATS-H10US-15A_5-15P1UNEMA x 10
ATS-H12US-15A_5-15P2UNEMA x 12
ATS-H16US-15A_5-15P2UNEMA x 16
ATS-H20US-15A_5-15P2U NEMA x 20
Model List - 20 Amp
HeightOutlet
ATS-H8US-20A_L5-20P1UNEMA x 8
ATS-H10US-20A_L5-20P1UNEMA x 10
ATS-H12US-20A_L5-20P2UNEMA x 12
Inlet x 2
( 3M cord attached )
NEMA 5-15P
input plug
Inlet x 2
( 3M cord attached )
NEMA L5-20P
input plug
ATS-H16US-20A_L5-20P2UNEMA x 16
ATS-H20US-20A_L5-20P2U NEMA x 20
UM-IP-ATS-Q215V2
P. 9
www.austin-hughes.com
< 2.3 > 110V ATS Specifi cation
Nominal input voltage110V
Electrical
Acceptable input voltage±10% nominal
Input frequency50 / 60Hz
Inlet plug & cord2 x NEMA 5-15P / L5-20P plug with 3-meter cord
Outlet connectorsMultiple NEMA 5-20R outlets
Local meter3-digital LED current meter
Physical
Overload protection
1 x 15-amp circuit breaker for NEMA 5-15P inlet
1 x 20-amp circuit breaker for NEMA L5-20P inlet
Transfer time25ms maximum
5
Electrical endurance1 x 10
operations
Power consumptionApprox. 8VA
Product dimensions ( 1U )442 x 270 x 43.5 mm ( W x D x H )
Packing dimensions ( 1U )530 x 380 x 80 mm ( W x D x H )
Net weight4.6 kg / 10.1 lb
Gross weight 5.1 kg / 11.2 lb
Product dimensions ( 2U )442 x 270 x 87.5 mm ( W x D x H )
Packing dimensions ( 2U )530 x 380 x 140 mm ( W x D x H )
Net weight6.5 kg / 14.3 lb
Gross weight 7 kg / 15.4 lb
Chassis color / materials Dark / Steel
Operating temperature-5 to 45°C degree ( 23 to 113°F )
Environmental
Storage temperature-25 to 65°C degree ( 13 to 149°F )
Operating humidity0~95%, non-condensing
Storage humidity0~95%, non-condensing
EMCFCC & CE certifi ed
Compliance
SafetyLVD certified
EnvironmentRoHS2 & REACH compliant
The company reserves the right to modify product specifi cations without prior notice and assumes no responsibility
for any error which may appear in this publication.
All brand names, logo and registered trademarks are properties of their respective owners.
Copyright 2015 Austin Hughes Electronics Ltd. All rights reserved.
UM-IP-ATS-Q215V2