AUMA SAR 16.2, SA 16.2, SAEx 16.2, SAREx 07.2, SAV 07.2 User Manual

...
Multi-turn actuators SA/SAR 07.2 – 16.2 / SAEx/SAREx 07.2 – 16.2 SAV/SARV 07.2 – 16.2 / SAVEx/SARVEx 07.2 – 16.2 with actuator controls AC 01.2/ACExC 01.2 ACV 01.2/ACVExC 01.2 SFC version
Functional safetyManual
Multi-turn actuators
Table of contents SA .2 with AC(V) 01.2/AC(V)ExC 01.2
This document is only valid with the latest operation instructions attached to the device, the attached manual, the attached declaration of incorporation as well as the respectively pertaining technical and electrical data sheets. They are understood as reference documents.
Purpose of the document:
The present documents informs about the actions required for using the device in safety-related systems in accordance with IEC 61508 or IEC 61511.
Reference documents:
exida report no. AUMA 10-12-035 R005E
Operation instructions (Assembly, operation, commissioning) for actuator
Manual (Operation and setting) actuator controls AC 01.2/ACExC 01.2
Manual (Operation and setting) actuator controls ACV 01.2/ACVExC 01.2
Manual (Device integration Fieldbus) AC 01.2/ACExC 01.2 / ACV 01.2/ACVExC 01.2
Reference documents are available on the Internet at: http://www.auma.com.
Table of contents Page
104. Safety instrumented systems and safety functions...........................................................
115. Installation, commissioning and operation.........................................................................
115.1. Installation
115.2. Commissioning
115.3. Operation
115.4. Lifetime
125.5. Decommissioning
41. Terminology............................................................................................................................
41.1. Abbreviations and concepts
62. Application and validity.........................................................................................................
62.1. Range of application
62.2. Standards
62.3. Valid device types
73. Architecture, configuration and applications......................................................................
73.1. Architecture (actuator sizing)
73.2. Configuration (setting)
73.3. Protection against uncontrolled operation (self-locking/brake)
83.4. Operation mode (low/high demand mode)
83.5. Further notes and indications on architecture
93.6. Applications (environmental conditions)
136. Tests and maintenance..........................................................................................................
136.1. Safety equipment: check
136.2. Proof test (verification of safe actuator function)
136.2.1. Preliminary tests
136.2.2. Review and validation of the Safe end position signal” safety function
146.2.3. Checking the collective fault signal
146.3. Partial Valve Stroke Test (PVST)
146.4. Maintenance
2
Multi-turn actuators SA .2 with AC(V) 01.2/AC(V)ExC 01.2 Table of contents
157. Safety-related figures.............................................................................................................
157.1. Determination of the safety-related figures
168. SIL Declaration of Conformity (example).............................................................................
21Index........................................................................................................................................
22Addresses...............................................................................................................................
3
Multi-turn actuators
Terminology SA .2 with AC(V) 01.2/AC(V)ExC 01.2

1. Terminology

Information sources

1.1. Abbreviations and concepts

IEC 61508-4, Functional safety of electrical/electronic/programmable electronic safety-related systems – Part 4: Definitions and abbreviations
IEC 61511-1, Functional safety - Safety instrumented systems for the process industry sector – Part 1: Fr amework, definitions, system, hardware and softw are requirements
To evaluate safety functions, the lambda values or the PFD value (Probability of Dangerous Failure on Demand) and the SFF value (Safe Failure Fraction) are the main requirements. Further figures are required to assess the individual components. These figures are explained in the table below.
Table 1: Abbreviations of safety figures
ation
S D DU
DD
PFD
proof
avg
Lambda Dangerous Undetectedλ
Diagnostic CoverageDC
Mean Time Between FailuresMTBF
Safe Failure FractionSFF
Aver age Probability of dangerous Fail­ure on Demand
Hardware Failure ToleranceHFT
DescriptionFull expressionAbbrevi-
Number of safe failuresLambda Safeλ Number of dangerous failuresLambda Dangerousλ Number of undetected dangerous fail-
ures Number of detected dangerous failuresLambda Dangerous Detectedλ Diagnostic Coverage - ratio between
the failure rate of dangerous failures detected by diagnostic tests and total rate of dangerous failures of the com­ponent or subsystem.The diagnostic coverage does not include any f ailures detected during proof tests.
Mean time between the occurence of two subsequent failures
Fraction of safe failures as well as of detectable dangerous failures
Average probability of dangerous fail­ures on demand of a safety function.
Ability of a functional unit to execute a required function while faults or devi­ations are present. HFT = n means that the function can still be safely ex ecuted for up to n faults occurring at the same time.
Interval for proof testProof test intervalT
Safety function
Safety instrumented
function (SIF)
Safety instrumented
system (SIS)
Safety-related system
4
Safety Integrity Level
SIL
The international standard IEC 61508 defines 4 levels (SIL 1 through SIL 4). Function to be implemented by a safety-related system for risk reduction with the
objective to achieve or maintain a safe state for the plant/equipment with respect to a specific dangerous event.
Function with specified safety integrity level (SIL) to achieve functional safety. Safety instrumented system for executing a single or several safety instrumented
functions. An SIS consists of sensor(s), logic system and actuator(s). A safety-related system includes all factors (hardware, software, human factors)
necessary to implement one or several safety functions. Consequently failures of safety function would result in a significant increase in saf ety risks for people and/or the environment.
A safety-related system can comprise stand-alone systems dedicated to perform a particular safety function or can be integrated into a plant.
Multi-turn actuators SA .2 with AC(V) 01.2/AC(V)ExC 01.2 Terminology
Proof test
MTTR (Mean Time To
Restoration)
MRT (Mean Repair Time)
Device type (type A and
type B)
Periodic test performed to detect dangerous hidden f ailures in a safety-related system so that, if necessary, a repair can restore the system to an "as new" condition or as close as practical to this condition.
Mean time to restoration once a failure has occurred. Indicates the expected mean time to achieve restoration of the system. It is therefore an important parameter for system availability.The time for detecting the failure, planning tasks as well as operating resources is also included. It should be reduced to a minimum.
Mean repair time indicates the mean time required to repair a system.The MRT is crucial when defining the reliability and availability of a system.The MRT should preferably be small.
Actuator controls can be regarded as type A devices if all of the follo wing conditions are met for all components required to achieve the safety instrumented function:
The failure modes for all constituent components involved are well defined
The behaviour under fault conditions can be completely determined.
There is sufficient dependable failure data from the field to show that the claimed rates of failure are met (confidence level min. 70 %).
Actuator controls shall be regarded as type B devices if one or sev eral of the follo wing conditions are met:
The failure of at least one constituent component is not well defined.
The fault behaviour is not completely known.
There is insufficient dependable failure data to support claims for rates of f ailure for detected and undetected dangerous failures.
PTC (Proof Test Cover-
age)
Proof test coverage describes the fraction of f ailures which can be detected by means of a proof test.
5
Multi-turn actuators
Application and validity SA .2 with AC(V) 01.2/AC(V)ExC 01.2

2. Application and validity

2.1. Range of application

AUMA actuators and actuator controls with the safety functions mentioned in this manual are intended for operation of industrial valves and are suitable for use in safety instrumented systems in accordance with IEC 61508 or IEC 61511.

2.2. Standards

Both actuators and actuator controls meet the following requirements: For safety functions “Safe end position fieedback”: IEC 61508-2:2010 The safety figures of the devices described meet the requirements of IEC 61508 in
the respective SIL level with regard to failure rates and architecture requirements. However, this does not imply that all further requirements of IEC 61508 are met.

2.3. Valid device types

The data on functional safety contained in this manual applies to the device types indicated.
Table 2: Overview on suitable device types
Type Actuator
SA 07.2 – SA 16.2 SAR 07.2 – SAR 16.2 in SFC version
SAEx 07.2 – SAEx 16.2 SAREx 07.2 – SAREx 16.2 in SFC version
SAV/SARV 07.2 – 16.2 SAVEx/SAR VEx 07.2 – 16.2 in SFC version
Information
Type Actuator controls
in SFC version
in SFC version
in SFC version
Power supply
Any supplyAC 01.2
S2 - 30 min S4 - 25 % S4 - 50 %
Any supplyACExC 01.2
S2 - 30 min S4 - 25 % S4 - 50 %
Any supplyACV/ACVExC 01.2
S2 - 30 min S4 - 25 % S4 - 50 %
ControlType of dutyMotor
Safe end position feedbackS2 - 15 min
Safe end position feedbackS2 - 15 min
Safe end position feedbackS2 - 15 min
Hardware, software and configuration of actuator and actuator controls must not be modified without prior written consent by AUMA. Unauthorised modification may have a negative impact on both safety figures and SIL capability of the products.
In applications with requirements on functional safety, only AUMA actuator controls and actuators in SFC or SIL version may be used. SFC stands for “Safety Figure Calculated.This designation identifies AUMA products for which saf ety figures were calculated on the basis of FMEDA from field data and generic data (for detailed in­formation refer to <Determination of the figures>). AUMA actuator controls and actuators in SFC v ersion can among others be identified from the letters "SFC" following the type designation on the name plate.
Figure 1: Example of name plate with “SFC” marking
6
Multi-turn actuators SA .2 with AC(V) 01.2/AC(V)ExC 01.2 Architecture, configuration and applications

3. Architecture, configuration and applications

3.1. Architecture (actuator sizing)

For actuator architecture (actuator sizing) the maximum torques, run torques and operating times are taken into consideration.
Incorrect actuator architecture can lead to device damage within the safety­related system!
Possib le consequences can be valve damage , motor overheating, contactor jamming, defective thyristors, heating up or damage to cables.
The actuator technical data must imperatively be observed when selecting the actuator.
Sufficient reserves have to be provided to ensure that actuators are capab le of reliably opening or closing the valve even in the event of an accident or under­voltage.
Information
For the Safe end position feedback” safety function, heed that signalling is made via mechanical switches. Since these elements have an unav oidab le h ysteresis , the actuator slightly leaves the end position before the end position signal is deleted. Consequently, there is a marginal range of actuator positions to the safety position, for which the end position is still signalled although the actuator has already left the end position during operation from safety position. If the range in question is ap­proached from the opposite direction, this limitation does not apply. In general this range is relatively small. However, for unfavourable configurations (low number of turns per stroke), this range can amount to more than 10 % of the total stroke. Should, within the framework of unfa v ourab le conditions, the eff ect described abov e represent an unacceptable limitation for the saf ety function, we recommend ev aluating both limit and torque switches for the end position feedback.
Power supply
Information
The plant operator is responsible for power supply.

3.2. Configuration (setting)

Configuration (setting) of the safety-related functions is performed as described in the operation instructions or in the present manual (functional safety).
Information
An exact setting of torque and end position switches f or the end positions is imperat­ively required to ensure correct function of Safe end position feedback. For setting details related to the respective switches, please refer to operation instructions.
Configuration of reaction monitoring diagnostics and Partial V alve Str oke T est (PVST)
Depending on the type of diagnostics required, the reaction monitoring or Partial Valve Stroke Test configurations have to be checked and adapted, if required.
For detailed configuration options on reaction monitoring as well as detailed information on the Partial Valve Stroke Test (PVST), refer to Manual (Operation and setting) AUMATIC AC 01.2.

3.3. Protection against uncontrolled operation (self-locking/brake)

For self-locking AUMA actuators, it can be assumed that a load up to maximum torque will not result in uncontrolled valve operation from standstill due to v alve torque load. Consequently, in these cases, further protection against uncontrolled operation is not imperatively required. Howe ver , certain applications may require activ e position locking, for e xample b y using a brake .There are user-specific standards demanding this type of protection.Therefore, each project must be subject to individual verification if any further protection is required. In any case, this protection is required for actuators without self-locking.
7
Multi-turn actuators
Architecture, configuration and applications SA .2 with AC(V) 01.2/AC(V)ExC 01.2
Table 3: Overview self-locking for AUMA actuators (at the time of printing of this document)
Self-lockingOutput speedType
60 Hz50 Hz
Self-locking≤ 108 rpm≤ 90 rpmSA 07.2 – SA 16.2 SAR 07.2 – SAR 16.2 SAEx 07.2 – SAEx 16.2 SAREx 07.2 – SAREx 16.2
SAV 07.2 – SAV 16.2 SARV 07.2 – SARV 16.2 SAVEx 07.2 – SAVEx 16.2 SARVEx 07.2 – SARVEx 16.2
and 12 – 120 1/min
NOT self-locking≥ 150 rpm≥ 125 rpm
Self-lockingSpeed range variants 6 – 60 1/min
NOT self-lockingSpeed range variant 24 – 240 1/min

3.4. Operation mode (low/high demand mode)

The safety functions of the actuators supplied by AUMA are suitable for the low demand mode and may only be used in this operation mode. If a non-safety instrumented function of basic process control system is executed via the same actuator in addition to the safety function, note that while considering the sum of non-safety instrumented function, required tests and safety function, the defined number of maximum permissible cycles1) for the respective actuator as well as the maximum number of starts2) may not be exceeded during deplo yment of the actuator within a safety instrumented system.
Only the safe end position feedback safety function can be operated beyond the limitations mentioned above under certain conditions even in operation mode with high demand rate, provided the following requirements and limitations are heeded:
When considering the sum consisting of non-safety instrumented function, re­quired tests and safety function, the number of maximum cycles of the actuator end position switches as well as the maximum number of starts during actuator deployment are not exceeded in a safety instrumented system.
When considering the sum consisting of non-safety instrumented function, re­quired tests and safety function, the number of maximum cycles f or the respect­ive actuator as well as the maximum number of permissible cycles1) or starts are not exceeded, if appropriate scaling rules are applied.
Lubrication is checked at regular intervals and the lubricant changed if required, however, at least every 10 years.
Every 20,000 cycles1) or starts2) (whatever occurs earlier), the crown wheel and the worm wheel are checked for wear and replaced if required.
The end user makes sure that a test rate (PVST) is achieved for the Saf e end position feedback safety function, complying with the demand r ate to be expec­ted according to the applicable standards for the respective application.
All requirements in accordance with the Technical data for switches (Y004.619) data sheet are respected. In particular , the permissible minimum and maximum currents and voltages.
The number of cycles1) as well as the number of cycles of each limit and torque switch do not exceed the values stipulated in the table below:
2)
Table 4:
switch as well as cycles according to EN 15714­2:2010

3.5. Further notes and indications on architecture

HFT is 0. Only flanges of F07 or FA 07 sizes or larger may be used for valve attachment.
1) Definition of cycles according to EN 15714-2:2010
2) Definition of starts according to DIN EN 15714-2:2010
8
Class C (Modulation)Classes A and B
GoldGoldSilverSilverGoldSilverContact material 50 V/400 mA30 V/30 mA250 V AC/5 A30 V/30 mAMaximum electrical load < 20,000< 100,000< 20,000< 100,000< 20,000< 20,000Number of permissible cycles of end position
Loading...
+ 16 hidden pages