Actuator controls
AUMATIC AC 01.2/ACExC 01.2
Profibus DP
Device integration FieldbusManual
Page 2
Actuator controls
Table of contents AC 01.2/ACExC 01.2 Profibus DP
Read operation instructions first.
●
Observe safety instructions.
Purpose of the document:
This document contains information for the commissioning staff of the distributed control system and DCS software
engineers.This document is intended to support the actuator integration into the DCS via fieldbus interface.
Reference documents:
●
Operation instructions (Assembly, operation, commissioning) for actuator
●
Manual (Operation and setting) AUMATIC AC 01.2 Profibus DP
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
Safety instructions AC 01.2/ACExC 01.2 Profibus DP
1.Safety instructions
1.1.Basic information on safety
Standards/directives
Safety instructions/warn-
ings
Qualification of staff
Commissioning
AUMA products are designed and manufactured in compliance with recognised
standards and directives.This is certified in a Declaration of Incorporation and a EC
Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
They include among others applicable configuration guidelines for fieldbus
applications.
All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to av oid personal injury or property
damage.
Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitab ly qualified personnel ha ving been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation.The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Operation
Protective measures
Prerequisites for safe and smooth operation:
●
●
●
●
●
●
The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance
Any device modification requires the consent of the manufacturer.
1.2.Range of application
AUMA actuator controls are e xclusively designed f or the operation of AUMA actuators .
Other applications require explicit (written) confirmation by the manufacturer.The
following applications are not permitted, e.g.:
●
●
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Correct transport, proper storage, mounting and installation, as well as careful
commissioning.
Only operate the device if it is in perf ect condition while observing these instructions.
Immediately report any faults and damage and allow for corrective measures.
Observe recognised rules for occupational health and safety.
Observe the national regulations.
During operation, the housing warms up and surface temperatures > 60 °C may
occur.To prev ent possib le burns, we recommend to the check surface temperature with an appropriate thermometer prior to working with device and to wear
protective gloves, if required.
motor control
pump control
4
Page 5
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Safety instructions
1.3.Warnings and notes
The following warnings draw special attention to saf ety-rele v ant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a medium level of risk. F ailure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning may result in minor or moderate injury . Ma y also be used
with property damage.
Potentially hazardous situation. Failure to observe this warning may result in
property damage. Is not used for personal injury.
Arrangement and typographic structure of the warnings
Type of hazard and respective source!
Potential consequence(s) in case of non-observance (option)
→
Measures to avoid the danger
→
Further measure(s)
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.4.References and symbols
The following references and symbols are used in these instructions:
InformationThe term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
Important information before the next step.This symbol indicates what is required
for the next step or what has to be prepared or observed.
Via the menu to parameter
Describes the path within the menu to the parameter. By using the push buttons of
the local controls you may quickly find the desired parameter in the display.
< >Reference to other sections
T erms in brack ets shown abov e refer to other sections of the document which provide
further information on this topic.These terms are either listed in the index, a heading
or in the table of contents and may quickly be found.
5
Page 6
Actuator controls
General information about Profibus DP AC 01.2/ACExC 01.2 Profibus DP
2.General information about Profibus DP
For exchange of information among automation systems and between automation
systems and the connected distributed field devices, the use of serial fieldbus systems
for communication is state-of-the-art.Thousands of applications have proved
impressively that, in comparison with conventional technology, cost savings of up to
40 % in wiring, commissioning, and maintenance are achieved by using fieldbus
technology.While in the past the fieldbus systems used were often manufacturer
specific and incompatible with other bus systems, the systems employed today are
almost exclusively open and standardiz ed.This means that the user does not depend
on individual suppliers and can choose within a large product range the most suitable
product at the most competitive price.
Profibus DP is the leading open fieldbus system in Europe and is also used
successfully throughout the world.The application range includes automation in the
areas of manufacturing, processing, and building. Profibus DP is an international,
open fieldbus protocol which has been standardized in the fieldbus standards IEC
61158 and IEC 61784.This standardization ensures that the investments by
manufacturers and users are protected to the best possible degree and the
independence of the manufacturer is guaranteed.
2.1.Basic characteristics
Profibus DP defines the technical and functional features of a serial fieldbus system
allowing interconnection of distributed, digital automation devices. Profibus DP
distinguishes between master and slave devices.
Profibus DP is designed for fast data transmission on the field level. Here, central
control devices, such as a PLC or PC , communicate via a f ast serial connection with
peripheral field devices such as input/output devices, valves, and actuators.
Data exchange among these field devices is based on cyclic communication.The
respectively necessary communication functions are defined by the Profibus DP
basic functions according to IEC 61158 and IEC 61784.
Master devices
Slave device
Master devices control data traffic on the bus . A master is allowed to send messages
without an external request.Within the Profibus protocol, masters are also called
‘active devices’.
Slave devices such as AUMA Profibus DP actuators are peripheral devices.Typical
slave de vices are input/output devices, v alves, actuators , and measuring transducers.
They do not have bus access rights, i.e. they may only acknowledge received
messages or, at the request of a master, transmit messages to that master. Slaves
are also called ‘passive devices’.
2.2.Basic functions of Profibus DP
On a cyclic basis, the master reads the input information from the slaves and writes
the output information to the slaves. In addition to this cyclic data transfer of the
process representation, Profibus DP also provides powerful functions f or diagnostics
and commissioning. Data traffic is monitored through the monitoring functions on
the master and slave side.
2.3.Transfer mode
●
RS-485 twisted pair cable or fibre optic cable
●
AUMA actuators support baud rates up to 1.5 Mbits/s.
2.4.Bus access
●
Token-passing between the masters and polling between master and slave
●
Mono-master or multi-master systems are possible.
●
Master and slave devices: max. 126 devices at a bus
2.5.Functionality
●
Peer-to-peer (process data exchange [DATA EX]) or Multicast (control commands to all slaves)
6
Page 7
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP General information about Profibus DP
●
Cyclic process data exchange between DP master and DP slaves.
●
Additional acyclic data exchange between DP master and DP slaves for
Profibus DP with V1 services.
●
DP-V2 redundancy according to PNO guideline 2.212
●
DP-V2 time stamp according to PNO guideline 2.192 or IEC 61158 / 64784
●
Checking the configuration of the DP slaves
●
Synchronisation of inputs and/or outputs
2.6.Protective functions
●
All messages are transmitted with Hamming Distance HD=4.
●
Watchdog timer at DP slaves
●
Access protection for the inputs/outputs of DP slaves (Sync and Freeze)
●
Process data exchange monitoring with configurable timer interval at the master
●
Adjustable failure behaviour
2.7.Device types
●
DP master class 2 (DPM2), e.g. programming/configuration tools
●
DP master class 1 (DPM1), e.g. central controllers such as PLC, PC
●
DP slave, e.g. AUMA Profibus DP devices. Devices with binary or analogue
inputs/outputs, actuators, plug valves
7
Page 8
Actuator controls
Commissioning AC 01.2/ACExC 01.2 Profibus DP
3.Commissioning
3.1.Introduction
When commissioning a Profibus DP network, the devices on the Profibus DP must
be parameterized and configured using the programming software at the controls
(Profibus configurator).
The programming software first reads the GSD file (GeneralStationData) of the
individual actuators.The GSD file contains information about the device properties
needed by the master.
Afterwards, the user can configure and parameterize the device at the Profibus DP
for the programming software of the process control system.
This information is then stored in the controls (DP master) and sent to the actuators
(DP slaves) each time cyclic communication is started.
The process representation input and output bytes are used to control the actuator
and to supply the feedback signals. If a configuration with consistent data is selected,
certain PLCs require special functional elements for the control of the Profibus DP
slaves.
Certification
ID number
Device Master Data
(GSD)
AUMA actuators with Profibus DP are certified by the Profibus user organisation
(PNO).
Each DP slave and each DP master have individual ID numbers.The ID number is
required for the DP master to identify the type of device connected without signification
protocol overhead.The master compares the ID numbers of the connected DP
devices to the ID number in the specified configuration data.The process data transfer
will only be started if the correct device types with the correct station addresses were
connected to the bus.This ensures a high security against configuration errors.
The PNO manages the ID numbers together with the device master data (GSD).
AUMA actuators with actuator controls AC 01.2 are listed under the following ID
numbers at the PNO:
●
ID number of the standard version:0x0C4F with functions for:
-Redundant Profibus DP interface according to AUMA redundancy (I or II)
-Optional Profibus DP V1 services
●
ID number of the extended version:0x0CBD with functions for:
-Redundant Profibus DP interface according to Profib us DP-V2 redundancy
-Time stamp and alarms according to Profibus DP-V2
-Optional Profibus DP V1 services
For Profibus DP, the performance features of the devices are documented by the
manufacturer and made available to the users as device data sheet and device
master data. Structure, contents and coding of the device master data (GSD) are
standardised.They enable comfortable configuration of any DP slaves with
configuration devices by different manufacturers.
For AUMA actuators with AC 01.2 controls, the following GSD files are available:
-Redundant Profibus DP interface according to AUMA redundancy
-Optional Profibus DP V1 services
●
Optional version:AUMA0CBD.GSD with functions for:
-Redundant Profibus DP interface according to Profib us DP-V2 redundancy
-Time stamp and alarms according to Profibus DP-V2
-Optional Profibus DP V1 services
InformationGSD files can be downloaded from our website: www.auma.com.
8
Page 9
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Commissioning
3.2.Parameter setting
The parameter setting is partly defined in the Profibus standard, e.g. one bit for
switching bus monitoring on and off (watchdog).
In addition, the Profibus DP interface can receive further user parameters thus
enabling complete configuration of the process representation input.These
parameters can be modified via the programming software of the controls. New
programming software supports the parameter setting via text and a menu selection.
For older versions, the parameters must be entered as hexadecimal numbers.
Table 1: Structure of the parameter telegram
RemarkBitByte
01234567
000WD_ONFreezeSyncUnlockLock1
WD factor 12
WD factor 23
MinTSDR4
ID no. high5
ID no. low6
Group ID7
DP-V1 status 100WD_Base0000DPV1 Enable8
DP-V1 status 2000000Enable Process AlarmPrmCmd9
DP-V1 status 3Alarm ModePrmStruct000010
WD_Base
MinTSDR
ID no.
Group ID
DPV1 Enable
Enable Process Alarm
Alarm Mode
PrmStruct
PrmCmd
Settings for basic functions of the Profibus:
WD_Base = 0 (time base 10 ms)
WD_Base = 1 (time base 1 ms)
Connection monitoring time of the Profibus DP communication:
TWD = (1 or 10 ms, depending on WD_Base) x (WD factor 1) x (WD factor 2)
Minimum response time of the actuator (in T
Bit
)
ID number of the actuator
Group assignment by the master
Settings for Profibus DP-V1 services (option):
Activates the DP-V1 services available as an option; must be set to 1 when using
DP-V1 services.
Settings for Profibus DP-V2 functions (option):
Enables the process alarm (required for time synchronisation with time stamp), must
be set to 1.
Number of supported alarms, must be set to 0 (i.e. one alarm of each type is
supported).
Structured parameter setting possible, must be set to 1.
Parameter command activated, must be set to 1 for Profibus DP-V2 redundancy.
In the bytes following byte 10 of the parameter telegram the user parameters for
adaptation of the process representation input to the DCS can among others be
found (AUMA specific parameters).
The GSD file available on the website does not contain any user parameters for
adapting the process representation input to DCS requirements.The actuator will
use the default process representation with this GSD file. For further information
please refer to <Process representation input (default process representation)>.
9
Page 10
Actuator controls
Commissioning AC 01.2/ACExC 01.2 Profibus DP
3.3.Bus address (slave address)
Each participant at the bus is addressed via its specific bus address (slave address).
The bus address may be assigned only once per fieldbus network.
The bus address is stored in a non-volatile memory.
On delivery, address 126 (default value) is set for all devices.
The bus address (slave address) can be set in the following ways:
●
Locally via push buttons (indication in the display).
For details on setting refer to the operation instructions to the actuator or
Manual (Operation and Setting) AUMATIC AC 01.1 Profibus DP.
●
Using the AUMA CDT service software (via PC or laptop with Bluetooth).
The latest version of the AUMA CDT can be downloaded from our website:
www.auma.com.
●
Via fieldbus. Please note that only one device with the address 126 (default
value) may be connected to Profib us DP. A new bus address may be assigned
to the actuator using the SAP 55 (Service-Access-Point Set Slave Address).
For redundant version according to Profibus DP-V2 redundancy, only the address
of the primary channel can be set; the address of the backup channel is derived from
the primary.
For redundant version according to AUMA redundancy, the addresses of both
channels can be set individually.
3.4.Configuring the Profibus DP interface
During configuration, the number of input and output bytes reserved for each de vice
in the controls’ memory is selected. Additionally, the method of data processing is
defined: consistently or non-consistently.
InformationOnly the number of bytes determined in the configuration is transferred between DP
master and DP slave.
The following configurations are possible with AUMA Profibus DP actuators:
Number of output bytesNumber of input bytes
11
41
81
12
42
82
162
14
44
84
164
86
166
48
88
128
412
812
1212
1612
420
820
1220
10
Page 11
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Commissioning
Number of output bytesNumber of input bytes
432
832
1232
1632
2640
All these configurations (except 1 In, 1 Out) can be selected as consistent or
inconsistent.
The number of input bytes indicates how many of the maximum 40 bytes are sent
to the DP master by the DP slaves.
The number of output bytes states how many of the maximum of 26 bytes the DP
master sends to the DP slave.
If, for example, the configuration with 8 bytes input is selected, only the first 8 bytes
are sent from the DP slave to the DP master. In this case , the master does not ha ve
access to bytes 9 to 40.This way, the DP master saves memory space since only
8 input bytes are reserved for the actuator.
The data of the AUMA actuators should be consistently processed b y the DP master.
This ensures that the value of a 2-byte variable (position transmitter, analogue
customer input) does not change after reading out the first byte and, thus, does not
distort the value. If a master does not offer the possibility to use consistent
configurations by means of the process control system, a non-consistent configuration
can be selected.
3.5.Communication start-up
When switching on the DP master , it first sends one parameter and one configuration
telegram to each DP slave . If parameters and configuration are correct, the DP sla ve
enters the ‘Data Exchange’ mode to exchange process data between controls and
slave.Then, the DP master can control the DP slave and read its current state via
the process representation.
If communication is interrupted (e.g. when switching the slave off or in the event of
Profibus cable rupture), it is automatically resumed by the DP master once the cause
of the fault is eliminated.
3.6.AUMA user parameters (AUMA specific parameters)
The process representation input can be updated by means of the user parameters.
Default values and selection options are defined in a specific GSD file available on
request.
Two GSD files are available for AUMATIC AC 01.2/ACExC 01.2. A standard version
(AUMA04CF for ident-no. 0x0C4F) and an optional version with additional user
parameters for setting time stamp and alarms according to Profibus DP-V2
(AUMA0CBD for ident no. 0x0CBD).
The process representation input data can be arranged in any order. Arrangement
is defined by means of the user parameters in the GSD file, available on request.
Users may assign a specific indication to each Profibus DP signal.The data volume
of the transmitted data depends on the type of signals selected (u8, u16, i, individual
signals).
Bit: Sel. sw. LOCAL
Bit: Sel. sw. REMOTE
Bit: Sel. sw. OFF
Bit: Limit sw. CLOSED
Bit: Limit sw. OPEN
Bit: Torque sw.CLOSE
Bit: Torque sw.OPEN
Bit: Device ok
Bit: Failure
Bit: Function check
Bit: Out of spec.
Bit: Maintenance requ.
DescriptionDesignation
For limit seating: Limit switch operated in direction CLOSE
For torque seating:Torque switch and limit switch operated
in direction CLOSE
For limit seating: Limit switch operated in direction OPEN
For torque seating:Torque switch and limit switch operated
in direction OPEN
End position CLOSED reached or intermediate position
reached
(The intermediate position is only indicated if parameter
Signal interm. pos. M0167 = OPEN/CLOSED = On.)
Signal blinking: Actuator runs in direction CLOSE.
End position OPEN reached or intermediate position
reached.
(The intermediate position is only indicated if parameter
Signal interm. pos. M0167 = OPEN/CLOSED = On.)
Signal blinking: Actuator runs in direction OPEN.
The position setpoint is is within max. error variable (outer
dead band). Is only signalled if Profibus DP master has set
the Fieldbus SETPOINT bit (process representation output).
An operation command in direction CLOSE is performed
via fieldbus:Fieldbus CLOSE or Fieldbus SETPOINT (process representation output).This bit remains also set during
operation pauses (e.g. due to the dead time or the rev ersing
prevention time).
An operation command in direction OPEN is performed via
fieldbus:Fieldbus OPEN or Fieldbus SETPOINT (process
representation output).This bit remains also set during operation pauses (e.g. due to the dead time or the reversing
prevention time).
Selector switch is in position LOCAL.
Selector switch is in position REMOTE.
Selector switch is in position OFF.
Limit switch operated in end position CLOSED
Limit switch operated in end position OPEN
Torque switch operated in direction CLOSE
Torque switch operated in direction OPEN
Collective signal 05:
The device is ready for remote control.
No AUMA warnings, AUMA faults or signals according to
NAMUR are present.
Collective signal 10:
Indication according to NAMUR recommendation NE 107
Actuator function failure, output signals are invalid.
Collective signal 08:
Indication according to NAMUR recommendation NE 107
The actuator is being worked on; output signals are temporarily invalid.
Collective signal 07:
Indication according to NAMUR recommendation NE 107
Actuator is operated outside the normal operation conditions.
Collective signal 09:
Indication according to NAMUR recommendation NE 107
Recommendation to perform maintenance.
12
Page 13
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Commissioning
(51) = "Bit: Service active"
(52) = "Bit: Interlock active"
(53) = "Bit: Sel. sw. not REMOTE"
(54) = "Bit: Handwheel active"
(process representation)
Bit: Fault
Bit: Warnings
Bit: Not ready REMOTE
Bit: Op. pause active
Bit: Start step mode
Bit: Actuator running
Bit: Running LOCAL
Bit: Running REMOTE
Bit: Handwheel oper.
Bit: In interm. position
Bit: Failure behav. act.
Bit: Interm. pos. 1
Bit: Interm. pos. 2
Bit: Interm. pos. 3
Bit: Interm. pos. 4
Bit: Interm. pos. 5
Bit: Interm. pos. 6
Bit: Interm. pos. 7
Bit: Interm. pos. 8
Bit: Input DIN 1
Bit: Input DIN 2
Bit: Input DIN 3
Bit: Input DIN 4
Bit: Input DIN 5
Bit: Input DIN 6
Bit: Input DIN 7
Bit: Input DIN 8
Bit: FailState fieldbus
Bit: I/O interface
Bit: EMCY behav. act.
Bit: EMCY stop active
Bit: Service active
Bit: Interlock active
Bit: Sel. sw. not REMOTE
Bit: Handwheel active
DescriptionDesignation
Collective signal 03:
Contains the result of a disjunction (OR operation) of all
faults.
The actuator cannot be operated.
Collective signal 02:
Contains the result of an OR disjunction of all warnings.
Collective signal 04:
Contains the result of a disjunction (OR-operation) of the
signals, forming the "Not ready REMOTE" group.
The actuator cannot be operated from REMOTE.
The actuator is in off-time (e.g. stepping mode or reversing
prevention time).
The actuator is within the set stepping range.
Actuator is running (output drive is moving)
Hard wired collective signal consisting of signals:
●
(26) Bit: Running LOCAL
●
(27) Bit: Running REMOTE
●
(28) Bit: Handwheel oper.
Output drive rotates due to operation command from LOCAL.
Output drive rotates due to operation command from RE-
MOTE.
Output drive rotates without electric operation command
(manual operation).
The actuator is in an intermediate position e.g. neither in
end position OPEN nor in end position CLOSED.
The failure behaviour is active.
Intermediate position 1 reached
Intermediate position 2 reached
Intermediate position 3 reached
Intermediate position 4 reached
Intermediate position 5 reached
Intermediate position 6 reached
Intermediate position 7 reached
Intermediate position 8 reached
A high signal (+24 V DC) is present at digital input 1.
A high signal (+24 V DC) is present at digital input 2.
A high signal (+24 V DC) is present at digital input 3.
A high signal (+24 V DC) is present at digital input 4.
A high signal (+24 V DC) is present at digital input 5.
A high signal (+24 V DC) is present at digital input 6.
Parameter not available
Parameter not available
No valid communication via fieldbus (despite a vailab le con-
nection)
The actuator is controlled via the I/O interface (parallel).
Operation mode EMERGENCY is active (EMERGENCY
signal was sent).
Operation mode EMERGENCY stop is active (EMERGENCY
stop button pressed).
Operation mode Service (via Bluetooth) is active.
Actuator is interlocked.
Selector switch is in position Local control (LOCAL) or 0
(OFF).
Manual operation is active (handwheel is engaged); optional
Bit: Torque fault CLOSE
Bit: Torque fault OPEN
Bit: Torque fault
Bit: Op. time warning
Bit: On time warning
Bit: 24 V AC internal
Bit: 24 V DC control volt.
Bit: 24 V DC internal
Bit: 24 V DC, external
Bit: Internal error
Bit: Internal warning
Bit: No reaction
Bit: Configuration error
Bit: Temp. fault controls
Bit: Temp. fault motor
Bit: Temp. fault gear
Bit: Wrn heater
Bit: RTC not set
Bit: Wrn humidity
Bit: WrnRefActPos
Bit: WrnSigRgeActPos
Bit: WrnSigLossActPos
Bit: WrnActPosition
DescriptionDesignation
Received setpoint cannot be performed as the positioner is
not available.
Motor protection tripped.
●
When connecting to a 3-ph AC system and with internal
24 V DC supply of the electronics: Phase 2 is missing.
●
When connecting to a 3-ph or 1-ph AC system and with
external 24 V DC supply of the electronics: One of the
phases L1, L2 or L3 is missing.
The phase conductors L1, L2 and L3 are connected in the
wrong sequence.
Due to insufficient mains quality, the controls cannot detect
the phase sequence (sequence of phase conductors L1, L2
and L3) within the pre-set time frame provided for monitoring.
Torque fault in direction CLOSE
Torque fault in direction OPEN
Torque fault in directions CLOSE or OPEN
Warning: Max. permissible operating time for an operation
(OPEN-CLOSE) exceeded
Warning: Max. number of motor starts (starts) or max. run-
ning time/h exceeded
The internal 24 V AC v oltage supply of the controls has ex-
ceeded the power supply limits.
The 24 V A C v oltage supply is used to control the re v ersing
contactors, to assess the thermoswitches, to supply the internal actuator heater and, as an option, to generate the 115
V AC supply for the customer.
The 24 V DC auxiliary voltage (e.g. for supply of the control
outputs) is outside the supply voltage limits.
The internal 24 V DC supply voltage of the controls for
supply of the electronic components is outside the supply
voltage limits.
The external 24 V DC voltage supply of the controls has
exceeded the power supply limits.
Collective signal 14: Internal error
Collective signal 15: Internal warning
No actuator reaction to operation commands within the set
reaction time.
Incorrect configuration, i.e. the current setting is invalid.
Parameter not available
Parameter not available
Parameter not available
Heater failure at actuator (control unit)
Real time clock has not yet been set.
Parameter not available
Warning:
Position feedback of actuator was not yet referenced for
limit end positions.
Warning:
Current position feedback signal range is outside the permissible range.
Warning:
A signal loss has occurred for actuator position feedback.
Warning: Actual position of actuator
Collective signal consisting of:
●
(79) Bit: WrnRefActPos
●
(80) Bit: WrnSigRgeActPos
●
(81) Bit: WrnSigLossActPos
14
Page 15
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Commissioning
Warning:
Optical receiving signal (channel 1) incorrect (no or insufficient Rx receive level) or RS-485 format error (incorrect
bit(s))
Warning on time max. running time/h exceeded
Warning on time max. number of motor starts (starts) ex-
ceeded
Parameter not available
Parameter not available
Warning:Temperature within controls housing too high
Parameter not available
Parameter not available
Warning: Loss of signal analogue input 1
Warning: Loss of signal analogue input 2
Warning: Loss of signal actual process value
Warning: Loss of signal process setpoint
Warning: Loss of signal of actuator setpoint position
Fieldbus failure
A local STOP is active.
Push button STOP of local controls is operated.
Wrong operation command
Indicates that several operation commands were received
simultaneously via Profibus DP (e.g. Remote OPEN and
Remote CLOSE simultaneously or Remote CLOSE/Remote
OPEN and Remote SETPOINT simultaneously) or that the
max. value for a setpoint position has been exceeded (setpoint position > 1,000).
Channel 1 is the active operation command channel.
Channel 2 is the active operation command channel.
Motor runs in direction CLOSE.
Motor runs in direction OPEN.
Time synchronisation is active.
The Interlock function prevents an operation in operation
mode REMOTE.
The Interlock function prevents an operation in operation
mode LOCAL.
The Interlock function prevents an operation in operation
mode REMOTE or in operation mode LOCAL.
Operation mode disabled.
Warning: Configuration setting is incorrect.
The device can still be operated with restrictions.
Channel 1 is in the data exchange state (DataEx).
Channel 2 is in the data exchange state (DataEx).
Warning: FO cable system reserve reached (critical or per-
missible Rx receive level)
No valid fieldbus communication via channel 1 (application
does not communicate with the DCS).
No valid fieldbus communication via channel 2 (application
does not communicate with the DCS).
Bus communication available on channel 1.
Bus communication available on channel 2.
Partial Valve Stroke Test (PVST) is active.
Partial Valve Stroke Test (PVST) could not be successfully
(126) = "Bit: RTC button cell"
(127) = "Bit:Wrn FOC connection"
(128) = "u16: Actual position"
(129) = "u16: Input AIN 1"
(130) = "u16: Input AIN 2"
(131) = "u16:Torque CLOSE %"
(132) = "u16:Torque OPEN %"
(133) = "u16:Torque CLOSE Nm"
(134) = "u16:Torque OPEN Nm"
(135) = "u16: torque CLOSE ft-lb"
(136) = "u16:Torque OPEN ft-lb"
(137) = "u16:Torque"
(139) = "u16: Actual P osition 0-100%"
(process representation)
Bit: PVST abort
Bit: Interlock OPEN
Bit: Interlock CLOSE
Bit: Interlock by-pass
Bit: No reaction (fault)
Bit: Config. error REMOTE
Bit: Torque warn. OPEN
Bit: Torque warn. CLOSE
Bit: RTC button cell
Bit: Wrn FOC connection
u16: Actual position
u16: Input AIN 1
u16: Input AIN 2
u16: Torque CLOSE %
u16: Torque OPEN %
u16: Torque CLOSE Nm
u16: Torque OPEN Nm
u16: torque CLOSE ft-lb
u16: Torque OPEN ft-lb
u16: Torque
Actual position 0-100 %
DescriptionDesignation
Partial Valve Stroke Test (PVST) was aborted or could not
be started. Remedy: Perform RESET or restart PVST.
Release signal OPEN not active: Operation commands in
direction OPEN are disabled.
Release signal CLOSE not active: Operation commands in
direction CLOSE are disabled.
Bypass of interlock function is active.
No reaction detected at actuator output drive.
Config. error of REMOTE interface active.
Warning: Limit value for torque warning in direction OPEN
exceeded.
Warning: Limit v alue f or torque w arning in direction CLOSE
exceeded.
Warning:Voltage of RTC button cell too low.
Warning: FO cable connection is not available.
Actual actuator position (0 – 1,000 per mil)
Analogue input 1
Analogue input 2
Torque in direction CLOSE, unit in %
Torque in direction OPEN, unit in %
Torque in direction CLOSE, unit in Nm
Torque in direction OPEN, unit in Nm
Torque in direction CLOSE, unit in ft-lb
Torque in direction OPEN, unit in ft-lb
Actual torque value
Actual actuator position (0 – 100 percent)
fault
Bit: Wrn hydraulics
Bit: Safe ESD
Bit: Safe STOP
Bit: SIL fault
Bit: SIL function active
1)
1)
1)
1)
Bit: PVST required
Bit: Maintenance mechan-
ics
Parameter not available(160) = "i16: Actual position"
Parameter not available(161) = "i16: Input AIN 1"
Parameter not available(162) = "i16: Input AIN 2"
Parameter not available(163) = "i16:Torque CLOSE %"
Parameter not available(164) = "i16:Torque OPEN %"
Parameter not available(192) = "float: Actual position"
Parameter not available(193) = "float: Input AIN 1"
Parameter not available(194) = "float: Input AIN 2"
Parameter not available(195) = "float:T CLOSE %"
Parameter not available(196) = "float:T OPEN %"
Parameter not available(197) = "float:T CLOSE Nm"
Parameter not available(198) = "float:T OPEN Nm"
Parameter not available(199) = "float:T CLOSE lbs/ft."
Parameter not available(200) = "float:T OPEN lbs/ft."
Parameter not available
Parameter not available
Parameter not available
Safe ESD function (Emergency Shut Down) is active.
Safe STOP function is active.
A SIL fault has occurred (collective signal).
A SIL function is active.
(PVST) Partial Valve Stroke Test should be executed
Mechanic maintenance requirement
16
Page 17
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Commissioning
Parameter description of additional user parameters for setting the time stamp and
alarms according to Profibus DP-V2, available with the optional version
AUMA0CBD.gsd.
No function–1 "Setpoint valid bit"
DP-V2 time stamp deactivated.Text(0) = "disable"2 "Timestamp (TS)"
DP-V2 time stamp activated.Text(1) = "enable"
DP-V2 time stamp of End position CLOSED signal deactiv-
ated.
DP-V2 time stamp of End position CLOSED signal activated.
DP-V2 time stamp of End position OPEN signal deactivated.
DP-V2 time stamp of End position OPEN signal activated.
DP-V2 time stamp of Torque sw. CLOSED signal deactiv-
ated.
DP-V2 time stamp of Torque sw. CLOSED signal activated.
DP-V2 time stamp of Torque sw. OPEN signal deactivated.
DP-V2 time stamp of Torque sw. OPEN signal activated.
DP-V2 time stamp of Selector sw. REMOTE signal deactiv-
ated.
DP-V2 time stamp of Selector sw. REMOTE signal activated.
DP-V2 time stamp of Fault signal deactivated.
DP-V2 time stamp of Fault signal activated.
DP-V2 time stamp of Phase fault signal deactivated.
DP-V2 time stamp of Phase fault signal activated.
Without function (reserved)–10 "TS -> reserved"
Without function (reserved)–11 "reserved Byte"
3.6.4.Further adaptation options
From firmware 04.05.xx, the actuator controls provide the option to adapt to the
existing DCS configurations of the actuator type range A C 01.1/ACExC 01.1. Actuator
controls of type range AC 01.2/A CExC 01.2 can be adapted as to support the default
arrangement of the Profibus DP-V0 process representation input of
AC 01.1/ACExC 01.1 without changing the Profibus configuration of the DCS.
Setting is performed using the following parameter:Deviceconfiguration>Profibus>Connection type = AUMATIC .1
17
Page 18
Actuator controls
Commissioning AC 01.2/ACExC 01.2 Profibus DP
●
Information
Only the Profibus DP-V0 standard arrangement of the process representation
input of AC 01.1/ACExC 01.1 is supported, deviating arrangements of the
Profibus DP-V0 process data input require use/installation of AUMA04CF.gsd
or AUMA0CBD.gsd file in the DCS.
●
With connection type = AUMATIC.1 the AC 01.2/A CExC 01.2 does not provide
any diagnostic NAMUR NE 107 information within the cyclic process data representation.
●
EDD or DTM of the AC 01.2/ACExC 01.2 m ust imperativ ely be used f or acyclic
communication via Profibus DP-V1 with AC 01.2/ACExC 01.2!
●
Factory setting:Connection type = AUMATIC.2
3.7.Communication monitoring
3.7.1.Connection monitoring of the Profibus DP communication
The connection monitoring within the master has to be activated to monitor both
master and cable connection between master and actuator (parameter telegram
byte 1, bit 3, WD_ON = 1).
Only if the connection monitoring is active can the actuator react in the even of loss
of communication once the monitoring time also set in the master has elapsed.
The reaction of the actuator also depends on the settings for failure behaviour or
EMERGENCY BEHAVIOUR.
3.7.2.Fail Safe and Global Control Clear telegrams
Another possibility to set the slave to a safe state in the event of a fault are the fail
safe telegrams (telegr ams with data length = 0). If fails safe telegrams are received,
the actuator remains in the DataExchange state; depending on the respectiv e setting,
the actuator may initiate the failure behaviour or the EMERGENCY behaviour.The
actuator quits the Fail Safe state as soon as valid telegrams with the data length ≠
0 are received.
Furthermore, the Global Control Clear (GC Clear) master telegrams can also be
used to initiate the failure behaviour or the EMERGENCY behaviour.This state can
be disabled using a Global Control Operate telegram (GC Operate).
For activated EMERGENCY behaviour:
The actuator can start its operation due to an EMERGENCY signal or a loss
of communication.
Risk of personal injuries or damage to the valve.
→
For commissioning and maintenance work: Set selector switch to position 0
(OFF).The motor operation can only be interrupted in this selector switch position.
→
If the actuator starts its operation by accident: Set selector switch to position 0
(OFF).
3.8.I & M functions
18
The actuator controls support the I & M functions according to PNO guideline 3.502.
With the term Identification & Maintenance (I & M) functions, the Profibus user
organisation e.V. (PNO) introduced a new functionality for all Profibus devices with
acyclic communication channel that may prove very useful for plant operators.The
I & M functions define how certain device-describing data (according to name plate)
is to be uniformly stored in the Profibus devices. Engineering tools may then read
and inteprete the data according to a code which can be accessed on the PNO
server.This provides uniform and powerful access to all important and current device
data, one of the major requirements for asset management.
Part of the device-specific I & M information is the unambiguous asset identification
using a manufacturer ID (MANUFACTURER_ID, for AUMA actuators = 319), the
Page 19
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Commissioning
order number (ORDER_ID) of the actuator as well as the individual serial number
(SERIAL_NUMBER). Further data supplements the asset information.
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
4.Description of the data interface
4.1.Input data (process representation input) – signals
The process representation input allows the master (controls) to read the state of
the slave (actuator).
4.1.1.Process representation input (default process representation)
Grey bits are collective signals.They contain the results of a disjunction (OR
operation) of other information.
20
Page 21
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
21
Page 22
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
4.1.2.Description of the bytes in the process representation input
Byte 1: Logical signals
Bits 3, 6, and 7 are collective signals.
Bits 5 and 4 of the logical signals (byte1) indicate a logical operation of the actuator ,
i.e. they are set when the actuator has received the command to perf orm an electrical
operation (also active when e.g. the actuator is in a stepping pause during stepping
mode or waiting for the end of the dead time).
Table 4: Byte 1: Logical signals
Bit
(process representation)
0
Bit: End p. OPEN
1
Bit: End p. CLOSED
2
Bit: Setpoint reached
3
Bit: Not ready REMOTE
4
Bit: Running OPEN
5
Bit: Running CLOSE
6
Bit: Warnings
7
Bit: Fault
MOTE"
DescriptionValuePrm-Text-Def GSD fileDesignation
For limit seating: Limit switch operated in direction OPEN
1(2) = "Bit: End p. OPEN"
For torque seating:Torque switch and limit switch operated in direction OPEN
No signal0
For limit seating: Limit switch operated in direction
1(1) = "Bit End p. CLOSED"
CLOSE
For torque seating:Torque switch and limit switch operated in direction CLOSE
No signal0
The setpoint is within max. error variable (outer dead
1(5) = "Bit: Setpoint reached"
band). Is only signalled if Profibus DP master has set
the Fieldbus SETPOINT bit (process representation
output).
No signal0
Collective signal 04:
1(22) = "Bit: Not ready RE-
Contains the result of a disjunction (OR-operation) of all
bits comprised in bytes 13 and 14 (Not ready REMOTE
1 and Not ready REMOTE 2).
The actuator cannot be operated from REMOTE.
The actuator can only be operated via the local controls.
In bytes 13 and 14, no signals are active (all bits are set
0
to 0).
An operation command in direction OPEN is performed
1(7) = "Bit: Running OPEN"
via fieldbus:Fieldbus OPEN or Fieldbus SETPOINT
(process representation output).This bit remains also
set during operation pauses (e.g. due to the dead time
or the reversing prevention time).
Operation in direction OPEN via fieldbus is not ex ecuted.0
An operation command in direction CLOSE is performed
1(6) = "Bit: Running CLOSE"
via fieldbus:Fieldbus CLOSE or Fieldbus SETPOINT
(process representation output).This bit remains also
set during operation pauses (e.g. due to the dead time
or the reversing prevention time).
Operation in direction CLOSE via fieldbus is not ex-
0
ecuted.
Collective signal 02:
1(21) = "Bit:Warnings"
Contains the result of a disjunction (OR-operation) of all
bits of bytes 17 to 20 (Warning 1 to Warning 4).
In bytes 17 and 20, no warnings are active (all bits are
0
set to 0).
Collective signal 03:
1(20) = "Bit: Fault"
Contains the result of a disjunction (OR-operation) of all
bits of bytes 15 and 16 (Fault 1 and Fault 2).
The actuator cannot be operated.
In bytes 15 and 16, no faults are active (all bits are set
0
to 0).
22
Page 23
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
Byte 2: Actuator signals
Table 5: Byte 2: Actuator signals
Bit
(process representation)
0
Bit: Thermal fault
1
Bit: Phase failure
2
Bit: Sel. sw. REMOTE
3
Bit: Sel. sw. LOCAL
4
Bit: Limit sw. OPEN
5
Bit: Limit sw. CLOSED
6
Bit: Torque sw.OPEN
7
Bit: Torque sw.CLOSE
MOTE"
LOCAL"
CLOSED"
OPEN"
CLOSE"
DescriptionValuePrm-Text-Def GSD fileDesignation
Motor protection tripped1(56) = "Bit:Thermal fault"
No signal0
●
1(57) = "Bit: Phase fault"
When connecting to a 3-ph AC system and with internal 24 V DC supply of the electronics: Phase 2 is
missing.
●
When connecting to a 3-ph or 1-ph AC system and
with external 24 V DC supply of the electronics: One
of the phases L1, L2 or L3 is missing.
All phases are available.0
Selector switch is in position REMOTE.1(9) = "Bit: Sel. sw. RESelector switch is not in position REMOTE.0
Selector switch is in position LOCAL.1(8) = "Bit: Selector sw.
Selector switch is not in position LOCAL.0
Limit switch operated in end position OPEN1(12) = "Bit: Limit sw. OPEN"
No signal0
Limit switch operated in end position CLOSED1(11) = "Bit: Limit sw.
No signal0
Torque switch operated in direction OPEN.1(14) = "Bit:Torque sw.
No signal0
Torque switch operated in direction CLOSE.1(13) = "Bit:Torque sw.
No signal0
Table 6: Byte 5: Device status
Bit
(process representation)
0
Bit: Not ready REMOTE
1
Bit: Warnings
2
Bit: Fault
Bytes 3 and 4: Actual position
Byte 3 = high byte, byte 4 = low byte.
If a position transmitter (potentiometer, RWG, EWG, or MWG) is installed in the
actuator, b ytes 3 and 4 are used to tr ansmit the current actuator position.The value
is transmitted in per mil (value: 0 – 1,000).
Byte 5: Device status
DescriptionValuePrm-Text-Def GSD fileDesignation
Collective signal 04:
1(22) = "Bit: Not ready RE-
MOTE"
Contains the result of a disjunction (OR-operation) of all
bits comprised in bytes 13 and 14 (Not ready REMOTE
1 and Not ready REMOTE 2).
The actuator cannot be operated from REMOTE.
The actuator can only be operated via the local controls.
In bytes 13 and 14, no signals are active (all bits are set
0
to 0).
Collective signal 02:
1(21) = "Bit:Warnings"
Contains the result of a disjunction (OR-operation) of all
bits of bytes 17 to 20 (Warning 1 to Warning 4).
In bytes 17 and 20, no warnings are active (all bits are
0
set to 0).
Collective signal 03:
1(20) = "Bit: Fault"
Contains the result of a disjunction (OR-operation) of all
bits of bytes 15 and 16 (Fault 1 and Fault 2).
The actuator cannot be operated.
In bytes 15 and 16, no faults are activ e (all bits are set to
0
0).
23
Page 24
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
Bit
(process representation)
3
Bit: Maintenance requ.
4
Bit: Out of spec.
5
Bit: Function check
6
Bit: Failure
7
Bit: Device ok
requ."
DescriptionValuePrm-Text-Def GSD fileDesignation
Collective signal 09:
1(19) = "Bit: Maintenance
Indication according to NAMUR recommendation NE 107
Recommendation to perform maintenance.
Contains the result of a disjunction (OR-operation) of all
bits of byte 24 (Maintenance required).
In all bits of byte 24, no signals are active (all bits are set
0
to 0).
Collective signal 07:
1(18) = "Bit: Out of spec."
Indication according to NAMUR recommendation NE 107
Actuator is operated outside the normal operation conditions.
Contains the result of a disjunction (OR-operation) of all
bits of bytes 25 to 28 (Out of specification 1 to 4).
In bytes 25 and 28, no signals are active (all bits are set
0
to 0).
Collective signal 08:
1(17) = "Bit: Function check"
Indication according to NAMUR recommendation NE 107
The actuator is being worked on; output signals are temporarily invalid.
Contains the result of a disjunction (OR-operation) of all
bits of bytes 29 and 30 (Function check 1 and 2).
In bytes 29 and 30, no signals are active (all bits are set
0
to 0).
Collective signal 10:
1(16) = "Bit: Failure"
Indication according to NAMUR recommendation NE 107
Actuator function failure, output signals are invalid.
Contains the result of a disjunction (OR-operation) of all
bits of byte 23 (Failure).
In all bits of byte 23, no signals are active (all bits are set
0
to 0).
Sammelmeldung 05:
1(15) = "Bit: Device ok"
The device is ready for remote control.
No AUMA warnings, AUMA faults or signals according to
NAMUR are present.
Bit 7 is set if bits 0 to 6 are deleted.
Contains the result of a disjunction (OR-operation) of bits
0
0 to 6 (device status).
Byte 6: Operation status
This byte stores information about actuator movement.
Table 7: Byte 6: Operation status
Bit
(process representation)
0
Bit: Op. pause active
1
Bit: In interm. position
2
Bit: Start step mode
4
Bit: Actuator running
ive"
tion"
mode"
ning"
DescriptionValuePrm-Text-Def GSD fileDesignation
The actuator is in off-time (e.g. rev ersing prevention time)1(23) = "Bit: Op. pause actNo signal0
The actuator is in an intermediate position e.g. neither in
1(29) = "Bit: In interm. posi-
end position OPEN nor in end position CLOSED.
No signal0
The actuator is within the set stepping range.1(24) = "Bit: Start step
The actuator is outside the set stepping range.0
No signal (reserved)——3
Actuator is running (output drive is moving)
1(25) = "Bit: Actuator run-
Hard wired collective signal consisting of signals:
●
(26) Bit: Running LOCAL
●
(27) Bit: Running REMOTE
●
(28) Bit: Handwheel oper.
No signal0
24
Page 25
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
Bit
(process representation)
5
Bit: Handwheel oper.
6
Bit: Running REMOTE
7
Bit: Running LOCAL
handw."
MOTE"
AL"
Byte 7: Intermediate positions
Table 8: Byte 7: Intermediate positions
Bit
(process representation)
0
Bit: Interm. pos. 1
1
Bit: Interm. pos. 2
2
Bit: Interm. pos. 3
3
Bit: Interm. pos. 4
4
Bit: Interm. pos. 5
5
Bit: Interm. pos. 6
6
Bit: Interm. pos. 7
7
Bit: Interm. pos. 8
pos. 1"
pos. 2"
pos. 3"
pos. 4"
pos. 5"
pos. 6"
pos. 7"
pos. 8"
DescriptionValuePrm-Text-Def GSD fileDesignation
Output drive rotates without electric operation command.1(28) = "Bit: Running via
No signal0
Output drive rotates due to operation command from
1(27) = "Bit: Running RE-
REMOTE.
No signal0
Output drive rotates due to operation command from
1(26) = "Bit: Running LOC-
LOCAL.
No signal0
DescriptionValuePrm-Text-Def GSD fileDesignation
Intermediate position 1 reached1(31) = "Bit: Intermediate
No signal0
Intermediate position 2 reached1(32) = "Bit: Intermediate
No signal0
Intermediate position 3 reached1(33) = "Bit: Intermediate
No signal0
Intermediate position 4 reached1(34) = "Bit: Intermediate
No signal0
Intermediate position 5 reached1(35) = "Bit: Intermediate
No signal0
Intermediate position 6 reached1(36) = "Bit: Intermediate
No signal0
Intermediate position 7 reached1(37) = "Bit: Intermediate
No signal0
Intermediate position 8 reached1(38) = "Bit: Intermediate
No signal0
Table 9: Byte 8: Discrete inputs
Bit
(process representation)
0
Bit: Input DIN 1
1
Bit: Input DIN 2
2
Bit: Input DIN 3
3
Bit: Input DIN 4
4
Bit: Input DIN 5
5
Bit: Input DIN 6
Byte 9 = high byte, byte 10 = low byte.
Byte 8: Discrete inputs
DescriptionValuePrm-Text-Def GSD fileDesignation
A high signal (+24 V DC) is present at digital input 1.1(39) = "Bit: Input DIN 1"
No signal0
A high signal (+24 V DC) is present at digital input 2.1(40) = "Bit: Input DIN 2"
No signal0
A high signal (+24 V DC) is present at digital input 3.1(41) = "Bit: Input DIN 3"
No signal0
A high signal (+24 V DC) is present at digital input 4.1(42) = "Bit: Input DIN 4"
No signal0
A high signal (+24 V DC) is present at digital input 5.1(43) = "Bit: Input DIN 5"
No signal0
A high signal (+24 V DC) is present at digital input 6.1(44) = "Bit: Input DIN 6"
No signal0
No signal (reserved)——6
No signal (reserved)——7
Byte 9 and byte 10: Input AIN 1
25
Page 26
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
Bytes 9 and 10 transmit the value of the first additional free analogue current input
of the Profibus DP interface.The start and end values can be set at the AC via push
buttons and display. (For operation, please refer to the respective operation
instructions for the actuator.)
If the measuring values are 0.3 mA below the initial value, a signal loss is indicated.
The value is transmitted in per mil (value: 0 – 1,000).
Byte 11 and byte 12:Torque
Byte 11 = high byte, byte 12 = low byte.
Bytes 11 and 12 transmit the current torque of the actuator (only if an MWG is installed
in the actuator).
The value transmitted is the current torque in percent or per mil of the nominal actuator
torque.
The value is transmitted in per mil (value: 0 – 1,000).
●
The value 1,000 corresponds to 127.0 % torque in direction OPEN.
●
The value 500 is the torque zero point.
●
The value 0 corresponds to 127.0 % torque in direction CLOSE.
Byte 13: Not ready REMOTE 1
Table 10: Byte 13: Not ready REMOTE 1
Bit
(process representation)
0
Bit: Wrong oper. cmd
1
Bit: Sel. sw. not REMOTE
2
Bit: Interlock active
3
Bit: Local STOP
4
Bit: EMCY stop active
5
Bit: EMCY behav. act.
6
Bit: FailState fieldbus
7
Bit: I/O interface
tion cmd"
REMOTE""
active"
hav.act."
bus"
DescriptionValuePrm-Text-Def GSD fileDesignation
Wrong operation command
1(98) = "Bit:Wrong opera-
Indicates the fact that sev eral oper ation commands were
received simultaneously via Profibus DP (e.g. Remote
OPEN and Remote CLOSE simultaneously or Remote
CLOSE/Remote OPEN and Remote SETPOINT simultaneously) or that the max. value for a setpoint position has
been exceeded (setpoint position > 1,000).
Operation commands are ok.0
Selector switch is in position Local control (LOCAL) or
1(53) = "Bit: Sel. sw. not
0 (OFF).
Selector switch is in position Remote control (REMO TE).0
Actuator is interlocked.1(52) = "Bit: Interlock activ e"
No signal0
Push button STOP of local controls is operated.1(97) = "Bit: Local Stop"
No signal0
Operation mode EMERGENCY stop is active (EMER-
1(50) = "Bit: EMCY stop
GENCY stop button has been pressed).
EMERGENCY stop button not pressed (normal operation).0
Operation mode EMERGENCY behaviour is active
1(49) = "Bit: EMCY be-
(EMERGENCY signal was sent).
No signal0
No valid communication via fieldbus (despite available
1(47) = "Bit: FailState field-
connection)
Communication via fieldbus is ok.0
The actuator is controlled via the I/O interface (parallel).1(48) = "Bit: I/O interface"
The actuator is controlled via fieldbus.0
26
Page 27
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
Byte 14: Not ready REMOTE 2
Table 11: Byte 14: Not ready REMOTE 2
Bit
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
No signal (reserved)——0
No signal (reserved)——1
2
Bit: SIL function active
3
Bit: Disabled
1)
ive"
The safety function of the SIL sub-assembly is active.1(207) = "SIL function actNo signal.0
Actuator is in operation mode Disabled.1(107) = "Bit: Disabled"
No signal0
4
Bit: Interlock by-pass
5
Bit: PVST active
lock"
By-pass of interlock function is active.1(121) = "Bit: Bypass InterNo signal0
Partial Valve Stroke Test (PVST) is active.1(116) = "Bit: PVST active"
No signal0
6
Bit: Service active
Operation mode Service is active.1(51) = "Bit: Service active"
No signal0
Manual operation is active (handwheel is engaged); op-
7
Bit: Handwheel active
active"
1(54) = "Bit: Handwheel
tional signal
No signal0
The safety function indications via fieldbus are for information only and must not be used as part of a safety function.The I/O signals of
1)
the SIL module must be used for this purpose.
Byte 15: Fault 1
The fault signals contain the causes why the actuator cannot be operated.
Table 12: Byte 15: Fault 1
Bit
(process representation)
0
Bit: Configuration error
1
Bit: Mains quality
2
Bit: Thermal fault
3
Bit: Phase failure
4
Bit: Torque fault OPEN
5
Bit: Torque fault CLOSE
6
Bit: Internal error
7
Bit: No reaction
error"
OPEN"
CLOSE"
DescriptionValuePrm-Text-Def GSD fileDesignation
Incorrect configuration, i.e. the current setting of the actu-
1(72) = "Bit: Configuration
ator controls is invalid.
Configuration is ok.0
Due to insufficient mains quality, the controls cannot de-
1(59) = "Bit: Mains quality"
tect the phase sequence (sequence of phase conductors
L1, L2 and L3) within the pre-set time frame provided for
monitoring.
No signal0
Motor protection tripped1(56) = "Bit:Thermal fault"
No signal0
●
1(57) = "Bit: Phase fault"
When connecting to a 3-ph AC system and with internal 24 V DC supply of the electronics: Phase 2 is
missing.
●
When connecting to a 3-ph or 1-ph AC system and
with external 24 V DC supply of the electronics: One
of the phases L1, L2 or L3 is missing.
No signal0
Torque fault in direction OPEN1(61) = "Bit:Torque fault
No signal0
Torque fault in direction CLOSE1(60) = "Bit:Torque fault
No signal0
Collective signal 14: Internal fault1(69) = "Bit: Internal fault"
No internal fault0
No actuator reaction to operation commands within the
1(71) = "Bit: No reaction"
set reaction time.
No signal0
27
Page 28
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
Byte 16: Fault 2
The fault signals contain the causes why the actuator cannot be operated.
Table 13: Byte 16: Fault 2
Bit
(process representation)
6
Bit: Config. error REMOTE
7
Bit: Incorrect phase seq
remote"
sequence"
DescriptionValuePrm-Text-Def GSD fileDesignation
No signal (reserved)——0
No signal (reserved)——1
No signal (reserved)——2
No signal (reserved)——3
No signal (reserved)——4
No signal (reserved)——5
Configuration error of REMOTE interface active.1(123) = "Bit: Config error
No signal.0
The phase conductors L1, L2 and L3 are connected in
1(58) = "Bit:Wrong phase
the wrong sequence.
Phase sequence is ok.0
Byte 17:Warnings 1
The warning signals are for information only and do not interrupt or disable an
operation (as opposed to faults).
Table 14: Byte 17:Warnings 1
Bit
(process representation)
4
Bit: Torque warn. CLOSE
5
Bit: Torque warn. OPEN
6
Bit: SIL fault
7
Bit: No reaction
The safety function indications via fieldbus are for information only and must not be used as part of a safety function.The I/O signals of
1)
the SIL module must be used for this purpose.
1)
CLOSE"
OPEN"
DescriptionValuePrm-Text-Def GSD fileDesignation
No signal (reserved)——0
No signal (reserved)——1
No signal (reserved)——2
No signal (reserved)——3
Warning: Limit value for Torque warning CLOSE ex-
1(125) = "Bit:Torque wrn
ceeded
No signal0
Warning: Limit v alue for Torque warning OPEN exceeded1(124) = "Bit: Torque wrn
No signal0
Warning: A SIL fault of the SIL sub-assembly has oc-
1(206) = "SIL fault"
curred.
No signal0
Warning: No actuator reaction to operation commands
1(71) = "Bit: No reaction"
within the set reaction time.
No signal0
Table 15: Byte 18:Warnings 2
Bit
(process representation)
0
Bit: Wrn controls temp
3
Bit: 24 V DC, external
28
Byte 18:Warnings 2
sTemp"
al"
DescriptionValuePrm-Text-Def GSD fileDesignation
Warning:Temperature within controls housing too high1(88) = "Bit:WrnControlNo signal0
No signal (reserved)——1
No signal (reserved)——2
The external 24 V DC voltage supply of the controls has
1(68) = "Bit: 24 V DC, e xtern-
exceeded the power supply limits.
No signal0
Page 29
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
Bit
(process representation)
5
Bit: RTC button cell
6
Bit: RTC not set
7
Bit: Config. warning
Table 16: Byte 19:Warnings 3
Bit
(process representation)
0
Bit: Wrn FOC budget
1
Bit: Wrn FO cables
2
Bit: Wrn input AIN 2
3
Bit: Wrn input AIN 1
4
Bit: Internal warning
5
Bit: WrnOnTiStarts
6
Bit: WrnOnTiRunning
7
Bit: Op. time warning
cell"
ing”
Byte 19:Warnings 3
budget”
2"
1"
ing"
ning"
warning"
DescriptionValuePrm-Text-Def GSD fileDesignation
No signal (reserved)——4
Warning:The voltage of the RTC button cell is too low.1(126) = "Bit: RTC button
No signal0
The real time clock has not yet been set on the basis of
1(77) = "Bit: RTC not set"
valid values.
No signal0
Warning: Configuration setting is incorrect.
1(108) = “Bit: Config.Warn-
The device can still be operated with restrictions.
No signal0
DescriptionValuePrm-Text-Def GSD fileDesignation
Warning: FO cable system reserve reached (critical or
1(111) = “Bit:Wrn FOC
permissible Rx receive level)
No signal0
Warning:
1(83) = "Bit:Wrn FO loop"
Optical receiving signal (channel 1) incorrect (no or insufficient Rx receive lev el) or RS-485 f ormat error (incorrect
bit(s))
No signal0
Warning: Loss of signal analogue input 21(92) = "Bit:Wrn input AIN
No signal0
Warning: Loss of signal analogue input 11(91) = "Bit:Wrn input AIN
No signal0
Collective signal 15: Internal warning1(70) = "Bit: Internal warnNo internal warning0
Warning: Max. number of motor starts (starts) exceeded1(85) = "Bit:WrnOnTiStarts"
No signal0
Warning: Max. running time/h exceeded1(84) = "Bit:WrnOnTiRunNo signal0
Warning: Max. permissible operating time f or an operation
1(63) = "Bit: Operat. time
(OPEN-CLOSE) exceeded
No signal0
Table 17: Byte 20:Warnings 4
Bit
(process representation)
2
Bit: WrnSetpointPos
3
Bit: PVST required
4
Bit: Wrn FOC connection
5
Bit: Failure behav. act.
Byte 20:Warnings 4
Pos"
connection"
active"
DescriptionValuePrm-Text-Def GSD fileDesignation
No signal (reserved)——0
No signal (reserved)——1
Warning: Loss of signal of actuator setpoint position1(95) = "Bit:WrnSetpointNo signal0
Warning: A Partial Valve Stroke Test (PVST) should be
1(208) = "PVST required"
performed.
0
Warning: FO cable connection not available.1(127) = "Bit:Wrn FOC
No signal0
The failure behaviour is active.1(30) = "Bit: Failure behav.
No signal0
29
Page 30
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
Bit
(process representation)
6
Bit: PVST abort
7
Bit: PVST error
Table 18: Byte 23: Failure
Bit
(process representation)
7
Bit: Fault
DescriptionValuePrm-Text-Def GSD fileDesignation
Partial Valve Stroke Test (PVST) was aborted or could
1(118) = "Bit: PVST abort"
not be started. Remedy: P erf orm RESET or restart PVST.
No signal0
Partial V alv e Stroke Test (PVST) could not be successfully
1(117) = "Bit: PVST fault"
completed.
No signal0
Byte 21 and byte 22: Input AIN 2
Byte 21 = high byte, byte 22 = low byte.
Bytes 9 and 10 transmit the value of the second additional free analogue current
input of the Profibus DP interface.The start and end values can be set at the AC via
push buttons and display. (For operation, please refer to the respective operation
instructions for the actuator.)
If the measuring values are 0.3 mA below the initial value, a signal loss is indicated.
The value is transmitted in per mil (value: 0 – 1,000).
Byte 23: Failure
Causes of the Failure signal in accordance with NAMUR recommendation NE 107.
DescriptionValuePrm-Text-Def GSD fileDesignation
No signal (reserved)——0
No signal (reserved)——1
No signal (reserved)——2
No signal (reserved)——3
No signal (reserved)——4
No signal (reserved)——5
No signal (reserved)——6
Collective signal 03:
1(20) = "Bit: Fault"
Contains the result of a disjunction (OR-operation) of all
bits of bytes 15 and 16 (Fault 1 and Fault 2).
The actuator cannot be operated.
In bytes 15 and 16, no faults are activ e (all bits are set to
0
0).
Byte 24: Maintenance required
Causes of the Maintenance required signal in accordance with NAMUR
recommendation NE 107.
Table 19: Byte 24: Maintenance required
Bit
(process representation)
0
Bit: Maintenance mechanics
1
Bit: Maintenance seals
2
Bit: Maintenance lubricant
3
Bit: Maintenance contactors
4
Bit: Maintenance interval
30
val"
DescriptionValuePrm-Text-Def GSD fileDesignation
Mechanic maintenance requirement (AUMA service)1(209) = "Mechanic lifetime"
No signal0
Seal maintenance requirement (AUMA service)1(210) = "Seal lifetime"
No signal0
Lubricant maintenance requirement (AUMA service)1(211) = "Seal lifetime"
No signal0
Contactor maintenance requirement (AUMA service)1(212) = "Contactor lifetime"
No signal0
The set maintenance interval has expired.1(213) = "Maintenance interNo signal0
Page 31
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
Bit
(process representation)
DescriptionValuePrm-Text-Def GSD fileDesignation
No signal (reserved)——5
No signal (reserved)——6
No signal (reserved)——7
Byte 25: Out of specification 1
Causes of the Out of specification signal in accordance with NAMUR recommendation
NE 107.
Table 20: Byte 25: Out of specification 1
Bit
(process representation)
4
Bit: Torque warn. CLOSE
5
Bit: Torque warn. OPEN
6
Bit: SIL fault
7
Bit: No reaction
The safety function indications via fieldbus are for information only and must not be used as part of a safety function.The I/O signals of
1)
the SIL module must be used for this purpose.
1)
CLOSE"
OPEN"
DescriptionValuePrm-Text-Def GSD fileDesignation
No signal (reserved)——0
No signal (reserved)——1
No signal (reserved)——2
No signal (reserved)——3
Warning: Limit value for Torque warning CLOSE ex-
1(125) = "Bit:Torque wrn
ceeded
No signal0
Warning: Limit v alue for Torque warning OPEN exceeded1(124) = "Bit: Torque wrn
No signal0
Warning: A SIL fault of the SIL sub-assembly has oc-
1(206) = "SIL fault"
curred.
No signal0
Warning: No actuator reaction to operation commands
1(71) = "Bit: No reaction"
within the set reaction time.
No signal0
Byte 26: Out of specification 2
Table 21: Byte 26: Out of specification 2
Bit
(process representation)
0
Bit: Wrn controls temp
3
Bit: 24 V DC, external
5
Bit: RTC button cell
6
Bit: RTC not set
7
Bit: Config. warning
sTemp"
al"
cell"
ing”
DescriptionValuePrm-Text-Def GSD fileDesignation
Warning:Temperature within controls housing too high1(88) = "Bit:WrnControlNo signal0
No signal (reserved)——1
No signal (reserved)——2
The external 24 V DC voltage supply of the controls has
1(68) = "Bit: 24 V DC, e xtern-
exceeded the power supply limits.
No signal0
No signal (reserved)——4
Warning:The voltage of the RTC button cell is too low.1(126) = "Bit: RTC button
No signal0
The real time clock has not yet been set on the basis of
1(77) = "Bit: RTC not set"
valid values.
No signal0
Warning: Configuration setting is incorrect.
1(108) = “Bit: Config.Warn-
The device can still be operated with restrictions.
No signal0
31
Page 32
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
Byte 27: Out of specification 3
Table 22: Byte 27: Out of specification 3
Bit
(process representation)
0
Bit: Wrn FOC budget
1
Bit: Wrn FO cables
2
Bit: Wrn input AIN 2
3
Bit: Wrn input AIN 1
4
Bit: Internal warning
5
Bit: WrnOnTiStarts
6
Bit: WrnOnTiRunning
7
Bit: Op. time warning
budget”
2"
1"
ing"
ning"
warning"
DescriptionValuePrm-Text-Def GSD fileDesignation
Warning: FO cable system reserve reached (critical or
1(111) = “Bit:Wrn FOC
permissible Rx receive level)
No signal0
Warning:
1(83) = "Bit:Wrn FO loop"
Optical receiving signal (channel 1) incorrect (no or insufficient Rx receive lev el) or RS-485 f ormat error (incorrect
bit(s))
No signal0
Warning: Loss of signal analogue input 21(92) = "Bit:Wrn input AIN
No signal0
Warning: Loss of signal analogue input 11(91) = "Bit:Wrn input AIN
No signal0
Collective signal 15: Internal warning1(70) = "Bit: Internal warnNo internal warning0
Warning: Max. number of motor starts (starts) exceeded1(85) = "Bit:WrnOnTiStarts"
No signal0
Warning: Max. running time/h exceeded1(84) = "Bit:WrnOnTiRunNo signal0
Warning: Max. permissible operating time f or an operation
1(63) = "Bit: Operat. time
(OPEN-CLOSE) exceeded
No signal0
Byte 28: Out of specification 4
Table 23: Byte 28: Out of specification 4
Bit
(process representation)
2
Bit: WrnSetpointPos
3
Bit: PVST required
4
Bit: Wrn FOC connection
5
Bit: Failure behav. act.
6
Bit: PVST abort
7
Bit: PVST error
Pos"
connection"
active"
Byte 29: Function check 1
DescriptionValuePrm-Text-Def GSD fileDesignation
No signal (reserved)——0
No signal (reserved)——1
Warning: Loss of signal of actuator setpoint position1(95) = "Bit:WrnSetpointNo signal0
Warning: A Partial Valve Stroke Test (PVST) should be
1(208) = "PVST required"
performed.
0
Warning: FO cable connection not available.1(127) = "Bit:Wrn FOC
No signal0
The failure behaviour is active.1(30) = "Bit: Failure behav.
No signal0
Partial Valve Stroke Test (PVST) was aborted or could
1(118) = "Bit: PVST abort"
not be started. Remedy: P erf orm RESET or restart PVST.
No signal0
Partial V alv e Stroke Test (PVST) could not be successfully
1(117) = "Bit: PVST fault"
completed.
No signal0
32
Causes of the Function check signal in accordance with NAMUR recommendation
NE 107.
Page 33
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
Table 24: Byte 29: Function check 1
Bit
(process representation)
0
Bit: Local STOP
1
Bit: Sel. sw. not REMOTE
2
Bit: Service active
3
Bit: Handwheel active
4
Bit: EMCY stop active
5
Bit: PVST active
DescriptionValuePrm-Text-Def GSD fileDesignation
Push button STOP of the local controls is operated.1(97) = "Bit: Local Stop"
No signal0
Selector switch is in position Local control (LOCAL) or
1(53) = "Bit: Sel. sw. not
REMOTE""
active"
active"
0 (OFF).
Selector switch is in position Remote control (REMO TE).0
Operation mode Service is active.1(51) = "Bit: Service active"
No signal0
Manual operation is active (handwheel is engaged); op-
1(54) = "Bit: Handwheel
tional signal
No signal0
Operation mode EMERGENCY stop is active (EMER-
1(50) = "Bit: EMCY stop
GENCY stop button has been pressed).
EMERGENCY stop button not pressed (normal operation).0
Partial Valve Stroke Test (PVST) is active.1(116) = "Bit: PVST active"
No signal0
No signal (reserved)——6
No signal (reserved)——7
Byte 30: Function check 2
The contents are reserved for further Function check signals in accordance with
NAMUR recommendation NE 107.
Byte 31: Status fieldbus
Information on the fieldbus status.
Table 25: Byte 31: Status fieldbus
Bit
(process representation)
0
Bit: Channel 1 active
1
Bit: Channel 2 active
2
Bit: Channel 1 DataEx
3
Bit: Channel 2 DataEx
4
Bit: Chan 1 FailState fieldbus
5
Bit: Chan 2 FailState fieldbus
6
Bit: Channel 1 activity
7
Bit: Channel 2 activity
1 active"
2 active"
Ch1”
Ch2”
FailsafeAct.1”
FailsafeAct.2”
BusComm”
BusComm”
DescriptionValuePrm-Text-Def GSD fileDesignation
Channel 1 is the active operation command channel.1(99) = "Fieldbus Channel
No signal0
Channel 2 is the active operation command channel.1(100) = "Fieldbus Channel
No signal0
Channel 1 is in the data exchange state.1(109) = “Bit: Pb DataEx
No signal0
Channel 1 is in the data exchange state (DataEx).1(110) = “Bit: Pb DataEx
No signal0
No valid fieldbus communication via channel 1 (application
1(112) = “Bit: Fieldbus-
does not communicate with the DCS).
No signal0
No valid fieldbus communication via channel 2 (application
1(113) = “Bit: Fieldbus-
does not communicate with the DCS).
No signal0
Fieldbus communication on channel 11(114) = “Bit: Chan1
No signal0
Fieldbus communication on channel 21(115) = “Bit: Chan2
No signal0
Byte 32: SIL indications
Causes of the Maintenance required signal in accordance with NAMUR
recommendation NE 107.
33
Page 34
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
Table 26: Byte 32: SIL indications
Bit
(process representation)
1
Bit: Safe ESD
2
Bit: Safe STOP
3
Bit: SIL fault
4
Bit: SIL function active
The safety function indications via fieldbus are for information only and must not be used as part of a safety function.The I/O signals of
1)
the SIL module must be used for this purpose.
1)
1)
1)
1)
ive"
DescriptionValuePrm-Text-Def GSD fileDesignation
Safe ESD (Emergency Shut Down) saf ety function of the
1(204) = "Safe ESD"
SIL sub-assembly is active.
No signal0
Safe STOP safety function of the SIL sub-assembly is
1(205) = "Safe Stop"
active.
No signal0
Collective signal
1(206) = "SIL fault"
Warning: A SIL fault of the SIL sub-assembly has occurred.
No signal0
A safety function of the SIL sub-assembly is active.1(207) = "SIL function actNo signal0
No signal (reserved)——4
No signal (reserved)——5
No signal (reserved)——6
No signal (reserved)——7
Byte 33 to byte 40: Reserve
The contents are reserved for future extensions.
4.2.Output data (process representation output)
The master (controls) can control the slave (actuator) via the process representation
output.
4.2.1.Process representation output arrangement
InformationTo perform remote operations, the selector switch must be in position Remote
control (REMOTE).
34
Page 35
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
4.2.2.Description of the output data
Byte 1: Commands
Table 27: Byte 1: Commands
Bit
(process representation)
0
Fieldbus OPEN
1
Fieldbus CLOSE
2
Fieldbus SETPOINT
3
Fieldbus RESET
DescriptionValueDesignation
Operation command in direction OPEN1
No command0
Operation command in direction CLOSE1
No command0
Run to setpoint
1
Setpoint is provided via bytes 3 and 4.
In combination with a proces controller, this bit is
used to change-over between process controller
mode and OPEN-CLOSE control.
No command0
Certain indications of the actuator controls can be
1
reset via fieldbus while the selector switch is in position Remote control (REMOTE) via fieldbus (e.g.
PTC tripping device and torque fault).
The function of this bit corresponds to the push button RESET at the local controls.
No command0
No command (reserved)—4
35
Page 36
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
Bits 0, 1, 2 = operation
commands
Bits 4, 5, 6 , 7
Bit
(process representation)
DescriptionValueDesignation
No command (reserved)—5
No command (reserved)—6
No command (reserved)—7
Bits 0 – 2 are used to transmit operation commands to the actuator. Only one of
these bits may be set to 1 at any given time. If several bits are set, no operation is
performed and the following signal is given: Wrong oper. cmd
For operation commands via bit 2 (Fieldbus SETPOINT):
●
Condition: Position transmitter (potentiometer, RWG, EWG or MWG) installed
in the actuator
●
If the setpoint is 0 per mil, the actuators runs to the end position CLOSED; it
runs to the end position OPEN for 1000 per mil.
●
If the limit of 1,000 is exceeded, the actuator completely runs to end position
OPEN.
●
To avoid placing too much strain on the mechanics, the reversing of direction
is delayed.The default setting in the factory for the reversing prevention time
is 300 ms.
Bits 4 through 7 are not used and must be set to 0.
Byte 2: Reserved 1
The contents are reserved for future extensions.
Bytes 3 and 4: Setpoint position /(process setpoint, option)
Byte 3 = high byte, byte 4 = low byte.
The setpoint position is transmitted via bytes 3 and 4 (value: 0 – 1,000), using the
position controller.
●
The value 1,000 corresponds to the maximum setpoint, i.e. end position OPEN.
●
The value 0 corresponds to the minimum setpoint, i.e. end position CLOSED.
As an alternative, the process setpoint can be transmitted via bytes 3 and 4 (value
0... 1,000), using a process controller (option).Value 1,000 corresponds to the
maximum process setpoint, value 0 to the minimum process setpoint.
Byte 5: Additional commands
Table 28: Byte 5: Additional commands
Bit
(process representation)
0
Fieldb. enable LOCAL
1
Fieldb. enable OPEN
2
Fieldb. enable CLOSE
4
Fieldbus channel 1
5
Fieldbus channel 2
6
Fieldbus EMCY
7
PVST
DescriptionValueDesignation
Actuator operation via local controls enabled1
Actuator operation via local controls disabled0
Enabling operation command in direction OPEN1
Operation command in direction OPEN disabled.0
Enabling operation command in direction CLOSE1
Operation command in direction CLOSE disabled.0
No command (reserved)—3
Initiate change-over to channel 11
No operation command0
Initiate change-over to channel 21
No operation command0
EMERGENCY signal, triggers EMERGENCY beha-
1
viour.
No command0
Start Partial Valve Stroke Test (functional test)1
No operation command0
36
Page 37
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
Byte 6: Intermediate positions
Table 29: Byte 6: Intermediate positions
Bit
(process representation)
0
Fieldb. interm. pos. 1
1
Fieldb. interm. pos. 2
2
Fieldb. interm. pos. 3
3
Fieldb. interm. pos. 4
4
Fieldb. interm. pos. 5
5
Fieldb. interm. pos. 6
6
Fieldb. interm. pos. 7
7
Fieldb. interm. pos. 8
DescriptionValueDesignation
Run to intermediate position 1.1
No command0
Run to intermediate position 2.1
No command0
Run to intermediate position 3.1
No command0
Run to intermediate position 4.1
No command0
Run to intermediate position 5.1
No command0
Run to intermediate position 6.1
No command0
Run to intermediate position 7.1
No command0
Run to intermediate position 8.1
No command0
Bits 0 – 7 allow the direct selection of 8 intermediate positions via fieldbus commands.
Hereby the selected intermediate position is approached directly, without stopping
in another intermediate position.
In this case, the actuator continues running until the selected intermediate position
has been reached. Example: Operation from position 5 to 7 without stopping at
position 6.
For further information, please refer to Manual (Operation and setting) AUMATIC
AC 01.2 Profibus DP.
If the multiport valve function is active (option), the entire byte 6 is used for coding
of multiport valve operation commands. Up to 12 positions can either be approached
selecting the shortest path, in clockwise direction (CW), or in counterclockwise
direction (CCW). Furthermore, the actuator can also be operated without any position
indications in clockwise or counterclockwise direction (CW or CCW).
Table 30: Operation commands via byte 6 for activated multiport valve function
Value
0x01
0x02
0x04
0x08
0x10
0x20
0x40
0x80
0x81
≙ Operation direction/position
Position 1
Position 2
Position 3
Position 4
Position 5
Position 6
Position 7
Position 8
Position 9
Behaviour
Position 1 is approached selecting the shortest
path
Position 2 is approached selecting the shortest
path
Position 3 is approached selecting the shortest
path
Position 4 is approached selecting the shortest
path
Position 5 is approached selecting the shortest
path
Position 6 is approached selecting the shortest
path
Position 7 is approached selecting the shortest
path
Position 8 is approached selecting the shortest
path
Position 9 is approached selecting the shortest
path
37
Page 38
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
Value
0x82
0x83
0x84
0x90
0x91
0x92
0x93
0x94
0x95
0x96
0x97
0x98
0x99
0x9A
0x9B
0x9C
0xA0
0xA1
0xA2
0xA3
0xA4
0xA5
0xA6
0xA7
0xA8
0xA9
0xAA
0xAB
0xAC
≙ Operation direction/position
Position 10
Position 11
Position 12
CW
CW Position 1
CW Position 2
CW Position 3
CW Position 4
CW Position 5
CW Position 6
CW Position 7
CW Position 8
CW Position 9
CW Position 10
CW Position 11
CW Position 12
CCW
CCW Position 1
CCW Position 2
CCW Position 3
CCW Position 4
CCW Position 5
CCW Position 6
CCW Position 7
CCW Position 8
CCW Position 9
CCW Position 10
CCW Position 11
CCW Position 12
Behaviour
Position 10 is approached selecting the shortest
path
Position 11 is approached selecting the shortest
path
Position 12 is approached selecting the shortest
path
Actuator operates in clockwise direction (without
stop at any position)
Position 1 is approached in clockwise direction
(CW).
Position 2 is approached in clockwise direction
(CW).
Position 3 is approached in clockwise direction
(CW).
Position 4 is approached in clockwise direction
(CW).
Position 5 is approached in clockwise direction
(CW).
Position 6 is approached in clockwise direction
(CW).
Position 7 is approached in clockwise direction
(CW).
Position 8 is approached in clockwise direction
(CW).
Position 9 is approached in clockwise direction
(CW).
Position 10 is approached in clockwise direction
(CW).
Position 11 is approached in clockwise direction
(CW).
Position 12 is approached in clockwise direction
(CW).
Actuator operation in counterclockwise direction
(without stop at any position)
Position 1 is approached in counterclockwise direction (CCW).
Position 2 is approached in counterclockwise direction (CCW).
Position 3 is approached in counterclockwise direction (CCW).
Position 4 is approached in counterclockwise direction (CCW).
Position 5 is approached in counterclockwise direction (CCW).
Position 6 is approached in counterclockwise direction (CCW).
Position 7 is approached in counterclockwise direction (CCW).
Position 8 is approached in counterclockwise direction (CCW).
Position 9 is approached in counterclockwise direction (CCW).
Position 10 is approached in counterclockwise direction (CCW).
Position 11 is approached in counterclockwise direction (CCW).
Position 12 is approached in counterclockwise direction (CCW).
38
Page 39
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
Byte 7: Digital outputs 1
The digital outputs Fieldbus DOUT 1 – DOUT 6 of the fieldbus interf ace can be used
as commands for the output contact. For this , the outputs of the output contacts have
to be assigned with the signals Fieldbus DOUT 1 – Fieldbus DOUT 6.
Table 31: Byte 7: Digital outputs 1
Bit
(process representation)
Byte 8: Digital outputs 2
Table 32: Byte 8: Digital outputs 2
Bit
(process representation)
0
Fieldbus DOUT 1
1
Fieldbus DOUT 2
2
Fieldbus DOUT 3
3
Fieldbus DOUT 4
4
Fieldbus DOUT 5
5
Fieldbus DOUT 6
DescriptionValueDesignation
No command (reserved)—0
No command (reserved)—1
No command (reserved)—2
No command (reserved)—3
No command (reserved)—4
No command (reserved)—5
No command (reserved)—6
No command (reserved)—7
DescriptionValueDesignation
Digital output 1 is activated.1
Output is deactivated.0
Digital output 2 is activated.1
Output is deactivated.0
Digital output 3 is activated.1
Output is deactivated.0
Digital output 4 is activated.1
Output is deactivated.0
Digital output 5 is activated.1
Output is deactivated.0
Digital output 6 is activated.1
Output is deactivated.0
No command (reserved)—6
No command (reserved)—7
Bytes 9 and 10: Actual process value
Byte 9 = high byte, byte 10 = low byte.
Byte 9 and byte 10 in combination with a process controller (option) can be used to
transmit the actual process value.
Bytes 11 and 12: Fieldbus output AOUT 1
Byte 11 = high byte, byte 12 = low byte.
Bytes 11 and 12 can be used to send an analogue value to the actuator.
The value is transmitted in per mil (value: 0 – 1,000). 0 – 1000
The outputs "Fieldbus output AOUT 1" and "Fieldbus output AOUT 2) can be used
as output values via the analogue outputs. For this, the outputs of the analogue
outputs have to be assigned with the signals Fieldbus AOUT 1 or Fieldbus AOUT 2.
Bytes 13 and 14: Fieldbus output AOUT 2
Byte 13 = high byte, byte 14 = low byte.
A second analogue value can be sent to the actuator using bytes 13 and 14.
39
Page 40
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
The value is transmitted in per mil (value: 0 – 1,000).
Bytes 15 to 26: Reserve
The contents are reserved for future extensions.
4.3.Profibus DP V1 services
— Option —
Apart from the cyclic DP-V0 process data exchange, the Profibus DP-V1 services
can establish an additional acyclic communication via the fieldbus.
Actuator controls with activated Profibus DP-V1 services grant access to the contents
of the device ID, the operating data, and the most important parameters for setting
and the maintenance information.
Access to the data of all actuators connected by the Profibus DP network is therefore
enabled for preventive maintenance or uniform parameter setting.
Actuator controls support an acyclic DP-V1 connection with controls (DPM1 = master
of class 1) and one acyclic DP-V1 connection with engineering stations (DPM2 =
master of class 2).
The following DP-V1 fault indications are supported:
4.4.Redundancy
Fault ind.
Error
class
CauseError
code
An invalid slot was accessed.211Access.Invalid SlotRead
An invalid index was accessed.011Access.Invalid Index
An invalid slot was accessed.211Access.Invalid SlotWrite
An invalid index was accessed.011Access.Invalid Index
The transmitted data length is invalid.111Access.write length
Invalid parameter value811Access.invalid parameter
No write access permitted611Access.access denied
Slot/index can only be read.110Application write error
Depending on the DCS, either a DTM (Device Type Manager) or an EDD (Electronic
Device Description) is required to integrate device-specific information, data and
parameters, which can be accessed via Profibus DP-V1, into the engineering station.
The availability of the Profibus DP-V1 services is preset in the factory. For a
description of the DP-V1 services, refer to the appendix.
— Option —
To increase the security of the installation, the actuator controls may be equipped
with a redundant Profibus DP interface.
The following redundant operation modes are supported:
1.Redundant behaviour according to AUMA redundancy (A UMA redundancy I or
AUMA redundancy II)
(use of AUMA 0C4F.GSD in combination with the ident. no. of the standard
version:0x0C4F)
2.Redundant behaviour according to Profibus DP-V2 redundancy in accordance
with PNO guideline 2.212 (system redundancy or flying redundancy)
(use of AUMA AUMA 0CBD.GSD in combination with the ident. no. of the
standard version:0x0CBD)
The redundant behaviour is set using the following parameter: Device configuration
> Profibus > Redundancy M0601
4.4.1.Redundant behaviour according to AUMA redundancy
This redundancy type can be selected if the DCS does not support Profibus DP-V2
redundancy according to Profibus DP guideline 2.212 but a redundant structure is
nevertheless required.
40
Page 41
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
The physical structure of the redundant Profibus DP interfaces within the controls is
based on two independent, galvanically isolated Profibus DP interfaces with an
internal RedCom data channel for exchanging the communication status.
AUMA redundancy I
In general, the actuator decides autonomously which of the Profibus DP
communication channels will be the active channel and therefore be ab le to oper ate
the actuator and which channel will be the passive channel only providing f eedback
signals of the actuator.The slave addresses can be individually assigned for
both channels.
Figure 1: Basic structure for AUMA redundancy I
The operation of both communication channels is logically, physically and
chronologically separated.
The communication channel, which first exchanges process data with the controls
(data exchange state), is the active channel, the second channel will automatically
become the passive channel.The actuator can only be controlled via the active
channel.
Controls (DPM1 = master of class 1) can only write and read acyclic data via the
active channel. Engineering stations (DPM2 = master of class 2) can use both
channels to read and write acyclic DP-V1 data (writing the same parameter via both
communication channels simultaneously is, however, not possible).
Byte 31 Fieldbus status is used to signal the following communication states of the
two channels to the DCS:
●
Active or passive channel (Bit: Channel 1 active, Bit: Channel 2 active)
Availab le fieldbus communication (Bit: Channel 1 activity, Bit: Channel 2 activity),
i.e. Profibus Watchdog Status ≠ Baud Search
The DCS may change over the active channel if both channels do not signal a fault
state (neither Global Control Clear nor telegrams with the data length 0) and are in
the DataEx state. Change-over is made during the logical 0–1 change of bits Fieldbuschannel 1 or Fieldbus channel 2 in byte 5 of the output data (process representation
output).
Change-over can be initiated both via the active and the passive channel.
Automatic change-ov er to another channel is perf ormed if either the communication
of the active channel fails or if Fail Safe telegrams (telegrams with the data length
= 0) or Global Control Clear (GC Clear) telegrams are received via the activ e channel.
Changing channels does not result in a loss of data.
If neither of the channels exchange process data with the controls or if both channels
receive Fail Safe telegrams (telegrams with the data length = 0) or Global Control
Clear (GC Clear) telegrams, the set failure behaviour or EMERGENCY behaviour
is started.
41
Page 42
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
AUMA redundancy II
In general, the actuator decides autonomously which of the Profibus DP
communication channels will be the active channel and therefore be ab le to oper ate
the actuator and which channel will be the passive channel only providing f eedback
signals of the actuator. Only one slave address can be assigned for both
channels.
Figure 2: Basic structure for AUMA redundancy II
Response path of the active channel
Response path after change-over
The operation of both communication channels is physically separated, however
they are logically and chronologically synchronised.
The communication channel, which first exchanges process data with the controls
(data exchange state), is the active channel, the second channel will automatically
become the passive channel.The actuator can only be controlled via the active
channel.
Controls (DPM1 = master of class 1) can only write and read acyclic data via the
active channel. Engineering stations (DPM2 = master of class 2) can use both
channels to read and write acyclic DP-V1 data (writing the same parameter via both
communication channels simultaneously is, however, not possible).
Byte 31 Fieldbus status is used to signal the following communication states of the
two channels to the DCS:
●
Active or passive channel (Bit: Channel 1 active, Bit: Channel 2 active)
Availab le fieldbus communication (Bit: Channel 1 activity, Bit: Channel 2 activity),
i.e. Profibus Watchdog Status ≠ Baud Search
The DCS may change-over the active channel if both channels do not signal a fault
state (neither Global control clear nor telegrams with the data length 0) and are in
the DataEx state. Change-over is made during the logical 0–1 change of bits Fieldbuschannel 1 or Fieldbus channel 2 in byte 5 of the output data (process representation
output).
Change-over can be initiated both via the active and the passive channel.
Changing channels does not result in a loss of data.
If neither of the channels exchange process data with the controls or if both channels
receive Fail Safe telegrams (telegrams with the data length = 0) or Global Control
Clear (GC Clear) telegrams, the set failure behaviour or EMERGENCY behaviour
is started.
42
Page 43
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
The special feature of AUMA redundancy II is its absolute, chronologically
synchronised response of the Profibus telegrams via both communication channels
with simultaneous monitoring of the passive channel on the basis of the received
DataEx request telegrams.This redundancy behaviour is imperatively required in
combination with DCS splitting a Profibus Stack to two redundant channels using a
voter.
The Behaviour Tx parameter can be used to influence the transmission of response
telegrams via the passive channel:
Tx active channel
Tx both channels
Response telegrams are only sent via the active channel.
Response telegrams are sent via both channels, the active and the passiv e channel.
4.4.2.Redundant behaviour according to Profibus DP-V2 redundancy (PNO guideline 2.212)
This redundancy type can be selected if the DCS supports Profibus DP-V2
redundancy according to Profibus DP guideline 2.212.
The physical structure of the redundant Profibus DP interfaces within the actuator
corresponds to the structure for AUMA redundancy; two independent, galvanically
isolated Profibus DP interfaces with an internal Redcom data channel for e xchanging
the communication status.
Figure 3: Structure for DP-V2 redundancy according to guideline 2.212
The master generally uses parameter telegrams to determine which Profibus DP
communication channel is the primary channel and which is the backup channel.
The primary channel is used to operate the actuator, the backup channel can also
be used to establish a Profibus DP connection as an option; operation commands
of the backup channel will, however, be ignored by the actuator.
Feedback signals on the communication status of the two Profibus DP interfaces
and on received requests for changing the channels are perf ormed by the extended
diagnostic (Red_Status, 3 bytes); not all DCS support this extended diagnostic
telegram.
Controls (DPM1 = master of class 1) can only write and read acyclic DP-V1 data via
the primary channel. Engineering stations (DPM2 = master of class 2) can use both
channels to read and write acyclic DP-V1 data (writing the same parameter via both
communication channels simultaneously is, however, not possible).
Details for change-over and behaviour are stipulated in PNO guideline 2.212.
If neither of the channels exchange process data with the controls or if both channels
receive Fail Safe telegrams (telegrams with the data length = 0) or Global Control
Clear (GC Clear) telegrams, the set failure behaviour or EMERGENCY behaviour
is started.
The redundant behaviour according to Profibus DP-V2 redundancy requires activation
of the Profibus DP-V2 functions.
43
Page 44
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
4.5.Profibus DP-V2 functions
— Option —
In addition to the cyclic Profibus DP-V0 process data exchange and in addition to
the acyclic Profibus DP-V1 data exchange, the Profibus DP-V2 functions define
further, more comprehensive functions:
●
Isochronous mode
●
Cross traffic between slaves
●
Upload and download
●
Redundancy
●
Time synchronisation with time stamp
The actuator controls AUMATIC AC 01.2 supports the following functions:
●
Redundancy
●
Time synchronisation with time stamp
This means the two functions are only available combined. If only the time
synchronisation with time stamp is exclusively required, the redundant channel can
remain unconnected (connection with Profibus DP master not imperatively required.)
Profibus DP-V2 functions can be activated via the following parameters:Deviceconfiguration > Application functions > Activation > Profibus DP-V2 M0587
4.5.1.Profibus DP-V2 redundancy
The behaviour and the states of a redundant slave are defined in the "Specification
Slave Redundancy 2.212" (also ref er to <Redundant behaviour according to Profibus
DP-V2 redundancy (PNO guideline 2.212)>). A distinction is made betw een a primary
and a backup channel, with different effects on the properties of Profibus DP
communication:
●
Cyclic Profibus DP-V0 communication
-Operation commands of the primary channel are processed and executed
-Feedback signals of the actuator can be sent via both channels.
-Diagnostic feedback signals of the primary channel contain diagnostic
●
Acyclic Profibus DP-V1 services of the controls (DPM1 = master class 1) are
only supported by the primary channel.
●
Acyclic Profibus DP-V1 services of the engineering stations (DPM2 = master
class 2) are only supported by the primary channel.
Furthermore, a distinction is made between two configuration types within the Profibus
DP-V2 redundancy:
●
Flying redundancy (FR)
The slave address of the primary channel is different from the address of the
backup channel (slave address backup = slave address primary + 64, for this
reason the slave address of the primary must be < 62).
●
Only the slave address of the primary channel has to be set.
●
The master never communicates via the backup channel with the slave.
●
System redundancy (SR)
The slave address of the primary channel corresponds to the slave address of
the backup channel.
●
The master can configure both channels and can establish a cyclic DP-V0
connection via both channels.
by the actuator; operation commands b y the backup channel are ignored,
the communication for the backup channel is only used for monitoring.
status data of both the primary and the backup channel.
44
Page 45
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
Figure 4: Configuration type for Profibus DP-V2
Setting the bus address (slave address)
Each channel has its own address. After setting the primary address, the backup
automatically accepts the address of the primary plus a configurable offset (either 0
or 64).
Startup behaviour
The channels automatically change between the startup_primary and startup_waiting
states until the master starts the communication with the actuator. In the
startup_primary state, the actuator waits with the primary slave address for the master
to start the communication.The cycle starts with 2 s, this time is doubled after each
cycle to max. 32 s.
Change over
The actuator does not decide autonomously on change-over.The master detects a
loss of communication of the primary channel and may initiate change-over using a
parameter telegram (parameter command PrmCmd).The former backup channel
becomes the new primary channel.
Parameter command
Apart from the change-over commands, different parameters for the configuration
of the Profibus DP-V2 redundancy are transmitted using the PrmCmd parameter
command.
For Profibus DP-V2, the parameter command is part of the parameter telegram which
is sent to the actuator on startup of the communication.
Table 33: Structure of the PrmCmd parameter command
RemarkBitByte
01234567
Block length (= 0x08)000100001
010000002
Structure type (= 0x02,
PrmCmd parameter
command for DP-V2
redundancy
Slot000000003
SpecifierReservedSequence number4
45
Page 46
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
RemarkBitByte
01234567
Res5
State
Clear
Reserved6
ResMaster
Check
Properties
Start
MSAC1S
Address
Offset64
MSAC1S
Address
Change
Start/ Stop MSAC1S
used
Req_MS0_MS1
used
FunctionResPrimary RequestStop
PropertiesPrimary
Output Hold Time high7
Output Hold Time low8
Output Hold Time
In the event of change-over, the outputs will not be changed during this time (time
base = 10 ms)
Address Offset64/ Ad-
ress Change
Change-over between flying redundancy and system redundancy
AddressOffset64 = 1 and AddressChange = 1, > Flying redundancy is selected
AddressOffset64 = 0 and AddressChange = 1, > System redundancy is selected
Extended diagnostic
For activated Profib us DP-V2 redundancy , the primary channel of the actuator sends
a high priority response telegram; after that, the master reads the e xtended diagnostic
data Red_Status (Status_Type = 0x9F) with the new states.
When transmitting the PrmCmd parameter command via the master, the actuator
responds with Prm_Cmd_Ack (Status_Type = 0x9E).
With Red_Status/ Prm_Cmd_Ack, the actuator signals both the status of the primary
and of the backup channel.
4.5.2.Profibus DP-V2 time-synchronisation with time stamp
Certain events within the actuator can be marked with a time stamp.The event is
sent to the master using an alarm signal; the master then reads the event with time
stamp from the actuator.
46
Page 47
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the data interface
Figure 5:Time synchronisation
To ensure that all events within an installation are recorded in the correct sequence,
all Profibus DP-V2 field devices must have the same time information. For this
purpose, the master cyclically sends the current time to all field devices.
Basic procedure during communication startup
1.During communication startup, a parameter telegram is sent from the master
to the actuator.The parameter telegram contains parameters for configuring
the time stamp and time synchronisation.
2.The master then cyclically sends Time_Event and Clock_Value telegrams to
synchronise the time.
3.The actuator sends the startup data of the time stamp (current state of the signals to be stamped).
Procedure during operation:
1.The actuator detects an event, stamps the time and sends a high priority response telegram (in the DataExchange state).
2.The master reads the alarm information from the actuator using a diagnostic
telegram.
3.The master acknowledges the alarm.
4.The master reads the indicated data record (event with time) from the actuator .
The following events are stamped by the actuator with a resolution of 10 ms
End position CLOSED
End position OPEN
Torque sw. CLOSED
Torque sw. OPEN
Selector sw. REMOTE
Fault
Phase fault
A time stamp is made for any change of state of these signals, for both rising and
falling signal flank.
47
Page 48
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
Configuration of the time stamp
The parameters of the time stamp are part of the AUMA user parameters transmitted
to the actuator during communication startup.
The time stamp is activated via byte 2 of the parameters.
Table 35: Parameters of the time stamp
RemarkBitByte
01234567
Reserved000000001
X00000002
Activate time stamp
0 = deactivated
1 = activated
Res3
FaultPhase
fault
Selector
sw. RE-
Torque
sw. OPEN
MOTE
Torque
sw.
CLOSED
End position
OPEN
End position
CLOSED
Enabling the individual
indications
0 = not active
1 = active
ReservedNot used4
Configuration of the time synchronisation
This parameter block is part of the structured parameterisation transmitted to the
actuator during communication startup.
The information of Clock_Value_Status1 and Clock_Value_Status2 is used for the
transmission of time corrections (C and CV), the synchronisation status (SYF), the
daylight saving time information (ANH and SWT) and the accuracy (CR).
Process alarm
The diagnostic telegram is used to signal to the master that a time-stamped event
has been recorded.The actuator only supports process alarms.
RemarkBitByte
01234567
Block length (= 0x08)000100001
010000002
Restarted5
Buffer Overrun
101100008
Alarm_Type
0x02 = Time Stamped Process Alarm
Slot000000003
Specifier000Sequence number4
Time stamp state
Buffer Overrun = Internal buffer full,
time stamp stopped
Restarted = Time stamp started anew
Index of the data record (value range
100 to 115)
Number of indications within the data
record (value range 1 -17)
Type of data record
Permanently assigned to 0x0D:
Delta_Trigger_Discrete
Read time-stamped data
The data record signalled via a process alarm (slot 0 index 100 to 115) can be read
using the Profibus DP-V1 services once the alarm has been acknowledged.
A data record may contain up to 17 alarms, each data record consists of 14 bytes.
49
Page 50
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profibus DP
Table 39: Alarms
RemarkBitByte
01234567
Type of signal
0x01 = Delta_Trigger_Discrete
0x02 = Time_Trigger_Discrete
0x80 = Start-up data
0x84 = End of time stamp
0x85 = Buffer overrun
0x86 = Channel change-over for redundancy
0x87 = Loss of information for redundancy
Slot000000002
Signal
1 = End position CLOSED
2 = End position OPEN
3 = Torque sw. CLOSED
4 = Torque sw. OPEN
5 = Selector sw. REMOTE
6 = Fault
7 = Phase fault
Status of the indication
Active = 1: Indication active (rising
signal flank)
Active = 0: Indication not active (falling signal flank)
Not used5
Not used6
Time- stampSeconds (231 .. 0) since 1.1.1900 0:00,00
Time-stamped data is only sent via the primary channel. During a channel
change-over , the time-stamped indications are b uff ered and sent to the master after
change-over. In case of a buffer overrun, the startup data is sent.
50
Page 51
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Description of the Profibus DP board
5.Description of the Profibus DP board
The Profibus DP boards is directly located below the local controls.
Figure 6: Profibus DP board
Hazardous voltage!
Risk of electric shock.
→
When connected to the mains, the local controls may only be remov ed by suitably
qualified personnel (electricians).
5.1.Indications (indication and diagnostic LEDs)
Figure 7: Indication and diagnostic LEDs
[BA2] Profibus channel 2 active (green)
[DX1] Data Exchange channel 1 (yellow)
[BA1] Profibus channel 1 active (green)
[CH1] Communication via channels 1/2 (yellow)
[DX2] Data Exchange channel 2 (yellow)
[BA2]
[DX1]
[BA1]
[CH1]
Option for redundancy
Illuminated in green if Profibus channel 2 is active.
If the LED is illuminated in yellow, the Profibus DP interface has entered the ‘Data
Exchange’ state on channel 1. Controlling the actuator by the Profibus DP master
and reading the actuator status can be performed in this state only.
Illuminated in green if Profibus channel 1 is active.
Option for redundancy
ON (illuminated in yellow): Communication via channel 1
51
Page 52
Actuator controls
Description of the Profibus DP board AC 01.2/ACExC 01.2 Profibus DP
OFF: Communication via channel 2
[DX2]
Option for redundancy
If the LED is illuminated in yellow, the Profibus DP interface has entered the ‘Data
Exchange’ state on channel 2. Controlling the actuator by the Profibus DP master
and reading the actuator status can be performed in this state only.
Illuminated in green after Reset phase: 3.3 V voltage supply is ok.
Blinking in green after Reset phase: 5 V voltage supply is ok
Blinking at 1 Hz: PCB test
Blinking at 2 Hz: Application is ok.
Illuminated in red: Communication to logic is faulty.
Not illuminated: Communication with logic is ok.
52
Page 53
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Corrective action
6.Corrective action
6.1.Troubleshooting
In case of problems with Profibus DP communication, the AUMATIC provides
important information with regard to troubleshooting via the display (menu DiagnosticM0022).
The indication and diagnostic LEDs on the Profibus DP board can also be used as
support.
Table 40: Troubleshooting table
Causes and remedies
1
trolled via Profibus DP?
Select menu:
2
Diagnostic M0022
Select menu:
3.
for channel 1:
Profibus DP1 M0240
for channel 2 (option):
Profibus DP2 M0549
Select menu:
4
for channel 1:
DP1 Profibus status
for channel 2 (option):
DP2 Profibus status
Select menu:
5
for channel 1:
DP1 GC clear M0556
for channel 2 (option):
DP2 GC clear
Select menu:
6
for channel 1:
DP1 data length 0
for channel 2 (option):
DP2 data length 0
7
button of the local controls
possible?
No
Data Ex
or LEDs on Profibus DP
board:
[DX1] is illuminated: Channel 1
[DX2] is illuminated: Channel 2
Wait Prm
Wait Cfg
GC Clear active
Data length 0 active
YesOperation via the push
No
No faultYesCan the actuator be con-
→ Continue with 2
→ Continue with 3
→ Continue with 4
Profibus DP communication is ok.
→ Continue with 5
No communication between slave and master
Possible causes and remedies:
●
Parameter data incorrect→ Correct parameter data in master .
●
Parameters not yet sent→ Send parameters
●
Incorrect GSD file was possibly used→ Check GSD file
●
Cable connection may either be interrupted or connected with
the wrong polarity.→ Check cable connection
No communication between slave and master
Possible causes and remedies:
●
Configuration data incorrect → Correct configuration in master.
●
Configuration data not yet sent → Send configuration data.
Slave is in the Fail Safe state.
Possible remedies:
→ Check all other implemented slaves at the Profibus.
→ Deactivate Autoclear function in the master, if required.
→ Send GC OPERATE telegram.
→ Continue with 6GC Clear inactive
Slave is in the Fail Safe state.
Possible remedies:
→ Check all other implemented slaves at the Profibus.
→ Deactivate Autoclear function in the master, if required.
→ Send GC OPERATE telegram.
→ Continue with 7Data length 0 inactive
Possible causes and remedies:
●
Master does not send an operation command.
●
Master sends wrong operation command.
→ Check program of the controls.
Possible causes and remedies:
Faults such as torque fault, thermal fault or internal fault
→ Check logic board, motor control and motor.
→ continue with 8
53
Page 54
Actuator controls
Corrective action AC 01.2/ACExC 01.2 Profibus DP
Causes and remedies
8
board is illuminated in
green.
9
board
is not illuminated
3.3 V power supply is ok.YesLED [RES] on Profibus DP
3.3 V power supply not availableNo
5 V power supply is ok.is blinking in green.LED [DBG] on Profibus DP
5 V power supply not available
Possible causes and remedies:
→ Check power supply of the AUMATIC (check fuses).
→ Check Profibus DP board.
6.2.Diagnostics
V arious Profibus DP interface states can be check ed via the menu Diagnostic M0022.
The <Information on Profibus DP 1> tables shows the men us for the 1st DP interf ace.
In case a second, redundant DP interface is installed, this table ma y be used as well.
In the menu, DP2 is displayed instead of DP1.
Bus address (slave address)
Baud rate
Watchdog status
Baud search
The Profibus DP interface searches a baud rate. If no baud rate
was found:
●
●
●
Baud control
The detected baud rate is monitored.The DP watchdog within
the master is not activated. In this case, the f ailure function is not
available.
DP control
The DP communication is monitored, the DP watchdog within
the master is activated.Therefore, the failure function is also
available.
Profibus status
Wait Prm
Wait Cfg
Data Ex
The Profibus DP interface is waiting for correct parameter data.
The Profibus DP interface is waiting f or correct configuration data.
The Profibus DP interface is currently exchanging data with the
master.
Global Control Clear Status
GC Clear inactive
GC Clear active
The Profibus DP interface has receiv ed the Global Control Clear
telegram and is waiting for the Global Control Oper ate telegram.
In this mode, DP communication works perfectly, however the
actuator cannot be operated via PLC. If the safety function is
activated it will be initiated.
Data length 0 status
Data length 0 inactive
Data length 0 active
The Profibus DP interface receives data telegrams of the length
0. In this mode , DP communication w orks perf ectly, however the
actuator cannot be operated via PLC. If the safety function is
activated it will be initiated.
Global Control Freeze Status
GC Freeze inactive
With Unfreeze Global Control telegram the Freeze state is deactivated again.
GC Freeze active
The Freeze Global Control telegram can be used to freeze the
Profibus DP inputs (feedback signals).
Connect bus cables.
Check bus cables.
Switch on DP master.
54
Page 55
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Corrective action
Value and descriptionIndication in display
DP1 GC sync M059
DP1 config. data M1195
Global Control Sync Status
GC Sync inactive
GC Sync active
Configuration data (number of input and output bytes) set by the master.
With the Unsync Global Control telegram is the Sync state is
deactivated again.
The Sync Global Control telegram can be used to freeze the
Profibus DP outputs (operation commands).
Table 42: Profibus details
Value and descriptionIndication in display
DP-V1 control
DP-V1 active
Channel 1 active
Channel 2 active
Primary
Backup
Profibus ID no.
Redundancy
DP-V1 (SetPrm)
Alarms (SetPrm)
Redundancy (SetPrm)
Behaviour Tx
In this state, the actuator can only be operated by means of the acyclic Profibus DP-V1
services (only possible if there is no cyclic DP-V0 connection available.
At least one acyclic Profibus DP-V1 connection is active.
Profibus interface of channel 1 is used.
Profibus interface of channel 2 is used.
Profibus DP2 (Profibus DP, channel 1)
None
Channel 1
Channel 2
Profibus DP2 (Profibus DP, channel 2)
None
Channel 1
Channel 2
The actuator controls are assigned different ident numbers depending on the function.
0x0C4F
0x0CBD
Redundancy
None
DP-V2 (SR)
DP-V2 (FR)
AUMA redundancy I
AUMA redundancy II
DP-V1 function in the parameter telegram (SetPrm)
Deactivated
Activated
Signalling alarms in the parameter telegram (SetPrm)
Deactivated
Activated
Redundancy function in the parameter telegram (SetPrm)
Deactivated
Activated
Response behaviour (response) for AUMA redundancy II
Tx active channel
Tx both channels
No channel is used as primary channel.
Channel 1 is used as primary channel.
Channel 2 is used as primary channel.
No channel is used as backup channel.
Channel 1 is used as backup channel.
Channel 2 is used as backup channel.
For Profibus DP-V0 and DP-V1
for Profibus DP-V0 and DP-V1 including the DP-V2 functions
Redundancy with time synchronisation, time stamp and alarms.
No redundancy available.
Redundancy activated according to Profibus DP-V2 (SR).
Redundancy activated according to Profibus DP-V2 (FR).
General Profibus DP redundancy (AUMA redundancy I)
AUMA redundancy II
The DP-V1 services were deactivated using the parameters in
the parameter telegram (SetPrm).
The DP-V1 services were activated using the parameters in the
parameter telegram (SetPrm).
The alarms were deactivated using the parameters in the parameter telegram (SetPrm).
The alarms were activated using the parameters in the parameter
telegram (SetPrm).
The redundancy function according to Profibus DP-V2 was deactivated using the parameters in the parameter telegram (SetPrm).
The redundancy function according to Profibus DP-V2 was activated using the parameters in the parameter telegram (SetPrm).
Profibus DP response telegrams are exclusively sent via the
active channel
Profibus DP response telegrams are sent via both channels.
55
Page 56
Actuator controls
Technical data AC 01.2/ACExC 01.2 Profibus DP
7.Technical data
InformationThe following technical data includes standard and optional features. For detailed
information on the customer-specific version, refer to the order-related data sheet.
The technical data sheet can be downloaded from the Internet at www.auma.com
in both German and English (please state the order number).
7.1.Profibus DP interface
Settings/programming the Profibus DP interface
Automatic baud rate recognitionBaud rate setting
face
Configurable process represent-
ation via GSD file
Commands and signals of the Profibus interface
Process representation output
(command signals)
Process representation input
(feedback signals)
Process representation input
(fault signals)
Behaviour on loss of communication
The setting of the Profibus DP address is made via the display of the AUMATICSetting the Profibus DP inter-
For an optimum adaptation to the process control system, the process representation may
be freely configured.
OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY, Interlock OPEN/CLOSE,
Enable LOCAL
●
End position OPEN, CLOSED
●
Actual position value
●
Actual torque value
●
Selector switch in position LOCAL/REMOTE
●
Running indication (directional)
●
Torque switch OPEN, CLOSED
●
Limit switch OPEN, CLOSED
●
Manual operation by handwheel or via local controls
●
2 analogue and 4 digital customer inputs
●
Motor protection tripped
●
Torque switch tripped in mid-travel
●
One phase missing
●
Loss of the analogue customer inputs
1)
The behaviour of the actuator is programmable:
●
Stop in current position
●
Travel to end position OPEN or CLOSED
●
Travel to any intermediate position
Requires magnetic limit and torque transmitter (MWG) in actuator1)
General Profibus DP interface data
Profibus DP according to IEC 61158 and IEC 61784-1Communication protocol
Network topology
●
●
●
Twisted, screened copper cable according to IEC 61158Transmission medium
EIA-485 (RS485)Fieldbus interface
56
Line (bus) structure
When using repeaters, tree structures can also be implemented.
Coupling and uncoupling of devices during operation without affecting other devices is
possible
Page 57
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Technical data
General Profibus DP interface data
Transmission speed/cable
length
Device types
Bus access
Profibus DP ident no.
●
Baud rate and maximum cable length (segment length) without repeater:
between 9.6 and 93.75 kbit/s: 1,200 m
-
for 187.5 kbit/s: 1,000 m
-
for 500 kbit/s: 400 m
-
for 1,500 kbit/s: 200 m
-
●
Baud rate and possible cable length with repeater (total network cable length):
between 9.6 and 93.75 kbit/s: approx. 10 km
-
for 187.5 kbit/s: approx. 10 km
-
for 500 kbit/s: approx. 4 km
-
for 1,500 kbit/s: approx. 2 km
-
●
DP master class 1, e.g. central controllers such as PLC, PC, ...
●
DP master class 2, e.g. programming/configuration tools
●
DP slave, e.g. devices with digital and/or analogue inputs/outputs such as actuators,
sensors
32 devices without repeater, with repeater expandable to 126Number of devices
●
Token-passing between masters and polling for slaves
●
Mono-master or multi-master systems are possible.
Cyclic data exchange, sync mode, freeze mode, fail-safe modeSupported fieldbus functions
0x0C4F: Standard applications with Profibus DP-V0 and DP-V1
0x0CBD: Applications with Profibus DP-V2
57
Page 58
Actuator controls
Appendix AC 01.2/ACExC 01.2 Profibus DP
8.Appendix
8.1.Proposed wiring diagram for external sensors, 2-wire technology
58
Page 59
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Appendix
8.2.Proposed wiring diagram for external sensors, 3-wire technology
59
Page 60
Actuator controls
Appendix AC 01.2/ACExC 01.2 Profibus DP
8.3.Proposed wiring diagram for external sensors, 4-wire technology
60
Page 61
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Appendix
8.4.Parameters
The present appendix contains notes on the parameterization of the actuator controls
via Profibus DP-V1 as a table (with read/write access codes).
Several par ameters (Vie w Objects) are read or written per DP-V1 request.The data
lengths indicated in the tables have to be considered accordingly.
View Objects
View Objects group several parameters enabling easy write access to the grouped
parameters.The bus load is reduced as the parameters do no longer have to be
read out individually.
Explanations to the table:
No.
View Object number (corresponds to Profibus DP-V1 index). Profibus DP-V1 slot is
always 254.
2 : English
3 : Français
4 : Español
5 : Italiano
6 : Pусский
7 : Polski
8 : Português
9 : Türkçe
10 : Magyar
11 : 中国
12 : Nederlands
13 : Čeština
14 : Română
15 : 日本語
16 : Български
17 : Dansk
18 : Ελληνικά
19 : Suomi
20 : 한국어
21 : Svenska
22 : Tiếng Việt
23 : يبرع
24 : Eesti keel
25 : Hrvatski
26 : Lietuvių
27 : Latviešu
28 : Norsk
29 : Slovenčina
30 : Slovenščina
31 : Srpski
32 : ไทย
33 : Bahasa Indonesia
1R/W
1 : DD.MM.YYYY
2 : YYYY-MM-DD
1R/W
1 : 24h
0R/W
1 : xx,x
0R/W
1 : ft-lb
2 : %
0R/W
1 : °F
0R/W
0 : AUMA
1 : NAMUR
Language setting1 : Deutsch
Date format setting0 : MM/DD/YYYY
Time format setting0 : 12h
Number format setting0 : xx.x
Torque unit setting0 : Nm
Temperature unit setting0 :°C
Selection of diagnostic classification to be indicated within the
status area of the display
62
Page 63
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Appendix
Enabling/disabling torque bypass. Torque by-pass' = function
active means that the torque
monitoring is suspended for
each start and this for the time
as defined in the field 'Time
torque by-pass'. Consequently,
unseating is possible without
torque fault tripping.
By-pass duration of torque
monitoring at actuator start
Tripping torque in direction
CLOSE [Nm]
Tripping torque in direction
OPEN [Nm]
64
Page 65
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Appendix
0 : Off (push-to-run op.)
1 : OPEN
2 : CLOSE
3 : OPEN and CLOSE
4 :OPEN & CL w/o STOP
0 : Off (push-to-run op.)
1 : OPEN
2 : CLOSE
3 : OPEN and CLOSE
4 :OPEN & CL w/o STOP
Setting the operation behaviour
(push-to-run opereration or selfretaining) for binary operation
commands (OPEN, STOP,
CLOSE) from remote.
0 : Off
1 : Adaptive I
Min = 2 [0.1 s]5R/W
Max = 600 [0.1 s]
Min = 0 [0.1 %]5R/W
Max = 100 [0.1 %]
Min = 0 [0.1 %]5R/W
Max = 100 [0.1 %]
Min = 0 [0.1 %]5R/W
Max = 50 [0.1 %]
Min = 0 [0.1 %]5R/W
Max = 50 [0.1 %]
Min = 0 [0.1 %]0R/W
Max = 50 [0.1 %]
Min = 950 [0.1 %]1000R/W
Max = 1000 [0.1 %]
Min = 11200R/W
Min = 1800
Min = 1 [0.1 %]10R/W
Max = 100 [0.1 %]
1 : Function active
Min = 0 [0.1 %]1000R/W
Max = 1000 [0.1 %]
Min = 0 [0.1 %]0R/W
Max = 1000 [0.1 %]
Setting the adaptive behaviour
of the positioner
Setting the dead time
Setting dead band OPEN (irrelevant for adaptive behaviour)
Setting dead band CLOSE (irrelevant for adaptive behaviour)
Hysteresis in direction OPEN
(for adaptive positioner only)
Hysteresis in direction CLOSE
(for adaptive positioner only)
Tolerance for the function
"Closing fully" for end position
CLOSED
Tolerance for the function
"Opening fully" for end position
OPEN
Permissible number of starts/h
(only in combination with Adaptive behaviour = Adaptive II)
Setting the outer dead band (irrelevant for adaptive behaviour)
Function Limit positioner range0 :Function not active
Min = 0 [0.1 %]500R/W
Max = 1000 [0.1 %]
Min = 1 [0.1]10R/W
Max = 100 [0.1]
Min = 1 [s]1000R/W
Max = 1000 [s]
Min = 0 [s]0R/W
Max = 100 [s]
Min = 0 [0.1 %]0R/W
Min = 100 [0.1 %]
Min = 100 [0.1 %]1000R/W
Max = 1000 [0.1 %]
Min = 0 [s]0R/W
Max = 100 [s]
0 : I/O interface
1 : Fieldbus interface
0: P controller
1: PI controller
2: PID controller
Internal setpoint 2 for process
controller
Proportional gain Kp
Reset time Ti
Rate time Td
Minimum reaction required of
actual process value within reaction time
Maximum reaction required of
actual process value within reaction time
Reaction time for monitoring
min. or max. reaction of actual
process value
0 : Off
1 : Remote
2 : Local
3 : Remote and local
Min = 10 [0.1 s]50R/W
Max = 1800 [0.1 s]
Min = 10 [0.1 s]50R/W
Max = 1800 [0.1 s]
Min = 1 [0.1 %]1000R/W
Max = 1000 [0.1 %]
Min = 0 [0.1 %]0R/W
Max = 999 [0.1 %]
0 : Off
1 : Remote
2 : Local
3 : Remote and local
Min = 10 [0.1 s]50R/W
Max = 1000 [0.1 s]
Min = 10 [0.1 s]50R/W
Max = 1000 [0.1 s]
Setting the operation mode:
Stepping mode in direction
CLOSE
Setting the on time in direction
CLOSE
Setting the off time in direction
CLOSE
Setting the start of stepping
mode in direction CLOSE
Setting the end of stepping
mode in direction CLOSE
Setting the operation mode:
Stepping mode in direction
OPEN
Min = 10 [0.1 s]50R/W
Max = 1800 [0.1 s]
Min = 10 [0.1 %]10R/W
Max = 100 [0.1 %]
Min = 1 [0.1 s]5R/W
Max = 20 [0.1 s]
With active motion detection the
verification is made whether the
actuator position changes due
to the manual operation within
the detection time dt by the
travel difference dx. Consequently, a mechanical movement can be detected at output
drive (signal: 'Handwheel operation')
Setting the detection time dt
Setting the travel difference dt
Setting the detection time dt
70
Page 71
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Appendix
0 : OPEN
1 : CLOSE
Min = 0 [0.1 %]100R/W
Max = 1000 [0.1 %]
Min = 10 [0.1 s]600R/W
Max = 3000 [0.1 s]
Min = 1 [0.1 s]20R/W
Max = 600 [0.1 s]
Min = 1 [0.1 s]20R/W
Max = 600 [0.1 s]
0 : Function not active
1 : Function active
Min = 00R/W
Max = 65535
Setting the operation mode
PVST: Stroke = stroke-controlled PVST; based on travel
across a defined stroke (stroke
PVST) within a given time
(PVST monitoring time); can be
started in any valve position
(even outside the end position)
End position test = PVST based
on test when leaving the end
position within a defined time
(PVST travel time); Can only be
started from an end position
PVST (Partial Valve Stroke
Test) behaviour
PVST (Partial Valve Stroke
Test) stroke
PVST (Partial Valve Stroke
Test) monitoring time
PVST (Partial Valve Stroke
Test) operating time
Waiting time during PVST prior
to returning to initial position.
When function is active, a message is generated if no PVST
can be executed during reminder period.
Reminder period of PVST function. Generates message if no
PVST was executed during this
reminder period.
Table 66: Local controls
Data length = 22 bytes
enum28-1
enum28-2
enum28-3
enum28-4
enum28-5
Setting values for parameter no.: 28-1/-2/-3/-4/-5
1 : NC
2 : NO
0 : Function not active
1 : Function active
Min = 600 [0.1 s]3000R
Max = 36000 [0.1 s]
Signal behaviour of motor protection (thermal monitoring). Auto:
Automatic thermal fault reset
after cooling down. Reset: requires manual thermal fault reset after colling down via a RESET command.
Setting the direction of rotation0 :Clockwise rotation
Handwheel switch0 : Without
Montitoring the heater in actuator
Monitoring time of heater resp.
of the heating system (warning
"Wrn heater" is issued if a fault
has continuously occurred during this period)
Table 70: MWG
Data length = 44 bytes
U1637-1
U1637-2
U1637-3
U1637-4
U1637-5
U1637-6
U1637-7
U1637-8
U1637-9
U1637-10
U1637-11
U1637-12
U1637-13
U1637-14
Nom. torque CLOSE
Nom. torque OPEN
CLOSE min. angle
CLOSE min. torque
CLOSE max. angle
CLOSE max. torque
OPEN min. angle
OPEN min. torque
OPEN max. angle
OPEN max. torque
Correction CLOSE
Correction OPEN
Hysteresis torque
Dead band torque
Min = 0 [Nm]100R
Max = 65535 [Nm]
Min = 0 [Nm]100R
Max = 65535 [Nm]
Min = 65120R
Max = 125
Min = 20 [%]50R
Max = 80 [%]
Min = 8105R
Max = 122
Min = 80 [%]100R
Max = 125 [%]
Min = 129134R
Max = 189
Min = 20 [%]50R
Max = 80 [%]
Min = 132149R
Max = 247
Min = 80 [%]100R
Max = 125 [%]
Min = 80100R
Max = 120
Min = 80100R
Max = 120
Min = 05R
Max = 20
Min = 22R
Max = 20
Min = 03R
Max = 100
Min = 200R
Max = 20
Min = 0 [Nm]20R
Max = 65535 [Nm]
Min = 0 [Nm]100R
Max = 65535 [Nm]
Min = 0 [Nm]20R
Max = 65535 [Nm]
Min = 0 [Nm]100R
Max = 65535 [Nm]
Hysteresis of limit switching
Adjust zero point for torque
Low limit setting (initial value)
for tripping torque CLOSE
High limit setting (final value) for
tripping torque CLOSE
Low limit setting (initial value)
for tripping torque OPEN
High limit setting (final value) for
tripping torque OPEN
1 : EMCY stop
2 : Off
3 : Service
4 : Local
5 : Interlock
6 : EMERGENCY
7 : Remote
8 : Remote II
9 : Fieldbus
10 : Disabled
Min = 0R
Max = 0xFFFFFFFF
Min = 0R
Max = 1
Min = 0R
Max = 1
Min = 0R
Max = 1
Min = 0R
Max = 1
Min = 0R
Max = 1
Min = 0R
Max = 1
Min = 0R
Max = 1
0 : Off
1 : Adaptive I
Min = 0 [0.1 %]R
Max = 1000 [0.1 %]
Min = 0 [0.1 %]R/W
Max = 1000 [0.1 %]
Min = 0 [0.1 %]R
Max = 1000 [0.1 %]
Min = 0 [0,1 %]R
Max = 1000 [0,1 %]
Min = 0 [0,1 %]R
Max = 1000 [0,1 %]
Setting the adaptive behaviour
of the positioner
Setpoint position
Actual position
Outer dead band
Outer dead b. OPEN
Outer dead b. CLOSE
78
Page 79
Actuator controls
AC 01.2/ACExC 01.2 Profibus DP Appendix
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Number of limit switch CLOSE
trippings throughout the lifetime
Number of limit switch OPEN
trippings throughout the lifetime
Number of torque switch
CLOSE trippings throughout the
lifetime
Number of torque switch OPEN
trippings throughout the lifetime
Total number of all time intervals
throughout the lifetime during
which an on time warning was
indicated.
Max. time span during which an
on time warning was indicated.
Number of AUMATIC system
starts throughout the lifetime
Maximum temperature of controls
Minimum temperature of controls
Maximum temperature of motor
Minimum temperature of motors
Maximum temperature of gearbox
Minimum temperature of gearbox
Maximum temperature of MWG
Minimum temperature of MWG
Table 88: Operational info
Data length = 82 bytes
U3260-1
U3260-2
U3260-3
U3260-4
U3260-5
U3260-6
U3260-7
U3260-8
Motor running time
Motor starts
Thermal fault
Torque fault CLOSE
Torque fault OPEN
Limit trip CLOSED
Limit trip OPEN
Torque trip CLOSE
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = 0 [s]R
Max = 4294967295 [s]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Min = –100 [°C]R
Max = +150 [°C]
Number of torque switch OPEN
trippings
Total number of all time intervals
during which an on time warning
was indicated.
Max. time span during which an
on time warning was indicated.
22 : Collective signal 23
23 : SIL status
24 : Collective signal 25
25 : Collective signal 26
26 : Collective signal 27
27 : Collective signal 28
28 : FOC status
29 : Service 1
30 : Service 2
31 : Service 3
The event filter for Events is
used to define which collective
signals are to be recorded into
the event report. As soon as the
memory is full, the oldest events
are overwritten.
0 : Not available
1 : Available
0 : Not available
1 : Available
0 : Not available
1 : Available
0 : None
1 : Potentiometer
2 : RWG
4 : MWG
0 : None
1 : Potentiometer
2 : RWG
4 : MWG
Version for explosion-proof applications
Version for applications with hydraulic actuators