AuCom CSXI-007, CSXI-015, CSXI-030, CSXI-037, CSXI-045 User Manual

...
CAUTION STATEMENTS
WARNING - ELECTRICAL SHOCK HAZARD CSXi soft starters contain dangerous voltages when connected to mains voltage. Only a qualified electrician should carry out the electrical installation. Improper installation of the motor or the soft starter may cause equipment failure, serious injury or death. Follow this manual and local electrical safety codes.
GROUNDING AND BRANCH CIRCUIT PROTECTION It is the responsibility of the user or person installing the soft starter to provide proper grounding and branch circuit protection according to local electrical safety codes.
SHORT CIRCUIT CSXi soft starters are not short circuit proof. After severe overload or short circuit, the operation of the soft starter should be fully tested by an authorised service agent.
Ce manuel est également disponible en français à partir de www.aucom.com.
Dieses Handbuch ist auch in deutscher Sprache aus www.aucom.com.
Questo manuale è disponibile anche in italiano da www.aucom.com.
Este manual também está disponível em Português no site www.aucom.com.
Este manual también está disponible en español a partir de www.aucom.com.
该手册也可在中国从 www.aucom.com.
1 Caution Statements
© 2012 AuCom Electronics Ltd. All Rights Reserved.
Isolate the soft starter completely from the power supply before attempting any work on the
starter or motor.
Cables to the control inputs must be segregated from mains voltage and motor cabling. Some electronic contactor coils are not suitable for direct switching with PCB mount relays.
Consult the contactor manufacturer/supplier to confirm suitability.
Do not apply incorrect voltages to the control input terminals. Do not connect power factor correction capacitors to the output of CSXi soft starters. If static
power factor correction is employed, it must be connected to the supply side of the soft starter.
The examples and diagrams in this manual are included solely for illustrative purposes. The information contained in this manual is subject to change at any time and without prior notice. In no event will responsibility or liability be accepted for direct, indirect or consequential damages resulting from the use or application of this equipment.
AuCom cannot guarantee the correctness or completeness of the translated information in this document. In case of dispute the master document in English is the Reference Document.
710-02408-00H CSXi Page 1
MECHANICAL INSTALLATION
2.1 Dimensions and Weights
A B C D E F G H
Weight
Model
mm
(inch)
mm
(inch)
mm
(inch)
mm
(inch)
mm
(inch)
mm
(inch)
mm
(inch)
mm
(inch)
kg
(lb)
CSXi-007
CSXi-015
CSXi-018
98
82
201
188
165
55
90.5
23
2.2
CSXi-022
(3.85)
(3.22)
(7.91)
(7.40)
(6.49)
(2.16)
(3.6)
(0.9)
(4.85)
CSXi-030
CSXi-037
CSXi-045
145
124
215
196
193
-
110.5
37
4.0
CSXi-055
(5.70)
(4.88)
(8.46)
(7.71)
(7.59)
(4.4)
(1.5)
(8.81)
CSXi-075
CSXi-090
200
160
240
216
214
-
114.5
51
6.5
CSXi-110
(7.87)
(6.29)
(9.44)
(8.50)
(8.42)
(4.5)
(2.0)
(14.33)
CSXi-007 ~ CSXi-055: Allow 100 mm (3.9 inch) between soft starters. CSXi-075 ~ CSXi-110: Allow 200 mm (7.9 inch) between soft starters.
CSXi-007 ~ CSXi-055: Allow 50 mm (2.0 inch) between the soft starter and solid surfaces. CSXi-075 ~ CSXi-110: Allow 200 mm (7.9 inch) between the soft starter and solid surfaces.
Soft starters may be mounted side by side with no clearance (that is, if mounted without communications modules).
The soft starter may be mounted on its side. Derate the soft starter's rated current by 15%.
2 Mechanical Installation
2.2 Physical Installation
Page 2 CSXi 710-02408-00H
ELECTRICAL INSTALLATION
3.1 Power Terminations
L1/1, L2/3, L3/5, T1/2, T2/4, T3/6
mm2 (AWG)
A1, A2, A3, 01, 02, B4,
B5, 13, 14, 23, 24 mm2
(AWG)
007 - 030
037 - 055
075 - 110
007 - 110
10 42 7.A
10 - 35 (8 - 2)
10 42 8.A
14 (0.55) mm (inch)
25 - 50 (4 ­1/10)
10 42 8.A
14 (0.55) mm (inch)
N.A.
26
(1 .02 )
11
(0 .43 )
Ø 8. 5
(0 .33 )
10429 .A
mm (inch)
0.14 - 1.5 (26 - 16)
10 42 8.A
6 (0.24) mm (inch)
Torx (T20) 3 Nm
2.2 ft-lb
Torx (T20) 4 Nm
2.9 ft-lb
N.A.
N.A.
7 mm 3 Nm
2.2 ft-lb
7 mm 4 Nm
2.9 ft-lb
N.A.
3.5 mm
0.5 Nm max
4.4 in-lb max
WARNING Always apply control voltage before (or with) mains voltage.
CAUTION With 24 VAC/VDC use contacts rated for low voltage and low current (gold flash or similar).
Two-wire
Three-wire
Start/stop. To reset a trip, open then close 02.
Start.
Stop. To reset a trip, open then close 02.
3 Electrical Installation
3.2 Control Voltages
CSXi soft starters can be supplied in either of two control voltage configurations:
CSXi-xxx-xx-C1 .... 110-240 VAC (+ 10% / - 15%) or 380-440 VAC (+ 10% / - 15%)
CSXi-xxx-xx-C2 .... 24 VAC/VDC (± 20%)
3.3 Control Circuits
710-02408-00H CSXi Page 3
ELECTRICAL INSTALLATION
B4
B5
B4
B5
B4
B5
WARNING Isolate the soft starter completely from the power supply before attempting any work on the starter or motor. Control terminals may be at phase voltage potential.
Soft starter installed with a system protection circuit breaker complete with a shunt trip device
Soft starter installed with a system protection circuit breaker and main contactor
M
Motor (three phase)
KM1
Main contactor
13, 14
Main contactor output
23, 24
Programmable output (set to Trip)
6/ T3
4/ T2
2/ T1
5 /L 3
3 /L 2
1 /L 1
13
14
M
23
24
K M 1
6 /T 3
4 /T 2
2 /T 1
5/ L 3
3/ L 2
1/ L 1
1 3
1 4
M
KM 1
K M 1
2 3
2 4
Motor Thermistor
Motor thermistors can be connected directly to the CSXi terminals B4, B5. If motor thermistors are not used, there must be a link between B4, B5 (the CSXi is supplied with a link fitted).
3.4 Outputs
Main Contactor Output
The Main Contactor output (terminals 13, 14) closes as soon as the soft starter receives a start command and remains closed while the soft starter is controlling the motor (until the motor starts a coast to stop, or until the end of a soft stop). The Main Contactor output will also open if the soft starter trips.
The Main Contactor output can be used to directly control a main contactor coil.
Programmable Output
The programmable output relay (terminals 23, 24) can be used to signal either trip or run status. This relay is normally open.
Trip: The relay closes when the CSXi trips. The relay can be used to operate the shunt-trip mechanism of an upstream circuit breaker (in order to isolate the motor branch circuit), or to signal the trip to an automation system or externally. The relay will open when the trip is reset.
Run: The relay operates when the soft start is complete, the bypass relays are closed and full voltage is being applied to the motor. The relay can be used to operate a contactor for power factor correction capacitors, or to signal soft starter run status to an automation system.
3.5 Electrical Schematics
Page 4 CSXi 710-02408-00H
ADJUSTMENTS
03 24 6.D
1
6
4
3
2
5
87
Current Ramp
Current Limit
Motor Trip Class
Motor FLC
Soft Stop Time
Excess Start Time
Auxiliary Relay Function
Phase Sequence Protection
Current Ramp
Select the initial start current (A) and ramp time (B). Current ramp starting extends the time soft starter takes to reach the current limit and is suitable for generator set supplies, loads requiring an extended start time or applications with extreme load variation between starts. The ramp time does not control the time the motor will take to reach full speed.
Current
Time
Current Limit
Select the current limit (C). The current limit is the maximum level of current the soft starter will deliver to the motor during the soft start.
Current
Time
Motor Trip Class
Select the trip class for motor overload protection. The trip class reflects the maximum time (in seconds) that the motor can run at locked rotor current. The Motor Trip Class setting assumes a locked rotor current of 600%.
Setting the motor trip class to "Off" disables motor overload protection.
Motor Full Load Current
Configure the soft starter to match the motor's full load current (FLC). Configure according to the motor's nameplate current. Divide the motor's FLC by the soft starter's maximum current rating (on the soft starter's nameplate label).
4 Adjustments
710-02408-00H CSXi Page 5
ADJUSTMENTS
Soft Stop Time
Select the soft stop ramp time (D). Soft stop extends the time soft starter takes to reduce voltage to zero. The ramp time does not control the time the motor will take to stop completely.
Voltage
Time
Excess Start Time
Configure the soft starter's excess start time protection. Select a time slightly longer than the motor requires for a normal healthy start. The soft starter will trip if the start does not complete within the selected time (E).
Current
Time
Auxiliary Relay Function
Select the function of the soft starter's programmable output (terminals 23, 24). When set to "Run", the relay will operate when the soft start is complete. When set to "Trip", the relay will operate when the soft starter trips.
Time
Phase Sequence Protection
Configure the soft starter's phase sequence protection. Select the allowable phase sequences. A setting of "Fwd" allows forward sequence (positive rotation) only and a setting of "Any" defeats the protection.
NOTE Auxiliary relay function and phase rotation are configured using a shared switch. Set the auxiliary relay function as required, then set phase rotation protection.
Page 6 CSXi 710-02408-00H
TROUBLESHOOTING
LED
Status
Ready
Run
Off
No control power
Motor not running
On
Ready
Motor running at full speed
Flash
Starter tripped
Motor starting or stopping
Ready LED
Description
x 1
Power Circuit: Check mains supply (L1, L2, L3), motor circuit (T1, T2, T3), soft starter SCRs and bypass relays.
x 2
Excess Start Time: Check load, increase Current Limit or adjust Excess Start Time setting.
x 3
Motor Overload: Allow motor to cool, reset soft starter and restart. The soft starter cannot be reset until the motor has cooled.
x 4
Motor Thermistor: Check motor ventilation and thermistor connection B4, B5. Allow motor to cool.
x 5
Phase Imbalance: Check for mains supply or line current imbalance (L1, L2, L3).
x 6
Supply Frequency: Check mains voltage is available and supply frequency is in range.
x 7
Phase Rotation: Check for correct phase rotation.
x 8
Network Communication Failure (between interface and network): Check network connections, settings and configuration.
x 9
Starter Communication Failure (between starter and interface): Remove and refit accessory interface.
x 10
Bypass Overload: Starter rating may be too low for the application.
NOTE Motor overload protection does not protect the soft starter, and does not protect the motor from short circuit.
5 Troubleshooting
5.1 LEDs
5.2 Trip Codes
The Ready LED will flash a different number of times to indicate the cause of the trip.
5.3 Protections
The CSXi includes the following types of protection for the motor and starter:
Excess Start Time Protection
The CSXi will trip on excess start time if the motor does not successfully start within the time selected in the Excess Start Time setting. This may indicate that the load has stalled.
If the soft starter frequently trips on excess start time:
check that the Current Limit setting is high enough for the application check that the Excess Start Time setting is long enough for the application check that the load has not stalled or increased since the soft starter was installed
Motor Overload Protection
The CSXi will trip on motor overload if it calculates that the motor has been running above its operating range for longer than the time selected in the Motor Trip Class setting. Motor Trip Class should be set to match the motor's locked rotor time. If this information is not available from the motor datasheet, use the default setting (Motor Trip Class = 10). Using a higher setting can damage the motor.
710-02408-00H CSXi Page 7
TROUBLESHOOTING
Phase Imbalance Protection
The CSXi will trip on phase imbalance if the highest and lowest currents on the three phases vary by an average of 30% for more than 3 seconds. Phase imbalance protection is not adjustable, and is only active when the average motor current is 50% or more of the programmed motor FLC.
If the soft starter frequently trips on phase imbalance:
check that there is no imbalance on the mains voltage (on the input side of the soft starter) insulation test the motor move all input cables over one position (move L1 cable to L2, move L2 cable to L3, move L3 cable
Supply Frequency Protection
The soft starter will trip on supply frequency if the frequency rises above 72 Hz or falls below 40 Hz for more than five seconds while the soft starter is running. These trip points are not adjustable.
In pre-start, starting and stopping modes the high and low frequency limits both apply with no time delay. A supply frequency trip will also occur if:
all three input phases are lost while the soft starter is running all three input phases fall below 120 VAC at start or while the soft starter is running the line contactor opens while running
Bypass Overload Protection
Bypass overload protection protects the soft starter from severe operating overloads while running. The protection is not adjustable and has two components:
The soft starter will trip if it detects overcurrent at 600% of the programmed motor full load The soft starter models the temperature of the internal bypass relays and will trip if the
If the trip occurs frequently, this indicates that the soft starter has not been selected correctly for the application.
5.4 Reset
to L1) to rule out a cabling fault
current. temperature exceeds the safe operating level.
Trips can be cleared by pressing the Reset button on the soft starter, sending a Reset command from the serial communications network, or by switching the control inputs.
To clear a trip via the control inputs, the soft starter requires a closed to open transition on the stop input (02).
In three-wire control, use the external stop button to momentarily open the stop input (open
A1-02).
In two-wire control, if the soft starter tripped with a start signal present, remove the start signal
(open A1 to 01, 02).
In two wire control, if the CSXi tripped with no start signal present (eg CSXi motor thermistor
The Reset button is located on the front of the unit, above the adjustment switches. The soft starter will trip again immediately if the cause of the trip still exists.
trip), apply then remove the start signal (close then reopen A1 to 01, 02).
Page 8 CSXi 710-02408-00H
ACCESSORIES
6.1 Finger Guard Kit
6 Accessories
Finger guards may be specified for personnel safety and can be used on CSXi soft starter models 075~110. Finger guards (x 6) fit over the soft starter terminals to prevent accidental contact with live terminals. Finger guards provide IP20 protection when used with cable of diameter 22 mm or greater.
6.2 Remote Operator
The Remote Operator can control and monitor the soft starter's performance. Functionality includes:
Operational control (Start, Stop, Reset, Quick Stop) Starter status monitoring (Ready, Starting, Running, Stopping, Tripped) Performance monitoring (motor current, motor temperature) Trip code display 4-20 mA analog output (Motor Current)
6.3 Communication Interfaces
CSXi soft starters support network communication using the Profibus, DeviceNet, Modbus RTU and USB protocols.
6.4 PC Software
WinMaster can be used with AuCom soft starters to provide the following functionality for networks of up to 99 soft starters:
Operational control (Start, Stop, Reset, Quick Stop) Starter status monitoring (Ready, Starting, Running, Stopping, Tripped) Performance monitoring (motor current, motor temperature)
To use WinMaster with the CSXi, the soft starter must be fitted with a USB interface, Modbus Interface or a Remote Operator.
710-02408-00H CSXi Page 9
SPECIFICATIONS
7.1 Model Code
CSX
- -
-
Control voltage C1 = 110-240 VAC & 380-440 VAC C2 = 24 VAC/VDC
Mains voltage V4 = 200 ~ 440 VAC V6 = 200 ~ 575 VAC
Nominal kW rating @400 VAC
30 kW AC53b 4-6-354 37 kW AC53b 4-6-594
Motor protection Blank = Without motor protection i = With motor protection
AC53b 4-6:354
< 1000 metres
AC53b 4-20:340
< 1000 metres
40 °C
50 °C
40 °C
50 °C
CSXi-007
18 A
17 A
17 A
15 A
CSXi-015
34 A
32 A
30 A
28 A
CSXi-018
42 A
40 A
36 A
33 A
CSXi-022
48 A
44 A
40 A
36 A
CSXi-030
60 A
55 A
49 A
45 A
AC53b 4-6:594
< 1000 metres
AC53b 4-20 580
< 1000 metres
40 °C
50 °C
40 °C
50 °C
CSXi-037
75 A
68 A
65 A
59 A
CSXi-045
85 A
78 A
73 A
67 A
CSXi-055
100 A
100 A
96 A
87 A
CSXi-075
140 A
133 A
120 A
110 A
CSXi-090
170 A
157 A
142 A
130 A
CSXi-110
200 A
186 A
165 A
152 A
7 Specifications
7.2 Current Ratings
Page 10 CSXi 710-02408-00H
SPECIFICATIONS
7.3 Semiconductor Fuses
Model
SCR I2T
(A2S)
Ferraz Fuse
European/IEC Style
(North American Style)
Bussmann Fuse
Square Body
(170M)
Bussmann Fuse
British Style (BS88)
CSXi-007
1150
6.6URD30xxxA0063
(A070URD30xxx0063)
170M-1314
63 FE
CSXi-015
8000
6.6URD30xxxA0125
(A070URD30xxx0125)
170M-1317
160 FEE
CSXi-018
10500
6.6URD30xxxA0160
(A070URD30xxx0160)
170M-1318
160 FEE
CSXi-022
15000
6.6URD30xxxA0160
(A070URD30xxx0160)
170M-1318
180 FM
CSXi-030
18000
6.6URD30xxxA0160
(A070URD30xxx0160)
170M-1319
180 FM
CSXi-037
51200
6.6URD30xxxA0250
(A070URD30xxx0250)
170M-1321
250 FM
CSXi-045
80000
6.6URD30xxxA0315
(A070URD30xxx0315)
170M-1321
250 FM
CSXi-055
97000
6.6URD30xxxA0315
(A070URD30xxx0315)
170M-1321
250 FM
CSXi-075
168000
6.6URD31xxxA0450
(A070URD31xxx0450)
170M-1322
500 FMM
CSXi-090
245000
6.6URD31xxxA0450
(A070URD31xxx0450)
170M-3022
500 FMM
CSXi-110
320000
6.6URD31xxxA0450
(A070URD31xxx0450)
170M-3022
500 FMM
Semiconductor fuses can be used with CSXi soft starters to reduce the potential for damage to SCRs from transient overload currents and for Type 2 coordination. CSXi soft starters have been tested to achieve Type 2 coordination with semiconductor fuses. Suitable Bussmann and Ferraz semiconductor fuses are detailed below.
xxx = Blade Type. Contact Ferraz for options.
7.4 General Technical Data
Mains Supply
Mains voltage (L1, L2, L3)
V4 ............................................................................................................. 3 x 200 VAC ~ 440 VAC (+ 10% / - 15%)
V6 ............................................................................................................. 3 x 200 VAC ~ 575 VAC (+ 10% / - 15%)
Mains frequency (at start) ................................................................................................................................. 45 Hz to 66 Hz
Rated insulation voltage ................................................................................................................................................... 600 VAC
Form designation ................................................................................. Bypassed semiconductor motor starter form 1
Control Voltage (A1, A2, A3)
CSXi-xxx-xx-C1 ................................................................................................ ................... 110-240 VAC (+ 10% / - 15%)
................................................................................................................................................. or 380-440 VAC (+ 10% / - 15%)
CSXi-xxx-xx-C2 ................................................................................................ .................................... 24 VAC/VDC (± 20%)
Current consumption (during run) ......................................................................................................................... < 100 mA
Current consumption (inrush)
CSXi-xxx-xx-C1...................................................................................................................................................................... 10 A
CSXi-xxx-xx-C2......................................................................................................................................................................... 2 A
Inputs
Start (terminal 01) ................................................................................................................................................. Normally open
............................................................................................................... 150 k @ 300 VAC and 5.6 k @ 24 VAC/VDC
Stop (terminal 02) ................................................................................................................................................ Normally closed
............................................................................................................... 150 k @ 300 VAC and 5.6 k @ 24 VAC/VDC
710-02408-00H CSXi Page 11
SPECIFICATIONS
Outputs
710-02408-00H
Main contactor relay (terminals 13, 14) ...................................................................................................... Normally open
..................................................................................................................................... 6 A, 30 VDC / 6 A, 250 VAC resistive
Programmable relay (terminals 23, 24) ....................................................................................................... Normally open
..................................................................................................................................... 6 A, 30 VDC / 6 A, 250 VAC resistive
Environmental
Degree of protection CSXi-007 to CSXi-055 ............................................................................................................... IP20
Degree of protection CSXi-075 to CSXi-110 ............................................................................................................... IP00
Operating temperature .............................................................................................................................. - 10 °C to + 60 °C
Storage temperature ......................................................... -25 °C to + 60 °C (to +70 °C for less than 24 hours)
Humidity ....................................................................................................................................... 5% to 95% Relative Humidity
Pollution degree .............................................................................................................................................. Pollution Degree 3
Vibration ........................................................................................................................................ IEC 60068 Test Fc Sinusoidal
................................................................................................................................ 4 Hz to 13.2 Hz: ± 1 mm displacement
........................................................................................................................................................... 13.2 Hz to 200 Hz: ± 0.7 g
EMC Emission
Equipment class (EMC) ................................................................................................................................ ........................ Class A
Conducted radio frequency emission ............................................................ 0.15 MHz to 0.5 MHz: < 90 dB (µV)
............................................................................................................................................ 0.5 MHz to 5 MHz: < 76 dB (µV)
........................................................................................................................................... 5 MHz to 30 MHz: 80-60 dB (µV)
Radiated radio frequency emission ............................................................. 30 MHz to 230 MHz: < 30 dB (µV/m)
............................................................................................................................. 230 MHz to 1000 MHz: < 37 dB (µV/m)
This product has been designed as Class A equipment. Use of this product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods.
EMC Immunity
Electrostatic discharge .................................................................................. 4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field ........................................................ 0.15 MHz to 1000 MHz: 140 dB (µV)
Rated impulse withstand voltage (Fast transients 5/50 ns) ...................... 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption ................................................................... 100 ms (at 40% nominal voltage)
Harmonics and distortion ................................................................................. IEC61000-2-4 (Class 3), EN/IEC61800-3
Short Circuit
Rated short-circuit current CSXi-007 to CSXi-022 ...................................................................................................... 5 kA
Rated short-circuit current CSXi-030 to CSXi-110 ................................................................................................... 10 kA
Heat Dissipation
During Start ........................................................................................................................................................... 3 watts / ampere
During Run ............................................................................................................................................................... 10 watts typical
Approvals
C .......................................................................................................................................................................... IEC 60947-4-2
UL / C-UL ....................................................................................................................................................................................... UL 508
CE ............................................................................................................................................................................ IEC 60947-4-2
CCC ......................................................................................................................................................................................... GB 14048.6
Lloyds ............................................................................................................................................................................ IEC 60947-4-2
Operational Life
CSXi-007~055 ........................................................................................................................................... 1,000,000 operations
CSXi-075~110 .................................................................................................................................................. 30,000 operations
Page 12 CSXi 710-02408-00H
Loading...