Auber Instruments TH220A Instruction Manual

AUBER INSTRUMENTS WWW.AUBERINS.COM
Instruction Manual
TH220A TEMPERATURE AND HUMIDITY CONTROLLER
INSTRUCTION MANUAL
Version 1.3 (May, 2019)
1. Overview
2. Specifications
Temperature Control Range - 40°C ~ 80°C, - 40°F ~ 176°F
0.1°C (between -9.9°C ~ 80°C)
Temperature Resolution
Temperature Accuracy 0.5°C Temperature Control Mode On/Off Control. Heating or Cooling Temperature Control Output 15 A, 120 V or 240 V AC * Humidity Control Range 0 ~ 99.9% RH Humidity Resolution 0.1% RH Humidity Accuracy 4% RH
Humidity Control Mode
Humidity Control Output 15 A, 120 V or 240 V AC * Operating Temperature 0°C ~ 50°C Dimension 91 x 140 x 46 mm Input Power 85 ~242 V AC, 50 Hz / 60 Hz Sensor Cable Length 6 ft (2 m) Power Cable Length 3 ft (1 m)
* Please note: Although both temperature and humidity output can handle up to 15A, the combined total power of the two channels are limited to 15A due to the limitation of input power cord.
3. Front Panel
1°C (between -40°C ~ 10°C)
0.1°F (between -9.9°F ~ 99.9°F) 1°F (between -40°F ~ 10°F,100°F ~176°F)
On/off control. Humidifying or dehumidifying
Figure 1. Front Panel.
Measured temperature window: In normal operating mode, this window shows measured temperature. In parameter setting mode, this window shows parameter name. Measured humidity window: In normal operating mode, this window shows measured humidity. In parameter setting mode, this window shows parameter value. Alarm indicator: When the alarm is muted, the alarm indicator (the small dot on the last digit) will be on.
SET key: Access the program settings and parameter settings. UP key (Unmute): Increase the value. Press down momentarily to unmute the
alarm. DOWN key (Mute): Decrease the value. Press down momentarily to mute the alarm.
Temperature socket: Supply power to heater/cooler. Temperature indicator: Red LED indicator; it is on when the temperature
socket is energized.
Humidity socket: Supply power to the humidifier/dehumidifier. Humidity indicator: Green LED indicator; it is on when the humidity socket is
energized.
4. Getting Started
4.1 Power up the controller and connect the sensor
To power up the controller, simply plug its power plug to a wall outlet. Then connect the 4-pin connector from the humidity sensor to the sensor input port on the bottom of the controller. Please align the notch on the sensor plug with the key on the sensor socket. You can refer to the Section 6 in the manual for details.
4.2 Displayed Information
The top LED window displays the measured temperature, and the bottom LED window displays the relative humidity reading. If sensor is not connected or defective, the controller will show “ERR” in its display window.
There is one LED indicator on each side of the controller to show the output status of each output socket. The red LED on the left is for the temperature­control socket, and the green LED on the right is for the humidity-control socket.
4.3 Decide the Control Mode for Each Output Socket
The temperature-control socket can be set either to drive a heating device or to drive a cooling device. This temperature-control mode is determined by the parameter tCM (tCM), which can be set to “Ht” for heating, or “CL” for cooling.
Similarly, the humidity-control socket can be set either to drive a humidifying device or to drive a dehumidifying device. This humidity-control mode is determined by the parameter hCM (hCM), which can be set to “H” for humidifying, or “DeH” for dehumidifying.
2019.05 P1/5
AUBER INSTRUMENTS WWW.AUBERINS.COM
A
A
A
The user should decide the appropriate configuration for each output socket based on the user’s particular application. Please refer to section 4.5 and second 5 for details.
4.4 Change the Setpoints The setpoint for temperature is TSP (TSP) and the setpoint for humidity is HSP (HSP). To access the setpoints, simply short-press the SET key, and
then the top window will show TSP and the bottom window will show its value. Use UP or DOWN arrow keys to adjust the value, and short-press the SET key again to save the new value and go to the HSP setting. The way to adjust and save the setting is the same as for temperature setpoint. Once you press the SET key again, the controller will return to its normal operation mode. Please see Figure 2 for how to access the setpoints.
Tem p
RH
Normal
Operati ng
Mode
72.0
50.5
SET
Sho rt-pr ess
Tem p
Temp eratur e
75.0
RH
Setp oint
TSP
SET
Sho rt-pr ess
Temp
RH
Humidity
Setp oint
HSP
40.0
SET
Sho rt-pr ess
Figure 2. How to access setpoints.
4.5 Adjust Parameters
Other control parameters are grouped into three sub-menus: temperature (tE), humidity (Hu), and system (SYS)*. To access these parameters, long­press SET key for 3 seconds, the top window will show EDT (EDT). Then use UP or DOWN arrow key to select the sub-menu item (tE, Hu, or SYS) in the bottom window, then press SET key again to confirm the selection. Please see Figure 3 for how to access these parameters. The details for each parameter are explained in section 5.
Norm al Operati ng Mode
72.0
Temp
50.5
RH
Long- press
SET
3 second s
EDT
Temp
SYS
RH
shor t-press
SET
to confirm
Go th rough all pa ramete rs in
system menu
EDT
Temp
TE
RH
shor t-press
SET
to confirm
Go th rough all pa ramete rs in
temper ature m enu
72.0
Temp
50.5
RH
Norm al Operati ng Mode
EDT
Temp
HU
RH
shor t-press
SET
to confirm
Go th rough all pa ramete rs in
humi dity men u
Figure 3. How to access parameter menus.
5. Parameter Settings
All parameters are listed in Table 1. When a parameter is displayed in the top window, its value is displayed in the bottom window. The user can use the UP or DOWN arrow key to adjust the value in the bottom window, then press the SEK key to save the new value and go to the next parameter. If no key is pressed for 10 seconds, the controller will exit to its normal operating mode.
Table 1. Parameters.
Code Description Setting Range
Short-press SET Key
tSP tSP Temp. Setpoint
-40ºF ~ 176ºF 80ºC
-40ºC ~
HSP HSP Humidity Setpoint 0 ~ 99.9% RH 40.0 1
Long-press SEK Key
tE: temperature menu
Edt EDT Edit parameters
Hu: humidity menu
SYS*: system menu
C-F C-F Temp. Unit
tCM tCM Temp. Control Mode
TDF
tdF
toF toF
tAH TAH
tAL TAL
Temp. control settings (tE)
Temp. Control
Differential
Temp. Calibration
Offset Temp. High Limit Alarm
Temp. Low
larm
Limit
C: Celsius
F: Fahrenheit
Ht: heating mode
CL: cooling mode
0 ~ 50.0 3.0 1
-10.0 ~ 10.0 0 2
-40ºF ~ 176ºF 80ºC
-40ºC ~
-40°F ~ 176ºF 80ºC
-40°C ~
Temp. Anti-short
tAS TAS
Cycle Delay (only for
0 ~ 12 min 0 4
cooling)
ON: output energized
OFF: output de-
energized
tSF TSF
Temp. Sensor
Failure Operation
Humidity control settings (Hu)
HCM HCM
HdF HDF
HoF HoF
HAH HAH
HAL HAL
Humidity Control
Mode
Humidity Control
Differential
Humidity Calibration
Offset
Humidity High Limit
larm
Humidity Low Limit
larm
deH: dehumidifying
H: humidifying
0% ~ 50.0%
-10.0% ~ 10.0% 0% 2
0% ~ 99.9%
0% ~ 99.9%
Humidity Anti-short
HAS HAS
Cycle Delay (only for
0 ~ 12 min 0 4
dehumidifying)
HSF HSF
HdM2 HDM
hdt
HdT2
Humidity Sensor
Failure
Operation
Humidity Output
Delay Mode
Humidity Delay
Timer
ON: output energized
OFF: output de-
energized
0, 1, 2 0 8
0 ~ 999 min 5 9
No
Initi
te
al
75.0 1
tE 6
F 7
CL 1
95.0 3
32.0
OFF 5
H 1
3.0 1
%
90.0 %
3
10.0 %
OFF 5
2019-05 P2/5
Loading...
+ 3 hidden pages