Auber Instruments SYL-1512A Instruction Manual

SYL-1512A PID TEMPEARATURE CONTROLLER INSTRUCTION MANUAL
Version 2.2, July. 2007
Auber Instruments, 730 Culworth, Alpharetta, GA 30022
www.auberins.com e-mail: info@auberins.com Tel: 770-569-8420
WARNING
·Wiring precautions
-In order to prevent instrument damage or failure, protect the power line and the input/output lines from high currents by using fuses with appropriate ratings. A very fast blowing fuse (such as an I2t fuse) is needed when the output device is a solid-state relay (SSR). Please check with your fuse supplier for the correct fuse for your SSR.
·Power supply
-Supply power of the specified rating.
-Do not turn on the power until all of the wiring is completed.
-Never use this instrument in the presence of inflammable gases or vapor.
-In order to prevent electric shock or burns, never touch the inside of the instrument.
-Do not attempt to modify this instrument.
·Maintenance
-Only authorized service engineers should replace parts.
-In order to use this instrument continuously and safely, conduct periodic maintenance. Some parts used in this instrument have a limited service life and may deteriorate over time.
Caution
·Only clean the instrument when power is off.
·Please use a soft cloth or tissue to clean up stains on the display.
·Never use sharp & hard objects such as screwdrivers or ball pens to touch the buttons on the panel. =============================================================
1. Features
Compact size, 1/32 DIN that is only 24 x 48 x 75 mm (1x2 x3”)
Supports 10 different types of commonly used temperature sensors, including Pt100 and Cu50 RTDs, TRJBSKEand WRe3-WRe25 thermocouples.
The PID control output can be configured by user for either relay contact or SSR.
The relay contact output can also be configured as the alarm output, or on/off control
Auto-tune function can automatically find the best PID parameters.
Temperature can be displayed in Fahrenheit and Celsius.
Can be used with either DC or AC power source.
Figure 1
2. Specification
Power supply85260VAC or 85~360VDC
Power consumption<2W
Sampling rate4 sample/sec
Accuracy0.2% full scale
1
Display range-19999999
Display resolution1 , 1℉, or 0.1 , 0.1℉ with Pt100 RTD sensor input.
SSR driving output: 10VDC, 40 mA
LED display0.28” red color
Out of range display“EEEE”
Working condition:0~50℃,85%RH
Relay contact rating220VAC @ 3A
Outside dimensions48×24×75mm
Mounting cutout dimension45×22mm
3. Front Panel and Operation
Figure 2
AL- Relay J1 indicator Select next parameter/value increment. Select previous parameter/value decrement Digit shift/Auto tuning Set/Confirm OUT- Output indicator
AT - blinking during auto-tuning process
Parameter Display
4. Parameter Setting
a) Configuration Parameters
Table 1, Configuration Parameter Setting
Code Description Setting
Range
Initial
Setting
Note
Inty Input Type See table 2 K
outy Controlled output
device
012 2 1
Atdu Autotune offset 0200(deg) 10 2 PSb Input offset -100
100(deg)
0
rd Control function 0heating
1Cooling
0
CorF Display Unit 0:℃ 1:℉ 1
End Exit
Note 1.0Relay J1 as alarm output; SSR output disabledCan be used as On/Off control 1:Relay J1 as PID controlled relay contact output. SSR output disabled. 2:Relay J1 as alarm output; SSR PID controlled with 12 V output. Note 2.The autotune offset will shift the SV value down by the the Atdu value during the auto tune
2
Loading...