Auber Instruments JSL-71 Instruction Manual

AUBER INSTRUMENTS WWW.AUBERINS.COM
Instruction Manual
JSL-71 Easy Timer with Dual Settings
Version 1.3 (October, 2016)
1. Overview
This JSL-71 timer can count from 0.01 second to 9999 minutes. Operating function modes include single delay, double delay, and cycle delay. It can count-down or count-up. The timer can be activated automatically when powering up, by front key pad, or via remote switch. Two different time delay settings can be programmed. User can switch the setting with a single key press. Lock function can be activated to prevent any accidental change.
2. Specification
Timer range: 0.01 second to 9999 minutes Timer mode: single delay, double delay, cycle delay Timer trigger: power on, front key pad, or remote switch Timer accuracy: < 1 s/day. Power supply: 90 – 260 V AC or DC. Power consumption: < 2 W Relay output: 7 A @ 240 VAC,10 A @ 120 VAC and 24 VDC Relay life: 100,000 times. Operating temperature: 0 - 60°C. Humidity: 0 - 95% RH Panel cutout: 44.5 x 44.5 mm Outer dimension: 48 x 48 x 85 mm.
3. Front Panel
3
4
5
67 89
Figure 1. Front Panel of JSL-71.
1. RUN indicator: (the red dot at the lower right corner). It turns on when timer starts running; turns off when timer stops.
2. Time unit indicator: turns on when time units are M:S or H:M. Turns off when time unit is M or S.
3. Time range indicator: turns on when the time base is H:M (Hours: Minutes) or M (Minutes). Turns off when the time base is M:S (Minutes : Seconds) or S (Seconds).
4. Timer indicators: T1 for first delay time, T2 for second delay time.
5. OUT indicator: Turns on when relay is on. Turns off when relay is off.
6. SET key. When timer is not running, press it will switch between first delay time setting (T1) and second delay time setting (T2); press and hold it for 3 second will enter the programming mode.
2
1
10
7. Down key / STP key: When timer is not running, press it will lower the time setting value. When timer is running, press it will stop the timer. In the programming mode, press it will go to the next programming value.
8. Up key / PAU key: When timer is not running, press it will increase the time setting value. When timer is running, press and hold it will pause the timer. The timer will continue running after this key is released. In the programming mode, press it will go to the previous programming value.
9. RST key: Reset key. When timer is running, press it will restart the timer. If "RUN" parameter is set to RST, press it will start the timer after powered up.
10. LED digital display. During normal operation as a timer, the top displays the actual time; the bottom displays the set value. In programming mode, the top displays setting parameters; the bottom displays programming value.
4. Terminal Assignment
Figure 2. Terminal assignment of JSL-71.
Terminal functions when timer is running: Pause(PAU), Stop(STP), Reset(RST), Common(COM). Connecting PAU and COM: Timer stops running. Timer will resume running when they are disconnected. Connecting STP and COM: Timer stops running. Connecting RST and COM: Timer stops running and reset. Timer will restart when they are disconnected.
5. How to Set the Timer and Relay Delay Time T1/T2 When timer is not running, press “SET” key to shift between relay delay time
T1 and T2. Simply press up/ down key will increase/decrease the set value of each delay time. (hold up/down key to speed up changing). For how to program the relay delay time in different relay output mode, please see the definition of Func in next section.
6. Programming
Press SET key for 3 seconds to enter programming mode. For each parameter setting, use up/down key to select different programming values. Press SET key to confirm and move on to next parameter. See figure 3 next page for the procedure. For the definition of each programming value, see following section.
2016.10 P1/3
AUBER INSTRUMENTS WWW.AUBERINS.COM
0000
0000
trnG
s
TDIR
dn
OUT
OFD L
RUN
RST
FUN C
SDL
LU.SP
ONON
SE T
SE T
SE T
SE T
SE T
SE T
Process Value Set Value
3s
trnG S
tdir dn
OUT OFDL
RUN rSt
Func SdL
LU.SP ON.ON
Figure 3. Flow chart of programming
Definition of Programming Values
trnG: Timer range. S: 0.01 s ~ 99.99 s; M:S: 1 s ~ 99 m 59 s; M: 1 m ~ 9999 m; H:M: 1 m ~ 99 h 59 m.
tdir: Timing direction. up: Counting up. dn: Counting down.
OUT: Relay output mode. OFDL (off delay): Relay will be on at the start of timer and off when time reach
the set point. ONDL (on delay): Relay will stay off at the start of timer and on when time reach the set.
RUN, Timer starting run mode. PU (power up): Timer starts when powered up. rSt (reset): Timer starts when reset button is pressed and released.
Func, Timer operating function mode sdL (single delay): Relay turns on at the beginning of relay delay time T1/T2
(OFDL); Relay turns on at the end of relay delay time T1/T2 (ONDL). It will not change until the timer is reset or powered off and on again.
Dint (delayed interval): Relay turns on at the end of T1 time delay then off at the end of T2 time delay (OFDL); Relay turns off at the end of T1 time delay then on at the end of T2 time delay (ONDL). There is no repeat. CYCL (cycle): Repeat relay on and off in cycle. Relay turns on at the end of T1 time delay then off at the end of T2 time delay (OFDL); Relay turns off at the end of T1 time delay then on at the end of T2 time delay (ONDL). It will repeat this cycle until power is off.
LU.SP: Key locker for the two key pads in the middle. This parameter determines if the two keys in the middle will be locked for timer value setting or stop/pause function. For applications that repeat the same time setting, user may want the lower and up key to be locked to prevent any accidental change. For some applications, user may want the Stop and Pause function to be deactivated to prevent stopping the timer by accident. LU.SP represents Lower, Up, Stop and Pause function. OF means the function is turned off and ON means the function is turned on. LU.SP set to OF.ON means the lower and up keys are deactivated (turned off), but Stop and Pause keys are still functional (turned on) ON.OF means lower and up keys are functional, but Stop and Pause functions are turned off.
OF.OF means lower and up keys, Stop and Pause functions are all locked up . ON.ON means lower and up keys, Stop and Pause functions are all functional.
*Note: When the Stop and Pause are locked from the front keys, the Stop and Pause function can still be executed from the back terminals.
7. Wiring Example
Please see figure 4 on the next page for the wiring example.
Figure 4. Wiring example of JSL-71.
Power (120 or 240V AC) is sent to terminal 9 and 10. The external reset (RST) and pause (PAU) switch should be momentary type. They are needed only if you want to control the timer remotely. Otherwise, you can use the front keys on the timer. These switches can also be replaced with a control signal from computer or other control devices. The alarm speaker used in this example
is also optional. It is to show how to wire the output. You can substitute it with any output such as a coffee grinder. The output terminals (#6, 7 and 8)
are from a “C form” internal relay. It is a dry switch that does not provide the power by itself. In this case, the alarm is powered by the 120VAC. The external switch connected to the alarm is for disabling the sound if needed.
8. Timing Diagrams
Following diagrams show relay output ON/OFF time under different relay output modes and operating function modes. Please note: 1) “RUN” is set to “rSt” in following examples, powering up to start the timer is not discussed here. 2) Timer starts counting from the moment when reset key/switch is released or input (TTL) signal is from low to high. 3) Timer display stops
2016.10 P2/3
AUBER INSTRUMENTS WWW.AUBERINS.COM
counting as soon as stop key/ switch is pressed (from high to low), but relay output will only be triggered when stop key/switch is released (from low to high).
Power
Relay
output
Reset
Pause
Stop
Power
Relay output
Reset
Pause
Stop
Power
Relay
output
Reset
Pause
Stop
Power
Relay output
Reset
Pause
Stop
Ta+Tb=T1
T2
T1 Ta Tb
C. delay interval (delay on)
Ta+Tb=T1
T1
T2
D. delay interval (delay off)
Ta+Tb=T1
T1 Ta Tb
Ta+Tb=T1
T1
Ta Tb
T2
E. cycle (delay on)
T2 T2
Ta Tb
F. cycle (delay off)
T2
T2
T2
T2
T1
T1
T2
Auber Instruments
5755 North Point Parkway, Suite 99
Alpharetta, GA 30022, USA
www.auberins.com
E-mail: info@auberins.com Tel: 770-569-8420