ATTACK DP STANDARD, ATTACK DP PROFI Instructions For Use Manual

W W W . A T T A C K . S K
WOOD GASIFYING BOILER
ATTACK DP
STANDARD / PROFI
INSTRUCTIONS FOR USE
2
- Assembly, pre-heating and training of the attendance is perfomed by an assembly technician trained by the manufacturer, who also fills in a document on the installation of the boiler.
-During wood gasifying, tar and condensates (acids) are created in the fuel bin. Therefore behind the boiler the mixing appliance regumat must be installed to keep the minimum temperature of return water of 65°C into the boiler.
- Operation temperature of water in the boiler must be of 80-90°C.
- The boiler must not be permanently operated with the output lower than 50%.
- When a circulation pump is used, it must be controlled by a separated thermostat in order to keep the prescribed minimum temperature of return water.
- Ecological operation of the boiler is during nominal output.
- We recommend to install the boiler with storage reservoirs and Regumat which guarantees economy in fuel in 20 to 30% and longer service life of the boiler as well as comfortable attendance.
- If the boiler cannot be attached to the accumulation, we recommend to connect it at least with one equalisation basin with the volume of about 25l for 1 kW of the boiler output.
- During the mode with decreased output (summer mode and water heating) it is necessary to star t burning daily.
- Fuel must be used only dried of 12 - 20% moisture content (with a higher moisture content of fuel the output of boiler decreases and its consumption increases)
- The choice of the right boiler size, that is its heating output, is a very important condition for economic operation and right function of the boiler. The boiler must be chosen so that its nominal output responds to heat loss of the heated object.
The guarantee does not apply for the boiler if:
- it is operated with wood exceeding 20% moisture content or with fuel not prescribed by the manufacturer.
- if a proper mixing appliance Regumat is not installed in the system, which provides for return water the temperature of 65°C.
- a functional thermostatic valve (WATTS STS20) is not installed on the cooling circuit of boiler and connected to the source of cooling water.
This appliance is not suitable for using by those persons (including children), whose physical, mental and sense- disability or the lack of skills obstucts the safe operation, if they are not under restraint, or they were not trained by the responsible person for using the appliance. It is necessary to look after the children to assure, that they will not play with the appliance.
3
Content:
2 Important 3 Content 4 Introduction, general description 5 Technical parameters 6 Dimensions of the boilers 7,8 Control board of ATTACK DP STANDARD, PROFI 9 Purpose of use, technical parameters, operational rules 10 Warning 11 Technical description of DP PROFI 12 Overheating of the boiler, the ways of regulation, displaying faults 13 Maintenance of heating system, prescribed fuel 14 Location of the boiler 15 Chimney, exhaust pipe, connecting boiler to the mains, connection to the heating system 16 Protection of boiler against corrosion 17 Installation and change of the fireproof concrete shaped peaces 18 Variants of connections 19 Variants of connections, variants of protection and boiler durability increase 20 Operation with the accumulation tanks 21 Protection of boiler against overheating 22 Possible faults and the means of their elimination 23 Scheme of dependency of resistance on the temperature of heating water by the thermal probe ( DP PROFI ) 24-27 The schemes ofelectrical connections of ATTACK DP boilers 28 Notes
4
Introduction:
Dear customer,
Thank you for confidence that you showed us by purchasing our product - ATTACK wood
gasifying boiler. We wish you long and reliable operation. Proper attendance of the boiler is one of the conditions for reliable and right operation, so please read this instruction for use carefully. The manual is written in the way to respect the right operation of the boiler in central heating system. The conditions of right boiler operation:
- to choose the right type and output of the boiler
- impeccable putting into operation
- sensitive attendance
- regular technical maintenance
- reliable service
General description:
ATTACK DP wood gasifying boiler is designed for economic and ecological heating of family houses, bungalows, small plants, workshops and similar objects. Specified fuel for ATTACK DP boilers is dry wood, e.g. logs of lengths, depending on the type of boiler. The wood gasifying boiler is the holder of 101 5 certificate.
Description of ATTACK DP brand:
ATTACK DP 25 Standard
35 45 75 95
ATTACK DP 25 Profi 35 45 75 95
Boiler output
Wood gasification boiler
Version type
Boiler output
Wood gasification boiler
Version type
5
Specified min.temperature of returnable water in operation is 65°C. Specified temperature of water during operation in the boiler is 80-90°C.
Technical parameters:
ATTACK, s.r.o. producer reserves the right to change technical parameters and dimensions of boilers without previous warning.
DP25 DP35 DP45 DP75 DP95
25 35 45 75 95
10-25 14-35 18-45 30-75 43-95
1,52 1,74 1,95 3,60 5,60
96 112 128 305 440
235x445 235x445 235x445 292x542 292x542
23 23 23 23 25
250 250 250 250 250
370 405 430 650 800
150 150 150 219 219
1235 1235 1235 1320 1535
690 690 690 750 766
1090 1190 1295 1600 1750
590 690 790 1100 1100
21 21 21 21 21
50 50 60 60 90
85 85 86 86 81
3
230 225 220 262 287
0,019 0,021 0,027 0,045 0,059
65 65 65 65 65
7,75 9,75 11,75 18,7 29,2
550 650 750 1000 1000
3 3 3 3 3
68 78 87 164 250
600 900 1200 1800 2375
230/50
3
1kW = 1m
65-90
10-27
230 / 2
kW
kW
2
m
3
dm
mm
Pa
kPa
kg
mm
mm
mm
mm
IP
W
%
°C
kg/s
dB
-1
kgh
mm
hod.
l
l
V/Hz
°C
°C
V/A
mm
Type of boiler
Boiler output STANDARDversion )
Output range ( PROFIversion)
Heating surface
Feed hopper capacity
Dimensions of feeding opening
Prescribed chimney drought
Max.operating pressure of water
Weight of boiler
Diameter of the flue connection
Boiler height - "A"
Boiler width - "B"
Boiler depth - "C"
The depth of the chamber - "D"
Shield of the electric parts
Electrical input
Boiler efficiency
CO emission class
Flue gas temperature in nominal output
Flow of flue gas in nominal output
Maximum noise level
Prescribed fuel
Average fuel consumption
Max. length of wood logs
Burning time in min. output
Volume of water in the boiler
Range of temperature of heating water
Min.volume of equalisation basin
Connection voltage
Consumption per season
Range of room tempereature ( PROFIversion) Current carrying capacity of boiler regulator contacts (PROFI version)
Dry wood of 15-17 Mj/kg-1 calorific value,water content min. 12% - max. 20% diameter 80-150mm
6
Dimensions of ATTACK DP boilers
Key:
1. Boiler body
2. Upper cover
3. Feeding door
4. Ashtray door
5. Pull rod of the heat up flap
6. Cover of cleaning opening
7. Aftercooling circuit
8. Chimney
9. Suction fan
10. Outlet valve
11. C.H. return connection
12. C.H. flow connection
13. Primary air flap
14. Secondary air flap
15. Regulation door
16. Output regulator
17. Control electronics - PROFI version
18. Pressure gauge
ATTACK DP 25-45
ATTACK DP 75 ATTACK DP 95
DP25-35 DP45-95
G6/4" G2"
G6/4" G2"
Rising pipe - "E"
Return pipe - "F"
7
ATTACK DP 75-95
ATTACK DP 25-45
2 3 51 4 6
Control board – ATTACK DP STANDARD
Wood gasifying boiler "ATTACK DP Standard" is controlled by a boiler and flue gas thermostat.
1 - Reset
2 - Fuse
3 - The main switch
4 - Flue gas thermostat
5 - Boiler thermostat
6 - Thermometer
Description:
1. Reset - protection of the boiler against overheating (in case the temperature is higher than
110°C, the boiler is disconnected from the power net)
2. Fuse - protection of the boiler against short circuit
3. Main switch - switching on of the boiler,switching off if necessary
4. Flue gas thermostat - when the temperature of flue gas drops below the set up value, the fan
is switched off
5. Boiler thermostat - serves for setting up maximum temperature of water in the boiler (after
exceeding set up temperature the fan is switched off and the boiler works with minimum output. After decreasing set up temperature the fan is switched on again and the boiler works with maximum output.
6. Thermometer - indicates the temperature of outlet water from the boiler
7. Pull rod control - serves for opening and closing of fuel cut-off flap
8
1 – Electronic regulator PROFI 2 – Manometer
1 – Main switch 2 – Display indicating boiler temperature and
parameters 3 – Control light of additional thermostat 4 – Button of boiler thermostat 5 – Button of additional thermostat 6 – Button STOP/parameter options/Alarm cancel 7 – Button START/ parameter options 8 – Start button of programming in service menu /
confirmation of settings 9 – Control light of circuiting pump
1 – Connection of mixing valve (12V) 2 – Connection of additional thermostats 3 – Fuse 2A
ATTACK PROFI
The ATTACK PROFI boiler version in comparison to the ATTACK STANDARD version represents higher comfort of attendance, possibility of output regulation and possibility to connect control and regulation elements. Boiler temperature is kept at the level set at by user by means of control of the flue gas ventilator´s rotations. Boiler regulator of the ATTACK PROFI boilers performs permanent measuring of temperature of water in the boiler and indicates it on display. Regulator controls rotations of the flue gas ventilator and the central heating (C.H.) pump adequately to this temperature. To the boiler regulator, the flue gas thermostat is connected, that switches boiler into the mode of the fuel shortage control, when the flue gas temperature decreases under the set temperature. There is also an option to control the gear of the mixing 4-way valve.
Frontal view on electronic regulator
Backward view on electronic regulator
9
Technical description and ways of regulation of the ATTACK PROFI boiler
Boiler temperature is kept at the level set at by user by means of control of the flue gas ventilator´s rotations. Regulator measures temperature of water in boiler, indicates it on display and controls suction fan and circuiting pump. Regulator is equipped with additional flue gas thermostat and terminals to connect its sensor. Adequately to the situation, it is possible to use thermostat to set the flue gas temperature for indication of fuel shortage and boiler stop, or for setting of required temperature in the room. In dependence of the chosen usage, the sensor of the flue gas temperature or the sensor of the room temperature should be connected into terminals for connection of the flue gas thermostat and an adequate mode of regulation should be chosen through parameter setting. From production is thermostat used for setting of flue gas temperature. When it is set up for the first time, producer recommends to set value of the flue gas thermostat in the range of 100-120°C. Temperature is set by button of the additional thermostat in the temperature display mode. When the flue gas temperature decreases, the boiler is switched into the mode of fuel shortage. Design of appliance also enables connection of external contact thermostat into the terminals of the room temperature sensor.
Connection
Before you start appliance by the main switch, connect regulator, ventilator, circuiting pump and connection cords into suitable sockets in the rear part of appliance. Sensor of boiler temperature has to be placed into the boiler case.
WARNING! Before you connect regulator into the mains, check, if it is properly grounded and if the terminal screws are fitted well. ATTENTION! Max. total output of the appliances connected regulator must not exceed 450W. ATTENTION! For extended function of regulator, it is possible to connect the UM-1 Module that enables control of additional boiler or C.H. pump. Connection of additional appliances to modules contacts have to be separated by appropriate relay.
The unused contacts of this module can stay unconnected.
Operation
After start of appliance, all points of display light for a while to check their correct function. After reset, the regulator switches back to the last state before stop or power shortage. Basic operation of appliance is controlled by setting of required boiler temperature set by thermostat, all other functions are performed adequately to parameters programmed in the service mode. In case that the boiler temperature setting is changed by the boiler temperature button, the change is indicated on display for several seconds (e.g. [C 75] ) and this value represents temperature that will the regulator struggling to achieve. This value can be checked in the temperature display mode. In accordance to the type of installation and service settings can be the button of additional thermostat used to set flue gas temperature or room temperature. From production is this button intended to set the flue gas temperature. When the flue gas temperature decreases under the set value, the regulator switches into the mode of fuel shortage control and after the set time period - parameter [Fb30] - is the boiler stopped. This function prevents from eventual discharging of accumulation tank after fuel burn-out in the boiler, when
- after expiration of time set by parameter [Fb30] - ensures boiler operation stop to avoid of inverse heat flow from charged accumulation tank into cold boiler. Change of position of the button of additional thermostat is for few seconds indicated on display, e.g. [100°].
! !
!
10
Actual value of this setting can be also checked in the temperature display mode. If the flue gas temperature is in the operation mode after burning-up lower than the value set by the button of additional thermostat, then the suction fan and the circuiting pump are blocked, which is signalized by flickering of additional thermostat´s control light. In this case it is necessary to decrease the adjusted flue gas temperature value by the button of additional thermostat, until the control light stops to flicker. Consequently it comes to restart of the suction fan and circuiting pup operation.
When the fuel is being burned-down and the flue gas temperature decreases under the value set by flue gas thermostat, the boiler is switched into the fuel shortage control mode and after expiration of the set time – parameter [Fb30] – it comes to automatic boiler stop.
It is necessary to make setting of the boiler stop at flue burn-down adequately to flue gas temperature, when the boiler is started-up and then to check it from time-to-time.
After pressing the START button, ventilator starts to work and the control process begins. Ventilator is stopped by the STOP button. If the regulator is not in the operation mode, temperature of water in the boiler is indicated on display. Example: [70°C] - STOP mode [70°C] - Operation mode [70°C] - Fire keeping in operation mode
Manual start of ventilator
During the boiler operation might the user need to turn the fan on manually (e.g. for suction of gas from boiler before and during fuel load). After pressing and holding of START button for 3 seconds, the ventilator starts. Ventilator will work for period set in service mode or until the STOP button is pressed.
Temperature display mode
To enter into the temperature display mode, press the OK button. Enter into this mode will be indicated by quick flickering of the additional thermostat´s control light. Use buttons < and > to browse in the information displayed to different temperatures. To exit the temperature display mode, select [END] and press the OK button or wait for 1 min.
List of temperatures, which are disposable in the temperature display mode:
Indication Parameter
C 80 Required boiler temperature
C
100
Temperature set by the additional thermostat’s button (flue gas / room)
180° Actual temperature of additional thermostat (flue gas / room)
End Exit from menu of the temperature display
11
Required boiler temperature [C 80] - is temperature that the regulator tries to reach in the operation mode. It is set by direct turning of button of the boiler thermostat and it is indicated by short displaying. Set temperature of the flue gas / room thermostat [100C] - this parameter indicates temperature set by additional flue gas / room thermostat. In accordance to installation of heating and setting of parameter FC (1 or 0) it represents the flue gas temperature (at lower actual temperature, the regulator switches into the fuel shortage mode) or the room temperature. Actual flue gas temperature or room temperature [180°] - this parameter indicates actually measured flue gas temperature or room temperature.
Setting of parameters – service menu
When the OK button is held for longer than 3 seconds, it is switched to the service mode, where you can see and change programmed parameters. Service mode is indicated by flickering of the additional thermostat´s control light. It is possible to browse parameters by the + and - buttons. After selection of the required parameter you can switch into the mode for parameter change by pressing of the OK button - this mode is indicated by flickering of the parameter value. To change the value, use the + and - button. New setting can be confirmed by the OK button. Then it is possible to select next parameter (by + and -). If you wish to close service mode, select [END] by + and - and press OK or wait for 1 minute. Devices finishes service mode and starts to display boiler temperature. First column in the schedule represents display indications and in the next columns are: parameter description, minimum value, maximum permitted value of setting, step of parameter setting during adjustment, production settings to which it is possible to come by selecting of the [Prod] option..
Loading...
+ 28 hidden pages