ATP Electronics A1DP-RI30 Installation & Operation Manual

Installation & Operation
Manual
A1DP-RI30
Please read these instructions
completely before operating
these units.
General Case Information
My Case Serial number is:
General Information
Store Conditions: The Single Door Refrigerators have been designed to operate in an air conditioned environment with a system that can maintain 24 C (75 F) store temperature and 55 percent (maximum) relative humidity (CRMA conditions). Case operation will be adversely affected by exposure to excessively high ambient temperatures and/or humidity.
Case opening: Examine the case fixture carefully for shipping damage.
Apparent Damage: A claim for obvious damage must be noted on the freight bill or express receipt and signed by the carriers agent, otherwise the carrier may refuse the claim.
Concealed Damage: If damage is not apparent until after the equipment is unpacked, retain all packing materials and submit a written request to the carrier for inspection within 15 days of receipt of the equipment .
Contacting Factory: Should you need to contact ATP regarding a specific fixture, be sure to know the case model and serial number. This information is on the serial plate located on the rear upper panel of the case.
Case Dimensions :
Changing the set point:
- To change the set point, press and release the “SET” button. A number will now be flashing on the screen; this number is the set point.
- To change the desired set point, simply press the up or the down arrow until the flashing number reads the desired set point.
- When the desired set point is flashing on the screen there is no need to do anything further. In a few seconds the flashing set point will be replaced with the solid readout of the current case temperature, and the new set point will be stored in the controller’s memory.
- The box will now cycle on and off between the value of the set point and the value of the set point plus the differential. See Section (Changing Settings) for more information.
- Allow up to two hours, depending on product loading and ambient temperatures for the unit to reach the new set point.
Initiating a manual defrost:
- The default settings for the cooler will automatically initiate an off cycle defrost every 12 hours. However, if at any time a one-time manual defrost is desired, simply press and hold the manual defrost button for six seconds. There will be an audible beep and the LED indicator for “defrost” will activate.
- At default settings the defrost will last for 30 minutes. At this point the defrost LED indicator will change from solid to indicate “in defrost” to a blinking indicator to indicate that the unit has just come out of defrost. This blinking will continue for 15 minutes.
Changing Settings:
-Press and hold the “SET” button for five seconds, until the control emits an audible beep release the “SET” button. The display will now show a blinking “E1.” This is the first of the adjustable settings.
- To make a change to any setting, press and release either the up or the down arrow until the desired setting is reached.
- To move to the next setting press and release the “SET” button. If more than ten seconds go by without any buttons being pressed, the control will save all settings, exit the parameter set-up mode, and go back to reading the box temperature.
- To either lock or unlock the parameter set-up mode, press and hold the down arrow while the display is reading box temperature. After ten seconds the control will emit an audible beep and the display will read “ON,” indicating that settings E1 through C1 can be changed, or “OFF,” indicating that E1 through C1 cannot be modified.
Factory Settings : E1 The lowest value the end user can choose as the set point. E2 The highest value the end user can choose as the set point. E3 The differential. With a set point of 2°C and a differential of 4°C, the unit will cool until it
reaches 2°C. At this point, the compressor will then shut off and not come back on until the unit reaches 6°C (2 + 4). The unit will cycle on and off between these two temperatures, maintaining an average box temperature half way between. E4 The compressor start delay is the shortest amount of time between the compressor cycling off and coming back on. It also will delay the compressor from starting when the unit is plugged in. E5 & E6 will offset the temperatures read by the box and evaporator sensors. This setting is rarely used. F1 The maximum amount of time that a defrost can last. A defrost will last for the value set in F1 or until the evaporator sensor reads the value set in F3. F2 The defrost interval controls how often the unit goes into defrost. A setting of six corresponds to every six hours, or four times a day. In addition, the first defrost will start an F2 number of hours after the unit is first plugged in. F3 The defrost termination temperature value will bring the unit out of defrost before the full amount of time set in F1 has been reached if the evaporator sensor ever reaches the value set in F3. F4 The display during defrost. A setting of “00” will show the current box temperature as it rises during a defrost, while a setting of “01” will lock in the last temperature value before the defrost began.
F5, F6, F7, F8 & F9 are advanced settings and are advised not to be changed. C1 The temperature display units. “00” for Celsius, “01” for Fahrenheit.
Parameter Description Setting
E1 Low Set Limit, Celsius, (Fahrenheit)
E2 High Set Limit, Celsius, (Fahrenheit)
E3 Differential, Celsius, (Fahrenheit)
E4 Compressor Star Delay, (Minutes) 3 Min
E5 Case Temperature Offset, Celsius, (Fahrenheit)
F1 Maximum Defrost Duration, (Minutes) 20 Min
F2 Defrost Interval, (Hours) 6 Hours
F3 Defrost Termination, Celsius, (Fahrenheit)
F4 Display During Defrost 0
C1
Temperature Units, 0 = Celsius, (1 = Fahrenheit)
2°C (36F°)
20°C (68F°)
4°C (7F°)
0°
8°C (46F°)
0
Troubleshooting the SF-102 :
If the unit is not cooling:
Is the compressor LED indicator on?
- If the set point is higher than the box temperature, the compressor will not come on.
If the compressor LED indicator is on, but the compressor is not:
- If the box was just plugged in, there will be a compressor start delay (setting E4).
- Check for voltage out of terminal one on the back of the control. The voltage should be 12V DC.
- Check for voltage at the compressor relay. There should be 120V AC to the compressor.
If the compressor LED indicator is on, and there is 120V AC out of the compressor relay:
- Check operation of compressor.
Is the temperature the box sensor reading the true box temperature?
- Ohm out the sensor. The sensor should read 28,000 at 32°F and 10,000 at 77°F.
If the unit is too cold:
Is the compressor LED indicator on?
- If the set point is lower than the current box temperature, the compressor will stay on until it reaches the set point.
If the compressor LED indicator is not on:
- Check for voltage out of terminal one on the back of the control. There should not be voltage if the compressor LED indicator is not lit.
- Check for voltage out of the compressor relay. There should not be voltage out of the relay when the compressor LED is not lit.
Is the temperature the box sensor reading the true box temperature?
- Ohm out the sensor. The sensor should read 28,000 at 32°F and 10,000 at 77°F.
If the unit is building up ice:
Are the defrost settings (F1-F9) set to factory settings?
- Check the settings (see Basic Operation and Changing Settings) and reset to factory values if needed.
If defrost settings are at factory recommendations:
- Verify gasket seals, and product moisture levels.
- If needed, change the frequency or duration of the defrost cycle. Settings F1 - F3 can
TROUBLE SHOOTING
Before calling your serviceman, please make sure these simple checks: If the unit is not operating:
1. Is the cabinet plugged in?
2. Is there a main-power failure?
3. Is there a blown fuse?
If the Fluorescent light is off:
1. Is the fluorescent light tube properly connected to the socket?
2. Dose the fluorescent light need to be changed?
If the cabinet temperature is too warm:
1. Is the thermostat set correctly?
2. Is the cabinet located in direct sunlight?
3. Is the cabinet located in a strong air-flow path?
4. Is the distance between the upper surface of the displayed merchandise and the self directly above it at least 1”?
5. Is the unit away from the wall at least as 4”?
6. Is the air temperature around the cabinet above 75ºF?
Is there water in the door track or water leaking down the inside walls:
1. Is the case level from side to side?
2. Is the case level from front to back?
3. Is the upper drain pan sagging?
Condensate drain is located in the center of the upper pan running down the center channel along the back wall.
Case Cleaning
In order to keep the unit running at peak design efficiency the intake air grill and the condenser coil should be cleaned at least once a month.
To avoid shock hazard, be sure to check all electrical power is turned off before cleaning. Un-plug the electrical cord!
Avoid spraying cleaning solutions directly on surfaces, fans or electrical connections.
Use a mild detergent, warm water and a soft cloth. When necessary, water and baking soda will help remove case odors. Avoid abrasive scouring powders or pads.
1425 Osprey Drive, Ancaster Business Park
Ancaster, Ontario, Canada L9G 4V5
Tel: 905-648-3741 Fax: 905-648-9625
www.atpcanada.ca
Loading...