The information contained in this document is the property of Atop Technologies, Inc. and is supplied for the sole
purpose of operation and maintenance of Atop Technologies, Inc. products. No part of this publication is to be used
for any other purposes, and it is not to be reproduced, copied, disclosed, transmitted, stored in a retrieval system, or
translated into any human or computer language, in any form, by any means, in whole or in part, without the prior
explicit written consent of Atop Technologies, Inc., offenders will be liable for damages. All rights, including rights
created by patent grant or registration of a utility model or design, are reserved.
Disclaimer
We have checked the contents of this manual for agreement with the hardware and software described. Since
deviations cannot be precluded entirely, we cannot guarantee full agreement. However, the data in this manual is
reviewed regularly and any necessary corrections included in subsequent editions. Suggestions for improvement
are welcome. All other product names referenced herein are registered trademarks of their respective companies.
User Manual Version 1.0
SE5001A Serial Device Server
3
Preface
Purpose of the Manual
This manual supports you during the installation and configuring of the SE5001A Ethernet Serial Server only, as well
as it explains some technical options available with the mentioned product. As such, it contains some advanced
network management knowledge, instructions, examples, guidelines and general theories designed to help users
manage this device and its corresponding software; a background in general theory is a must when reading it.
Please refer to the Glossary for technical terms and abbreviations (if any).
Who Should Use This User Manual
This manual is to be used by qualified network personnel or support technicians who are familiar with network
operations; it might be useful for system programmers or network planners as well. This manual also provides
helpful and handy information for first time users. For any related problems please contact your local distributor,
should they be unable to assist you, please redirect your inquiries to www.atop.com.tw or www.atop-tech.com .
Supported Platform
This manual is designed for the SE5001A Ethernet Serial Server and that model only.
Warranty Period
We provide a 5 year limited warranty for SE5001A Ethernet Serial Server.
FCC WARNING
Class A for Serial Device Server (Model SE5001A)
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15
of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment uses, generates and radiates radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference
to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expenses.
A shielded-type power cord is required in order to meet FCC emission limits and also to prevent interference to the
nearby radio and television reception. It is essential that only the supplied power cord be used.
Use only shielded cables to connect other devices to this equipment by RS-232 or RS-485 ports.
Be cautioned that changes or modifications not expressly approved by the party responsible for compliance could
void ones’ authority to operate the equipment.
User Manual Version 1.0
SE5001A Serial Device Server
4
Model Name
Power Interface
Serial Interface
Firmware
SE5001A
TB3
DB9
Serial Device Server
SE5001A-TB
TB3
TB5
Serial Device Server
1 Introduction
The SE5001A Ethernet Serial device server acts as a gateway between Ethernet (TCP/UDP) and
RS-232/RS-422/RS-485 communications. The information transmitted by SE5001A is transparent to both host
computers (Ethernet) and serial devices (RS-232/RS-422/RS-485). Data coming from the Ethernet is sent to the
designated RS-232/RS-422/RS-485 port and data received from RS-232/RS-422/RS-485 port is sent to the
Ethernet transparently allowing bidirectional communication.
In the computer-aided manufacturing or industrial automation areas, SE5001A is used by field devices to directly
connect to an Ethernet network. The user can then use a network application or use Virtual COM software to
simulate a virtual com port in the PC to fetch serial data from SE5001A remotely over Ethernet.
With SE5001A, it is possible to communicate with a remote serial device in the LAN or even in the Internet, which
dramatically increases reach in distance and scalability.
1.1 SE5001A Series Comparison
Note: The Adapter’s DC connector has the following dimensions:
5.5mm inner radius, 2.1mm outer radius, and 9.5mm length
User Manual Version 1.0
SE5001A Serial Device Server
5
Optional Accessories
Name
Part Number
Description
DK-25
30200000000022G
DIN-Rail Kit
ADP-DB9(F)-TB5
59906231G
Female DB9 to Female 3.81mm TB5 Converter
US315-12(US-Y)
50500151120009G
Y-Type (BT1-10V) power adaptor, 100-240VAC input, 1.25A @ 12VDC
output, US plug
USE315-12(EU-Y)
50500151120019G
Y-Type (BT1-10V) power adaptor, 100-240VAC input, 1.25A @ 12VDC
output, EU plug
1.2 Packaging
The package should contain following items:
Atop SE5001A Ethernet Serial device server x 1
5 pins Terminal Block for Serial Connector x 1 (SE5001A-TB only)
3 pins Terminal Block for Power Connector x 1
Product CD containing configuration utility and documents x 1
Wall-mounting screws x 2
Atop Serial device server quick start guide x 1
User Manual Version 1.0
SE5001A Serial Device Server
6
1.3 Application Connectivity
TCP Server Mode:SE5001A can be configured as a TCP server in a TCP/IP Network to listen for an incoming
TCP client connection to a serial device. After the connection is established between the serial device server and
the host computer, data can be transmitted in both directions. This also applies to Virtual COM running in the server
mode.
Figure 1.1 TCP Server Mode
User Manual Version 1.0
SE5001A Serial Device Server
7
TCP Client Mode
SE5001A can be configured as a TCP client in TCP/IP Network to establish a connection with a TCP server in the
host computer. After the connection is established, data can be transmitted between a serial device and a host
computer in both directions. This also applies to Virtual COM running in the client mode.
Figure 1.2 TCP Client Mode
User Manual Version 1.0
SE5001A Serial Device Server
8
UDP Mode
UDP is a faster but connectionless network protocol. It does not guarantee the delivery of network datagrams.
SE5001A can be configured to transfer data using unicast or multicast UDP from the serial device to one or multiple
host computers. Data can be transmitted between serial device and host computer in both directions.
Figure 1.1 UDP Mode
User Manual Version 1.0
SE5001A Serial Device Server
9
Tunneling Mode
In the case that the serial device needs to communicate with each other without a host computer, two SE5001As
can be paired together (pair connection) to communicate over TCP or UDP transparently. The serial device would
be unaware of the change in the communication medium.
Figure 1.1 Tunneling Mode
User Manual Version 1.0
SE5001A Serial Device Server
10
2.1 Panel Layout
2 Getting Started
User Manual Version 1.0
SE5001A Serial Device Server
11
Pin#
RS-232 Full Duplex
2-Wire RS-485 Half Duplex
RS-422/4-Wire RS-485 Full Duplex
1
DCD
N/A
N/A
2
RXD
N/A
TXD+
3
TXD
DATA+
RXD+
4
DTR
N/A
N/A
5
SG (Signal Ground)
SG (Signal Ground)
SG (Signal Ground)
6
DSR
N/A
N/A 7 RTS
DATA-
RXD-
8
CTS
N/A
TXD-
9
N/A
N/A
N/A
Pin#
RS-232
2-Wire RS-485 Half Duplex
RS-422/4-Wire RS-485 Full Duplex
1
RxD
NC
T+
2
CTS
NC
T- 3 TxD
DATA+
R+ 4 RTS
Data-
R- 5 SG (Signal Ground)
SG (Signal Ground)
SG (Signal Ground)
2.2 Pin Assignments
2.2.1 Serial Port
DB9 Pin Assignments
TB5 Pin Assignments
User Manual Version 1.0
SE5001A Serial Device Server
12
Pin Assignment
568A Definition
568B Definition
Pin1
Green-White
Orange-White
Pin2
Green
Orange
Pin3
Orange-White
Green-White
Pin4
Blue
Blue
Pin5
Blue-White
Blue-White
Pin6
Orange
Green
Pin7
Brown-White
Brown-White
Pin8
Brown
Brown
2.2.2 Ethernet Port
1. Category 5 UTP Ethernet cable.
2. RJ45 Connector.
3. RJ45 Pin Assignment
One can choose either 568A or 568B definition. If one wants to make a crossover cable, one should use 568A and
568B definition respectively in each terminal of a UTP cable.
2.2.3 Power Port
Note: Note: Reverse polarity protection is available in SE5001A, so VIN+ and VIN- could be reversed.
User Manual Version 1.0
SE5001A Serial Device Server
13
Message
Description
^===^===^===^===^===^===^... (1sec)
Watchdog problem, return service is required
^^^^^^^^^^^^^^^^^^^^^^^...
Memory problem, return service is required
^==^========^^ (5sec)
Startup OK but AP firmware is disabled
^==^========^^^ (5sec)
Startup OK and AP firmware is enabled
Table 1. Buzzer Message
Name
Color
Status
Description
PWR
Green
On
Device is powered on
Off
Power is not connected
RUN
Green
On
AP firmware is disabled
Blinking
AP firmware is running
Off
Kernel firmware is damaged
LAN
Green
On
Ethernet is connected
Blinking
Data is transmitting
Off
Ethernet is disconnected
COM
(Tx/Rx)
Green
Blinking
Data is transmitting
Off
Data is not transmitting
2.3 Buzzer
“ ^ “: Beep twice
“ = “: Beep off
2.4 LED
User Manual Version 1.0
SE5001A Serial Device Server
Type: TCP Server, Listen port 4660, Filter=0.0.0.0, Virtual COM disabled
SysName of SNMP
name
SysLocation of SNMP
location
SysContact of SNMP
contact
3 Software Setup
SE5001A Ethernet Serial device server is shipped with default settings shown in the following table:
User Manual Version 1.0
SE5001A Serial Device Server
15
3.1 Configuration by Serial Manager
SE5001A could be configured by Serial Manager, for more information, refer to Serial Manager’s manual.
3.2 Configuration by Telnet Utility
You can use a Telnet utility to change configuration settings of SE5001A by following steps:
3.2.1. Login to the System
->Open MS-DOS command prompt window or any other telnet application
->Telnet to SE5001A using command “telnet IP_address”. (For example:”telnet 10.0.50.100” in MS-DOS
command prompt window). After telnet into SE5001A, system will prompt for a password, the default password is
blank. (Figure 3.1)
Figure 3.1 Login to the system
Note: Press the default button of SE5001A to reset the password to the default value.
User Manual Version 1.0
SE5001A Serial Device Server
16
Note
1. If SE5001A does not receive any commands within 1 minute, Telnet connection will terminate automatically.
2. After “0. Exit” is selected; the console will ask the user to save the configurations.
3. Changes to networking parameters will take effect only SE5001A is restarted.
1. After verifying the password, the following terminal screen appears (Figure 3.2).
Figure 3.2 Main menu
->Select “1” from “Input choice and enter (0~4):” to enter “Overview” (Figure 3.3):
Figure 3.3 Overview
This page gives one the general information of SE5001A including IP and MAC address, SNMP information, kernel
and AP version, and connection status of the device.
User Manual Version 1.0
SE5001A Serial Device Server
17
3.2.2. Networking
Select “2” from “Input choice and enter (0~4):” to enter Networking page as following (Figure 3.4):
Figure 3.4 Network settings
Change network settings of the device including IP address, subnet mask, gateway IP address and SNMP
information on this page. Please note that any changes made on this page won’t take effect until the device is
restarted.
Note: Press “ESC” key to return to the previous menu.
User Manual Version 1.0
SE5001A Serial Device Server
18
3.2.3. Change the Password
1. Select “3” from “Input choice and enter (0~4):” the following screen appears. (Figure 3.5)
Figure 3.5 Change the Password
3.2.4. COM1 Setup
Select “4” from “Input choice and enter (0~4):” the following screen appears (Figure 3.6):
Figure 3.6 Com1 setup
This page includes the option to configure different COM1 parameters, including link mode, serial port settings,
serial buffer, packet delimiter, and advanced control commands.
User Manual Version 1.0
SE5001A Serial Device Server
19
Note:
1. IP filtering function is disabled if setting FILTER_IP to “0.0.0.0”.
2. IP filter is disabled by default
3. If IP filter is enabled, only source IP assigned can connect to SE5001A’s COM.
4. If the multi-connection firmware is installed, SE5001A will prompt for “Multi_Port”, meaning multiple
connection
3.2.5. Configure SE5001A as TCP server
Figure 3.7 Link Mode: TCP Server Setup
Type 1(Link Mode) from “Input choice and enter (1~4):” of COM1
Type 1(TCP Server) in the “Input choice(1~5) and enter:”
Input local port in the “Please input local port:”
To Enable IP filter:
Input yin the “Do one want to enable IP filter(y/n)?” to enable IP Filter. Otherwise input n.
Input source IP in the “Please input Filter_IP :”
Double click “Enter” key
Input idle time in “Please input idle time to send TCP alive packet(x*10sec):”(ex. Input 2 to change the
sending TCP keep alive packet period to 20 sec)
User Manual Version 1.0
SE5001A Serial Device Server
20
3.2.6. Configure SE5001A as TCP Client
Figure 3.8 Link Mode: TCP Client Setup
Type 2in the “Input choice(1~5) and enter:“
Input destination IP in the “Please input Destination IP:”
Input destination port in the “Please input Destination port:”
Select TCP connection behavior: 1 for connect always, 2 for connect on serial data
If 2 is selected, console will prompt for additional configurations.
Input idle time to disconnect in the “Please input idle time to disconnect(0sec , 1~255):” (Input 0 to
disable; Input 2 to disconnect TCP connection after 2 seconds of serial Inactivity)
Input error retrying time in “Please input waiting time for error retrying(0 minute,1~255):” (Input 0
to disable; Input 2 to try to connect to a TCP Server every 2 minutes)
Input idle time in “Please input idle time to send TCP alive packet(x*10sec):”(Input 2 to the send TCP
keep alive packet every 20 seconds)
User Manual Version 1.0
SE5001A Serial Device Server
21
3.2.7. Configure SE5001A as UDP
UDP is a connectionless protocol. It is faster than TCP, but does not guarantee packet delivery to the remote
host. Figure 3.9 shows how to setup UDP.
Figure 3.9 Link Mode: UDP Client Setup
Type 3in the “Input choice(1~5) and enter:“
Input SE5001A’s local listening port in the “Please input local port:”
Input remote device’s IP in the “Please input Destination IP:”
Input remote device’s listening port in the “Please input Destination port:”
User Manual Version 1.0
SE5001A Serial Device Server
22
3.2.8. Enable / Disable Virtual COM
Enable or disable Virtual COM on this page. For more information on how to setup Virtual COM on different
operating systems, please refer to chapter Using Virtual COM.
Figure 3.10 Configure Virtual COM
User Manual Version 1.0
SE5001A Serial Device Server
23
3.2.9. Enable / Disable Pair Connection
Enable or disable “Pair Connection” on this page. For more information on how to configure two serial device
servers to work in pair connection, please refer to the pair connection section 3.3.13.
Figure 3.11 Configure Pair Connection
User Manual Version 1.0
SE5001A Serial Device Server
24
3.2.10. COM Port Setting
Type 2from “Input choice and enter (1~4):” of COM1, the following screen appears. It is possible to give the COM
port alias name, set the baud rate and parity, determine number of data bit and stop bit, and the type of flow control
to use here (Figure 3.12).
Figure 3.12 COM Port Settings
User Manual Version 1.0
SE5001A Serial Device Server
25
3.2.11. Emptying Serial Buffer when TCP connection is established
Figure 3.13 Com Port: Enabling Serial Buffer
Type 3from “Input choice and enter (1~4):” of COM1, by default COM port serial buffer is enabled meaning that
once a TCP connection is established, old serial data received from serial device before the connection will be
emptied. If this option is disabled, SE5001A will keep old serial data when the connection is broken (Figure 3.13).
User Manual Version 1.0
SE5001A Serial Device Server
26
3.2.12. Setting Packet Delimiter
Packet delimiter is a way of packaging serial data. It can prevent serial data from being truncated by packing them in
the same Ethernet packet. SE5001A provides two kinds of packet delimiter: Timer and Character. The default timer
is 2 ms (0ms to disable this function). This means that if SE5001A does not receive new serial data within 2ms, it will
send out all the serial data in buffer in one packet over Ethernet. The way to change the delimiter timer is shown in
the following figure (Figure 3.14):
Figure 3.14 Setting packet delimiter timer
Another kind is character delimiter. If the character delimiter is set to 0x0d, this means SE5001A will send out all the
serial data in buffer in one packet over Ethernet only if it reads 0x0d. The following figure shows how to configure
character delimiter:
(Figure 3.15)
Figure 3.15 Setting Packet Delimiter: Character Pattern
User Manual Version 1.0
SE5001A Serial Device Server
27
3.2.13. Accept Control Command from COM port
SE5001A can also accept serial control commands (RFC2217) directly from the COM port. For more details and
information about this function, please contact our Technical Support.
3.2.14. Backup EEPROM to Flash
Select “5” from “Input choice and enter (0~5):” the following screen should appear (Figure 3.16):
Figure 3.16 Backup EEPROM to Flash
Type 1from “Input choice and enter (0~2):” to back up the settings from the EEPROM to the Flash.
SE5001A would then show “EEPROM Backup (Yes)”.
Type 2from “Input choice and enter (0~2):” to erase the settings stored in the Flash. SE5001A would
then show “EEPROM Backup (No)”.
3.3 Configuration Using Web Browser
1. Make sure the PC is located in the same network sub-net as SE5001A
2. Open a web browser, then Enter in the IP address of SE5001A. Default user name is admin and default
password is null (leave it blank).
3. SE5001A’s network, link mode and COM ports settings can be configured in different web pages.
4. Click “Save Configuration” to save settings.
5. Click ”Restart” button in “System” link to make the change effective if necessary.
User Manual Version 1.0
SE5001A Serial Device Server
28
It is also possible to modify various settings through the web server interface. To do so, please follow the steps
below.
3.3.1. Log in to the System
1. After opening the web browser, ex. Microsoft IE, Firefox or any other web browser, enter the IP address of
SE5001A in the URL bar. Example: http://10.0.50.100
2. The following authentication screen should appear. Enter the user name and passwordthen click on “OK / Log in”. The default user name is admin and password is Null (Leave it blank).
Figure 3.17 Login Security Check
3. The following overview page should show (Figure 3.18). Click on the links on the left to go to different
configuration pages, which are “Networking”, “Security”, and “COM”.
Figure 3.18 Overview
User Manual Version 1.0
SE5001A Serial Device Server
29
3.3.2. Networking Setup
Configure IP, SNMP, and alert settings on this page. Please fill in the IP information in the fields under the TCP/IP
header (Figure 3.19). Alternatively, enable DHCP to obtain IP address, gateway and subnet mask from a DHCP
server automatically.
Figure 3.19 IP Information Setup
User Manual Version 1.0
SE5001A Serial Device Server
30
Enable SNMP and Alert Events by checking “Enable” (Figure 3.20). Fill in SNMP information in the fields under the
SNMP header. Enable different Alert Events to send these events to a SNMP Trap Server.
Cold/Warm Start: Triggers when the device is rebooted from the application level or physical level.
Link Down: Triggers when the TCP connection of the designated COM port is closed
Link Up: Triggers when the TCP connection of the designated COM port is established
Authentication Failure: Triggers when the username/password entered in the Telnet console or the WebUI is
incorrect.
After all the settings are entered, please click on the “Save Configuration” button to save the changes. Note that
the settings would become active only after SE5001A is restarted.
Figure 3.20 SNMP Setup
User Manual Version 1.0
SE5001A Serial Device Server
31
3.3.3. Security Setup
Change the login password on this page (Figure 3.21).
Figure 3.21 Security Setup
Please enter the old password in the “Old Password” field and enter the new password in the “New Password” and
the “Verified Password” fields. Then click on the “Save Configuration” to save and apply the new password.
Note: Press the reset button next to the RJ-45 Jack to reset the settings back to the default value.
User Manual Version 1.0
SE5001A Serial Device Server
32
3.3.4. Backup EEPROM to Flash
This backup function could recover settings from the Flash to the EEPROM if the settings in the EEPROM are lost. If
SE5001A detects that there is an EEPROM backup in the flash. It will compare the backup values in the Flash and
EEPROM. If the values do not match, it will write the backup settings in the Flash to the EEPROM. To enable this
function, follow Figure 3.21 in the Security Settings.
Click on Backup EEPROM to back up the settings from the EEPROM to the Flash. SE5001A would then
show Have Backup.
Click on Erase Backup to erase the settings stored in the Flash. SE5001A would then show No Backup.
3.3.5. Link Mode Configuration
SE5001A supports different Link Modes, which are TCP Server, TCP Client, and UDP (Figure 3.22). Under the three
Link Modes, TCP Server can support Virtual COM, Pair Connection, or Reverse Telnet applications. TCP Client can
support Virtual COM or Pair Connection application. If none of the application is enabled, the SE5001A will run in
RAW mode. In the upcoming sections, we will discuss how to setup different Link Modes properly.
Figure 3.22 Link Modes
3.3.6. Link Mode: Configure SE5001A as a TCP Server
SE5001A defaults in TCP Server mode, there are additional connection settings that can be configured (Figure 3.23).
By selecting the TCP Server mode, a TCP Client program should be prepared to connect to SE5001A.
Click on the “COM1” link on the left hand side.
Select TCP Server. TCP Server is the default link mode.
Enter the Local Listening Port. This is the port specified in the TCP Client program connecting to the serial
device server. The default local port is 4660.
IP Filter: Only the designated IP address will be able to access the COM port if this option is enabled. This
option is disabled by default.
TCP Keep-Alive: Specify the interval in the “Idle Time Before Sending TCP Alive Packet” to force
SE5001A to send TCP Keep-Alive packets in the set interval to prevent disconnection from the client. Note
that this field has a multiplier of 10, so the default value 4 means to send Keep-Alive packets every 40
seconds.
TCP Inactivity Timeout: Specify the value in “TCP Inactivity Time Before Disconnect” to force SE5001A
actively close a TCP connection after some specific inactivity time (no packets). The default value is 0,
which means the SE5001A would never actively close an established connection.
User Manual Version 1.0
SE5001A Serial Device Server
33
Scroll to the bottom of the page and click on “Save Configuration” button to save the changes.
Go to the ApplicationConfiguration section starting from 3.3.9 to apply Virtual COM, Pair Connection, or
Reverse Telnet application if applicable. Otherwise go to the COM Configuration (section 3.3.19) for serial
settings directly.
Figure 3.23 TCP Server Setup
Note:
LINK1 is associated with COM1; LINK2 is associated with COM2, and so on.
User Manual Version 1.0
SE5001A Serial Device Server
34
3.3.7. LINK Mode: Configure SE5001A as a TCP Client
By selecting the TCP Client mode, it means that a TCP Server program should be prepared to connect to SE5001A.
Figure 3.24 shows all the settings provided for the TCP Client.
Click on the “COM1” link on the left hand side.
Select TCP Client.
Enter the preferred Destination IP and Port. This should match the IP settings of the TCP Server program.
Connect Rule: Decide how SE5001A should connect to the TCP Server here. If SE5001A should always
keep the connection, select TCP Connect on Power-on. This means SE5001A would connect to the TCP
Server program when SE5001A is powered on. By default, TCP Connect on Any Serial Character is
selected. This means that SE5001A would only connect to the TCP Server program when it receives data
from its serial interface. If TCP Connect on Any Serial Character is selected, there are two additional
options to change, which are Serial Inactivity Time Before Disconnect and Waiting Time Between Re-connect Attempts. Serial Inactivity Time Before Disconnect determines how long SE5001A should
wait before closing a TCP connection if there is no incoming serial data. The default value is 40 seconds.
Waiting Time Between Re-connect Attempts determines the time SE5001A should wait before it tries to
establish a connection with a TCP Server again if it fails to connect to the TCP Server. The default value is 1
minute.
TCP Keep-Alive: Specify the interval in the “Idle Time Before Sending TCP Alive Packet” to force
SE5001A to send TCP Keep-Alive packets in the set interval to prevent disconnection from the client. Note
that this field has a multiplier of 10, so the default value 4 means to send Keep-Alive packets every 40
seconds.
TCP Inactivity Timeout: Specify the value in “TCP Inactivity Time Before Disconnect” to force SE5001A
actively close a TCP connection after some specific inactivity time (no packets). The default value is 0,
which means the SE5001A would never actively close an established connection.
Scroll to the bottom of the page and click on “Save Configuration” button to save the changes.
Go to the ApplicationConfiguration section starting from 3.3.11 to apply Virtual COM, Pair Connection, or
Reverse Telnet application if applicable. Otherwise go to the COM Configuration (section 3.3.19) for serial
settings directly.
User Manual Version 1.0
SE5001A Serial Device Server
35
Figure 3.24 TCP Client Setup
User Manual Version 1.0
SE5001A Serial Device Server
36
3.3.8. Link Mode: Configure SE5001A in UDP
SE5001A also supports connectionless UDP protocol compared to the connection-oriented TCP protocol. Please be
aware that even though UDP provides better efficiency in terms of response time and resource usage, it does not
guarantee data delivery. It is recommended to utilize UDP only with cyclic polling protocols where each request is
repeated and independent, such as Modbus Protocol. Figure 3.25 shows the UDP settings.
Click on the “COM1” link on the left hand side.
Select UDP.
Destination IP and Port: Specify the Begin and End IP here. Four groups of range IPs are allowed. This is
the IP address of the UDP program and the Port it is listening to. Note that the maximum number of UDP
nodes that SE5001A can handle would highly depend on the traffic load. We have tested that SE5001A can handle up to 32 UDP nodes (baud rate 9600 bps, request interval 100ms, and data length 30bytes).
Enter the Local Listening Port. This is the port that SE5001A should listen to. Match this setting in the
UDP program (usually called destination port in the UDP program).
Scroll to the bottom of the page and click on “Save Configuration” button to save the changes.
Go to the section 3.3.16 to apply Pair Connection application if applicable. Otherwise go to the COM
Configuration (section 3.3.19) for serial settings directly.
Figure 3.25 UDP Setup
User Manual Version 1.0
SE5001A Serial Device Server
37
3.3.9. TCP Server Application: Enable Virtual COM
SE5001A will encapsulate control packets on top of the real data when Virtual COM is enabled. This will allow the
Virtual COM port in the Windows/Linux system to access SE5001A’s COM ports. The benefit of using Virtual COM is
that rewriting an existing COM program to read IP packets is unnecessary. In other words, it is possible to use an
ordinary serial (COM) program. The conversion/virtualization of IP to COM is all done in the system driver
transparently. Figure 3.26 shows SE5001A in TCP Server mode with Virtual COM enabled.
Figure 3.26 TCP Server with Virtual COM Enabled
Follow section 3.2.5 to configure SE5001A in TCP Server mode properly.
Check Enable VirtualCOM for Serial/IP to enabled Virtual COM application in SE5001A.
Check Enable VirtualCOM Authentication (Note: An empty password will fail to authenticate) to lock
up Virtual COM access with SE5001A’s login password.
Scroll to the bottom of the page and click on “Save Configuration” button to save the changes.
Configure Virtual COM in the Operating System. For Windows, refer to Using Virtual COM. Remember
SE5001A’s IP address and the Local Listening Port here in order to enter this information in Serial/IP
Virtual COM’s Control Panel later.
User Manual Version 1.0
SE5001A Serial Device Server
38
3.3.10. TCP Server Application: Enable RFC 2217
The underlying protocol of Virtual COM is based on RFC 2217, the Telnet COM Control Option. Therefore, it is
possible to use RFC 2217 with SE5001A in the TCP Server mode. To do so, refer to section 3.3.9 to enable Virtual
COM, so that SE5001A becomes aware of the commands. Note that there is no need to configure Virtual COM on
the Operating System because Virtual COM ports would not be used.
3.3.11. TCP Client Application: Enable Virtual COM
It is also possible to run Virtual COM in TCP Client mode (Figure 3.27). It is usually easier to use Virtual COM in the
Client mode if SE5001A uses dynamic IP (DHCP) because setting a static IP address in Virtual COM’s Control
Panel is not possible.
Follow section 3.2.6 to configure SE5001A in TCP Client mode properly.
Check Enable VirtualCOM for Serial/IP to enabled Virtual COM application in SE5001A.
Scroll to the bottom of the page and click on “Save Configuration” button to save the changes.
Configure Virtual COM in the Operating System. For Windows, refer to Using Virtual COM. Remember
SE5001A’s IP address and the Local Listening Port here in order to enter this information in Serial/IP
Virtual COM’s Control Panel later.
Figure 3.27 TCP Client with Virtual COM Enabled
User Manual Version 1.0
SE5001A Serial Device Server
39
3.3.12. TCP Client Application: Enable RFC 2217
The underlying protocol of Virtual COM is based on RFC 2217, the Telnet COM Control Option. Therefore, it is
possible to use RFC 2217 with SE5001A in the TCP Client mode. To do so, refer to section 3.3.11 to enable Virtual
COM, so that SE5001A becomes aware of the commands. Note that there is no need to configure Virtual COM on
the Operating System because Virtual COM ports would not be used.
3.3.13. TCP Server Application: Configure SE5001A as a Pair Connection Master
Pair Connection is useful when pairing up two serial devices over the Ethernet or when it is impossible to install
Virtual COM in the serial device. Pair connection does require two SE5001As to work in pair, one would be the Pair
Connection Master (0) and the other would be the Pair Connection Slave.
Follow section 3.2.5 to configure SE5001A in TCP Server mode properly.
Check Enable Pair Connection to enabled Pair Connection application in SE5001A.
Scroll to the bottom of the page and click on “Save Configuration” button to save the changes.
Go to the Pair Connection Slave Setup below (section 3.3.14). Remember SE5001A’s IP address and the
Local Listening Port here in order to enter this information in the Pair Connection Slave later.
Figure 3.28 TCP Server with Pair Connection Enabled
User Manual Version 1.0
SE5001A Serial Device Server
40
3.3.14. TCP Client Application: Configure SE5001A as a Pair Connection Slave
A Pair Connection Slave (Figure 3.29) needs to pair up with a Pair Connection Master. Please setup a Pair
Connection Master first before proceeding.
Follow section 3.2.6 to configure SE5001A in TCP Client mode properly.
Check Enable Pair Connection to enabled Pair Connection application in SE5001A.
Scroll to the bottom of the page and click on “Save Configuration” button to save the changes.
Match the Destination IP and Port here with the settings of Pair Connection Master’s IP and Listening
Port setup previously.
Figure 3.29 TCP Client with Pair Connection Enabled
User Manual Version 1.0
SE5001A Serial Device Server
41
3.3.15. TCP Server Application: Enable Reverse Telnet
Reverse Telnet application is useful if a telnet program is used to connect to SE5001A and the serial interface of the
SE5001A is connected to a Terminal Server. Telnet programs in Windows / Linux usually require special
handshaking to get the outputs and formatting show properly. SE5001A will interact with those special commands
(CR/LF commands) if Reverse Telnet is enabled.
Figure 3.30 TCP Server with Reverse Telnet Enabled
Follow section 3.2.5 to configure SE5001A in TCP Server mode properly.
Check Enable Pair Connection to enabled Pair Connection application in SE5001A.
Scroll to the bottom of the page and click on “Save Configuration” button to save the changes.
User Manual Version 1.0
SE5001A Serial Device Server
It is also possible to setup pair connection in UDP mode to have more than one Pair Connection Master or Slave to
communicate to each other. For example, it is possible to setup one Modbus Master and six Modbus Slaves in UDP
(Figure 3.31). Note again that UDP does not guarantee data delivery and only data would be transmitted over Ethernet; other serial pings are not transmitted. If RS-232 along with flow control, it is recommended to use
Multi-Point Pair Connection in TCP (section 3.3.18).
Note that the Destination IP and Port of the Slaves need to be equal to the Master’s IP and Port. Local
Listening Port of the Slaves needs to be equal to the Master’s Destination Port.
Sample Configuration:
Figure 3.31 Multi-Point UDP Pair Connection with Modbus
User Manual Version 1.0
SE5001A Serial Device Server
43
3.3.17. TCP Server Application: Multiple TCP Connections
To have more than one TCP Client connecting to SE5001A in TCP Server mode, contact Atop Technical Support to
obtain a special multi-connection version firmware. After the firmware is uploaded to SE5001A, the WebUI will have
one additional option called “Multiple_Connections” (Figure 3.32). The Multi-Connection option will allow up to a
maximum of four TCP Client connections. SE5001A will broadcast serial data to all connected TCP Clients. Note
that it is also possible to use this multi-connection feature in conjunction with other TCP Server applications, such as
Virtual COM, Pair Connection, and Reverse Telnet. For example, enabling multi-connection along with Pair
connection will result in Multi-Point Pair Connection in TCP mode (section 3.3.18).
Figure 3.32 TCP Server with Multiple Connections Enabled
User Manual Version 1.0
SE5001A Serial Device Server
44
IP Address
Link Mode
Local Listening Port
Destination IP
Destination Port
SE5001A Master
10.0.50.100
TCP Server
5000
-
5000
SE5001A Slave 1
10.0.50.200
TCP Client
5000
10.0.50.100
5000
SE5001A Slave 2
10.0.50.201
TCP Client
5000
10.0.50.100
5000
SE5001A Slave 3
10.0.50.202
TCP Client
5000
10.0.50.100
5000
SE5001A Slave 4
10.0.50.203
TCP Client
5000
10.0.50.100
5000
3.3.18. TCP Server Application: Multi-Point TCP Pair Connections
The difference between Multi-Point TCP Pair Connection and Multi-Point UDP Pair Connection is that the TCP
implementation would also exchange flow controls pins of RS-232. However, the TCP Server is limited to a
maximum of four connections. If there are than four serial devices and does not use flow control pins with RS-232 or
RS-485, it is possible to setup pair connection in UDP mode (section 3.3.16). After multi-connection is enabled in the
WebUI, refer to the following table to setup Pair Connection as in Figure 3.33.
Figure 3.33 Multi-Point TCP Pair Connection
User Manual Version 1.0
SE5001A Serial Device Server
45
3.3.19. COM Configuration
Configure serial settings in this page (Figure 3.34). Note that these settings need to match the ones in the serial
device.
Alias Name:
This field is for identification purpose only.
Baud Rate:
Select one of the baud rates from the dropdown box, or select Other and then enter the desired baud rate in the
input box. Baud rates higher than 230400bps are not supported.
Parity / Data Bits / Stop Bits:
Configure them accordingly.
Flow Control:
Choose between No Flow Control, RTS/CTS (Hardware Flow Control), DTR/DSR, Xon/Xoff (Software Flow Control).
If Xon/Xoff is selected, Xon and Xoff characters are changeable. Defaults are 0x11 for Xon and 0x13 for Xoff. If the
serial device uses Xon/Xoff in conjunction with DTR/DSR, enable Controlling DTR to simulate receiving Xon/Xoff
and reading DSR to get Xon/Xoff currently.
Empty Serial Buffer When TCP Connection is Established:
By default, SE5001A will empty its serial buffer when a new TCP connection is established. This means that the TCP
application will not receive buffered serial data during a TCP link breakage. To keep the serial data when there is no
TCP connection and send out the buffered serial data immediately after a TCP connection is established, set this
option to No.
Data Packet Delimiter:
Packet delimiter is a way of packing data in the serial communication. It is designed to keep packets in track.
SE5001A provides two types of delimiter: Time Delimiter, and Character Delimiter. When the selected delimiter
condition is met, SE5001A would transmit the serial data in its buffer over the network.
Time Delimiter: SE5001A will transmit the serial data in its buffer when the specified time interval has
reached and no more serial data comes in. The default time is 2ms, which means SE5001A will push out its
serial buffer if it does not receive any serial data with in 2ms. This delimiter is selected by default.
Character Delimiter: will transmit the serial data in its buffer when it sees the incoming data include the
specified character (in HEX format). This field allows one or two characters. If character delimiter is set to
0x0d, SE5001A will push out its serial buffer when it sees 0x0d (carriage return) in the serial data.
User Manual Version 1.0
SE5001A Serial Device Server
46
COM Type Selection:
Select between RS-232, RS-422, and RS-485. Note that RS-485 refers to 2-Wire RS-485 and RS-422 is compatible
with 4-Wire RS-485.
Click on “Save Configuration” button to save the changes.
Figure 3.34 COM Configuration
User Manual Version 1.0
SE5001A Serial Device Server
47
4 Using Virtual COM
Virtual COM allows remote access of serial devices over TCP/IP networks through Serial/IP Virtual COM ports that
work like local native COM ports. The following figure is a Virtual COM connection diagram. (Figure 4.1)
Figure 4.1 Virtual Com connection diagram
4.1 Setup of a Virtual COM Driver
4.1.1 System Requirements
Windows 7, 2008, Vista, 2003, XP, 2000, NT 4.0, 9x, Microsoft NT/2000/2003 Terminal Server, Citrix MetaFrame
Access Suite, native and virtual, 32 and 64-bit versions. Note that upgrading the operating systems to the latest
Service Packs is required, especially for older Windows versions.
To run Virtual COM in Linux, there is a separate package called TTYredirector available for download on Atop
website or in the product CD. The zipped package includes a binary file for installation and a manual for Linux
systems.
4.1.2 Limitation
The Virtual COM driver allows up to 256 Virtual COM ports in a single PC. Selecting in the range from COM1
to COM4096 is allowed. Note that COM ports already occupied by the system or other devices will not be
available.
User Manual Version 1.0
SE5001A Serial Device Server
48
4.1.3 Installation
Run the Virtual COM setup file included in the CD or download a copy from our website to install the Virtual
COM driver for the operating system. Turn off anti-virus software and try again if installation fails. At the end of
the installation, please select at least one Virtual COM port from the Serial/IP Control Panel.
4.1.4 Uninstalling
From Windows Start Menu select Control Panel, Add/Remove Programs.
Select Serial/IP Version x.x.x in the list of installed software.
Click the Remove button to remove the program.
4.2 Enable Virtual COM Serial device servers and Select Virtual COM in Windows
4.2.1 Enable Virtual COM in Serial Device Servers
Enable Virtual COM in our serial device servers by logging into our WebUI. It is located under COM configuration.
Following figures show how to enable Virtual COM in different serial device servers that we offer. For detailed Link
Mode configuration with Virtual COM, please refer to the previous sections starting from section 3.3.9 on Link Mode
configurations.
It is also possible to enable Virtual COM in serial device servers using Telnet. Please refer to the section 3.2.8 on
Telnet.
Figure 4.2 Enable Virtual COM in SE5001A
User Manual Version 1.0
SE5001A Serial Device Server
49
4.2.2 Running Serial/IP in Windows
Find Serial/IP Control Panel from:
Start->All Programs-> Serial/IP->Control Panel
In the Windows Control Panel, open the Serial/IP applet.
In the Windows notification area (Figure 4.5), right click in the Serial/IP tray icon and click on Configure to
open the Control Panel.
Figure 4.5 Serial/IP Notification Tray Icon
If no Virtual COM port is selected, a dialog will pop up and asks to select at least one port as the Virtual COM port
before proceeding (Figure 4.6).
Figure 4.6 Select Virtual COM Ports
User Manual Version 1.0
SE5001A Serial Device Server
50
After at least one Virtual COM port is selected, the Control Panel will show (Figure 4.7).
Figure 4.7 Serial/IP Control Panel
The left hand side of the Control Panel shows the list of selected Virtual COM ports. Click on Select Ports to add or
remove Virtual COM ports from the list. The right hand side of the Control Panel shows the configurations of the
selected Virtual COM port marked in blue. Each Virtual COM port can have its own settings.
Note: The changes to Virtual COM ports apply immediately, so there is no need to save the settings manually.
However, if the Virtual COM port is already in use, it is necessary to close the Virtual COM port and open it after the
TCP connection closes completely in order for the changes to take effect.
4.3 Configuring Virtual COM Ports
To Configure Virtual COM ports (Figure 4.7):
i. If the serial device server is running in TCP Server mode (recommended), Serial/IP should be
the TCP Client connecting to the serial device server. Enable Connect to Server and enter
the IP Address of the serial device server with the Port Number specified. The Port Number here is the Local Listening Port of the serial device server.
ii. If the serial device server is running in TCP Client mode, Serial/IP should be the TCP Server
waiting for SE5001A to connect it. Enable Accept Connections and enter the Port Number.
The Port Number here is the Destination Port of the serial device server. Do not enable
Connect to Server and Accept Connections together.
iii. If Enable VirtualCOM Authentication is enabled in the serial device server (this is only
User Manual Version 1.0
SE5001A Serial Device Server
51
available in limited serial device servers), it is necessary to enable Use Credentials From
and select Use Credentials Below from the list (Figure 4.8). Enter the Username and
Password of the serial device server in the respective fields.
iv.
Figure 4.8 Virtual COM with Credentials
v. Enable Restore Failed Connections to force Virtual COM to automatically restore failed
connections with the serial device server in the case of unstable network connections.
vi. To test the Virtual COM connection, click the Configuration Wizard button and then click Start
button in the pop up window (Figure 4.9). If the test passes, all checks should be in green. To
apply the changes in the Configuration Wizard window to the Control Panel, click on Use Settings. Click on Copy to copy the results to the system clipboard.
vii. To transfer the settings between Virtual COM ports, click on the Copy Settings To button.
User Manual Version 1.0
SE5001A Serial Device Server
52
Figure 4.9 Configuration Wizard
User Manual Version 1.0
SE5001A Serial Device Server
53
Exceptions:
a. If the exclamation mark begins with Warning: timeout trying x.x.x.x (Figure 4.10), recheck the Virtual COM IP
and Port configuration or the PC’s network configuration.
Figure 4.10 Virtual COM Timeout Exception
User Manual Version 1.0
SE5001A Serial Device Server
54
b. If there is a check with Raw Connection Detected and an exclamation mark with Client not
licensed for this server (Figure 4.11), enable Virtual COM in the serial device server.
Figure 4.11 Virtual COM Raw Connection Exception
User Manual Version 1.0
SE5001A Serial Device Server
55
c. If there is a check with Telnet Protocol Detected and an exclamation mark with Client not licensed
for this server (Figure 4.12), this means that there is a licensing issue between the serial device
server and Serial/IP. Please contact Atop technical support to obtain the correct Virtual COM
software.
Figure 4.12 Virtual COM License Exception
User Manual Version 1.0
SE5001A Serial Device Server
56
d. If the exclamation mark begins with Server requires username/password login (Figure 4.13), it
means VirtualCOM Authentication in the serial device server is enabled, but credentials in the
Serial/IP is not enabled.
Figure 4.13 Virtual COM Credentials Exception
User Manual Version 1.0
SE5001A Serial Device Server
57
e. If the exclamation mark begins with Username and/or password incorrect (Figure 4.14), this
means the wrong username and/or password was entered and the authentication failed.
Figure 4.14 Virtual COM Username Password Exception
User Manual Version 1.0
SE5001A Serial Device Server
58
f. If the exclamation mark begins with No login/password prompts received from server (Figure
4.15), it means credentials in the Serial/IP is enabled, but VirtualCOM Authentication in the serial
device server is not enabled.
Figure 4.15 Virtual COM Credentials Exception
User Manual Version 1.0
SE5001A Serial Device Server
59
4.4 Using Serial/IP Port Monitor
4.4.1. Opening the Port Monitor
The Serial/IP Port Monitor can be opened by:
Start->All Programs-> Serial/IP->Port Monitor
Double click the Serial/IP tray icon in the Windows notification area (Figure 4.5).
In the Windows notification area (Figure 4.5), right click in the Serial/IP tray icon and click on Port
Monitor to open the Port Monitor.
Click on the Port Monitor button in the Serial/IP Control Panel
4.4.2. The Activity Panel
The Activity panel provides a real-time display of the status of all Serial/IP COM ports (Figure 4.16). If the Virtual
COM Port is open and is properly configured to connect to a serial device server, the status would be Connected. If
Serial/IP cannot find the specified serial device server, the status would be Offline.
Figure 4.16 Port Monitor Activity Panel
User Manual Version 1.0
SE5001A Serial Device Server
60
4.4.3. The Trace Panel
Figure 4.17 Port Monitor Trace Panel
The Trace panel provides a detailed, time-stamped, real-time display of all Serial/IP COM ports operations (Figure
4.17). Click on Enable Trace to start logging Virtual COM communication. Click on File->Save As and send the log
to Atop for analysis If problems arises with Virtual COM.
User Manual Version 1.0
SE5001A Serial Device Server
61
4.5 Serial/IP Advanced Settings
In the Serial/IP Control Panel, Click on the Advanced button to open Advanced Settings window (Figure 4.18). Click
on Use Default Settings to load the default settings.
Figure 4.18 Serial/IP Default Advanced Settings
Extend Server Connection Maintains the TCP connection for specified amount of time after COM port is closed
Attempt Server Connection Terminates pending connection attempts if they do not succeed in the specified time
Synchronize with Server Upon COM Port Open Required by NT Systems (2000, XP, Vista, 7)
Update Routing Table Upon COM Port Open Maintains IP route to a server in a different subnet by modifying the IP routing table
Enable Nagle Algorithm Provides better network efficiency by imposing a minor latency on the data stream while it waits to fill network
packets
Always Limit Data Rate to COM Port Baud Rate Limits the data rate to the baud rate that is in effect for the virtual COM port
User Manual Version 1.0
SE5001A Serial Device Server
62
Attempt Server Connection If credential is set to Windows Credentials, VCOM automatically adds the current Windows domain to the
username
COM Port Control Keep-Alive Controls the interval at which VCOM will issue the keep-alive message, if no there is no activity
Maximum Connection Recovery Interval Controls the maximum time for “Restore Failed Connection”
Enable SETXON/SETXOFF COM Port Commands
This option enables additional negotiation on SETXON and SETXOFF commands and is only available for the
“V” series serial device servers. If the application requires SETXON/SETXOFF feature, please contact Atop Tech
Support.
User Manual Version 1.0
SE5001A Serial Device Server
63
4.6 Using Serial/IP with a Proxy Server
The Serial/IP Redirector supports TCP network connections made through a proxy server, which may be controlling
access to external networks (such as the Internet) from a private network that lacks transparent IP-based routing,
such as NAT. Find Proxy Server settings from the Advanced Settings windows and switch to the Proxy Server tab
(Figure 4.19)
Figure 4.19 Serial/IP Proxy Settings
User Manual Version 1.0
SE5001A Serial Device Server
64
5 Diagnostics
There are several ways to can check the status and availability of the serial device server.
5.1 Using Standard Ping Command
From the Windows Start menu, select Runand type in “ping <TCP Server IP address>”.
If the serial device server can receive ping requests sent from the host, it will reply to the ping message (Figure
6.1). If the ping request cannot reach the serial device server, timed out message will show (Figure 6.2).
Figure 6.1 Successful Ping Reply
Figure 6.2 Ping Command Failed
User Manual Version 1.0
SE5001A Serial Device Server
65
5.2 Using Serial Manager Configuration Utility
Use Serial Manager configuration utility that comes with the product CD or download from Atop website to
check on the status of the serial device server. The status and version can be read from the tool. For example,
‘S’ means that COM1 is in TCP Server mode and is not connected to a TCP Client (Figure 6.3). ‘A’ means that
COM1 is in server mode and is connected to a TCP Client.
Figure 6.3 Serial Manager Utility
User Manual Version 1.0
SE5001A Serial Device Server
User Manual Version 1.0
SE5001A Serial Device Server
67
Link Modes
TCP Server
4 connections, Virtual COM, or Reverse Telnet
TCP Client
Single destination or Virtual COM
UDP
Up to 4 ranges of IPs
Upgrade System Firmware
Firmware is available for download on Atop website: http://www.atop.com.tw. Subscribe to our RSS system
http://www.atop.com.tw/en/rss.php to receive our latest firmware updates automatically.
Upgrade Procedures
This section introduces the command-line firmware upgrade utility included in the CD. Alternatively, use the GUI
management utility Serial Manager to upgrade the system firmware. Refer to Serial Manager’s manual to use Serial
Manager to upgrade the system firmware.
After the new firmware is obtained, follow the procedures below to upgrade SE5001A.
1. Connect a PC (Windows systems) and the SE5001A to the same subnet. Use ping command or Serial
Manager utility to verify its availability.
2. Locate dapdl.cfg (configuration file), gwdl.exe (download executable utility), and download.bat (download
batch file) in the \download folder of the CD. Copy them to the system disk.
3. Locate the new system kernel and/or AP firmware to download. Move them inside the copied \download
directory.
4. Double click on download.bat to start the firmware upgrade process.
Figure B.1 Prompt of download.bat
Note: It is also possible to edit dapdl.cfg and run gwdl.exe manually without using the batch file
download.bat.
5. Press any key to continue.
6. An editor will open dapdl.cfg automatically. Edit the content to match the IP address of SE5001A and the
file name of the new firmware. "dapdl.cfg" has the following structure:
Remote_IP 10.0.50.100
Load firmware.hex
The first line identifies the IP address of SE5001A, the second line identifies the name of the firmware (.Hex
file) to be downloaded.
User Manual Version 1.0
SE5001A Serial Device Server
68
Figure B.2 Dapdl.cfg Opened with an Editor
7. File->Save and File->Exit the text editor.
8. Enter the admin as the userid and the password of SE5001A. If a password is not set, press enter. The
batch file will upgrade the system firmware. SE5001A will restart automatically after the new firmware is
uploaded.
Figure B.3 System Firmware Upgraded
User Manual Version 1.0
SE5001A Serial Device Server
69
Error Cause
Message
Comments
Illegal Hex file format
Hex File Text Error
Hex File Check-Sum Error
Hex File Format Error
Hex File End of Record Error
Remote IP not found
Open configuration file failure
9. Repeat the process above again for kernel or AP firmware if necessary.
Note: After the upgrading process finishes, SE5001A will program the flash memory and buzzer beeps 6
times then restarts. Normally, it takes around 10 seconds to complete the programming process. If an error
occurs during the programming process, SE5001A will clear the corresponding memory and the system
remains intact of what it was.
Error Messages
Firmware upgrade may not be successful if errors occur during the process.
User Manual Version 1.0
SE5001A Serial Device Server
70
Emergency Firmware Recovery
The AP (application program) firmware of SE5001A can be disabled to restore the device to the proper firmware in
case an incompatible firmware was downloaded and the system crashes while loading the AP.
To disable the AP firmware and prevent it from executing, please do the following.
1. Power off the device.
2. While the reset button is pressed, power on the device.
3. In Serial Manager, SE5001A will show up with a default kernel firmware and no AP firmware.
4. Download the correct AP firmware to SE5001A.
5. The device will restart and recover to the downloaded firmware.
Figure C.1 SE5001A with no AP firmware disabled
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.