ATMOX EDGE Installation Manual

Installation Guide
ATMOX EDGE System
Moisture Control and Heat Reduction System for Attics
Easy Steps to Install
Thank you for purchasing the ATMOX Controlled Ventilation System.
For instructions on specific fans and accessories, please refer to Specification Sheets by product.
For questions not covered in this guide, please contact ATMOX for assistance: Phone: 704-248-2858 Email: info@atmox.com
Product Specifications Usage: Variable from 1.5-150 W Input Voltage: 85-132V AC Output Voltage: 12-13V DC Output Current Range: 0-12.5A Data Input: 2 Temperature/RH Power Output: 1 Switched
Use only approved ATMOX Fans and Accessories with the ATMOX EDGE System
Issue: 2018-03 © Copyright 2018 ATMOX INC
3
Table of Contents
Look for these
symbols
throughout
this guide
for important
information
regarding
installation.
SYMBOLS
EDGE System Components .......................................................................... 4
Controller........................................................................................................ 9
Sensors ........................................................................................................ 10
Fans & Components .................................................................................... 13
Low Voltage Wiring ...................................................................................... 14
Testing .......................................................................................................... 24
Setting Adjustments ..................................................................................... 30
Troubleshooting ........................................................................................... 35
Warranty ....................................................................................................... 39
TIP
CAUTION
WARNING
4
Box Contents
1. EDGE Controller
2. Outside Temperature and Humidity Sensor
3. Inside Temperature and Humidity Sensor
4. ATMOX screwdriver
5. Colored banana plugs: 1 black, 1 red
6. Quick splice connectors (4)
7. Extension cable (RJ11) with coupler (4 cables x 25 ft. each)
8. ATMOX EDGE User’s Guide
1
2
3
5
76
8
4
5
Tools and Supplies
Most supplies are already included with your ATMOX System.
Screws are not included for the following:
Controller Needs 4 screws Inside Sensor Needs 2 screws Outside Sensor Needs 2 screws
Choose the screws appropriate for the surface you are mounting to.
General tools and supplies needed:
6
Component Placement
5
2B
4
3
1
1
1
2A
7
Review Components
Before beginning installation, take a moment to review components that you will be using on this house. As you review the steps for each component, think about where components will be placed. A little pre-planning will make things go very smoothly when installing.
1 Controller placement options
2A Outside Sensor placement option
2B Inside Sensor placement option
Fan mounting throughout attic
Low voltage wiring for fans & accessories
Testing
Review the ATMOX System configuration to better understand use of components and wiring options.
TIP
1
2A/2B
3
4
5
Basic System Configuration
8
RED OUTPUT
Fans will run when
the outside air is
beneficial.
Sensors
measure
and
provide
data to the
controller.
9
Controller Installation
Step 1
Mount using four screw holes.
Placement Options
Place controller in a location that is viewable, such as a garage or closet. It needs to be near an electrical outlet. Wires will need to feed to attic and outside.
Use:
4 screws
Step 2
Use all four holes.
Step 3
Plug into power outlet.
Don’t place controller within two feet of roof rafters or in outside location.
WARNING
10
Installation of Outside Sensor
TIP
Avoid direct constant sun if possible. This may cause the sensor to give a higher temperature reading.
Placement Options
Place sensor in outside location within a few feet of wire feed into attic or inside location.
Use:
2 screws
Step 1
Mount using two screws.
Step 2
Use extension cables to extend to the controller as described on page 12.
Step 3
Plug jack into slot labelled “OUTSIDE SENSOR”.
.
11
Installation of Inside Sensor
TIP
Temperature measurements in attic can vary substantially between low and high points. Placing sensor higher will cause fans to run more frequently in heat reduction mode.
Placement Options:
Place sensor on a joist or beam inside attic.
Step 5
Plug jack into slot labelled “INSIDE SENSOR”.
Use:
2 screws
Step 1
Pull sensor from mounting bracket.
Step 2
Mount using two screws.
Step 3
Push sensor back into bracket.
Step 4
Use extension cables to extend sensor cable to the controller location as described on page 12.
12
Using Extension Cables
WARNING
All coupler connections must be installed inside the attic. If the jacks and couplers are outside, they will get wet and corrode causing a sensor defect.
Overview
25’ extension cables with couplers are provided to extend cables to the controller. These can be used in any combination.
Use:
Staples or fasteners to keep cables secure.
Step 1
Find coupler at end of extension cable.
Step 3
Connect additional extension cables as needed.
Step 4
Fasten cable to joists. Be careful not to staple through a cable.
Step 5
Create a drop loop at each coupler connection before securing to joist. Tension on jacks may cause internal damage to cable.
Step 2
Insert end of sensor cable into coupler.
CAUTION
It is not recommended to exceed 75’ in one cable run.
13
Fans & Components
ATMOX fans and accessories should be mounted in attic according to instructions supplied with each component.
As the installer, you should already have a plan on effective placement of fans.
For questions on specific component placement, contact ATMOX for more information.
WARNING
Use of components not compatible with the ATMOX System could cause an electrical surge and damage control box. This would not be covered under ATMOX warranty.
Power supply in the EDGE System is limited to 150 WATTS
- If you exceed 150 watts of power, you must add power booster supply. (Available as add-on)
- Refer to component spec sheet for power usage.
1
2
14
Low Voltage Overview
For all ATMOX Systems, use 14/2 gauge low voltage wire. It is very simple to use. Just remember that one side will always be used as the positive and the other as the negative.
Purchase separately. Usage depends on size of space.
The smooth side will generally have writing on it.
Banana Plugs
Included with controller set.
Positive = Colored Plug Negative = Black Plug
Fan Connector Wire
Included with each fan or accessory.
Positive = Black Side Negative = White Side
Two included with each fan or accessory.
Four included with controller set to add two supplemental wires if needed.
Quick Splice Connectors
TIP
Your wire may have different grooves or writing. Either side can be used as positive or negative as long as you are consistent.
Smooth Side = Positive
Grooved Side = Negative
15
Wiring Explanation
Black Banana Plug
Red Banana Plug
Primary Low Voltage Wire
Supplemental Low Voltage Wire
Positive (smooth side)
Negative (grooved side)
Quick Splice
Connectors
Fan Connector Wire
Fan
16
Preparing Primary Wire
CAUTION
Do not strip the wires when cutting for separation.
Step 1
Split wire about two inches from end.
Step 3
Remove outer coating to expose about 3/8 inch of internal copper.
Step 2
Pull the ends apart.
Step 4
Repeat on other side.
WARNING
Unplug controller from power source while completing next steps.
17
Attaching Banana Plugs
Use:
Step 1
Loosen screw in banana plug.
Step 3
Tighten screw.
Step 2
For red banana plug, insert the smooth side into bottom of plug.
Step 4
Repeat Steps 1-3 for the black banana plug. Insert the grooved side into bottom of plug in Step 2
.
Step 5
Plug red banana plug into red jack on
controller.
Step 6
Plug black banana plug into corresponding black jack on controller.
18
Fastening Primary Wire
TIP
Add a drop loop in locations where supplemental wire will be added to the primary wire.
Pull primary low voltage wire from controller to the fans.
Step 1
Secure wire to joists. Be careful not to puncture a wire.
Step 2
Create a drop loop at each fan location. This will give you extra wire to work with when attaching fan connector wire.
• If primary wire reaches all fans, then proceed to connecting fans.
• If more wire is needed, proceed to next page to add supplemental wires.
19
Preparing Supplemental Wires
CAUTION
Do not cut across the primary wire. Do not strip the wires when cutting for separation.
Use:
Step 1
On primary wire, select location where supplemental wire will be attached. Split wire.
Step 3
Cut end on supplemental wire to make sure it is smooth and even.
Step 2
Pull apart the two sides to make a loop of about three inches
.
Step 4
Cut middle of supplemental wire. Split about two inches from end.
Step 5
Pull the ends apart.
20
Attaching Supplemental Wires
Step 1
Find the positive side of the primary wire (smooth side) in the loop. Push the wire into the quick splice connector.
Step 2
Take the end of the positive side of the supplemental wire (smooth side). Insert the end of the wire into the connector until it hits the plastic stop.
Step 3
Use pliers on metal splice to make a connection with both wires.
Step 4
Push the cover of the quick splice connector down to close.
Step 5
Repeat Steps 1-4 with the negative side of the primary and supplemental wire (grooved side).
Step 6
When finished, both sides of wires will be connected to each other.
Once attached, pull supplemental wire to remaining fans. Secure wire and create drop loops in same manner as primary wire.
21
Attaching Connector Wire
TIP
All ATMOX fans and accessories will use the same fan connector wire.
Step 1
Go to the drop loop location where you want to attach your fan.
Step 2
Split wire.
Step 3
Pull apart the two sides to make a loop of about three inches.
Step 4
Find the positive side of the low voltage wire (smooth side) in the loop. Push the wire into the quick splice connector.
Use:
22
Attaching Connector Wire
Step 5
Open the fan connector wire.
Step 6
Take the end of the positive side of the fan connector wire (black wire). Insert the end of the fan connector wire into the connector until it hits the plastic stop.
Step 7
Use pliers on metal splice to make a connection with both wires.
Step 8
Push the cover of the connector down to close.
CAUTION
Avoid damage to wire tips. Do not use excessive force when pulling wires. If tip breaks, see page 38 for instructions.
23
Attaching Connector Wire
Step 9
Find the negative side of the low voltage wire (grooved side) in the loop. Push the wire into the connector.
Step 12
Push the cover of the connector down to close.
Step 10
Take the end of the negative side of the fan connector wire (white wire). Insert the end of the fan connector wire into the connector until it hits the plastic stop.
Step 13
Plug the jack on end of fan connector wire into the fan.
Step 11
Use pliers on metal splice to make a connection with both wires.
Attach all ATMOX fans
in the same manner.
24
Power System and Testing Checklist
Use the checklist to test all aspects of the ATMOX System.
Once the wiring is
complete, plug the
controller back into the
electrical outlet.
Checklist Page Reference
Power and readings on controller 25-28
No alarm lights 25-28
Testing red output (fans) 29
25
Testing Controller
The controller should have power, and display should have rotating screens.
For faster rotation of screens, press the M button to manually scroll.
Press the M button to light up screen for easier viewing.
The red light next to ALARM should not be illuminated. If there is an alarm, read notification on display screen for more information.
1
2
26
Informational Display Screens
Dew Point Screen
The Dew Point Screen displays the dew point outside and inside the attic.
Temperature Screen
The Temperature Screen displays the temperature outside and inside the attic.
The ATMOX system evaluates the outside and inside temperature to determine whether or not to ventilate the attic for general moisture control parameters. For heat reduction, the ATMOX System will ventilate based on a high inside temperature.
Note: If the outside sensor is located in direct sunlight, it will often heat the metal housing causing the sensor to read a temperature that is higher than the ambient outdoor temperature. The overall outside moisture calculations (dew point) will not be incorrect, so this generally does not affect basic operation of the ATMOX system in determining when fans should be running.
Dew point is the key to the ATMOX system. Dew point is calculated from the temperature and humidity measurements and gives you the best indicator of moisture in the air. A higher dew point means there is more moisture in the air, and a lower dew point means there is less moisture in the air. The ATMOX system does not activate ventilation on an absolute number but instead uses a comparison of air in the two locations. Under most circumstances, the fans will ventilate when the outside dew point is one degree lower than inside dew point. There are some exceptions to this built into the software, for example temperature parameters need to be met. There is also a time delay of 15 to 30 minutes to conserve energy and avoid constant on and off. This means that you will not always see instantaneous change in operations.
27
Informational Display Screens
Relative Humidity Screen
The Relative Humidity Screen displays the relative humidity outside and inside the attic.
Relative humidity is measured by the sensor along with temperature in each location and is used to calculate dew point. An important component of relative humidity is the word “relative.” Humidity is relative to temperature and can fluctuate significantly with changes in temperature. ATMOX ventilates based on a dew point comparison for this reason. It is possible for the humidity outside to be higher than inside but to still trigger fans to run. It all depends on the corresponding temperature. In general, the ATMOX system is not looking to target an exact humidity level but instead is looking to have variations mirroring the outdoors. The goal is not to have extremely high humidity in the attic for extended periods of time.
Fans On Screen
The Fans On Screen displays when the fans are activated.
When this screen is showing, the conditions outside are beneficial to the attic and fans have been triggered to run. All fans will be activated.
28
System Notifications
Humidity Too High
Missing, None, Defect (Def), with Inside or Outside Sensor
System notifications are designed to alert you of a potential problem. The following are all possible alerts:
Under the system default settings, this humidity alarm setting is turned to the off position, but could be active on the system. If this alert is on for a brief period of time, there is no reason for concern as humidity can fluctuate. If this alert is on for an extended period of time, the attic should be checked.
Any of these alerts indicate that there is a data connection problem with the corresponding sensor. See page 35 for “Troubleshooting.”
29
Testing Fans Output
All fans should be tested to make sure that they are working properly. The best way to do this is to start the fans manually and then go check the fans.
TIPS
After a manual start of fans, all fans will continue to operate for 24 hours. This will go back to Automatic Mode after this time. You cannot leave system in Manual Mode for more than 24 hours.
If any fans are not running, see Troubleshooting on pages 36 and 37.
1 2
Start the fans in Manual Mode:
Step 1: Press Arrow button. Step 2: Make sure the red Manual light is illuminated.
Step 3: Press + button. Step 4: Check display for “Manual on: 24h.”
Step 5: Check all fans by physically going to look at them.
Put system back to Automatic Mode:
Step 1: Press Arrow Button. Step 2: Make sure the red Manual light is illuminated. Step 3: Press + button. Step 4: Check to make sure it no longer displays “Manual on: 24h.”
Step 1
Step 3
Step 4
Step 2
30
System Settings
Most ATMOX Systems do not need any software adjustments for operation. There are instances where you may want to adjust a setting to better suit your needs. These adjustments are described here.
Heat Reduction
Heat Reduction Mode is designed to mitigate heat buildup in the attic. This mode allows for the attic fans to ventilate regardless of dew point calculations once the temperature exceeds the set inside temperature. The default setting is an inside temperature of 99.2° F. The trigger for Heat Reduction can be set lower or higher within the range of 80° F and 120.8° F. The fans will run continuously until the inside temperature goes five degrees below the set temperature.
No Ventilation Temperature Setting
The No Ventilation setting is designed to avoid bringing in cooler outside air in the winter time in most geographic climates. In colder climates, it may be desired to expand this temperature range for increased ventilation during the winter. This setting determines the minimum temperature inside the attic that will allow ventilation to occur. The default setting to stop ventilation is an inside temperature below 46° F. The setting can be set lower or higher within the range of 1.2° F and 85.2° F.
WARNING
Improper settings can negatively
affect the operation of the ATMOX system.
31
Making Setting Adjustments
To adjust settings follow these steps:
Step 1: Press
+
button one time.
Step 2: Press
M button until screen reads:
Step 3:
Use
+
and
-
buttons to adjust to desired setting.
Step 4: Press
Arrow button to return to main screen.
Step 4
Step 1 & 3
Step 3
Step 2
Step 2
or
32
Snow Mode
Snow Mode is a special setting in the ATMOX Attic systems designed to mitigate the potential for ice damming in climates where snow and ice buildup create challenges for the attic. Snow Mode is a tool in fighting ice damming but needs to be viewed as part of an overall strategy and may not eliminate all issues in all attics.
Often when attics are warmer than outside temperatures, it can create issues when snow and ice begin to melt and possibly cause water penetration into the home or attic. The Snow Mode creates a way to cool the attic to balance the temperature differential. When the Snow Mode is turned on, the fans will run when the inside temperature is above 32° F and the outside temperature is below 32° F in system default setting. The fans run to dissipate the heat in the attic to resist excessive melting of snow or ice.
Snow Mode is defaulted to OFF and will need to be turned on manually.
CAUTION
In order for ventilation to reduce temperatures effectively under Snow Mode, the fan setup may need to be adjusted. It is important that exhaust fans have clean outflow points and are not restricted by snow. Additionally, there need to be open intake points by soffit vents to get airflow to the low corners. There may need to be additional internal fans to get cold air to these corners. Please discuss the fan setup with ATMOX if you have any questions.
TIP
Snow Mode is only important when there is snow or ice on the roof. The homeowner may want to make it inactive during other parts of the winter to keep attic warmer from an energy efficiency standpoint.
33
Snow Mode Settings
To turn Snow Mode ON or OFF:
Step 1: Press
+ button one time.
Step 2: Press
M button until screen reads:
Step 3: Use
+
and
-
buttons to turn on or off.
Step 4: Press Arrow button to return to main screen.
or
When Snow Mode is active, the main rotating screen will include the Snow Mode display.
Step 4
Step 1 & 3
Step 3
Step 2
Step 2
34
Default Settings
If undesired changes have been made to settings, you can reset all settings back to the default settings.
Step 1: Press and hold both Arrow and M buttons
simultaneously for over five seconds until screen changes to:
Step 2: Press +
button one time. Screen will show:
Step 3: Press +
button again, screen will change to:
Step 4: Press Arrow button to return to main screen.
Step 1
Step 1 & 4
Step 2 & 3
35
Troubleshooting Alarm Lights
Problem:
There is an alarm light illuminated.
Explanation:
There is either a hardware problem or an alert notification.
Look at display reading
for alarm information.
A “DEF” (defective) for a
sensor reading.
Reboot the system.
“missing” or “none” for a
sensor reading.
Need to check sensor.
Sensor gives proper reading.
Issue is with extension cable or
coupler. Check the line.
Sensor does not
give reading. Issue is with jack on sensor or the
sensor is defective. Contact ATMOX for
assistance.
Error remains.
Issue is with sensor or
extension cable.
Look to see if it is Inside Sensor,
Outside Sensor, or both. Take
the sensor with the error and bring it to the controller. Plug
it into the controller with no
extension cables.
For any alerts or notifications,
check the attic for cause of alert. See page 28 for more
information.
Error cleared.
Problem solved.
If error comes back, then
contact ATMOX for assistance.
TIP
If there is an alarm of any kind, the ATMOX system will not operate. You cannot test other outputs until alarm is cleared.
36
Troubleshooting Fan Operation
Problem:
A fan or group of fans are not running.
Fans should be set to Manual On for testing and troubleshooting.
Some fans running and some fans not
running.
When all fans on primary
wire are running.
STEP 2:
Check fans on
supplemental wire
Check the quick splice
connectors connecting the
primary and supplemental wires. Look for full splice and consistency with positive and
negative sides.
If some fans on supplemental
wire not running.
If all fans on supplemental wire
not running.
Fan connector wire fixed.
Problem solved.
STEP 1:
On the primary wire,
some fans are not
running.
Check the fan connector wire
for the fan(s) not running.
Check to make sure fan
connector wire is completely
inserted into fan.
Look for full splice and
consistency with positive and
negative sides.
Still having issues, test fan in
working fan connector wire
and contact ATMOX
for assistance.
37
Troubleshooting Fan Operation
Problem:
All fans are not running.
Fans should be set to Manual On for testing and troubleshooting.
ALL fans not running.
On primary wire, temporarily switch the
colored and black banana plugs.
If fans are still not running,
insert banana plugs back into
the correct colored jacks.
Contact ATMOX for assistance.
If fans are now running, banana plugs
were attached on wrong side. Switch banana plugs and re-insert in correct
colored jacks. Recheck all fans on
primary wire.
38
Quick Splice Connectors and Connector Wires
Reset a Quick Splice Connector:
Reuse a Fan Connector Wire:
The following steps are only needed if the metal tip is missing or damaged.
Step 1
Open cover and wedge open.
Step 1
Cut end of wire.
Step 2
Pull apart and remove wires.
Step 2
Strip approximately two inches of outer sheathing.
Step 3A
If needed, reinsert metal piece.
Step 3
Twist copper back over sheathing.
Step 3B
If needed, push metal piece up.
Step 4
Use exposed copper to make splice connection.
1/2 inch
39
ATMOX Limited Three-Year Warranty
When installed, operated, used and maintained as intended in residential applications and according to the instructions supplied with ATMOX products, ATMOX warrants its products for a period of 3-years from the date of purchase against any defects in material and workmanship. The products covered by this warranty include the control boxes, fans, sensors and wiring manufactured by ATMOX. ATMOX will repair or replace, at ATMOX’s option, any ATMOX product or component found to be defective within the 3-year warranty period.
ATMOX products are designed to improve conditions in the crawlspace, basement or attic, yet are limited by atmospheric and natural conditions over which ATMOX has no control and which are not covered by this warranty. ATMOX products are not warranted against damage caused by electrical surges, fire or other casualty, vandalism, or acts of God (including lightning strikes and floods). This warranty does not make representations regarding mold, insects, termites, water, rot, electrical, HVAC, roof, framing, foundation, floors, drywall, gutters, ice dams or other problems that may occur in a house structure. The warranty does not include any costs of removal or reinstallation.
Third-party products by other manufacturers sold by ATMOX (such as dehumidifiers) are not covered by this warranty but may be covered under separate warranties by the product’s manufacturer. Purchaser should contact third party manufacturers for warranty claims and coverage of third-party products not manufactured by ATMOX.
ATMOX INC’S LIABILITY UNDER THIS LIMITED WARRANTY IS STRICTLY LIMITED TO REPAIR OR REPLACEMENT OF DEFECTIVE ATMOX PRODUCTS. OTHER THAN THE WARRANTIES EXPRESSLY DESCRIBED HEREIN, ATMOX DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. ATMOX WILL NOT BE LIABLE FOR ANY SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow certain limitations and exclusions of warranty, so these exclusions may not apply to you. This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state.
ATMOX INC
10612-D Providence Road #229 Charlotte, NC 28277
Phone: 704-248-2858 Fax: 704-675-9858 Email: info@atmox.com Website: www.atmox.com
Loading...