4. Safety, burner installation and commissioning 10
Safety and connection of the burner to the boiler 10
Basic dimensions of the opening for installation of the burner in a boiler 11
5. Type of environment and location of the boiler with the burner in the boiler room 12
6. Chimneyn 12
7. Flue gas duct of the boiler 13
8. Fire protection within the installation and use of heat appliances 13
9. Connection of the boiler D80P, P80 with a buffer tank and burner control by the TS and TV
sensors, separate control of the heating system by electronic control unit ACD 01 / ACD 03/04 15
10.
Connection of the boiler D80P, P80 with a buffer tank and controlled return water in to the boiler
from control unit ACD01 / ACD 03/04
11. Connection of the boiler and burner to the electric mains 17
12.
Connection diagram of the electronic unit AC07X with additional AC07X-C module for A85 burner
13. Electric diagram of the burner ATMOS A85 - 6-pin connector - model AC07X - (R, R2, sensors
TV, TS, TK, TSV) with additional module AC07X-C - (R5, R6) for control of pellet burner
pneumatic ash cleaning system 19
14. Wire diagram for D80P, P80 boiler with a exhaust fan, model AC07X with a 6-pin connector,
control of the boiler’s exhaust fan (R), pump in boiler circuit (R2) from the burner,
control of pneumatic cleaning operation from control unit of the burner with additional module
AC07X-C – compressor (R5) and pneumatic valve via (R6) 20
15. Commissioning 21
16. Control and setting of the burner 23
Display and control panel 23
Passwords and their functions 25
PARAMETERS menu 25
Setting up required output and combustion quality: 26
INFORMATION menu 49
TESTING menu 50
17. Information - error messages - troubleshooting 51
General troubleshooting 51
Table of error messages on the display - alarms 51
If no problem has been found, reset the regulation AC07X by the RESTART command. 57
If the system is working, but you are not satisfied with its function, proceed as follows: 57
18. Maintenance and cleaning of the burner 58
19. List of spare parts 60
20. Expanded view of the burner 61
GUARANTEE TERMS 62
RECORD OF INSTALLATION OF THE BOILER AND BURNER
ANNUAL INSPECTIONS RECORDS 64
RECORDS OF GUARANTEE PERIOD AND POST-GUARANTEE PERIOD REPAIRS 65
16
18
63
EN
www.atmos.cz
EN-3
Operation and Maintenance Manual - EN
1. General information
WA R N I NG - Before starting the burner you must get thoroughly acquainted with all provisions
of this manual. The manufacturer is not liable for damages caused by operation, maintenance
or wrong setting of the power of the burner that will cause heat overloading of the burner.
Introduction
This manual is intended for all users and contains information necessary for the installation,
EN
start-up, maintenance and safe operation of the burner.
We recommend you to pay great attention to the safety regulations. Interventions that require
removal of some parts should be carried out carefully by qualified authorized experts. Repairs and
settings that are not described in the manual should not be carried out at all.
Application
The burner is designed for ATMOS D80P, P80 special boilers.
Technical specifications
Name: ATMOS A85
Prescribed fuel: high-quality (white) wooden pellets with the diameter of 6 to 8 mm, length of 5 to
25 mm and calorific value of 16 - 19 MJ.kg
Nominal heat input of the burner: 89 kW
Minimum heat input of the burner: 27 kW
Maximum heating surface of the boiler that the burner may be installed in: 5 m2
Fuel bin: not part of the delivery - recomended volume 1000 l
Fuel feeding: with an external worm conveyor type DRA50 - not part of the delivery
Burner control: with an AC07X electronic control unit that controls the operation of the external
conveyor, two ignition spirals and the fan in accordance with requirements of the boiler and the
heating system. The electronic system is protected with the safety thermostat of the boiler, safety
thermostat at the pellet supply to the burner, the fan speed transducer and the flame sensing photocell.
The operation of the burner is indicated on the electronic control display.
Power supply: 230 V / 50 Hz
Maximum power input at the start with one ignition element: 490 W - normal setting
Maximum power input at the start with two ignition elements: 1052 W - special functions
Average power input at the nominal heat input operation: 72 W
Average power input at the minimum heat input operation: 43 W
Average heat input in the standby mode: 3.3 W
Prescribed fuse protection of the burner with the boiler: 6.3 A
Acoustic pressure level (noisiness): 59 dB
Burner weight: 46 kg
Burner dimensions, WxHxD: 37 x 59 x 89 cm
Minimum dimensions of the combustion chamber: diameter / width = 400 mm, length / depth = 400 mm
Minimum ashpan space of the boiler: must correspond to operation at the nominal output for at
least one week. (min. 6 l)
Minimum vacuum in the combustion chamber of the boiler: 2 Pa
Min. protection against inadvertent opening of the boiler chamber (door): with a safety screw
-1
4-EN
www.atmos.cz
Operation and Maintenance Manual - EN
2. Design
Description
Heating with pellets with the use of the ATMOS A85 pellet burner has a lot in common with
natural gas or oil heating. However, there is a difference that burning of pellets produces a certain
quantity of ashes that must be removed from the burner and boiler in an interval to avoid impairment
of efficiency or affecting the functionality of the burner.
The ATMOS A85 pellet burner is supplied with automatic fuel ignition as standard. The assembly
of the burner, external conveyor and fuel bin work completely automatically during operation and
is controlled by an electronic control unit with the use of a flame sensor (photocell). In the burner
body the fuel and combustion air are supplied in such a way to ensure maximum efficiency and
environment-friendliness of fuel burning.
Normally only high-quality pellets with the diameter of 6 to 8 mm and length of 5 to 25 mm
should be fed into the burner. Pellets made of soft wood without bark, called white pellets, are considered as high quality pellets.Ashes are normally removed from the burner through the open door once every 7 to 30 days as
necessary. Fly-ash and dirt accumulated in the combustion chamber of the burner and boiler considerably reduce the service life and output.For this reason the basic version of ATMOS burner A85 is equipped with pneumatic cleaning
which cleanses the burner’s combustion chamber after every burn out or at regular intervals (factory
setting is 4 hours – parameter S42, S43). Thanks to pneumatic cleaning you can check or clean the
burner’s combustion chamber only once in a fortnight or a month.
It is recommended to thoroughly clean the inner parts of the burner once a year; for this operation
the burner should be removed from the boiler. For ideal cleaning of the combustion chamber (pot) of
the burner you can use a special vacuum cleaner or a poker.
EN
The burner consists of the following parts:
85
7 6
1 - End switch
2 - Safety thermostat 95 °C
3 - Display of the burner electronic unit
4 - Combustion chamber (mouth) of the
burner
5 - Socket for the external conveyor
3
2
4
1
6 - connector for connection of TS, TV, TK and TSV
sensors
7 - connector for interconnection cable between the
boiler and the burner (power cable)
8 - connector for connecting speed sensor of boiler’s
exhaust fan
CAUTION - For the A85 burner DRA50 external shaft conveyors with the length of 1.7, 2.5,
4 and 5 m with the diameter of 80 mm.
www.atmos.cz
EN-5
EN
Operation and Maintenance Manual - EN
Fig. 1 - Combustion mouth of the burner
Fig. 3 - Combustion chamber with the nozzle
of the pneumatic cleaning and opening for 2
ignition spirals
Fig. 2 - Removable combustion chamber must be regularly cleaned
Fig. 4 - Disassembled plate with the ignition
spirals
Fig. 5 - AC07X electronic control unit with
AC07X-C additional module (R5, R6), keys,
bottom terminal board (1-18), upper distribution
frame for connection of TS, TV, TK, TSV sensors
and photocells
6-EN
Fig. 6 - Photocell - be careful about its proper
orientation - we recommend you to clean it at
least once a year
www.atmos.cz
Operation and Maintenance Manual - EN
EN
Fig. 7 - Burner fan with an air ap
Fig. 9 - Fan with speed sensor and a start
capacitor
Fig. 8 - End switch with a special stop
Fig. 10 - Safety thermostat on the pellet supply
pipe, 95 °C
Fig. 11 - connection of electric valve and
comperssor for pellet burner pneumatic ash
cleaning system
www.atmos.cz
Fig. 12 - Burner with two 6-pin connectors, left
- power, right - sensors, 3-pin connector for
connecting speed sensor of the boiler‘s fan and
socket for conveyor
EN-7
EN
Operation and Maintenance Manual - EN
Fig. 13 – View of the water temperature sensor in
the pocket of the accumulation tank (TV and TS)
Fig. 16 – View of the water temperature sensor
TK in the boiler pocket, DxxP, Pxx types
Fig. 14 – View of the ue gas sensor TS or TSV in
the ue gas duct pocket
Fig. 16 – Complete set of ATMOS A85 burner and
compressor for pneumatic cleaning
Fig. 17 – High-quality wooden pellets – white
without black dots (bark)
8-EN
Fig. 18 – Poor-quality wooden pellets – dark
with bark (with black dots)
www.atmos.cz
Operation and Maintenance Manual - EN
3. Burner accessories
Accessory - burner part
Stop for the end switch 1 piece
Interconnection cable between the boiler and the burner with a connector (6x1.5 mm)
Operation and Maintenance Manual 1 piece
Fuse - type F 3.15A/1500A/5x20mm (ignition spirals) 2 pieces
Fuse - type F 0.8A/1500A/5x20mm (conveyor) 1 piece
Fuse - type F 1.0A/1500A/5x20mm (ventilator) 1 piece
Poker for cleaning – small 1 piece
CP85KS set for the A85 burner with a compressor 1 piece
1 piece
EN
Accessories that are not part of the burner and can be purchased separately:
DRA50 pellet conveyor with the length of 1,7 m and diameter of 80 mm - 25 W - CODE: H0039
DRA50 pellet conveyor with the length of 2,5 m and diameter of 80 mm - 25 W - CODE: H0037
DRA50 pellet conveyor with the length of 4 m and diameter of 80 mm - 40 W - CODE: H0004
DRA50 pellet conveyor with the length of 5 m and diameter of 80 mm - 40 W - CODE: H0005
Water temperature sensor with a 5 m cable (range - 20 ...+ 110 °C)
- type KTF 20 - CODE: P0431
Flue gas temperature sensor with a 2.5 m cable (range -20 ...+ 300 °C)
- type VFF00-75P65 - CODE: P0414
Pocket for a flue gas sensor to be positioned in the flue gas duct, G1/2“ x 85 mm - CODE: V0524
Cavity with tin for extension of conductors (sensors) - CODE: P0445
www.atmos.cz
EN-9
Operation and Maintenance Manual - EN
4. Safety, burner installation and commissioning
Safety and connection of the burner to the boiler
WA R N I NG - Before starting the burner you must carefully read all the provisions of this
manual. At the same time you must observe all general safety regulations for work with
heating equipment resulting from the valid legislation.
• The premises where the equipment will be installed must comply with all fire protection regulations
EN
in accordance with valid standards and laws.
• The equipment must be positioned in such a way to ensure access for cleaning and removal of
ashes not only from the burner, but also from the boiler, flue gas duct and chimney.
• The burner must be installed to the boiler over a sealing cord, soft Sibral sealing or another
insulation and sealing material to prevent flue gas from escaping along the burner to the boiler
room. Under one of the nuts with the use of which the burner is attached to the boiler a SPECIAL SHEET-METAL PART - END SWITCH STOP must be positioned. It is used to compress the
end switch that monitors the proper position of the burner on the boiler. This protective device
must not be omitted in any case as it is directly related to fire safety.
• The connection between the burner and the boiler must be properly tightened to prevent flue gas
from escaping to the boiler room.
•
During the installation you must make sure that the pellets can freely fall through the hose to the
burner. The connections between the hose, burner and conveyor must also be properly tightened.
Design and technical measures for increasing safety
• The ignition and combustion process is controlled by the electronic control unit by means of the
flame sensor - photocell. If the sensor does not sufficiently see the flame during operation, it will
automatically put the burner out of operation.
• The electronic control unit senses the speed of the burner fan and at any problems of the fan it
automatically puts the burner out of operation.
• On the burner frame there is an end switch and end switch stop that does not make it possible to
start to burner if the burner is not properly fixed to the boiler (e.g. after cleaning of the burner).
If during normal operation of the burner the end switch gets disconnected, the burner will be
automatically put out of operation. If at the start after two attempts with the fuel supply and one
attempt without the fuel supply the pellets are not ignited, the burner will be automatically put out
of operation.
• If during normal operation of the burner the fuel bin runs out of pellets, the burner will try a new
start and subsequently will be put out of operation. After replenishing pellets in the fuel bin and
drawing pellets to the conveyor you can start the burner by merely turning off and on the burner
switch on the boiler panel.
• The flexible transparent hose between the burner and external conveyor is made of special material
that melts at high temperatures and the hose will change to a spring that will separate the burner
from the fuel bin.
10-EN
www.atmos.cz
Operation and Maintenance Manual - EN
• The safety thermostat - located on the fuel supply pipe of the burner, will shut down the burner
if its temperature is higher than 95 °C. Thus, it protects the burner from return ignition of pellets
in the conveyor and at the same time from operation with clogged flue gas exhaust from the boiler
(e.g. in case of a failure to remove dust from the boiler, flue gas duct and chimney). The safety
thermostat will also put the burner out of operation in case the hose between the burner and
conveyor gets perforated to prevent flue gas from escaping to the boiler room.
INFO - After any shutdown of the burner when an error message (ALARM) appears on
the display it is necessary to immediately find the cause and remove it. After removing the
cause of the error you can start the burner by merely turning off and on the burner switch,
which is located on the boiler panel.
Basic dimensions of the opening for installation of the burner in a boiler
In the case of the D80P, P80 boilers the boiler comprises a frame with a sealing cord - 18x32 mm.
EN
Explanatory notes:
1. A85 burner
2. Sealing
3. Screw - M10
4. Decorative nut - M10
www.atmos.cz
EN-11
Operation and Maintenance Manual - EN
5. Type of environment and location of the boiler with the
burner in the boiler room
Boilers with a pellet burner may be used in the AA5/AB5 basic environment in accordance with
the ČSN3320001 standard. Boilers must be installed in a boiler room with guaranteed sufficient supply
of combustion air. It is unacceptable to
locate boilers on residential premises
(incl. corridors). The cross-section of the
EN
opening for supply of combustion air to
the boiler room must be at least 350 cm
1. Chimney
2. Flue gas duct
3. Boiler
4. A85 burner
5. External conveyor
6. Bin (1000 l)
2
.
6. Chimneyn
A boiler with a burner must always be connected to the chimney vent with consent of the
responsible chimney maintenance company. The chimney vent must always produce sufficient
draught and exhaust flue gas to the free atmosphere in virtually all operation conditions. For proper
function of boiler the separate chimney vent must be properly dimensioned as the combustion, output and service life of the boiler depends on its draught. The draught of a boiler directly depends on
its cross-section, height and roughness of the inner wall. No other device may be connected to the
chimney to which a boiler is connected. The diameter of the chimney must not be smaller than the outlet on the boiler (min. 180 mm). The chimney draught must achieve prescribed values (see the
technical specifications in the boiler manual). However, the boiler must not be excessively high so as
not to reduce the efficiency of the boiler and not to disturb its combustion (tear the flame). In case of
too strong draught install a throttling flap or draught reducer in the flue gas duct between the boiler and
the chimney.
Guideline values of dimensions of the chimney cross-section:
20 x 20 cm height 9 m
Ø 20 cm height 10 m
The exact determination of chimney dimensions is defined by the ČSN 73 4201 standard.
The prescribed chimney draught is specified in the “Technical data” chapter of the manual
of the particular boiler.
12-EN
CAUTION - The draught of the chimney during operation must ensure the minimum
vacuum of 2 Pa in the combustion chamber of the boiler.
www.atmos.cz
Operation and Maintenance Manual - EN
7. Flue gas duct of the boiler
The flue gas duct from the boiler must lead to the
chimney vent. If the boiler cannot be connected directly to
the chimney vent, the corresponding flue gas duct adapter
must be as short as possible with regard to the particular
conditions, but not longer than 1 m, without additional
heating surface and it must rise towards the chimney. Flue
gas ducts must be mechanically strong and leak-proof for
flue gas and cleanable inside. Flue gas ducts must not lead
through other owners‘ residential or commercial units. The
inner cross-section of the flue gas duct must not be larger
than the inner cross-section of the smoke uptake and must
not get narrower towards the chimney. The use of smoke
elbows is not suitable. Designs of passages of flue gas ducts
through structures of flammable materials are defined in
Annexes 2 and 3 of ČSN 061008 and are mainly suitable for
mobile units, wooden huts, etc.
Boiler
EN
Chimney
1. Flue gas thermometer
2. Cleaning opening
Draught regulator (throttling flap)
INFO - In case of too strong draught of the chimney install a draught regulator (limiter) /3/
or a throttling flap in the flue gas duct, see the ATMOS price list.
8. Fire protection within the installation and use of heat appliances
Extract from ČSN 061008 - Fire safety of local appliances and sources of heat
Safe distances
On installation of an appliance the safe distance from building materials must be maintained, at
least 200 mm. This distance is valid for boilers and flue gas ducts located near flammable materials
of the B, C1 and C2 flammability class (the flammability class is specified in tab. no. 1). The safety
distance (200 mm) must be doubled if boilers and flue gas ducts are located near flammable materials
of the C3 class (see tab. no.1). The safety distance must be doubled if the flammability class of
flammable material is not evidenced. The safety distance may be reduced to a half (100 mm) if you
use a non-flammable heat insulating panel (asbestos panel) with the thickness of at least 5 mm,
located 25 mm from the protected flammable material (flammable insulation). A shielding panel or
protective screen (on the protected object) must exceed the outline of the boilers (incl. flue gas ducts)
at each side by at least 150 mm and the top surface of the boiler by at least 300 mm. A shielding panel
or protective screen must also be used to protect fixtures of flammable materials if the safe distance
cannot be maintained (e.g. in mobile units, huts, etc. - more details in ČSN 061008). The safety
www.atmos.cz
EN-13
Operation and Maintenance Manual - EN
distance must also be maintained in case of installation of fixtures near boilers.
If boilers are located on a floor of flammable materials, they must be installed on a non-flammable,
heat-insulating pad, exceeding the ground plan at the side of the feeding and ashpan opening by at
least 300 mm before the opening - at the other sides by at least 100 mm. As non-flammable, heat
insulation pads you can use all materials of the A flammability class.
WARNING - In circumstances leading to the danger of transient ingress of flammable
gases or vapours and during work that might result in a temporary risk of a fire or explosion
(e.g. gluing of linoleum, PVC, etc.) the boilers must be put out of operation in time before
the occurrence of the danger. No objects of flammable substances may be put on the
burner and boiler in a smaller distance than the safe distance from them (more - see
ČSN EN 13501-1).
In short, do not put any items that could easily catch fire in the vicinity of the boiler.
9. Connection of the boiler D80P, P80 with a buffer tank and
burner control by the TS and TV sensors, separate control of the
heating system by electronic control unit ACD 01 / ACD 03/04
SDW10/20
MKP1
M1
ventil
valve
ARU5/10/30
VF1
M
AF
ATMOS
ACD
odtahový ventilátor
exhaust fan
TK
MAX. 60°C
tlakoměr, přetlakový ventil,
R
odvzdušňovací ventil
pressure gauge, safety
valve, deaerator
bojler TUV
DHW boiler
SF
ventil
valve
odvzdušňovací
ventil deaerator
PF
SLP
ventil
valve
Tv
(R2) 75 °C
R5
A85
A85
R6
R2
tlaková
expansní
nádoba
pressure
expansion
vessel
filtr
filter
ventil
valve
vyrovnávací nádrž
buffer tank
1000 l
Ts
ventil
valve
obytné místnosti
haritable rooms
filtr
filter
čerpadlo
pump
ventil
valve
mísící ventil
mixing valve
ventil
valve
EN
Laddomat 22
ventil
filtr
valve
filter
termoregulační ventil
INFO – The TK sensor placed in boiler pocket (from production), the TV and TS sensors
(boiler accessory) on the buffer (accumulation) tank are connected directly to the burner.
Regulation of the boiler’s exhaust fan (R) and pump in boiler circuit (R2) from the burner
ATMOS A85. Regulation of the functions of the pneumatic cleaning from the burner’s
AC07X regulation with additional AC07X-C module – compressor (R5) and pneumatic el.
valve (R6).
ACD01 regulation controls the heating system only.
Required accessories (is part of the burner): nothing needs to be bought
(ACD 01 controler is not part of the delivery)
System configuration of parameters: S6 = 3, S14 = 12, S15 = 2, S67 = 15, S68 = 16
The pump in the boiler circuit is controled directly from the control unit of the ATMOS A85 burner
(the pump thermostat placed on the boiler control panel
connected in series with output R2 - factory
settings).
www.atmos.cz
EN-15
Operation and Maintenance Manual - EN
M
Max. 60°C
M
WF
PF = TV
M1
DKP
VF1
AF
SF
VF2
M2
SLP
MKP2
obytné místnosti
haritable rooms
filtr
filter
vyrovnávací nádrž
buffer tank
1000 l
čerpadlo
pump
ventil
valve
bojler TUV
DHW boiler
tlakoměr, pojistný
ventil, odvzdušnovač
pressure gauge, safety
valve, deaerator
filtr
filter
ventil
valve
mísící ventil
mixing valve
čerpadlo
pump
tlaková
expansní
nádoba
pressure
expansion
vessel
mísící ventil
mixing valve
KSPF = TS
A85
A85
R5
R6
odtahový ventilátor
exhaust fan
SDW10/20
ARU5/10/30
ATMOS
ACD
R
10.
Connection of the boiler D80P, P80 with a buffer tank and
controlled return water in to the boiler from control unit
EN
ACD01 / ACD 03/04
16-EN
INFO - If using electronic regulation ACD01 / ACD 03/04, we do not connect any set or
other sensors in the boiler.
The sensors supplied as a part of the burner can be also used for ACD01 / ACD 03/04
regulation (TV = PF and TS = KSPF).
Regulation of the boiler’s exhaust fan (R) directly from the burner ATMOS A85.
Regulation of the functions of the pneumatic cleaning from the burner’s AC07X with
additional AC07X-C module – compressor (R5) and pneumatic el. valve (R6).
ACD01 / ACD 03/04 regulation controls the whole operation of both the boiler and the
heating system except exhaust fan of the boiler and pneumatic cleaning of the burner (direct controled
from the burner).
System configuration of parameters:S6 = 3, S14 = 12, S15 = 1, S67 = 15, S68 = 16
www.atmos.cz
Operation and Maintenance Manual - EN
11. Connection of the boiler and burner to the electric mains
Only connect the burner to the 230 V, 50 Hz electric mains via the boiler with a mains cable
without a plug so that the conductors (L, N) should not be interchanged. The mains supply must be
replaced with the same type by a repair organization. The boiler must be positioned in such a way
that the connector on the burner can be within the operator’s reach (in accordance with ČSN EN
60335-1).
CAUTION - Boilers with a burner may only be connected by a qualified person in accordance
with all the relevant valid regulations of the particular country while great attention must be
paid to safe earthing of the boiler.
After the installation of the burner on the boiler the technician must connect the burner and
subsequently the entire boiler to the electric mains in accordance with the attached wiring
diagram (page 20).
Connection:
Between the burner and boiler a six-wire cable is newly used that is connected with one end to
the burner with a 6-pin connector (part of the burner) and the other end with a 6-pin connector to the
boiler.
EN
The meaning of the conductors is as follows:
Black – phase L1 (230V, 50Hz) – With the main switch of the boiler on the black conductor is
•
permanently live (independently of the control thermostat of the boiler). It is the supply voltage of
the burner. This phase must be fuse protected via the safety thermostat of the boiler (95 - 110 °C).
• Brown – phase L2 (230V, 50Hz) – The brown conductor is controlled by the control or another
thermostat on the boiler panel. It brings the phase, impulse for the burner start. It is perceived as
the starting (ignition) and shutdown signal. This phase must also be fuse protected via the safety
thermostat of the boiler. (95 – 110 °C).
• Grey - reserve R (L3) (230V/50Hz) - The grey conductor is connected directly to the 6-pin
connector on the boiler. It serves as the free reserve for various functions of the boiler, characterized
with the S6 parameter. In this case it serves to control the solenoid valve of the burner‘s pneumatic
cleaning.
• Red - reserve R2 (230V/50Hz) – The red conductor is connected directly to the 6-pin connector
on the boiler. It serves as the second free reserve for various functions of the boiler, characterized
with the S14 parameter. In this case it serves to control the compressor of the burner‘s pneumatic
cleaning.
• Blue - N – Neutral – The blue conductor is connected to the neutral conductor.
• Yellow and green - PE – Protective Earthing – The yellow and green conductor is connected to
the earth.
NOTE - The burner and the boiler fan are newly connected by a three line cable of the speed
sensor. One end of the cable connects to the burner by a 3-pin connector (part of the boiler
fan cable) and the other one connects to the draught fan connector in the boiler casing.
www.atmos.cz
EN-17
Operation and Maintenance Manual - EN
rozšiøující moduly Ac10C a Ac10D k regulátoru Ac10A - pøipojovací schéma
1234
N
N
R7(NO)
J2
AC07X-D
12. Connection diagram of the electronic unit AC07X with
additional AC07X-C module for A85 burner
EN
1112
34
1
2
10
78
9
34
5
6
1
2
AC07X-B
AC07X-A
FAN1
FAN2
JP 1
AC07X-C
J1
18-EN
1 23 45 6 78 9 10 11 12 13 14 15 16
12
R5
funkce
rezerva è. 5 - speciální
3
45 6
R6
funkce
rezerva è. 6 - speciální
CAUTION - For the connection of the TS, TV, TK and TSV sensors the connection of
individual wires is not decisive (can be interchanged). The TK and TSV sensors are not part
of the delivery, they must be purchased additionally within the set or separately.
AC07X-C additional module is for DxxPX and PXxx boilers designed to controle pneumatic
cleaning system of the pellet burner via paramteres S67 and S68.
www.atmos.cz
Operation and Maintenance Manual - EN
13. Electric diagram of the burner ATMOS A85 - 6-pin
connector - model AC07X - (R, R2, sensors TV, TS, TK,
TSV) with additional module AC07X-C - (R5, R6) for control
of pellet burner pneumatic ash cleaning system
EN
WARNING - ATMOS A85 pellet burner has two mains lead, therefore disconnect
(boiler, compressor) before uncover the burner hood.
www.atmos.cz
EN-19
Operation and Maintenance Manual - EN
14. Wire diagram for D80P, P80 boiler with a exhaust fan, model
AC07X with a 6-pin connector, control of the boiler’s exhaust
fan (R), pump in boiler circuit (R2) from the burner, control of
pneumatic cleaning operation from control unit of the burner
with additional module AC07X-C – compressor (R5) and
EN
pneumatic valve via (R6)
20-EN
www.atmos.cz
15. Commissioning
CAUTION - The system may only be put in operation if the burner is connected to the
boiler, the boiler to a chimney with sufficient draught via a flue gas duct and in the fuel bin
there is a sufficient quantity of pellets of the corresponding quality. Pellets made of soft
wood without bark, i.e. white pellets with the diameter of 6 to 8 mm and length of 5
to 25 mm are considered as high-quality pellets. These pellets do not cake. Burning of
dark pellets or pellets with bark that contain visible dark dots produces cake that must
be removed from the burner mouth once a day. Otherwise the combustion chamber
and the feeding hose from the conveyor will get clogged.
For this reason the basic version of ATMOS burner A85 is equipped with pneumatic
cleaning which cleanses the burner’s combustion chamber after every burn out
or at regular intervals (factory setting is 4 hours – parameter S42, S43). Thanks to
pneumatic cleaning you can check or clean the burner’s combustion chamber only once
in a fortnight or a month.
INFO - The pellets have to be stored in dry and clean containers (areas). When filling the fuel bin, the pellets must not be contaminated by foreign objects that could cause a
blockage of the conveyor or have an impact on the burning process.
Operation and Maintenance Manual - EN
EN
Requirements for the external conveyor and pellet bin at the first start of the burner:
• The worm conveyor must be positioned in the bin in such a way to be able to easily pick up
pellets. In the case of a fuel bin whose pellet level will be higher than 2 metres a roof will have
to be installed over the conveyor to prevent blocking of the conveyor. Blocking of the conveyor is
caused by dust in the pellets in combination with high pressure caused by the height of the pellet
level. ATMOS 250, 500 and 1000 l pellet bins do not require the installation of the roof.
• The hose between the burner and conveyor must be tensioned, properly fixed and must have such
an inclination to enable trouble-free falling of pellets to the burner.
• The connector of the work conveyor must be plugged into the socket on the burner.
Procedure of drawing pellets to the conveyor
• Plug the connector of the external worm conveyor to a standard wall socket. As soon as the first
pellets get over the top point and start to fall to the burner via the elastic hose, plug the connector
of the external worm conveyor back into the socket on the burner.
Normal operation:
• On the control thermostat on the boiler panel set the required operation temperature of 80 - 90 °C
and turn on the switch of the burner located on the boiler panel and the main switch.
The STARTup mechanism consists of the following steps:
At the start the worm conveyor and the ignition spiral are started (the fan on the burner and the boiler
•
is stopped).
• The worm conveyor will run for the time set by parameter T1, necessary for the delivery of the
amount for pellets for optimum ignition. After the delivery of the ignition amount of fuel the
www.atmos.cz
EN-21
Operation and Maintenance Manual - EN
worm conveyor will stop. The burner fan will be started at the ignition speed - parameter S2
as well as the extraction fan.
• After the ignition of pellets the photocell will sense light, which will cause the ignition spiral to
switch off with a slight delay.
• The burner will pass over to the stage of perfect burning of fuel - set by parameter T7.
The OPERATION algorithm consists of the following steps:
EN
• When the fuel burns perfectly, the burner will get to the stage of gradual increase of the power
to the nominal value - parameter T10.
• After achieving the nominal power the burner works in the normal mode until the heating system
or the accumulation tank is heated to the required temperature. The power of the burner results from the hourly quantity of pellets delivered by the worm conveyor to the combustion chamber.
The worm conveyor works in the intermittent mode set by parameters T4 and T6. Parameters
T4 and T6 are set in accordance with the instructions on page 25.
•
After setting the nominal power of the burner you must also set the amount of combustion air
necessary for complete burning of fuel. The setup is done using air flap of the burner fan and by
changing speed of the burner fan (parameter S3). The exact setting should be carried out by a
trained person with the use of a flue gas analyzer.
The burning out algorithm is designed as follows:
•
After the achievement of the set temperature at the boiler thermostat (e.g. 85 °C) or temperature
in the accumulation tank - temperature at the bottom sensor (TS), the electronic control unit of the
burner will switch off the external worm conveyor. Thanks to this, the pellets in the combustion
chamber will burn out. Optimal burning out of pellets in the combustion chamber is additionally
supported by the operation of the burner fan for a certain time - parameter T5. After subsequent
drop of the temperature of water in the boiler or discharge of the accumulation tank - temperature
at the top sensor (TV), the burner will be re-started in the same way as described in the text above.
If the accumulation tank is connected to a solar exchanger and activating functions for automatic
optimization (switching) of sensors, parameter S15 = 3, the burner may be turned off by sensor TK
instead of sensor TS.
The other algorithms are designed in the following way:
• If the first attempt for ignition with fuel supply fails, the burner will repeat the whole algorithm.
After the second unsuccessful attempt for ignition with fuel supply the burner will proceed to the
third attempt during which the fuel is not supplied any longer, but only the ignition spiral is active.
After this unsuccessful attempt the burner will be put out of operation as the system has probably
run out of pellets or a fault has occurred.
• In case of a short-term interruption of power supply to the burner, the burner will automatically
renew its operation after performing diagnostic checks, complete burning out of pellets,
pneumatic cleaning of the burner and a new start.
22-EN
INFO - This sequence has been set intentionally to ensure safe and trouble-free operation
of the burner.
www.atmos.cz
Operation and Maintenance Manual - EN
16. Control and setting of the burner
Display and control panel
The electronic control unit of the burner is equipped with four keys for easy and intuitive control.
Enter - key for confirming a command and parameter or for entering a menu
Esc - key for return from a menu
Up arrow - key for browsing in the menus or for increasing the value of a parameter
Down arrow - key for browsing in the menus or for decreasing the value of a parameter
INFO - To open the Main Menu, press the Enter key.
EN
The PA R AM E T E R submenu will appear on the display. To change the basic permitted parameters
of the burner, confirm again - press the Enter key.
To switch off OFF (STOP) or to switch on ON (START) the burner or to get to the INFOR M ATION,
PASSWORD
with the up or down arrow. Always confirm the ON (START) and OFF (STOP) command or
entering the particular submenu by pressing the Enter key. In the same way you can browse and
open individual menus and particular parameters in the menus. You can enter specific values or numbers with the up ( + ) or down ( - ) arrow. Confirm the desired value with the Enter key. To
return one step backwards or completely to the main screen press the Esc key once or repeatedly.
Display with keys:
1. Information about the burner status
START – start-up stage
RUN – normal operation
STOP – burning-down stage or
stand-by mode
2. Temeperature TV (see page 49) – only if TS
and TV sensor are connected
3. Temeperature TS (see page 49) – only if TS
and TV sensor are connected
4. Symbol line – information about the
operation of particular devices of
the burner (see page 56)
or TESTING submenus, do not confirm the (PA R AM ET E R) submenu, but continue
www.atmos.cz
EN-23
Operation and Maintenance Manual - EN
MAIN menu
ON (START) – This is the command to switch on the burner. Confirm the switch-on command by
pressing the Enter key.
OFF (STOP) –
PARAMETERS – This is a separate menu where individual parameters and functions can be set
EN
INFORMATION – This is a separate menu where you can view the current status of individual
PASSWORD – This is a very important parameter, designed only for service engineers. After entering
MODULE – shows actual connected additional module, e.g. AC07X-C.
PROFIL – shows actual set burner profile -A25, A25 pneu, A25 GSP, A25 GSP pneu, A25PX, A25PX
Basic authorization levels: User, service engineer (installer), manufacturer
Accessible parameters depending on authorization:
This is the command to switch off the burner. Confirm the switch-off command by pressing
the Enter key.
depending on the type of the boiler and heating system and the authorization
level.
devices and elements on the A25 burner.
the required password the service engineer is allowed to change some parameters
depending on the authorization level.
pneu, A45, A45 pneu, A85, A85 pneu, A85 pneu C
Customer: T1, T4, T6, S16, S17, S18, S19, Restart, Language
Service engineer:
Manufacturer: all
CAUTION - The customer is expressly prohibited to change parameters or functions
of the burner without consent of the manufacturer or service engineer although some
of them are not directly protected with a password. Otherwise the manufacturer reserves the right to decline the guarantee due to an inexpert intervention into the burner.
Particular passwords are production secret of the ATMOS Company and the
service engineer (installer) is not authorized to provide them to anybody without the
manufacturer’s consent.
INFO - After replacement of any ignition spiral the service engineer must enter the
password: 1234, which will reset the check algorithms for the ignition spirals. Without
entering of this password the ignition spirals will never be started (activated).
• Parameter Т1 – Time for feeding the ignition amount of pellets… (85 s)
• Parameter Т2 – Maximum time for ignition of pellets (then a new attempt for ignition
follows)… (15 min)
• Parameter Т4
• Parameter Т5 – Rundown time of the fan after the STOP command - for optimal burning out of
pellets in the combustion chamber… (25 min)
• Parameter Т6
• Parameter Т7 – Time to achieve complete burning of the ignition amount of fuel… (40 s)
• Parameter Т8 – Time of fixed start of the ignition spiral in case of insufficiently burned out
pellets in the combustion chamber after expiration of parameter T5 - only
valid for the first ignition attempt... (6 min)
– Running time of the worm conveyor after a standstill interval – power control… (8,3 s)
– Standstill time of the worm conveyor after a running interval - power control… (12 s.)
• Parameter Т10
if T10 = 0, the function is off.
– Time for gradual increase of the power of the burner to the nominal value… (20 min)
www.atmos.cz
EN-25
Operation and Maintenance Manual - EN
Setting up required output and combustion quality:
Required output is set up by parameters T4 and T6
The real output is, however, also affected by pellet diameter and an angle of the conveyor. That is why
it is necessary to know that when conveyor angle or pellet diameter were changed after set-up of the
burner, the burner must be set up again.
Quality of combustion is set up with the fan‘s air flap in such way that the flame ends at the front
edge of the combustion chamber spherical space. This means that in boiler D80P, P80 flames fill the
EN
entire space of the combustion chamber. However, reaching of the flames as far as the spherical space
of the boiler‘s body must be prevented.
Accurate final set-up of combustion is to be done after the boiler had been in continuous operation
for 30 to 60 minutes. The best way is to use an exhaust analyzer. We recommend to set up the burner so that surplus O2 in exhaust gas fluctuates between 7 to 10 % and average CO is less than 250 mg/
m3. Exhaust gas temperature must never drop below 110 °C and rise above 250 °C.
INFO - Although the burner has many functionalities (parameters), these only relate
to set up of the basic ones, which characterize output of the burner T4, T6 and quality
of combustion – fan‘s speed S3, air flap opening
Approximate recommended set up of the burner for separate outputs when using conveyors
DRA50 – 1.7, 2.5, 4 and 5 m, 6 mm pellets and the conveyor at an angle of 45°:
Opening of the air
Boiler
output
50 – 60 kW85 s5 s12 s30 %47 mm
70 – 80 kW85 s8,3 s12 s47 % 67 mm
CAUTION - Parameter T4 must never be set higher than 9 s.
INFO – If necessary, when there is little space in the boiler room, you may shorten the conveyor
(screw) or its legs as you wish at any time, but in such way that the conveyor angle remains
smaller than 45°.
Minimum length of the pipe between the burner and the conveyor must be more than
30 cm. Maximum length of the pipe should not exceed 1 m.
ParameterT1ParameterT4ParameterT6Parameter
S3
ap on the burner
fan of a boiler with
an exhaust fan
• Parameter S1 – Allowed number of attempts for ignition with fuel supply….(2).
If parameter S1 is set to 4, the fuel will always be ignited with both the ignition elements at the same time (Z1 + Z2) in 2 attempts for ignition with fuel supply.
26-EN
CAUTION - Always after the last attempt for ignition with fuel supply given by parameter
S1, an attempt for ignition without fuel supply will follow to test the equipment. If the fuel
is not ignited after this attempt, the system will be put out of operation and the ALARM START error message will appear.
www.atmos.cz
Operation and Maintenance Manual - EN
• Parameter S2 - fan speed at the START …(1 %) - do not change
CAUTION - 0 % = 700 rpm. If S2 = 0, the fan is off at the start.
• Parameter S3 – Fan speed during normal RUN …(47 %)
In normal circumstances we do not recommend you to change prescribe fan speed as it influen ces cooling and cleaning of inner parts of the burner. Only use the air flap to set the air quantity.
• Parameter S4– Fuel ignition control method …(1)
If:
a) S4 = 1 …. Photocell sensing
• Parameter S6– characterizes thefirst reserve R - additional output - function … (3)
The first reserve R is used for controlling boiler exhaust fan.
EN
CAUTION – In the standard setting when parameter S1 is set to 2, you can connect to
the reserve terminal
(approx. 566 VA).
In the setting when parameter S1 is set to 4, which means that at the start both the ignition
spirals are activated simultaneously, you can connect to the reserve terminal R, R2, R5 and
R6 an appliance with the maximum current of 0.29 A (approx. 67 VA).
If:
a) S6 = 1…. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be closed and the reserve output will be energized. Thanks to this you can start a spare source
of energy for heating of the building as e.g. a gas, electric or oil boiler.
b) S6 = 2….. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be opened and the reserve output will not be energized. Thanks to this a signal can be sent to
an electrically backed up AB01 ATMOS GSM module controller that will send information that
there is a system fault or the system is not energized. This is the opposite logic (to S6 = 1), which
means that during normal operation the reserve is energized.
c) S6 = 3…… The reserve function as the output function for the burner fan, when the reserve
output is closed, is energized always when the burner fan is running (fan mode only 100 % or
OFF). This function is applied if you want the boiler fan or extraction fan in the chimney to run
together with the burner fan. This function is designed for direct control of an fan directly from
the burner (e.g.
D80P, P80,
R, R2, R5 and R6
DxxPX, PXxx).
an appliance with the maximum current of 2.46 A
d) S6 = 4…… The reserve function as the reversed function of the output for the burner fan,
when the reserve output is off, is not energized always when the burner fan is running. This
function is always activated if you connect the A25 burner with the AS25 set containing the
AD02 or AD03 module, which in this case controls the extraction fan of the boiler. Install the
www.atmos.cz
EN-27
EN
Operation and Maintenance Manual - EN
AD02 or AD03 module under the instrument hood of the boiler and connect it electrically
between the boiler terminal board and the extraction fan, see the wiring diagram.
This setting and connection with AD02 or AD03 module and special connector (jumper to main
switch) is standardly used for SP(X) boilers with the function for automatic start after wood
is burnt out activated (AUTOSTART – S34 = 1 or S34 = 2). Boiler exhaust fan is running
simultaneously with the pellet burner during the AUTOSTART function.
e) S6 = 5…… Reserve function as the output function for the Z1 ignition spiral when the reserve copies the run of the ignition spiral.
f) S6 = 6….. Cleaning function of the combustion chamber or grill (flap). If the burner is in the
normal START, RUN and STOP mode, the output is not energized. The output is only energized
for the limited time T11, which continues immediately after the expiration of time T5 in the
STOP mode. It is not used with the A25 burner.
g) S6 = 7….. Reserve function as the output function for the external worm conveyor, when the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The
reserve output work independently of the condition of the actual output for the external worm
conveyor. This means that if the standard output for the external conveyor gets damaged, the
reserve will work independently in accordance with the same program, and therefore it can be
used as a replacement for the damaged output.
h) S6 = 8….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The reserve works in dependence on the status of the actual output for the external worm conveyor.
This means that if the output for the external conveyor gets damaged, the reserve will be switched
off automatically. This function is suitable in situations when you need to control another external
conveyor that supplies (feeds) pellets from a larger distance to the main conveyor from which the
pellets fall directly to the burner.
i) S6 = 9….. Reserve function as the output function for the external worm conveyor, when the
reserve copies the run of the external worm conveyor, but with the difference that it does not cycle, but
runs permanently both during the drawing of the ignition amount and during both the times T4
and T6. Thus, the other external conveyor runs continuously and works independently of the status
of the actual output for the external worm conveyor. This means that if the output to the main external
conveyor from which pellets directly fall to the burner gets damaged, the reserve will keepworking independently. This function can be used in cases when you need to control another external conveyor
that supplies (feeds) pellets from a larger distance to a pellet bin at the boiler from which the main
external conveyor draws pellets to supply them directly to the burner. Caution - the other external
conveyor must always be controlled with an additional level sensor (level meter) that will maintain the
level of pellets in the pellet bin at the boiler.
j) S6 = 10….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor, but with the difference that it does not
cycle, but runs permanently both during the drawing of the ignition amount and during
both the times T4 and T6. Thus, the other external conveyor runs continuously, but it works in
dependence on the status of the actual output for the external worm conveyor. This means that if
28-EN
www.atmos.cz
Operation and Maintenance Manual - EN
the output for the external conveyor from which pellets fall directly to the burner gets damaged,
the reserve will be switched off automatically. This function is convenient in cases when you
need to control another external conveyor that supplies (feeds) pellets from a larger distance to a pellet bin at the boiler from which the main external conveyor draws pellets to supply them
directly to the burner. Caution - the other external conveyor must always be controlled with an
additional level sensor (level meter) that will maintain the level of pellets in the pellet bin at the
boiler. This is a similar function to S6 = 9, but with a higher degree of safety.
k) S6 = 11….. Reserve function for controlling boiler exhaust fan for SP(X) boiler types when the
function for automatic start after wood is burnt out is activated. This function ensures that boiler
exhaust fan is running only during wood burning after the wood is burnt out. When the burner is
run on pellets, the boiler exhaust fan remains switched off. This function is used if you do not need
or want to use the boiler exhaust fan while the burner is running. Install the AD02 module under
the instrument hood of the boiler and connect it electrically between the boiler terminal board and
the extraction fan, see the wiring diagram.
WARNING – this is not a standard setting for SP(X) boilers with the function of automatic
start
(AUTOSTART – S34 = 1 or S34 = 2) after wood is burnt out (standard setting is S6 = 4).
EN
l) S6 = 12…..Reserve function for direct control of pump in the boiler circuit from the burner
regulation (boiler terminal board). This function controls the pump in the boiler circuit without
using AD02 or AD03 modules. This is applicable only for boilers that do not allow heating with
wood (not even in emergency situations). E.g. D14P, P14, D21P, P21, D25P, P25, D80P, P80,
DxxPX, PXxx. Pump output must be switched to reserve R on the boiler terminal board and the
TK sensor must be installed before this function can be activated. After activation, S37, S38, S39,
S40 temperature parameters must be checked and configured.
m) S6 = 13…..Reserve function is the reverse output function for controlling the pump in
the boiler circuit from the burner regulation (output cable from boiler with a connector – white
inside) via AD02 or AD03 modules. This function controls the pump in the boiler circuit using
AD02 or AD03 modules ranged into a set with pump thermostat installed into the boiler panel.
This method of pump controlling can be used for any ATMOS pellet boiler, and is therefore
recommended. AD02 or AD03 modules must be inserted and connected under the boiler hood
and the TK sensor must be installed before this function can be activated. After activation, S37,
S38, S39, S40 temperature parameters must be checked and configured.
n) S6 = 14….. Reserve function for direct control of solar heating pump from the burner regulation
(boiler terminal board). This function control solar pump when automatic sensor switching function
is activated (S15=3), where the boiler is connected with accumulation tank equipped with solar
exchanger and collectors. The system requires TV, TK, TS and solar sensors to be connected to the
TSV solar panel. This function never uses AD02 or AD03 modules.
After activation, S26, S27, S28, S29, S30, S31, S32, S33 temperature parameters must be checked
and configured.
This function is specially designed for boilers: D14P, P14, D15P, P15, D20P, P20, D21P, P21,
D25P and P25
www.atmos.cz
EN-29
EN
Operation and Maintenance Manual - EN
CAUTION - the direct controlling function of solar heating from pellet burner cannot be
used for SP(X) boilers and boilers with burner built into the upper doors. This function also
cannot be used when the pump is simultaneously controlled in the boiler circuit from the
burner regulation (TK sensor cannot be simultaneously in boiler and accumulation tank)
o) S6 = 15….. Reserve function for the compressor control during the function for automatic
burner cleaning using compressed air. Power element designed for switching and powering the
compressor (e.g. contactor) must be connected between reserve output R and the compressor. This
function is connected with S6(14), S41, S42, S43, S44, S45, S46, S47 parameter, which must be
checked and configured.
p) S6 = 16….. Reserve function for controlling el.fan during the function for automatic burner
cleaning using compressed air. This function is connected with S6 (14), S41, S42, S43, S44, S45,
S46, S47 parameter, which must be checked and configured.
Special function for turning on reserve output R according to the temperature of a concrete
sensor:
a) e.g. function: TS>……. means that if the TS sensor temperature is higher then the set value in
S48 parameter – Temperature A, reserve output R will be activated
b) e.g. function: TS<……. means that if the TS sensor temperature is higher then the set value in
S48 parameter – Temperature A, reserve output R will be deactivated
c) e.g. function: TS,TV>……. means that if the TS and TV sensor temperature is higher at the
same time then the set value in S48 parameter – Temperature A and S50 – Temperature B, reserve
output R will be activated (Temperature A = first position (TS), Temperature B = second position
(Tv)).
d) e.g. function TS,TK<……. means that if the TS and TK sensor temperature is higher at the
same time then the set value in S48 parameter – Temperature A and S50 – Temperature B, reserve
output R will be deactivated (Temperature A = first position (TS), Temperature B = second position
(Tk)).
• Parameter S7 – Function of the main external pellet conveyor – do not change in any case... (1)
if:
a) S7 = 1….. Standard function when in the START mode the external conveyor supplies the
ignition amount of fuel during time T1, when it runs continuously.
In the RUN mode the external conveyor doses fuel by alternating times T4 (run) and T6 (standstill).
• Parameter S10 – Specifies the behaviour of the burner in case of a power supply failure or when
the boiler is activated with the main switch – do not change in any case ….. (1)
a) S10 = 1… Function when after a power supply failure the electronic control unit tests the status
of the burner, evaluating with the use of the photocell or by means of the flue gas temperature that
the burner (boiler) is still burning. Subsequently, it first passes into the burning out mode T5
after which it proceeds to the new START immediately.
b) S10 = 2… Function when after a power supply failure the electronic control unit tests the status
of the burner, evaluating with the use of the photocell or by means of the flue gas temperature that
the burner (boiler) is still burning passes over directly to the normal RUN mode in accordance
with a certain algorithm.
CAUTION - Never use for the A85 burner - function for other types of devices (danger
of return burning)
• Parameter S11
– Photocell sensitivity – threshold for fuel ignition ……. (30 %) - do not change
• Parameter S12 – Photocell sensitivity for flame sensing - threshold for embers... (1 %) - do not change
• Parameter S13– Fixed running time of the ignition spiral ……. (0 min) - do not change
Function of the ignition spiral when at every start the ignition spiral runs for a fixed time defined
by a direct value, independently on flame evaluation by the photocell or flue gas sensor. It is
designed for special applications and in the case of its activation the function of automatic flame
sensing from embers, characterized by parameter S12, is automatically switched off.
EN
• Parameter S14 – characterizes the second reserve R2 - additional output - function … (12)
The second reserve R2 is used for controlling the pump in boiler circuit
CAUTION – In the standard setting when parameter S1 is set to 2, you can connect to the
reserve
A (approx. 566 VA).
In the setting when parameter S1 is set to 4, which means that at the start both the ignition
spirals are activated simultaneously, you can connect to the reserve
nal an applian¬ce with the maximum current of 0.29 A (approx. 67 VA).
if:
a) S14 = 1…. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be closed and the reserve output will be energized. Thanks to this you can start a spare source
of energy for heating of the building as e.g. a gas, electric or oil boiler.
R, R2, R5 and R6
reserve terminal an appliance with the maximum current of 2.46
R, R2, R5 and R6
www.atmos.cz
termi-
EN-31
EN
Operation and Maintenance Manual - EN
b) S14 = 2….. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be opened and the reserve output will not be energized. Thanks to this a signal can be sent to an
electrically backed up AB01 ATMOS GSM module controller that will send information that there
is a system fault or the system is not energized. This is the opposite logic (to S14 = 1), which
means that during normal operation the reserve is energized.
c)
S14 = 3…… The reserve function as the output function for the burner fan, when the
reserve output is closed, is energized always when the burner fan is running (fan mode only
100 % or OFF). This function is applied if you want the boiler fan or extraction fan in the chimney
to run together with the burner fan. This function is designed for direct control of an fan directly
from the burner (e.g.
d) S14 = 4…… The reserve function as the reversed function of the output for the burner fan,
when the reserve output is off, is not energized always when the burner fan is running. This
function is always activated if you connect the A25 burner with the AS25 set containing the
AD02 or AD03 module, which in this case controls the extraction fan of the boiler. Install the
AD02 or AD03 module under the instrument hood of the boiler and connect it electrically
between the boiler terminal board and the extraction fan, see the wiring diagram.
This setting and connection with AD02 or AD03 module and special connector (jumper to main
switch) is standardly used for SP(X) boilers with the function for automatic start after wood
is burnt out activated (AUTOSTART – S34 = 1 or S34 = 2). Boiler exhaust fan is running
simultaneously with the pellet burner during the AUTOSTART function.
D80P, P80,
DxxPX, PXxx).
e) S14 = 5…… Reserve function as the output function for the Z1 ignition spiral when the reserve
copies the run of the ignition spiral.
f) S14 = 6….. Cleaning function of the combustion chamber or grill (flap). If the burner is in the
normal START, RUN and STOP mode, the output is not energized. The output is only energized
for the limited time T11, which continues immediately after the expiration of time T5 in the
STOP mode. It is not used with the A25 burner.
g) S14 = 7….. Reserve function as the output function for the external worm conveyor, when the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The
reserve output work independently of the condition of the actual output for the external worm
conveyor. This means that if the standard output for the external conveyor gets damaged, the
reserve will work independently in accordance with the same program, and therefore it can be
used as a replacement for the damaged output.
h) S14 = 8….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The reserve works in dependence on the status of the actual output for the external worm conveyor.
This means that if the output for the external conveyor gets damaged, the reserve will be switched
off automatically. This function is suitable in situations when you need to control another external
conveyor that supplies (feeds) pellets from a larger distance to the main conveyor from which the
pellets fall directly to the burner.
32-EN
i) S14 = 9….. Reserve function as the output function for the external worm conveyor, when the
reserve copies the run of the external worm conveyor, but with the difference that it does not cycle,
www.atmos.cz
Operation and Maintenance Manual - EN
but runs permanently both during the drawing of the ignition amount and during both the
times T4 and T6. Thus, the other external conveyor runs continuously and works independently
of the status of the actual output for the external worm conveyor. This means that if the output
to the main external conveyor from which pellets directly fall to the burner gets damaged, the reserve will keepworking independently. This function can be used in cases when you need to
control another external conveyor that supplies (feeds) pellets from a larger distance to a pellet bin at the boiler from which the main external conveyor draws pellets to supply them directly to
the burner. Caution - the other external conveyor must always be controlled with an additional
level sensor (level meter) that will maintain the level of pellets in the pellet bin at the boiler.
S14 = 10….. Reserve function as the output function for the external worm conveyor, when
j)
the reserve copies the run of the external worm conveyor, but with the difference that it does not
cycle, but runs permanently both during the drawing of the ignition amount and during
both the times T4 and T6. Thus, the other external conveyor runs continuously, but it works in
dependence on the status of the actual output for the external worm conveyor. This means that if
the output for the external conveyor from which pellets fall directly to the burner gets damaged,
the reserve will be switched off automatically. This function is convenient in cases when you
need to control another external conveyor that supplies (feeds) pellets from a larger distance to a pellet bin at the boiler from which the main external conveyor draws pellets to supply them
directly to the burner. Caution - the other external conveyor must always be controlled with an
additional level sensor (level meter) that will maintain the level of pellets in the pellet bin at the
boiler. This is a similar function to S6 = 9, but with a higher degree of safety.
EN
k) S14 = 11….. Reserve function for controlling boiler exhaust fan for SP(X) boiler types when the
function for automatic start after wood is burnt out is activated. This function ensures that boiler
exhaust fan is running only during wood burning after the wood is burnt out. When the burner is
run on pellets, the boiler exhaust fan remains switched off. This function is used if you do not need
or want to use the boiler exhaust fan while the burner is running. Install the AD02 module under
the instrument hood of the boiler and connect it electrically between the boiler terminal board and
the extraction fan, see the wiring diagram.
WARNING – this is not a standard setting for SP(X) boilers with the function of automatic
start (AUTOSTART – S34 = 1 or S34 = 2) after wood is burnt out (standard setting is
S6 = 4).
l) S14 = 12…..Reserve function for direct control of pump in the boiler circuit from the burner
regulation (boiler terminal board). This function controls the pump in the boiler circuit without
using AD02 or AD03 modules. This is applicable only for boilers that do not allow heating with
wood (not even in emergency situations). E.g. D14P, P14, D21P, P21, D25P, P25, D80P, P80,
DxxPX, PXxx. Pump output must be switched to reserve R2 on the boiler terminal board and the
TK sensor must be installed before this function can be activated. After activation, S37, S38, S39,
S40 temperature parameters must be checked and configured.
m) S14 = 13…..Reserve function is the reverse output function for controlling the pump in
the boiler circuit from the burner regulation (output cable from boiler with a connector – white
inside) via AD02 or AD03 modules. This function controls the pump in the boiler circuit using
AD02 or AD03 modules ranged into a set with pump thermostat installed into the boiler panel.
www.atmos.cz
EN-33
EN
Operation and Maintenance Manual - EN
This method of pump controlling can be used for any ATMOS pellet boiler, and is therefore
recommended. AD02 or AD03 modules must be inserted and connected under the boiler hood
and the TK sensor must be installed before this function can be activated. After activation, S37,
S38, S39, S40 temperature parameters must be checked and configured.
n) S14 = 14….. Reserve function for direct control of solar heating pump from the burner regulation
(boiler terminal board). This function control solar pump when automatic sensor switching function
is activated (S15 = 3), where the boiler is connected with accumulation tank equipped with solar
exchanger and collectors. The system requires TV, TK, TS and solar sensors to be connected to the
TSV solar panel. This function never uses AD02 or AD03 modules.
After activation, S26, S27, S28, S29, S30, S31, S32, S33 temperature parameters must be checked
and configured.
This function is specially designed for boilers: D14P, P14, D15P, P15, D20P, P20, D21P, P21,
D25P and P25
CAUTION - the direct controlling function of solar heating from pellet burner cannot be
used for SP(X) boilers and boilers with burner built into the upper doors. This function also
cannot be used when the pump is simultaneously controlled in the boiler circuit from the
burner regulation (TK sensor cannot be simultaneously in boiler and accumulation tank)
o) S14 = 15….. Reserve function for the compressor control during the function for automatic
burner cleaning using compressed air. Power element designed for switching and powering the
compressor (e.g. contactor) must be connected between reserve output R2 and the compressor.
This function is connected with S6(14), S41, S42, S43, S44, S45, S46, S47 parameter, which must
be checked and configured.
p) S14 = 16….. Reserve function for controlling el.fan during the function for automatic burner
cleaning using compressed air. This function is connected with S6 (14), S41, S42, S43, S44, S45,
S46, S47 parameter, which must be checked and configured.
Special function for turning on reserve output R2 according to the temperature of a concrete
sensor:
a) e.g. function: TS>… means that if the TS sensor temperature is higher then the set value in S52
parameter – Temperature C, reserve output R2 will be activated
b) e.g. function: TS<… means that if the TS sensor temperature is higher then the set value in
S52 parameter – Temperature C, reserve output R2 will be deactivated
c) e.g. function: TS, TV>… means that if the TS and TV sensor temperature is higher at the same
time then the set value in S52 parameter – Temperature C and S54 – Temperature D, reserve output
R2 will be activated (Temperature C = first position (TS), Temperature D = second position (Tv)).
34-EN
d) e.g. function TS, TK<… means that if the TS and TK sensor temperature is higher at the same
time then the set value in S52 parameter – Temperature C and S54 – Temperature D, reserve output
R2 will be deactivated (Temperature C = first position (TS), Temperature D = second position
(Tk)).
• Parameter S15 – Operation function of the burner by the two temperatures in the accumulation
tank …(1)
a) S15 = 1… The function is off, the burner works based on the thermoregulator on the boiler panel
b) S15 = 2 …. The function is activated and the pellet burner works based on the two temperatures
(sensors) in the accumulation tank – TV and TS (recommended tank volume: 1000 l).
The temperature of the bottom sensor (TS) is the temperature at which the burner is switched off
and the fuel burns out.
The temperature of the top sensor (TV) is the temperature at which the burner is switched on again.
The burner screen displays the TV and TS temperatures.
EN
c) S15 = 3 …. The function is activated and the pellet burner works based on the two temperatures
(sensors) in the accumulation tank – TV and TS (recommended tank volume: 1000 l).
The temperature of the top sensor (TV) is the temperature at which the burner is switched on again.
The temperature of the bottom sensor (TS or TK) is the temperature at which the burner is stopped.
Whether the burner is switched off based on the TS or TK sensor is decided by the temperature of
the solar panel (TSV) and the temperature in the lower part of the accumulation tank (TS), where a
solar exchange is built-in. If the solar panel can efficiently heat up water in the accumulation tank,
the burner is turned off based on the TK sensor, so that the tank can store energy from the sun.
If the energy delivered from the solar collector drops below a certain limit (temperature), the
deactivation logic of the burner is automatically switched back to be based on the TS sensor (S26
= 1).
However, it is possible to set that the switching may only occur after a certain period of time
(S29 = 2nd digit means the length of delay between switches, in hours). Another variant is to have
the burner work permanently based on the TV and TK temperatures (S26 = 0).
d) S15 = 4 …. The function is off and the burner works based on the TK temperature, protected
by the thermoregulators on the boiler panel. After this function is activated, we need to check and
possibly setup its temperature parameters S18 and S19.
CAUTION - if S15 = 2 not possible to set S6 = 14 a S14 = 14. Je-li S15 = 3 not possible
to setS6 = 11, S14 = 11, S6 = 12, S14 = 12, S6 = 13, S14 = 13. Je-li S15 = 1, S15 = 4 not
possible to set S14 = 14.
www.atmos.cz
EN-35
Operation and Maintenance Manual - EN
• Parameter S16 - Temperature of the top sensor (TV) at which the burner is started….. (60 °C)
It is the minimum temperature of water that can be reasonably utilized in the heating system.
• Parameter S17 - The temperature of the bottom sensor ((TS, or TK for S15 = 3)) at which the
burner is stopped….. (75 °C)
It is the maximum temperature of water that corresponds to requirements of the heated building
and the designed heat exchangers in the system (radiators and floor heating).
EN
CAUTION – Do not set this value too high to avoid disconnection of the safety thermostat on
the boiler. Always set the control thermostat on the boiler to the maximum value (95 °C). If
the control thermostat on the boiler intervenes before the burner is switched off by the signal of
the TS sensor in the bottom part of the accumulation tank, the system probably finds itself in the
state of hydraulic imbalance and you should check and adjust it. You can e.g. throttle the shortcut
in the boiler circuit or the return line from the heating system towards the accumulation tank.
• Parameter S18 – describes the required temperature of boiler TK, which the burner is switched
off at if S15 = 4… (85 °C)
• Parameter S19
- difference between TK temperature (for re-starting the burner) for S15 = 4…(5 K)
• Parameter S24– maximum flue gas temperature... (250 °C)
If you connect a flue gas temperature sensor (TS) to the burner and in a mode of the burner this
limit value is exceeded, a warning message will appear on the display. It will notify the operator of the
necessity to clean the heat exchanger of the boiler or the installer of the necessity to reduce the burner
power to avoid unnecessary wasting of fuel. The operation of the burner is not limited by this message in any way and to clear the message you can just switch off and on the main switch on the
boiler.
•
Parameter S26
TK sensor, when S15 = 3. Connection of the boiler with a tank equipped with a solar exchanger… (1)
– is the function for defining the logic of deactivating the burner based on the TS or
a) S26 = 0…. The burner permanently works based on the upper TV sensor (activation temperature)
and via the TK sensor (deactivation temperature). The lower part of the tank permanently has
enough room for energy from the solar collector (TS sensor)
b) S26 = 1… the burner permanently works based on the upper TV sensor (activation temperature)
and the configured logic automatically takes care of switching between the middle TK sensor and
lower TS sensor. Whether the burner is deactivated based on TS or TK is decided based on the
temperature on the solar panel (TSV) and the temperature on the lower part of the accumulation
tank (TS), where the solar exchanger is located. If the solar panel can efficiently heat up water in
the accumulation tank, the burner is turned off based on the TK sensor, so that the tank can store
energy from the sun.
• Parameter S17 - activation difference of function S26 = 1… (10 K)
If the temperature on the solar panel (TSV) exceeds the temperature in the lower part of the tank
by the activation difference, the boiler deactivation function will be switched from the bottom TS
sensor to the middle TK sensor.
If a function for solar panel pump control is activated directly from the boiler regulation (S6 = 14
or S14=4), the same logic will be used to activate the solar pump.
36-EN
www.atmos.cz
Operation and Maintenance Manual - EN
• Parameter S28– deactivation difference of function S26 = 1… (3 K)
If the temperature on the solar panel (TSV) exceeds the temperature in the lower part of the tank
by the deactivation difference, the boiler deactivation function will be switched from the middle
TK sensor to the bottom TS sensor.
If a function for solar panel pump control is activated directly from the boiler regulation (S6 = 14
or S14 = 4), the same logic will be used to activate the solar pump.
• Parameter S29 – is the function for delaying the automatic switching from the TK sensor back to
the TS sensor for controlling the burner based on two temperatures (sensors, S15 = 3)... (0 hours)
This function will cause the function for deactivating the burner to be switched from the middle
TK sensor to the bottom TS sensor after the time listed in parameter S29 passes, if the temperature
on the solar panel TSV is lower or greater only by the deactivation difference (Parameter S28) than
the temperature in the lower part of the tank where the solar exchange is located.
The set value means the number of hours, e.g.: S29 = 2 means a switch delay of 2 hours.
• Parameter S30 – is the function of the minimal operating time of the solar pump when the
conditions for its activation and then deactivation are met (function S15 = 3)… (3 min)
The set value means the number of minutes, e.g.: S30 = 3 means 3 minutes
EN
• Parameter S31 – characterizes the required temperature TS in the lower part of the accumulation
tank where the solar exchanger is located, during the function of charging the accumulation tank
by the solar collector. (function S15 = 3)… (75 °C)
Once it is reached, the solar pump will be turned off.
• Parameter S32 – characterizes the maximum temperature TV in the accumulation tank during the
function of charging the accumulation tank by the solar collector (function S15 = 3)… (100 °C)
The solar pump will be turned off if it is exceeded.
• Parameter S33 – characterizes the maximum temperature TSV of the solar collector, for which
the solar pump will still remain in operation (function S15 = 3)… (115 °C)
The solar pump will be turned off if it is exceeded.
• Parameter S34 – is the function of automatically starting the pellet burner (AUTOSTART) after
the wood burns out. The function is specially created for SP(X) burners, however it may also be
used for two separate boilers… (0)
a) S34 = 0…. The automatic start function is off
b) S34 = 1…. The automatic start function is on. The pellet burner will be turned on when the
temperature of exhausts TSV drops below the set value (S36 = 80), e.g. below 80 °C
c) S34 = 2…. The automatic start function is on. The pellet burner will be turned on when two
conditions are met:
- the temperature of the boiler TK drops below the set value (S35 = 75), e.g. below 75 °C
- the temperature of exhausts TSV drops below the set value (S36 = 80), e.g. below 80 °C
www.atmos.cz
EN-37
Operation and Maintenance Manual - EN
If the function (parameter S34) is turned on in the boiler, the following practice is used for
boilers SP(X):
If the boiler is burning out but the wood container still contains enough wood, we may directly
switch the boiler switch from wood to pellets.
The pellet burner will perform a DIAGNOSTIC which will be used to ascertain the current status
of the boiler (temperature of exhausts, temperature of the boiler, temperature in the accumulation
tank)
If the conditions for immediate start of the burner are not met (see above), the burner will remain
EN
on standby, where the flue exhaust fan will remain in operation (if set) so that the wood can
properly finish burning (S6 = 4). AUTOSTART will start flashing on the burner screen.
If the AUTOSTART sign flashes slowly, the conditions set by the function (S34 = 1 or S34 = 2)
are not met.
If the AUTOSTART sign flashes quickly, the previous conditions are met, but the conditions set
by function (S15 = 2) are not, which means that the temperature on the accumulation tank did not
drop below the value set by S16 or the regulation thermoregulator on the boiler is not activated, i.e.
the end switch is not pressed (a star is not displayed on the boiler screen near the thermoregulator
symbol)
If all the conditions are met, the burner will start automatically.
INFO – In case of an electric outage, the burner will perform a DIAGNOSTIC and, if all
conditions are met, will burn out and return to normal operation. Otherwise it will await the
fulfillment of previous conditions (drop of exhaust and water temperature).
If we want to use wood to heat up the boiler, it suffices to place the switch on the wood
position. However, it is better to first keep the switch on the „0“ position for 10 - 15 minutes
so that the burner can properly burn out. This is an ideal time to prepare the fuel for stoking.
WARNING – SP(X) boilers do not allow you to control the solar heating function directly
from the pellet burner. Additionally the TK and TSV sensors are used for measuring the
temperature of the boiler and exhausts during this function.
• Parameter S35 – characterizes the limit (max.) temperature of the boiler TK, during which the
burner will automatically start during the AUTOSTART function (S34 = 2)… (75 °C)
• Parameter S36– characterizes the limit (max.) temperature of the exhausts TSV, during which the
burner will automatically start during the AUTOSTART function (S34 = 2)… (80 °C)
WARNING – after placing the exhaust sensor TSV on a side of the burner flue pipe, the
TSV temperature is not the exact temperature of the exhausts but the difference temperature
for the automatic start function. If we want to place the exhaust sensor directly on or into the
flue pipe to measure the exhaust temperature precisely, it is necessary to always use a sensor
with a higher heat resistance of up to 400 °C.
• Parameter S37 – characterizes the requires temperature of the boiler TK during which the pump in
the boiler circuit will be activated. This will only occur if the required temperature is reached and
the boiler is in OPERATION or burn-out mode (S14=13 with modules AD02 or AD03)… (75 °C)
It is also necessary to re-check or set parameters S38, S39, S40
38-EN
www.atmos.cz
Operation and Maintenance Manual - EN
• Parameter S38 – deactivation difference for parameter S37, of the pump in the boiler circuit
(S14 = 13 or S6 = 13)… (2 K)
If the temperature of the boiler TK drops by more than the deactivation difference S38, the pump
in the boiler circuit will be turned off in the OPERATION or STOP (burn-out) modes.
• Parameter S39 – characterizes the emergency temperature of the boiler TK, during which the
pump in the boiler circuit will be activated (S14 = 13 with modules AD02 or AD03)… (93 °C)
Activation will be carried out regardless of special functions of the burner (function S40). The
function works based on the deactivation difference specified in parameter S38.
• Parameter S40 – is the function for after-running of the pump in the boiler circuit used based on
boiler type (S14 = 13, S6 = 13)… (0)
a) S40 = 0…. The automatic deactivation function for the pump in the the boiler circuit after the
pellet burner burns out is off (after the time specified in parameter T5 runs out). The pump will
be switched off after the temperature of the boiler TK drops (S38, S39). Designated for ceramic
boilers with a large momentum (with the option of stoking with wood).
b) S40 = 1... The automatic deactivation function for the pump in the boiler circuit after the pellet
burner burns out is on. The pump will be switched off immediately after the burner burns out, after
the time specified in parameter T5 runs out. The function designated by parameter S39 is active.
Designated for boilers with minimal momentum without ceramics (D14P, P14, D21P, P21, D25P, P25).
EN
• Parameter S41 – is the function for automatic cleaning of the burner by compressed air after a
certain number of work cycles (burn-outs). The function utilizes both reserve outputs (S16 = 16,
S14 = 15) – nonstandard function… (11)
a) S41 = 1 - 9… function when the cleaning of the burner will be performed only once after
running a given number of cycles (1, 2, 3, 4, 5, 6, 7, 8, 9 - number of cycles)
b) S41 = 11 - 19… function when the cleaning of the burner will be performed always twice after
running a given number of cycles (11 = 1, 12 = 2, 13 = 3, 14 = 4, 15 = 5, 16 = 6, 17 = 7, 18 = 8,
19 = 9 - number of cycles)
If the parameter S41 = 0 or 10, the function is turned off.
• Parameter S42 – is the function for automatic cleaning of the burner by compressed air after a
certain period of operation. On the subsequent termination of a work cycle (burnout), the burner
mouth will be cleaned. The function utilizes both reserve outputs (S16 = 16, S14 = 15)… (4 hours)
After the time S42 runs out the pellet burner burns out and cleans. AUTO STOP will be shows on
the burner screen.
The set value represents the actual time in hours.
• Parameter S43 – is the function for automatic cleaning of the burner by compressed air after
a certain period of operation. After the set period elapses, the burner will immediately stop, be
cleaned and re-started if necessary and all conditions for START are met (regardless of parameters
S41 and S42). The function utilizes both reserve outputs (S16 = 16, S14 = 15)… (4 hours)
The set value represents the actual time in hours.
www.atmos.cz
EN-39
Operation and Maintenance Manual - EN
• Parameter S44 – is the compressor function for automatic cleaning of the burner by compressed
air, which determines the duration of compressor operation used for preparing a sufficient amount
of compressed air (pressure function S6 = 16)… (3 min)
The set value represents the actual time in minutes.
• Parameter S45 – is the electric valve function for automatic cleaning of the burner by compressed
air, which determines how long the el. valve is open to perfectly clean the combustion chamber of
the burner (S14 = 15)… (2 s)
The set value represents the actual time in seconds.
EN
• Parameter S46 – is the burner fan function which sets the type of used fan with rotation scanning.
Number of impulses.… (
1-EBM
)
• Parameter S47 – is the function of fan 2 which sets the type of used fan with rotation scanning.
Number of impulses – do not change the factory setting… (4)
a) S47 = 12 - EBM..... radial blower of the burner
b) S47 = 4 - ATAS..... exhaust blower of the boiler
c) S47 = 0..... second method for switching off the blower 2 speed sensing
• Parameter S48 – characterizes temperature TEMPERATURE A in the applications of function
S6 = 17 to 36… (75 °C)
This is a free function for the reserve output R (R5) on the first position (Temperature A = first
position in function S6 = 17 to 36 (S67 = 17 až 36)).
• Parameter S49 – characterizes the activation or deactivation difference for TEMPERATURE A
in the applications of function S6 = 17 to 36… (5K)
This is the difference for the free function of reserve output R (R5) on the first position (difference
for Temperature A = difference for the first position in the function S6 = 17 to 36 (S67 = 17 až 36)).
• Parameter S50 – characterizes TEMPERATURE B in the applications of function S6 = 25 to
36...….(75 °C)
This is a free function for the reserve output R (R5) on the first position (Temperature B = second
position in function S6 = 25 to 36 (S67 = 17 až 36)).
• Parameter S51 – characterizes the activation or deactivation difference for TEMPERATURE B
in the applications of function S6 = 25 to 36… (5K)
This is the difference for the free function of reserve output R (R5) on the first position (difference
for Temperature B = difference for the first position in the function S6 = 25 to 36 (S67 = 17 až 36)).
• Parameter S52 – characterizes TEMPERATURE C in the applications of function S6 = 25 to
36...… (75 °C)
This is a free function for the reserve output R2 (R6) on the first position (Temperature C = second
position in function S14 = 17 to 36 (S67 = 17 až 36)).
• Parameter S53 – characterizes the activation or deactivation difference for TEMPERATURE C
in the applications of function S14 = 17 to 36… (5K)
This is the difference for the free function of reserve output R2 (R6) on the second position
(difference for Temperature C = difference for the second position in the function S14 = 17 to 36
(S68 = 17 až 36)).
40-EN
www.atmos.cz
Operation and Maintenance Manual - EN
• Parameter S54 – characterizes TEMPERATURE D in the applications of function S14 = 25 to
36…. (75 °C)
This is a free function for the reserve output R2 (R6) on the first position (Temperature D = second
position in function S14 = 25 to 36 (S68 = 17 až 36)).
• Parameter S55 – characterizes the activation or deactivation difference for TEMPERATURE D
in the applications of function S14 = 25 to 36… (5K)
This is the difference for the free function of reserve output R2 (R6) on the second position
(difference for Temperature D = difference for the second position in the function S14 = 25 to 36
(S68 = 17 až 36)).
• Parameter S56 – characterizes control of functioning (speed sensing) of the exhaust blower of
the boiler (blower 2); setting may be different according to use – must never be changed...... (1)
a) S56 = 0 ..... control of the exhaust blower of the boiler turned off
a) S56 = 1 ..... control of the exhaust blower of the boiler turned on
If S56 = 1, parameters S47 and S57 are activated (visualized).
• Parameter S57 – characterizes minimum speed of the blower 2 ....... (1500 rpm) – must never
be changed
adjustable range..... 1000 – 3200 rpm
It is a function of the control of proper functioning of the exhaust blower of the boiler.
When the blower is running at the speed lower than set, “ALARM VENT 2” is declared.
EN
This function is not used standardly.
• Parameter S58 – characterizes the amount of compressed air for the first pre-cleaningoftheburner
when installing pneumatic cleaning the burner. This is the time at which the partial fillingcompressor
air tank for pre-cleaning of the burner ... (10 s) - standardly do not change
Adjustable range...OFF, 1 - 120 s.
• Parameter S59 – characterizes the amount of compressed air for the second pre-cleaning of the
burner when installing pneumatic burner cleaning. This is the time at which the partial filling
compressor air tank for pre-cleaning of the burner... (20 s) - standardly do not change
Adjustable range...OFF, 1 - 120 s.
• Parameter S60 – characterizes the amount of compressed air for the third pre-cleaning of the
burner when installing pneumatic burner cleaning. This is the time at which the partial filling
compressor air tank for pre-cleaning of the burner... (30 s) - standardly do not change
Adjustable range...OFF, 1 - 120 s.
• Parameter S61 – characterizes the function for control of the boiler exhaust fan from the outlet for
the burner discharge fan via the AD04 module. The function is intended for models DCxxSP(X),
CxxSP, ACxxSP without flap with actuator fitted with the pneumatic burner cleaning options and the
activated function for automatic start of the burner following wood burnout - AUTOSTART... (0)
a) S61 = 0....... function OFF
b) S61 = 1....... function ON (for for profile A25 pneu)
Never activate this function for boilers DCxxGSP and DCxxSP(X), CxxSP, ACxxSP (Model 2018
equipped with flap with actuator).
www.atmos.cz
EN-41
Operation and Maintenance Manual - EN
• Parameter S62 – characterizes the function for control of the air valve (flap) with actuator (servo
drive) located in the pellet burner. This valve is operated from the outlet of the burner discharge
fan via the AD04 module integrated in the burner (from serial production - default configuration).
The function is intended for models DCxxGSP, DCxxSP(X), CxxSP, ACxxSP (Model 2018)... (1)
a) S62 = 0....... funkce OFF (for burners without flap with actuator)
b) S62 = 1....... function ON (for burners with flap with actuator - for models DCxxGSP and
DCxxSP(X), CxxSP, ACxxSP (Model 2018))
(Burners equipped with internal flap with actuator with AD04 module and the third (additional)
EN
2-pins connector.)
• Parameter S63 – characterizes the function of start delay of the pellet burner (AUTOSTART),
with function of automatic burner start after burnout of the wood. Start delay of the pellet burner
we use in case, that the operator wants to switch the selector switch from the position - wood
to the position - pellets immediately after firing up without waitng till the boiler ran at nominal
output (TSV and TK temperatures not reached). This will always delay the start of the burner
60/120/180/240 minutes. When activating this function the display of the burner shows the time
remaining until the automatic start of the pellet burner (cold condition) or until the change to the
normal function of automatic start characterized with the parameter S34.
In case of that the operation waste gas temperature will be reached (parameter S36 = TSV + 20
K) ends the countdown of the automatic start and the burner goes directly to normal auto start
(parameter S34).
a) S63 = OFF... function switched off - factory stetting
b) S63 = 1... start delay of 1 hour (60 min) - recommended setting
This special function is active in the program version 38 and newer.
INFO - when putting burner into operation with activated function S63 = 1 (or 2, 3, 4) the
plumber may once enter the code 1111 and to skip from AUTOSTART directly to the burner
START (TSV and TK below than defined).
• Parameter S64 - characterizes the temperature of flue gas inside the heat exchanger of the boiler.
It serves to diagnoses the absense of pellets in the boiler tank or shows low output of the boiler. It
is not temperature of flue gas. Function is only for DxxPX (PXxx) boilers, burner profile A25PX.
Do not change… (130 °C)
• Parameter S65 - characterizes start up time of the burner in OPERATION mode during which has
to be reached minimal waste gas temperature in the heat exchanger of the boiler set by parameter
S64.
If in this time the boiler does not reach temperature the display shows ALARM SETTINGS –
REFILL PELLETS. In such case check the set output in parameters T4 and T6 and increase it.
In case of low pellets level in the tank fill up the fuel. Function is only for DxxPX (PXxx) boilers,
burner profile A25PX. Do not change… (120 min)
42-EN
www.atmos.cz
Operation and Maintenance Manual - EN
• Parameter S66 - characterizes run-out time of the burner in OPERATION mode during which the
burner stays in operation when waste gas temperature in the heat exchanger of the boiler descend
under the temperature characterized by the parameter S64.
After the time characterized by the paramater S66 is display ALARM PELLETS – REFILL
PELLETS. In this case check the pellet tank and fill up the fuel.
DxxPX (PXxx) boilers are designed that after fuel refill is neccesary only to turn off and on the
main swich on the boiler. So it is not neccesary fill up the pellets into the conveyor after showen
ALARM PELLETS – REFILL PELLETS.
Function is only for DxxPX (PXxx) boilers, burner profile A25PX. Do not change… (30 min)
• Parameter S67 - characterizes function of R5 reserve output similar with S6 and S14 parameters
with instaled AC07X-C additional module. Primary is this reserve used to control air pump for
Function is also for DxxPX (PXxx) boilers, burner profile A25PX (A25PX pneu)
if:
a) S67 = 1…. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be closed and the reserve output will be energized. Thanks to this you can start a spare source
of energy for heating of the building as e.g. a gas, electric or oil boiler.
EN
b) S67 = 2….. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be opened and the reserve output will not be energized. Thanks to this a signal can be sent to
an electrically backed up AB01 ATMOS GSM module controller that will send information that
there is a system fault or the system is not energized. This is the opposite logic (to S6 = 1), which
means that during normal operation the reserve is energized.
c) S67 = 4…… The reserve function asthe reversed function of the output for the burner fan,
when the reserve output is off, is not energized always when the burner fan is running. This
function is always activated if you connect the A25 burner with the AS25 set containing the
AD02 or AD03 module, which in this case controls the extraction fan of the boiler. Install the
AD02 or AD03 module under the instrument hood of the boiler and connect it electrically
between the boiler terminal board and the extraction fan, see the wiring diagram.
This setting and connection with AD02 or AD03 module and special connector (jumper to main
switch) is standardly used for DCxxSP boilers with the function for automatic start after
wood is burnt out activated (AUTOSTART – S34 = 1 or S34 = 2). Boiler exhaust fan is running simultaneously with the pellet burner during the AUTOSTART function.
d S67 = 7….. Reserve function as the output function for the external worm conveyor, when the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The
reserve output work independently of the condition of the actual output for the external worm
conveyor. This means that if the standard output for the external conveyor gets damaged, the reserve will work independently in accordance with the same program, and therefore it can be used
as a replacement for the damaged output.
e) S67 = 8….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor (cycles between time T4 and T6). The reserve works in dependence on the status of the actual output for the external worm conveyor.
www.atmos.cz
EN-43
Operation and Maintenance Manual - EN
This means that if the output for the external conveyor gets damaged, the reserve will be switched
off automatically. This function is suitable in situations when you need to control another external
conveyor that supplies (feeds) pellets from a larger distance to the main conveyor from which the
pellets fall directly to the burner.
f) S67 = 15….. Reserve function for the compressor control during the function for automatic
burner cleaning using compressed air. Power element designed for switching and powering the
compressor (e.g. contactor) must be connected between reserve output R5 and the compressor.
EN
This function is connected with S68, S41, S42, S43, S44, S45, S46, S47 parameter, which must be
checked and configured.
g) S67 = 16….. Reserve function for controlling el.fan during the function for automatic burner
cleaning using compressed air. This function is connected with S68, S41, S42, S43, S44, S45, S46,
S47 parameter, which must be checked and configured.
Special function for turning on reserve output R5 according to the temperature of a concrete sensor:
a) e.g. function: TS>……. means that if the TS sensor temperature is higher then the set value in
S48 parameter – Temperature A, reserve output R5 will be activated
b) e.g. function: TS<……. means that if the TS sensor temperature is higher then the set value in
S48 parameter – Temperature A, reserve output R5 will be deactivated
c) e.g. function: TS,TV>……. means that if the TS and TV sensor temperature is higher at the
same time then the set value in S48 parameter – Temperature A and S50 – Temperature B, reserve
output R5 will be activated (Temperature A = first position (TS), Temperature B = second position
(Tv)).
d) e.g. function TS,TK<……. means that if the TS and TK sensor temperature is higher at the
same time then the set value in S48 parameter – Temperature A and S50 – Temperature B, reserve
output R5 will be deactivated (Temperature A = first position (TS), Temperature B = second position (Tk)).
Function is also for DxxPX (PXxx) boilers, burner profile A25PX (A25PX pneu)
if:
a) S68 = 1…. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be closed and the reserve output will be energized. Thanks to this you can start a spare source
of energy for heating of the building as e.g. a gas, electric or oil boiler.
b)
S68 = 2….. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be opened and the reserve output will not be energized. Thanks to this a signal can be sent to an
electrically backed up AB01 ATMOS GSM module controller that will send information that there
is a system fault or the system is not energized. This is the opposite logic (to S14 = 1), which
means that during normal operation the reserve is energized.
c) S68 = 3…… The reserve function as the output function for the burner fan, when the re-
serve output is closed, is energized always when the burner fan is running (fan mode only
100 % or OFF). This function is applied if you want the boiler fan or extraction fan in the chimney
to run together with the burner fan. This function is designed for direct control of an fan directly
from the burner (e.g. DxxPX, PXxx).
EN
d) S68 = 9….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor, but with the difference that it does not
cycle, but runs permanently both during the drawing of the ignition amount and during both
the times T4 and T6. Thus, the other external conveyor runs continuously and works indepen-
dently of the status of the actual output for the external worm conveyor. This means that if the
output to the main external conveyor from which pellets directly fall to the burner gets damaged,
the reserve will keepworking independently. This function can be used in cases when you need
to control another external conveyor that supplies (feeds) pellets from a larger distance to a pel-let bin at the boiler from which the main external conveyor draws pellets to supply them directly
to the burner. Caution - the other external conveyor must always be controlled with an additional
level sensor (level meter) that will maintain the level of pellets in the pellet bin at the boiler.
e) S68 = 10….. Reserve function as the output function for the external worm conveyor, when
the reserve copies the run of the external worm conveyor, but with the difference that it does not
cycle, but runs permanently both during the drawing of the ignition amount and during both
the times T4 and T6. Thus, the other external conveyor runs continuously, but it works in de-
pendence on the status of the actual output for the external worm conveyor. This means that if the
output for the external conveyor from which pellets fall directly to the burner gets damaged, the
reserve will be switched off automatically. This function is convenient in cases when you need to
control another external conveyor that supplies (feeds) pellets from a larger distance to a pellet bin at the boiler from which the main external conveyor draws pellets to supply them directly to
the burner. Caution - the other external conveyor must always be controlled with an additional
level sensor (level meter) that will maintain the level of pellets in the pellet bin at the boiler. This
is a similar function to S6 = 9, but with a higher degree of safety.
www.atmos.cz
EN-45
Operation and Maintenance Manual - EN
f) S68 = 11….. Reserve function for controlling boiler exhaust fan for DCxxSP(X), CxxSP,
ACxxSP boiler types when the function for automatic start after wood is burnt out is activated.
This function ensures that boiler exhaust fan is running only during wood burning after the wood
is burnt out. When the burner is run on pellets, the boiler exhaust fan remains switched off. This
function is used if you do not need or want to use the boiler exhaust fan while the burner is running. Install the AD02 module under the instrument hood of the boiler and connect it electrically
between the boiler terminal board and the extraction fan, see the wiring diagram.
EN
WARNING – this is not a standard setting for DCxxSP(X), CxxSP, ACxxSP boilers with
the function of automatic start
(AUTOSTART – S34 = 1 or S34 = 2) after wood is burnt out (setting is S68 = 4).
g) S68 = 12…..Reserve function for direct control of pump in the boiler circuit from the burner
regulation (boiler terminal board). This function controls the pump in the boiler circuit without
using AD02 or AD03 modules. This is applicable only for boilers that do not allow heating with
wood (not even in emergency situations). E.g. D14P, P14, D21P, P21, D25P, P25, DxxPX, PXxx.
Pump output must be switched to reserve R5 on the boiler terminal board and the TK sensor must
be installed before this function can be activated. After activation, S37, S38, S39, S40 temperature
parameters must be checked and configured.
h) S68 = 13…..Reserve function is the reverse output function for controlling the pump in
the boiler circuit from the burner regulation (output cable from boiler with a connector – white
inside) via AD02 or AD03 modules. This function controls the pump in the boiler circuit using
AD02 or AD03 modules ranged into a set with pump thermostat installed into the boiler panel.
This method of pump controlling can be used for any ATMOS pellet boiler, and is therefore
recommended. AD02 or AD03 modules must be inserted and connected under the boiler hood
and the TK sensor must be installed before this function can be activated. After activation, S37,
S38, S39, S40 temperature parameters must be checked and configured.
i) S68 = 14….. Reserve function for direct control of solar heating pump from the burner regulation (boiler terminal board). This function control solar pump when automatic sensor switching function is activated (S15 = 3), where the boiler is connected with accumulation tank equipped with
solar exchanger and collectors. The system requires TV, TK, TS and solar sensors to be connected
to the TSV solar panel. This function never uses AD02 or AD03 modules.
After activation, S26, S27, S28, S29, S30, S31, S32, S33 temperature parameters must be checked
and configured.
This function is specially designed for boilers: D14P, P14, D15P, P15, D20P, P20, D21P, P21,
D25P and P25
CAUTION - the direct controlling function of solar heating from pellet burner cannot be
used for
upper doors. This function also cannot be used when the pump is simultaneously controlled
in the boiler circuit from the burner regulation (TK sensor cannot be simultaneously in boiler
and buffer (accumulation tank))
j) S68 = 16….. Reserve function for controlling el.fan during the function for automatic burner
cleaning using compressed air. This function is connected with S67 (S68), S41, S42, S43, S44,
DCxxSP(X)/(EP), CxxSP, ACxxSP
boilers and boilers with burner built into the
46-EN
www.atmos.cz
Operation and Maintenance Manual - EN
S45, S46, S47 parameter, which must be checked and configured.
Special function for turning on reserve output R6 according to the temperature of a concrete sensor:
a) e.g. function: TS>… means that if the TS sensor temperature is higher then the set value in S52
parameter – Temperature C, reserve output R6 will be activated
b) e.g. function: TS<… means that if the TS sensor temperature is higher then the set value in
S52 parameter – Temperature C, reserve output R6 will be deactivated
c) e.g. function: TS, TV>… means that if the TS and TV sensor temperature is higher at the same
time then the set value in S52 parameter – Temperature C and S54 – Temperature D, reserve output
R6 will be activated (Temperature C = first position (TS), Temperature D = second position (Tv)).
d) e.g. function TS, TK<… means that if the TS and TK sensor temperature is higher at the same
time then the set value in S52 parameter – Temperature C and S54 – Temperature D, reserve output
R6 will be deactivated (Temperature C = first position (TS), Temperature D = second position
(Tk)).
• Offset TV – This function is used to compensate the offset of the TV temperature sensor
(input) in the range of ± 9.9 °C.
• Offset TS – This function is used to compensate the offset of the TS temperature sensor
(input) in the range of ± 9.9 °C.
• Offset TK – This function is used to compensate the offset of the TK temperature sensor (input) in the range of ± 9.9 °C
EN
• Offset TSV – This function is used to compensate the offset of the TSV temperature sensor
(input) in the range of ± 9.9 °C
• Reset – By means of this function you can use one command to reprogram the electronic unit
of the burner to the default settings.
• Restart – By means of this function you can use one command to reprogram the electronic unit
of the burner to the settings last set by the installer (under the installer code).
This allows the resetting of the control unit without changing the system settings in case of any
problems.
• Calibr. – This function makes it possible to calibrate inputs for temperature sensors with the use of
special calibration aids – function for the manufacturer only.
• Language – This is the selection function of the language in which the burner communicates with
the user.
The basic version of the program contains these language versions:
CZ - Czech
DE - German
EN - English
FR - French
IT - Italian
SP - Spanish
SE - Swedish
PO - Portuguese
RO - Romanian
PL - Polish
HU - Hungarian
48-EN
www.atmos.cz
Operation and Maintenance Manual - EN
INFORMATION menu
• Photocell – Displays the current value that the photocell sees.
• Temperature TS – displays the current TS temperature - (exhaust temperature (S15 = 1) or
lower temperature (S15 = 2))
• Temperature TV – displays the current TV temperature - (water temperature (S15 = 1) or upper
temperature (S15 = 2))
• Temperature TK – displays the current TK temperature - (boiler temperature ( S15 = 1, S15 = 2,
S15 = 4, S6 = 12, S6 = 13, S14 = 12, S14 = 13), central tank temperature (S15 = 3, S6 = 14,
S14 = 14 ), central tank temperature as a second deactivation sensor for burner TS2 (S26 = 0))
• Temperature TSV – displays the current TSV temperature - (exhaust temperature (S15 = 1,
S15 = 2, S15 = 4, S34 = 1, S34 = 2), solar collector temperature (S15 = 3, S6 = 14, S14 = 14))
EN
Short explanation:
This always depends on whether the burner regulation function based on two temperatures on the
accumulation tank is on or off, and whether the automatic start function after wood burns out is
activated.
The default settings are S15 = 1 and S34 = 0, which means that the function for controlling the
burner by two sensors is deactivated and the AUTOSTART function for DCxxSP(X)/(EP), CxxSP,
KCxxSP burns is also off. The burner is only controlled by thermoregulators on the boiler panel.
The customer may connect the exhaust temperature sensors TS and TSV and the water temperature
sensors TV and TK to the burner so that they only serve as information.
If we set S15 = 2, the function for regulation by two temperatures on the tank is activated and
so we connect the water tempearture sensor in the lower part of the tank TS and the water
temperature sensor in the upper part of the tank TV to the clamps of the burner connector.
If we set S15 = 3, the function for regulation by two temperatures on the tank is also activated,
simultaneously with the solar functions. It is thus also necessary to connect the TK sensor
located in the middle of the accumulation tank between the TV and TS sensors and the TSV
solar collector sensor.
If we are going to use the AUTOSTART function for boilers DCxxSP (S34 = 1 or S34 = 2), we must
also connect the TK sensor as a boiler sensor and the TSV sensor as the exhaust temperature
sensor.
If we are going to control the pump in the boiler circuit (recommended S14 = 12 or S14 = 13),
we must always connect the TK sensor.
www.atmos.cz
EN-49
Operation and Maintenance Manual - EN
• Fan speed - displays the current speed of the fan
• Fan speed 2 – displays the current speed of fan 2 (not used)
• Conveyor - displays the current status of the conveyor
• Conveyor faults - displays information for the service engineer
• Spirals - displays the current status of the ignition spirals
EN
• Spiral faults - displays information for the service engineer
• Reserve R - displays the current status of the reserve output R (parameter S6)
• Reserve R2 - displays the current status of the reserve output R2 (parameter S14)
• Reserve R5 - displays the current status of the reserve output R5 (parameter S67)
• Reserve R6 - displays the current status of the reserve output R6 (parameter S68)
TESTING menu
• Autotest – This function is used for automatic testing of all the basic elements of the burner as the
fan, conveyor, ignition spirals, etc. The testing is carried out consecutively in 20-second intervals
so that the engineer can monitor the operation of individual devices.
If this test is not sufficient, individual devices can be run separately, namely with the use of the
following functions.
CAUTION – During testing the burner is put out of operation, therefore before the start of
testing always let the burner properly burn out with the use the STOP command.
• Fan - this function is used to test the operation of the fan
• Conveyor - this function is used to test the operation of the conveyor
• Spiral 1 - this function is used to test the operation of the ignition spiral 1
• Spiral 2 - this function is used to test the operation of the ignition spiral 2
• Reserve R – this function is used to test the switching device (relay) of the reserve output R
• Reserve R2 – this function is used to test the switching device (relay) of the reserve output R2
• Reserve R5 – this function is used to test the switching device (relay) of the reserve output R5
• Reserve R6 – this function is used to test the switching device (relay) of the reserve output R6
• Photocell -
inserted in the burner or outside the burner in the natural light (never on the sun – will cause an alarm).
50-EN
used to test the photocell. Conduct the test by observing its sensitivity when it is
www.atmos.cz
Operation and Maintenance Manual - EN
17. Information - error messages - troubleshooting
General troubleshooting
CAUTION - All interventions into the electric systems must be performed by a qualified
person that has read the operation manual and has been trained by the manufacturer.
The equipment is not working:
If you come to a boiler with a burner that has been put out of operation, proceed as follows:
- Check whether the boiler and burner are energized, if so
- Check whether the tank is filled with pellets
- Check whether the conveyor is filled with pellets after it has run out of pellets (must always be
drawn before a new start, see the instructions), if so
- Read the error message on the burner display and find the error in the table below
WA R N I NG – if the burner did not call any ALARM, it is not maufnctioning and is
performing its own testing. Do not reset it by shutting off the power supply (switch),
wait for the alarm to sound or normal operation (wait 1 hour).
Table of error messages on the display - alarms
EN
Alarm
no.
1ALARM CRC
2ALARM
3ALARM
Message on the
display
SENSOR TV
SENSOR TS
Meaning Remedy
Wrong program checksum - er-
ror of the electronic unit
Failure of the sensor of water temperature in the boiler or
temperature in the top part of
the tank (TV) - the sensor is
short-circuited (damaged) or
disconnected
Failure of the sensor of ue
gas temperature or water temperature in the bottom part of
the tank (TS) - the sensor is
short-circuited (damaged) or
disconnected
Replace the electronic control
unit
Check the connection of the
sensor in the burner
Check the cable and sensor
for damage
Repair or replace
Check the connection of the
sensor in the burner
Check the cable and sensor
for damage
Repair or replace
www.atmos.cz
EN-51
Operation and Maintenance Manual - EN
EN
4ALARM
SENSOR TK
5ALARM
SENSOR TSV
6ALARM
VENTILATOR
7ALARM
VENT 2
Failure of the boiler temperature sensor TK in the boiler or
in the middle part of buer tank
– the sensor is short-circuited
(damaged) or disconnected
Failure of the waste gas or solar sensor TSV – the sensor is
short-circuited (damaged) or
disconnected
Failure of the fan or fan speed
sensor
the same as ALARM
VENTILATOR
Failure of the exhaust blower of
the boiler or defective capacitor
under the hood of the boiler
Check the connection of the
sensor in the burner
Check the cable and sensor
for damage
Repair or replace
Check the connection of the
sensor in the burner
Check the cable and sensor
for damage
Repair or replace
Check the cable of the speed
sensor and its connectors
Check whether the fan does not
size, it must be possible to turn
it easily by hand
Check the fuse on the electronic
board for the fan (1.0 A)
Repair or replace
the same as ALARM
VENTILATOR
Change the starting capacitor
for the exhaust fan
Change the exhaust fan of the
boiler.
8ALARM RELE
Error at the output for the external conveyor (neither output is
functional)
The external conveyor does not
feed fuel to the burner
Check and if necessary replace the fuse for the conveyor
(0.8 A)
Check the wiring between
electronic board and socket
Broken gearbox of the conveyor or output for conveyor
control
If you are not using the reserve, reconnect the conveyor
terminals to the reserve and
set the parameter S6 = 7. If
you use the reserve for other
applications, replace the electronic control unit.
52-EN
www.atmos.cz
Operation and Maintenance Manual - EN
9ALARM SPIRAL
CAUTION – In case of the ALARM SPIRAL error message you must always replace
both the ignition spirals and enter the activation code 1234. If after the replacement of the
ignition spirals and entering of the code the burner does not ignite (no ignition element is
heating), replace the AC07X electronic control unit and use the reserve output for full control of one ignition spiral. In such a case set the parameter S6 = 5 or S14 = 5..
Failure of both the ignition spirals
Check and replace both the
ignition spirals and check and
replace faulty fuses (3.15 A) on
the electronic board
Enter the activation code:
1234
EN
10ALARM START
11ALARM
PHOTOCELL
All the allowed start (ignition)
attempts have been exhausted
There are no more pellets or the
bin is empty
Faulty ignition spirals
Faulty photocell
Flame sensing error in the OPERATION mode
Replenish fuel, draw pellets to
the conveyor and turn of and
on the main switch on the boiler
Check the supply wires of the
ignition spirals, check the fuses (3.15 A), check the ignition
elements with the function in
the TESTING menu
Check the supply cable of the
photocell with the connector,
test the photocell with the use
of the function in the TESTING menu
Clean the photocell
If necessary, replace
www.atmos.cz
EN-53
Operation and Maintenance Manual - EN
EN
12ALARM SAFETY
Disconnected end switch on the
burner body
Disconnected safety thermostat
(95 °C (55 °C for boilers DxxPX, PXxx)) on the supply pipe
of pellets to the burner
Due to burning of poor-quality
pellets that produce cake and
prevent trouble-free burning of
pellets in the burner mouth the
supply hose gets subsequently
clogged and the temperature at
the safety thermostat rises
Clogged ue gas exhaust from
the boiler caused by obstructed
ue gas ways in the boiler, ue
gas duct or chimney by dust and
soot; the clogging causes return
ow of ue gas and heat to the
pellet supply hose and subsequent disconnection of the safety thermostat.
Properly tighten the burner to
the boiler and check the con
tact of the end switch. Check the
function of the sheet-metal stop
of the end switch
Clean the combustion chamber
of the burner, if necessary, emp
ty the supply hose of pellets, turn
o and on the main switch on the
boiler
Clean the combustion chamber
of the burner every day until you
have good-quality pellets made
of wood without bark (white pellets) that do not produce cake
and where it is sucient to clean
the burner mouth once every 2 to
4 weeks
Clean the whole boiler, ue gas
duct and chimney from dust and
soot, turn o and on the main
switch on the boiler
-
-
13HIGH FLUE
TEMP.!
blown fuse for the fan
(0.8A - 1.0A)
This is not an error, but a message
that noties the operator that the
maximum set temperature of ue
gas has been exceeded
If this message appears when
installing sensors TV and TS
on the accumulation tank - it is
a warning that has not yet been
activated function control burner (boiler) by two sensors on the
accumulation tank (S15 = 2)
They have been interchanged
on the terminal board
Check and change tha fan with
the fuse
Clean the boiler and then turn
o and on the main switch on
the boiler to clear the error
message
S15 parameter set from the
factory setting (S15 = 1) to the
value S15 = 2 - turn o and on
the main switch on the boiler
to clear the error message
Change the connection of the
sensor on the terminal board
and turn o and on the main
switch on the boiler to clear
the error message
54-EN
www.atmos.cz
Operation and Maintenance Manual - EN
14ALARM MODUL
15ALARM
SETTINGS
REFILL
PELLETS
16ALARM
PELLETS
REFILL
PELLETS
disfunction of
ule for pneumatic ash cleaning
system or other devices
wrong setting of burner output
due to low temp of flue gas in
the heat exchanger
lack of pellets in the fuel tank
AC07X-C
mod-
For DxxPX and PXxx
boilers
lack of pellets in the fuel tank
For DxxPX and PXxx
boilers
Check the connector between
AC07X-C and AC07X
change the AC07X-C module
or change the electronic control unit AC07X
Change output by T4 and T6
parametres
EN
Full up pellets
To reset error message turn
the main switch of the boiler
off and on
Full up pellets
To reset error message turn
the main switch of the boiler
off and on
www.atmos.cz
EN-55
Operation and Maintenance Manual - EN
If you are not sure, proceed as follows:
- Check whether the worm conveyor is really working by plugging the conveyor connector directly
to a wall socket, if so
- Turn off and on the main switch of the boiler and watch the lighting and flashing symbols on the
display of the electronic unit. Each start over a particular symbol on the display means that the
element or function is in operation or should be.
Each symbol on the display characterizes one element or function of the burner.
EN
- Indicates operation of the external conveyor
-
Indicates connected control thermostat of the boiler
- Indicates connected ignition spiral 1
- Indicates connected ignition spiral 2
- Indicates the fan running at the starting or
operation speed
- Indicates connected reserve output R (bottom *)
- Indicates connected reserve output R2 (top *)
- Indicates that the photocell sees the flame
- If an error message related to the damage of a particular part on the burner appears immediately,
you should call the customer service to replace the damaged part
- If no error message appears, you must watch and compare the function of individual elements in
the burner by checking which symbol on the display is flashing or lighting up. This way you can
easily locate a possible defect within the burner (faulty part).
- If the burner or boiler is not energized, check the supply cable of the boiler or the cable between
the burner and the boiler
CAUTION - BEFORE OPERNING THE COVER TURN OFF THE MAIN SWITCH!
Checks of live parts may only be performed by a qualified person in accordance with
valid standards and laws.
Inspection procedure of the inner electric installation of the burner and boiler:
- Check whether the burner is energized
- Check whether the start signal is being sent to the burner - the control and safety thermostat
is connected - L2 - the symbol on the display is lit
- Check whether the supply phase - L1 - is flowing to the burner
- Check the fuses in the electronic board for the fan, conveyor and ignition spirals
- Check the terminal board for released contact
Check whether the ignition spiral at the start ignites (heats up) when the or symbol lights up
-
- Check the connection of the ignition spiral (supply wires)
- Check the connector of the supply cable of the burner for wrong connection - whether phase L1
(supply phase) is not interchanged with L2 (controlled phase) or reserve R, R2
56-EN
www.atmos.cz
Operation and Maintenance Manual - EN
If no problem has been found, reset the regulation AC07X by the RESTART command.
If the system is working, but you are not satisfied with its function, proceed as follows:
Check the quality of pellets
• Heating value - whether they are really pellets made of wood or whether something has been
added to them - crumble them and smell
• Colour - caking - white pellets do not cake, dark pellets or pellets with dark dots that contain bark
cake.
If the pneumatic cleaning does not manage to clean the burner combustion chamber sufficiently,
shorten the times defined by parameters S42 and S43. When the two hour time span for cleaning is
not sufficient, the pellets contain impurities that make it impossible to burn these pellets in a A85
burner (biological waste). Must be replaced.
• Dust in pellets - causes uneven operation of the burner and clogging of the burner hose
• Size - too small pellets - reduce the burner power (Ø 5 x 5 mm), long pellets do not fall freely to
the burner and clog the supply pipe.
Check the flue gas temperature
• It should be in the optimal range (130 ÷ 220 °С).
• If the temperature is too low, reduce the power of the burner (decrease parameter T4 and increase
T6) and reduce the quantity of combustion air or clean the boiler.
• If the temperature is too low, increase the power of the burner and quantity of combustion air
(increase parameter T4).
EN
Check the level of pellets in the burner mouth
•
If it is too low and the burner goes out, check the flue gas temperature (see above). Reduce the
quantity of combustion air or increase the quantity of supplied pellets - increase the power (increase
parameter T4).
• If the pellet level in the burner mouth is too high and the burner exhibits poor combustion - produces
smoke, increase the quantity of combustion air or reduce the quantity of supplied pellets - reduce the
power (decrease parameter T4).
At the start check how long it takes for combustion quality to improve - how long smoke is released
from the chimney
• If smoke is released from the chimney at the start for more than 5 minutes, extend the time of
gradual increase to the nominal power (parameter T10, e.g. increase by 5min). Be careful about
the setting of the air flap.
The burner regularly does not ignite at the first attempt, but always at the second one
• Extend the time for the supply of ignition fuel (parameter T1 e.g. by 10 s), extend time T2 for
ignition of pellets (e.g. to 15 minutes) or reduce the angle of the conveyor (max. 45°).
If after stopping of the burner and its burning out a lot of glowing unburnt pellets remain in the
combustion chamber (mouth) of the burner
•
Extend the rundown time of the fan - parameter T5 (e.g. extend the time by 5 minutes) - never shorten
www.atmos.cz
EN-57
Operation and Maintenance Manual - EN
18. Maintenance and cleaning of the burner
The system for burning wooden pellets is designed in such a way to require minimum maintenance.
The necessary degree of maintenance directly depends on the set power of the burner and quality of
used pellets.
CAUTION - Before starting repair or maintenance work during which you will handle
the burner always turn off the power supply with the main switch of the boiler or
EN
Regular removal of ashes:
Burning of wooden pellets leaves approximately 1 to 2 % of ashes. In practice you will gradually
find out how often the burner should be cleaned depending on the set power, intensity of heating and
quality of used fuel. Before the start of cleaning you must first shut down the burner and let the fuel
burn out, best by reducing the temperature on the control thermostat or by turning off the burner
switch on the boiler panel. The common interval of cleaning the burner mouth and boiler varies
in the range of 7 to 30 days (after burning of 300 to 1000 kg of high-quality pellets).
For this reason the basic version of ATMOS burner A85 is equipped with pneumatic cleaning
which cleanses the burner’s combustion chamber after every burn out or at regular intervals (factory
setting is 4 hours – parameter S42, S43). Thanks to pneumatic cleaning you can check or clean the
burner’s combustion chamber only once in a fortnight or a month.
Then remove ashes from the combustion space of the boiler and clean the heat exchanger of
the boiler (tube plate) as described in the boiler manual.
disconnect to supply cable of the burner with the connector!
CAUTION - Always put ashes in a closed vessel. During the removal of ashes and cleaning
of the combustion chamber use means of personal protection (gloves and protective goggles).
Annual maintenance
• At least once a year you must perform a complete check, maintenance and inspection of the
burner during which the burner must be removed from the boiler.
• During this maintenance remove and wipe the photocell that senses the flame.
• Thoroughly clean the space under the combustion chamber of the burner and behind the ignition
spiral. Disassemble the inlet pipe through which pellets fall to the burner and clean it.
• Dismount the covering metal sheet of the burner mouth attached with one screw and clean the
space under it where pellets fall and burn (scrape off dust and deposits). Clean the opening
through which the photocell sees the flame.
• Knock dust out of the flexible supply hose and visually check whether it is not perforated. In such
a case repair it or replace. On that occasion check the worm of the external conveyor by inspecting
58-EN
www.atmos.cz
Operation and Maintenance Manual - EN
it from the bottom where pellets fall into the flexible hose. Check whether is it not strangled by
some objects, e.g. wound strings, a piece of wood, etc. that are sometimes found in pellets.
• Then, assemble and seat everything in the boiler. Tighten all the connections.
• Finally, check the basic functions and safety of the electronic unit in the TESTING and
INFOR MATION submenus, see page 49 and 50. Check the function of the end switch and 95 °C
(55 °C for boilers DxxPX, PXxx) safety thermostat at the pellet inlet to the burner (contact of the
thermostat with the pipe), see page 10 and 11.
CAUTION - It is prohibited to do welding work on the equipment if the system is connected
to the electric mains and the electronic control unit is not removed. It might get damaged.
If the customer is not able to carry out the annual inspection and maintenance of the burner
by themselves, this service may be ordered from a service engineer. This service is subject
to a fee. Make a record of the annual maintenance and inspection in the operation manual
on page 64.
EN
www.atmos.cz
EN-59
Operation and Maintenance Manual - EN
19. List of spare parts
EN
POSITION
1ABurner body - front part A851H0443
1BBurner body - rear part A851H0444
2Burner cover - hood with a window for the display - AC07X1H0436
3Top cover of the burner mouth 1H0430
4Holder of the electronic unit 1H0405
5AElectronic unit of the burner - AC07X with a fixation plate 1H0222
5BAC07X-C addit iona l module1H0337
6Pellet supply pipe 1H0406
7Safety thermostat 95 °C1H0059
8Safety thermostat cover 1H0433
9Holder - plate with openings for the ignition spirals 1H0225
10Ignition spiral 500 W 2H0229
11Ignition spiral cover 1H0434
12Inner holder of the ignition spiral 1H0432
13Combustion chamber (pot) of the burner 1H0 431
14End switch - FR501 1H0210
15Burner connector - 6-pin - male - complete (power)1S0989
16Burner connector - 6-pin - female - complete (sensors)1S0987
17Socket for the external conveyor 1H0 211
18Air flap of the fan 1H0435
19Fan with a speed sensor 1H0 043
20Photocell - entire 1 H0231
21Photocell holder 1H0232
22Electronic unit connector (1 - 12) - top 1H0260
23Electronic unit connector (1 - 16) - bottom 1H0234
24Electric harness of the burner, incl. bushings and connectors 1H0265
25Bushing for the cable to ignition spirals 1H0214
Bushing for the cable for the end switch, safety thermostat and
26
pneumatic ash cleaning system
27Gasket under the flange of the pellet supply pipe - Sibral paper 1S0181
28Screw for fixation of the hood and connection of the burner body 4.2 x 131829Fan attachment screw M4 x 8430Screw for attachment of the pellet supply pipe M5 x 10331Screw for attachment of the safety thermostat cover M4 x 6132Screw for attachment of the end switch and safety thermostat cover M4 x 30333Screw for attachment of the conveyor socket and fan flap 3.9 x 9.5634Nut M6435Display self-sticking label 1H0236
36End switch stop 1H0437
37Fuse for ignitaton spiral - type F 3.15A/1500A/5x20 mm2H0238
38Fuse for conveyor - type F 0.8A/1500A/5x20 mm1H0239
39Fuse for fan - type F 1.0A/1500A/5x20 mm1H0251
40Sealing for photocell Ø 8/151S0155
41Sealing under fan 93 x 951S0158
42Start capacitor for the burner’s fan 2 μF1S0173
43Connector for connecting the speed sensor of the boiler draught fan1S1094
44Blow-off nozzle of the burner pneumatic cleaning1H0440
45Cover of a dilatation of the burner nose-piece1H0438
46Air screen2H0439
PART DESCRIPTION
and conection of
QUA NTI-
TY
5S0095
CODE
1 pc
60-EN
www.atmos.cz
Operation and Maintenance Manual - EN
20. Expanded view of the burner
EN
www.atmos.cz
EN-61
Operation and Maintenance Manual - EN
GUARANTEE TERMS
1. On condition of observance of the way of use, operation and maintenance described in the ma-
nual we guarantee that the product will have the characteristics dened by the relevant technical
standards and conditions for the whole guarantee period, namely for 24 months from acceptance
by the consumer and max. 32 months from the date of sale by the manufacturer to the sales repre-
EN
sentative.
2. If the product exhibits a defect in the guarantee period that was not caused by the user, the product
will be repaired free of charge for the customer within the guarantee terms.
3. The guarantee period will be extended by the time period for which the product was repaired.
4. The customer shall submit claims for guarantee repairs to the customer service.
5. The guarantee for the burner is only valid if the assembly of the burner and boiler was performed
by a person trained by the manufacturer in accordance with valid standards and the operation ma-
nual. A condition for acknowledgment of any guarantee is legible and complete lling-in of data
about the company that carried out the installation on page 63. If the burner gets damaged due to
inexpert damage, the resulting costs will be borne by the company that carried out the assembly.
6. The buyer has been provably instructed how to use and operate the product.
7. Requests for repairs after the expiration of the guarantee period are also directed by the customer
to the customer service. In this case the costs of the repair are borne by the customer.
8. The user is obliged to observe instructions in the operation and maintenance manual. In case of
non-observance of the operation and maintenance manual, careless or inexpert handling or burning of prohibited fuel the guarantee becomes invalid and repairs of possible damages are paid by
the customer.
9. At least once a year the burner must be completely inspected, checked and cleaned by a speciali-
zed company, which will conrm all the performed work in the operation manual on page 64 and
further.
Guarantee and after-guarantee repairs are provided by:
- The company that represents the ATMOS Company in the particular country for the
particular region