The DDC controller is located in the control panel on the energy recovery unit.
The face of the DDC controller has six buttons allowing the user to perform
various tasks such as viewing conditions or changing set points. A brief
description of the six buttons is provided. For additional details, refer to the
page references included.
Prior to accessing the controller, confirm the functions that were provided with
the unit by referencing the DDC Code shown
Greenheck Fan Corp.
ER DDC v3.##
Code: GY2X000B
on the controller Start-Up screen.
The Start-Up screen appears when power is applied to the controller. The program version
and code are shown on this screen. The code shows the user what components and
functionality were provided with the unit and also dicates how the program operates. Below
is a description of the code.
PART #469690
DDC CONTROLLER
for ENERGY RECOVERY
NameHeatCoolHGRHFrostEconomizer
GY 2 X 0 0 0B
GFC G None – Disable X None – Disable X None – Disable X None – Disable 0 None – Disable 0 None – Unit Off 0 NoneX
Indicates both visually on the controller (the button lights up) and to the Building
Management Systems (BMS) (field-wired) that something is not functioning normally.
The arrow keys allow the user to scroll through different screens and adjust
parameters.
A. In screens with adjustable parameters, pressing the Enter key moves the cursor
from the upper left corner of the screen to the parameter. The arrow keys can
then be used to adjust the parameter.
B. To move to the next parameter on the same screen, press the Enter button.
C. To save the change, press the Enter button until the cursor moves back to the
upper left corner of the screen.
Allows the user access to the Main Menu. The following adjustments can be made:
• Unit Status
• Set Points
• Manual Overrides
• Analog & Digital Input/Output Setup
• Time Clock Setup
• Miscellaneous Information
• Unit On/Off
UnOccupied
Mode
Communications
Page 3
Page 3
Page 3
Page 4
ProgramAllows the user access to the Program Menu
NOTE: If this controller needs to be interfaced with a BMS (ie: Lonworks, BACnet or Modbus), please refer to page 23 for an integration points list.
Page 17
24 VAC to Controller
DDC Controller for Energy Recovery
Outdoor Air Intake Temperature Sensor
Supply Discharge Temperature Sensor
Cold-Coil Temperature Sensor
Sensor B1, B2, B3 Commons
Room Temperature Sensor
or Digital Call for Cool
Humidistat
24 VAC for Analog Outputs
Analog Output to Energy Wheel
Analog Heating Output (HW or Electric)
Analog Cooling Output (CW)
Hot Gas Reheat Analog Output
Supply Fan Proving
Wheel Pressure
Wheel Rotation Alarm
Unit On/Off
Exhaust Fan Proving
Occupied/Unoccupied Input
Dirty Filter
Compressor Limit
Analog Sensor InputsAnalog Outputs Digital Inputs
Digital Outputs
24 VAC When Unit On
Frost Control Enable
Output to Supply Fan
Output to Exhaust Fan
24 VAC from Supply Fan Proving
Heating Enable (IG or Electric)
st
Call For Cooling
1
nd
Call For Cooling
2
24 VAC
Output to Dampers
Alarm
Dry Contact
UNIT SET POINTS
Example of parameter adjustment
The cursor always begins in the upper left corner of the display.
__Supply air low limit alarm
when supply is less than:
35.0°F
Alarm delay: 030s
Supply air low limit alarm
when supply is less than:
32.0°F
Alarm delay: 030s
__Supply air low limit alarm
when supply is less than:
32.0°F
Alarm delay: 030s
If an alarm occurs, the
controller (if enabled).
**ALARM**
B1 SENSOR ERROR
OUTSIDE TEMPERATURE
ALARMED@-hr:min.mm/dd
…ALARM OPTIONS…
Press UP to review.
Press Esc to exit.
Press ALARM to RESET
Use the up and down buttons to scroll through the display screens. The
cursor must be in the upper left corner of the display to scroll through the screens.
Press
Use the
cursor to the next parameter, or to the upper left corner.
When finished, make certain the cursor is in the upper left corner. If the cursor is not in
the upper left corner, the changes made will not be saved. (The cursor must be in the
upper left corner to enable screen advancement).
to move the cursor down for parameter adjustment.
keys to adjust the parameter up or down. Press to move the
Example of alarms
buttom will glow red, and a buzzer will sound if a remote display panel is connected to the
Step 1: Press the Alarm button once. This will disable the buzzer and
display which alarms have occurred.
Step 2: Scroll down through the alarm screens if more than one has occurred.
Use the arrow buttons or alarm button to scroll through the alarms.
Step 3: Note which alarms occurred and at what time.
Step 4: Scroll down until the “Alarm Options” screen is displayed.
Step 5: Press the Esc button to exit without resetting the alarms.
In this mode the unit will remain operational, as long as the alarm is
Step 6: Press the Alarm button to reset the alarms. If the alarm button
OR
stops glowing red, the alarm has been cleared. No action is required.
(Sometimes a sensor can jump out of range for a short period of time,
causing an alarm. The sensor is probably OK, as long as the sensor
does not continually alarm and the displayed value looks reasonable).
Step 7: If the alarm signals again, the problem still exists and action needs to
be taken. Fix the condition that has caused the alarm.
List of possible alarms
SUPPLY AIR AL:Indicates a loss of airflow in the supply fanAlarm & Shutdown
EXHAUST AIR AL:Indicates a loss of airflow in the exhaust fanAlarm & Shutdown
DIRTY WHEEL AL:Indicates a buildup of pressure across the energy recovery wheelAlarm
WHEEL ROTATION AL:Indicates a wheel rotation failureAlarm
DIRTY FILTER AL:Indicates a buildup of pressure across the filtersAlarm
COMPRESSOR TRIP AL:Indicates a high or low refrigerant pressureAlarm & Compressor Shutdown
AC LOCKOUT AL:Indicates either the low pressure or high pressure switch are open Alarm & Compressor Shutdown
SUPPLY LOW LIMIT AL:
MB1 FAIL:Indicates a failure of the outside air temperature sensorAlarm
MB2 FAIL:Indicates a failure of the supply air temperature sensorAlarm
MB3 FAIL:Indicates a failure of the after cooling coil air temperature sensorAlarm
Indicates a discharge temperature lower than the supply low limit
set point
Alarm & Shutdown
3
MAIN MENU / ESC BUTTON
Access the Main Menu by pressing the key. Scroll through the menu screens using the keys.
All controller menus are accessed through the Main Menu. See below for description of each menu. Refer to the page
references for additional details about each menu. For details on the Program Menu, see page 17.
SCREEN DESCRIPTIONADDITIONAL INFORMATION
Press (ENTER) to go to
*UNIT STATUS* menu.
Press (down) for more
menu options.
Press (ENTER) to go to
*SET POINTS* menu.
Press (up or down) for
more menu options.
Press (ENTER) to go to
*OVERRIDES* menu.
Press (up or down) for
more menu options.
Press (ENTER) to go to
*I/O SETUP* menu.
Press (up or down) for
more menu options.
The UNIT STATUS menu allows the user to view real time conditions of the unit.
Conditions that are displayed include:
• Temperature Sensors • Reheat • Compressors
• Fan Operation • Heating • Preheater
• Energy Recovery Wheel Operation • Cooling
For additional information, please refer to page 5
The SET POINTS menu allows the user to make adjustments to set points. The
adjustable set points relate to:
• Heating • Economizer Mode
• Cooling • Supply Air Low Limit
• Dehumidification • Wheel Defrost
The factory programmed default settings may need to be adjusted to achieve optimum
performance for the specific application.
For additional information, please refer to page 7
The OVERRIDES menu is for start-up/commissioning and troubleshooting the unit.
Components that can be overriden within the system are:
• Frost Control Preheater • Energy Wheel
• Heating • Hot Gas Reheat
• Cooling
For additional information, please refer to page 10
The I/O SETUP menu allows the user to view the status of the digital and analog
inputs and outputs of the DDC controller. In addition, adjustments can be made to
recalibrate sensors and change input and output parameters.
For additional information, please refer to page 12
Press (ENTER) to go to
*CLOCK SETUP* menu.
Press (up or down) for
more menu options.
Press (ENTER) to go to
*MISC INFO* menu.
Press (up or down) for
more menu options.
Press (ENTER) to go to
*UNIT ON/OFF* menu.
Press (up or down) for
more menu options.
- - End of MAIN MENU - -
Hrs:min:sec
month/day/year
4
The CLOCK SETUP menu shows the settings for the internal time clock. The Clock
Setup menu is capable of:
• Setting up occupied / unoccupied modes
• Adjusting the time and date
For additional information, please refer to page 15
The MISC INFO menu displays the version of the program and the DDC Code
programmed. The DDC Code provides details of how the unit was ordered and intended
to operate. Both the program version and the DDC Code are required when contacting
the factory for assistance.
For additional information, please refer to page 16
The UNIT ON/OFF menu allows the user to turn the unit on and off from the
controller.
For additional information, please refer to page 16
UNIT STATUS MENU
Access the UNIT STATUS menu through the Main Menu. Scroll through the menu screens using the
keys. Screens with a dashed line border are dependent upon an optional accessory and may not
always appear.
“STATUS LINE”
System Status
hr:min:sec
mm/dd/yyyy
“STATUS LINE”
Outside: 000. 0º F
Supply: 000. 0º F
Cold Coil: 000. 0º F
“STATUS LINE”
Room: 000. 0º F
“STATUS LINE”
Supply Fan:On
Exhaust Fan:On
THE STATUS LINEDISPLAYSWHICHMODETHEUNITISIN.
Possible modes include:
A. Initial Delay J. Sys On-Dehumidifying
B. Opening Dampers K. Sys On-Dehum & Reheat
C. Exhaust Fan Starting L. Unoccupied-Unit Off
D. Supply Fan Starting M. Unoccupied-Heating
E. System On N. Unoccupied-Cooling
F. Defrost Mode Active O. Manual Override!!
G. Sys On-Economizer P. Remote Off
H. Sys On-Heating Q. Press Alarm Button!
I. Sys On-Cooling
On indicates the fan is running. In most modes of operation, both fans will be On. There
are three modes in which one fan may be Off while the other is On. 1) Start-up of the
unit, 2) Timed exhaust frost control, and 3) Unoccupied, 100% return air mode. Other
than these three modes, if one fan is Off and the other is On, there may be a problem.
If the unit does not contain a VFD on the wheel motor, then 0% = OFF; 100% = ON. If
the unit contains a VFD to modulate the wheel speed for frost control or economizer
operation, this screen will display the percentage directly proportional to the 0-10 VDC
signal being sent to the wheel VFD
0 VDC = 000%, 10 VDC = 100%
To override: ‘MANUAL OVERRIDE’ menu >Energy Recovery Wheel Override
THISSCREENDISPLAYSTHECOOLINGCONTROLASAPERCENTAGE.
This screen only appears if a cooling option is provided.
Chilled Water Coil: The Loop Output % is directly proportional to a 0-10 VDC signal
000% = 0 VDC - Full Closed; 100% = 10 VDC - Full Open
000% = 2 VDC - Full Closed; 100% = 10 VDC - Full Open
The cooling control valve can either be 0-10 VDC or 2-10 VDC depending upon the
valve installed. The user may need to adjust the I/O SETUP menu so that 0-100%
cooling correlates with a 2-10 VDC signal (0-10 VDC is default).
To adjust: ‘I/O SETUP’ menu> Analog Output Y3
DX Coil: Cooling Control displays compressor engagement as a percent
• 000% Compressors OFF (1 or 2 compressor system)
• 050% First compressor ON (2 compressor system)
• 100% First & second compressor ON (2 compressor system)
First compressor ON (1 compressor system)
5
UNIT STATUS MENU - continued
“STATUS LINE”
Cooling Control:000%
Compressor: ##
“STATUS LINE”
Hot Gas Reheat:000%
Heater Control:000%
The Compressor line indicates which compressor is ON
1 First compressor
2 Second compressor
1 2 Both compressors
To override: ‘MANUAL OVERRIDE’ menu >Cooling Loop Override
Hot Gas Reheat only appears if provided with unit.
Hot Gas Reheat operation is on/off control displayed as a percent.
100% is ON and 000% is OFF
To override: ‘MANUAL OVERRIDE’ menu >Hot Gas Reheat Override
For Modulating Hot Gas Reheat Control:
000% is OFF and 001% HGRH is ON and the airflow damper is modulating
between 4 VDC and 10 VDC.
Heater Control displays the real-time percent heater output and is directly proportional
to a 0-10 VDC signal provided by the discharge temperature sensor.
To override: ‘MANUAL OVERRIDE’ menu >Heating Loop Override
Electric Heater: The Heater Control % is directly proportional to a 0-10 VDC signal
being sent to the SCR controller in the electric heater’s control center.
000% = 0 VDC = 0 kW output
100% = 10 VDC = Maximum kW output
Indirect Gas Furnace: The Heater Control % is directly proportional to a 0-10 VDC
signal being sent to the indirect gas furnace control board. The first stage is full ON at a
1% Heater Control. Once the Heater Control reaches 50%, the second stage modulates
between 50% and 100% output.
001 – 049% First stage: ON, Second stage: OFF
050 – 100% First stage: ON, Second stage: Modulating between
50% and 100% output
Hot Water Heater: The heating control valve (supplied by others) can either be 0-10 VDC
or 2-10 VDC depending upon what valve is installed. The user may have to adjust the
‘I/O SETUP’ menu so that a 0-100% heating correlates with a 2-10 VDC signal (0-10 VDC
is default).
“STATUS LINE”
Energy recovery
wheel differential
pressure is: Normal
This screen only appears if Electric Preheat frost control was provided.
To override: ‘MANUAL OVERRIDE’ menu >Energy Recover y Wheel Preheater
Outdoor Air Reset Function
55°
57°
59°
61°
63°
65°
67°
69°
71°
73°
55°60°6 5°70°75°
Outside Air Temperature (°F)
Discharge Temperature (°F)
SET POINTS MENU
Access the SET POINTS menu through the Main Menu. Scroll through the menu screens using the keys.
***ACCESS DENIED***
Enter Password:0000
WRONG PASSWORD
Unit Set Points
Supply set pt
is currently=###.#ºF
This set pt is reset
up/down by the DDC.
THISSCREENCANBELOCKEDTOPREVENTTAMP ERI NGWITHTHESETTINGS.
FROMTHEFACTORY, ACCESSISNOTPASSWORDPROTECTEDTOALLOWQUICKER
START-UP.
To set the password, go to the ‘PROGRAM’ menu by pressing the button. Once
there, scroll down until you arrive at the Change Password screen. The ‘Level 1’
password protects the ‘SET POINTS’ menu.
If there is no room temperature sensor (nothing wired to terminals B4 and BC4 on
controller), the controller changes the supply air discharge temperature of the unit
based on the outdoor air temperature (refer to outdoor air reset function below). With
no room temperature sensor, a BMS can override the controller and input directly the
desired supply temperature for the unit.
If a room temperature sensor is connected to terminals B4 and BC4 on the DDC
controller, then the supply temperature of the unit is adjusted based on the difference
between the actual room temperature (reading from the room temperature sensor) and
the desired room temperature which is programmed into the controller (refer to Room Set Point screen below). With a room temperature sensor connected to the controller, a
BMS can override the controller and input directly the desired room set point. This new
desired room set point will be used for comparing with the actual room temperature.
To activate the BMS override temperatures, refer to the Program Menu and change the
Set Point Source screen to BMS Interface.
This screen does not appear when the room supply temp sensor is wired into
terminals B4 and BC4 on the controller.
The unit monitors the outdoor air temperature and adjusts the desired supply
temperature accordingly. For example, when the outdoor air is below 60.0ºF, the
controller will change the Supply set pt to 72.0ºF. If the outdoor air is above 70.0ºF, the
controller would change the Supply set pt to 60.0ºF. If the outdoor air temperature is
between 60.0ºF and 70.0ºF, the Supply discharge temperature changes according to
the outdoor air reset function. A visual representation of the outdoor air reset function
is shown.
Cold coil set point
Normal Mode:55.0ºF
Dehumidify:50.0ºF
Active set pt:55.0ºF
THISSCREENDISPLAYSTHESPACETEMPERATURESETPOINT.
This screen only appears if the room supply temp sensor is wired into terminals B4
and BC4 on the controller.
The unit will reset the unit discharge temperature up and down to maintain the local
set point. If a BMS is interfaced with the controller, the user has the capability to
dictate the desired Room set point through the BMS. The screen will show a BMS
set point and an Active set point. The Active set point is the room temperature the
controller is currently tr ying to maintain.
This screen only appears if the room supply temp sensor is wired into terminals B4
and BC4 on the controller.
The supply air temp will integrate SLOWLY down (Pl loop) towards this minimum set
point to maintain room temperature. The supply air temp will integrate SLOWLY up (PI
loop) towards this maximum set point to maintain room temperature.
This screen only appears if a Cooling option was provided with the unit.
The Normal Mode set point is the after coil temperature the unit will maintain under
standard operation. If a Humidistat was provided with the unit, the Dehumidify set
point is the temperature the cooling coil will discharge on a call for dehumidification
from a humidistat.
The Active set pt is the temperature that the unit is currently trying to maintain off the coil.
Unit will energize
to maintain unocc
room set points.
Differential:5.0ºF
Unoccupied room set
point
Heating:65.0ºF
Cooling:85.0ºF
This screen only appears if the 7th character in the DDC Code is set to 1, meaning
the “Cycle on Room” unoccupied mode was chosen. Operation in “Cycle on Room”
unoccupied mode requires the room sensor be wired into terminals B4 and BC4 , and
a night setback damper in the unit.
This differential acts as a hysteresis to keep the heating and cooling from cycling too
often. For example, on a call for heating (room temp. set point - differential, 65.0ºF-
5.0ºF=60.0ºF) supply fan cycles on. Unit cycles off when the room temperature reaches
the Unoccupied room set point (65.0ºF, adjustable). For cooling, the differential is
added to the Unoccupied room set point (85.0ºF+5.0ºF=90.0ºF) to cycle supply fan
on. Unit cycles off when the room temperature reaches Unoccupied room set point
(85.0ºF).
This screen only appears if the “Cycle on Room” unoccupied mode was chosen
for the unit. A room sensor temp. must be wired into terminals B4 and BC4 on the
controller, and the unit must have a night setback damper.
In Unoccupied Mode when the temperature falls below the room Heating set point
(hysteresis = 5ºF), the supply fan and unit heating will turn on. Unit will discharge the
Supply Max temperature per the ‘Supply Reset Limits’ screen above until the room set
point is satisfied. Unit will then shut down. In Unoccupied Mode when the temperature
rises above the Cooling set point (hysteresis = 5ºF), the supply fan and unit cooling will
turn on. Unit will discharge the Supply Min temperature per the ‘Supply Reset Limits’
screen above until the room temperature set point is satisfied. Unit will then shut down.
Heater Lockout
Lockout heater when
outside air >:70.0ºF
Hysteresis=02.0ºF
This screen only appears if a Heating option was provided with the unit.
A Hysteresis of 2ºF helps to avoid short cycling of the heater. The hysteresis is similar
to a deadband above and below the Lockout heater set point.
(Example: If Lockout = 70ºF, heating is locked out for outside air conditions above 72ºF
and enabled below 68ºF).
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.