The DDC controller is located in the control panel on the energy recovery unit.
The face of the DDC controller has six buttons allowing the user to perform
various tasks such as viewing conditions or changing set points. A brief
description of the six buttons is provided. For additional details, refer to the
page references included.
Prior to accessing the controller, confirm the functions that were provided with
the unit by referencing the DDC Code shown
Greenheck Fan Corp.
ER DDC v3.##
Code: GY2X000B
on the controller Start-Up screen.
The Start-Up screen appears when power is applied to the controller. The program version
and code are shown on this screen. The code shows the user what components and
functionality were provided with the unit and also dicates how the program operates. Below
is a description of the code.
PART #469690
DDC CONTROLLER
for ENERGY RECOVERY
NameHeatCoolHGRHFrostEconomizer
GY 2 X 0 0 0B
GFC G None – Disable X None – Disable X None – Disable X None – Disable 0 None – Disable 0 None – Unit Off 0 NoneX
Indicates both visually on the controller (the button lights up) and to the Building
Management Systems (BMS) (field-wired) that something is not functioning normally.
The arrow keys allow the user to scroll through different screens and adjust
parameters.
A. In screens with adjustable parameters, pressing the Enter key moves the cursor
from the upper left corner of the screen to the parameter. The arrow keys can
then be used to adjust the parameter.
B. To move to the next parameter on the same screen, press the Enter button.
C. To save the change, press the Enter button until the cursor moves back to the
upper left corner of the screen.
Allows the user access to the Main Menu. The following adjustments can be made:
• Unit Status
• Set Points
• Manual Overrides
• Analog & Digital Input/Output Setup
• Time Clock Setup
• Miscellaneous Information
• Unit On/Off
UnOccupied
Mode
Communications
Page 3
Page 3
Page 3
Page 4
ProgramAllows the user access to the Program Menu
NOTE: If this controller needs to be interfaced with a BMS (ie: Lonworks, BACnet or Modbus), please refer to page 23 for an integration points list.
Page 17
Page 2
24 VAC to Controller
DDC Controller for Energy Recovery
Outdoor Air Intake Temperature Sensor
Supply Discharge Temperature Sensor
Cold-Coil Temperature Sensor
Sensor B1, B2, B3 Commons
Room Temperature Sensor
or Digital Call for Cool
Humidistat
24 VAC for Analog Outputs
Analog Output to Energy Wheel
Analog Heating Output (HW or Electric)
Analog Cooling Output (CW)
Hot Gas Reheat Analog Output
Supply Fan Proving
Wheel Pressure
Wheel Rotation Alarm
Unit On/Off
Exhaust Fan Proving
Occupied/Unoccupied Input
Dirty Filter
Compressor Limit
Analog Sensor InputsAnalog Outputs Digital Inputs
Digital Outputs
24 VAC When Unit On
Frost Control Enable
Output to Supply Fan
Output to Exhaust Fan
24 VAC from Supply Fan Proving
Heating Enable (IG or Electric)
st
Call For Cooling
1
nd
Call For Cooling
2
24 VAC
Output to Dampers
Alarm
Dry Contact
Page 3
UNIT SET POINTS
Example of parameter adjustment
The cursor always begins in the upper left corner of the display.
__Supply air low limit alarm
when supply is less than:
35.0°F
Alarm delay: 030s
Supply air low limit alarm
when supply is less than:
32.0°F
Alarm delay: 030s
__Supply air low limit alarm
when supply is less than:
32.0°F
Alarm delay: 030s
If an alarm occurs, the
controller (if enabled).
**ALARM**
B1 SENSOR ERROR
OUTSIDE TEMPERATURE
ALARMED@-hr:min.mm/dd
…ALARM OPTIONS…
Press UP to review.
Press Esc to exit.
Press ALARM to RESET
Use the up and down buttons to scroll through the display screens. The
cursor must be in the upper left corner of the display to scroll through the screens.
Press
Use the
cursor to the next parameter, or to the upper left corner.
When finished, make certain the cursor is in the upper left corner. If the cursor is not in
the upper left corner, the changes made will not be saved. (The cursor must be in the
upper left corner to enable screen advancement).
to move the cursor down for parameter adjustment.
keys to adjust the parameter up or down. Press to move the
Example of alarms
buttom will glow red, and a buzzer will sound if a remote display panel is connected to the
Step 1: Press the Alarm button once. This will disable the buzzer and
display which alarms have occurred.
Step 2: Scroll down through the alarm screens if more than one has occurred.
Use the arrow buttons or alarm button to scroll through the alarms.
Step 3: Note which alarms occurred and at what time.
Step 4: Scroll down until the “Alarm Options” screen is displayed.
Step 5: Press the Esc button to exit without resetting the alarms.
In this mode the unit will remain operational, as long as the alarm is
Step 6: Press the Alarm button to reset the alarms. If the alarm button
OR
stops glowing red, the alarm has been cleared. No action is required.
(Sometimes a sensor can jump out of range for a short period of time,
causing an alarm. The sensor is probably OK, as long as the sensor
does not continually alarm and the displayed value looks reasonable).
Step 7: If the alarm signals again, the problem still exists and action needs to
be taken. Fix the condition that has caused the alarm.
List of possible alarms
SUPPLY AIR AL:Indicates a loss of airflow in the supply fanAlarm & Shutdown
EXHAUST AIR AL:Indicates a loss of airflow in the exhaust fanAlarm & Shutdown
DIRTY WHEEL AL:Indicates a buildup of pressure across the energy recovery wheelAlarm
WHEEL ROTATION AL:Indicates a wheel rotation failureAlarm
DIRTY FILTER AL:Indicates a buildup of pressure across the filtersAlarm
COMPRESSOR TRIP AL:Indicates a high or low refrigerant pressureAlarm & Compressor Shutdown
AC LOCKOUT AL:Indicates either the low pressure or high pressure switch are open Alarm & Compressor Shutdown
SUPPLY LOW LIMIT AL:
MB1 FAIL:Indicates a failure of the outside air temperature sensorAlarm
MB2 FAIL:Indicates a failure of the supply air temperature sensorAlarm
MB3 FAIL:Indicates a failure of the after cooling coil air temperature sensorAlarm
Indicates a discharge temperature lower than the supply low limit
set point
Alarm & Shutdown
3
Page 4
MAIN MENU / ESC BUTTON
Access the Main Menu by pressing the key. Scroll through the menu screens using the keys.
All controller menus are accessed through the Main Menu. See below for description of each menu. Refer to the page
references for additional details about each menu. For details on the Program Menu, see page 17.
SCREEN DESCRIPTIONADDITIONAL INFORMATION
Press (ENTER) to go to
*UNIT STATUS* menu.
Press (down) for more
menu options.
Press (ENTER) to go to
*SET POINTS* menu.
Press (up or down) for
more menu options.
Press (ENTER) to go to
*OVERRIDES* menu.
Press (up or down) for
more menu options.
Press (ENTER) to go to
*I/O SETUP* menu.
Press (up or down) for
more menu options.
The UNIT STATUS menu allows the user to view real time conditions of the unit.
Conditions that are displayed include:
• Temperature Sensors • Reheat • Compressors
• Fan Operation • Heating • Preheater
• Energy Recovery Wheel Operation • Cooling
For additional information, please refer to page 5
The SET POINTS menu allows the user to make adjustments to set points. The
adjustable set points relate to:
• Heating • Economizer Mode
• Cooling • Supply Air Low Limit
• Dehumidification • Wheel Defrost
The factory programmed default settings may need to be adjusted to achieve optimum
performance for the specific application.
For additional information, please refer to page 7
The OVERRIDES menu is for start-up/commissioning and troubleshooting the unit.
Components that can be overriden within the system are:
• Frost Control Preheater • Energy Wheel
• Heating • Hot Gas Reheat
• Cooling
For additional information, please refer to page 10
The I/O SETUP menu allows the user to view the status of the digital and analog
inputs and outputs of the DDC controller. In addition, adjustments can be made to
recalibrate sensors and change input and output parameters.
For additional information, please refer to page 12
Press (ENTER) to go to
*CLOCK SETUP* menu.
Press (up or down) for
more menu options.
Press (ENTER) to go to
*MISC INFO* menu.
Press (up or down) for
more menu options.
Press (ENTER) to go to
*UNIT ON/OFF* menu.
Press (up or down) for
more menu options.
- - End of MAIN MENU - -
Hrs:min:sec
month/day/year
4
The CLOCK SETUP menu shows the settings for the internal time clock. The Clock
Setup menu is capable of:
• Setting up occupied / unoccupied modes
• Adjusting the time and date
For additional information, please refer to page 15
The MISC INFO menu displays the version of the program and the DDC Code
programmed. The DDC Code provides details of how the unit was ordered and intended
to operate. Both the program version and the DDC Code are required when contacting
the factory for assistance.
For additional information, please refer to page 16
The UNIT ON/OFF menu allows the user to turn the unit on and off from the
controller.
For additional information, please refer to page 16
Page 5
UNIT STATUS MENU
Access the UNIT STATUS menu through the Main Menu. Scroll through the menu screens using the
keys. Screens with a dashed line border are dependent upon an optional accessory and may not
always appear.
“STATUS LINE”
System Status
hr:min:sec
mm/dd/yyyy
“STATUS LINE”
Outside: 000. 0º F
Supply: 000. 0º F
Cold Coil: 000. 0º F
“STATUS LINE”
Room: 000. 0º F
“STATUS LINE”
Supply Fan:On
Exhaust Fan:On
THE STATUS LINEDISPLAYSWHICHMODETHEUNITISIN.
Possible modes include:
A. Initial Delay J. Sys On-Dehumidifying
B. Opening Dampers K. Sys On-Dehum & Reheat
C. Exhaust Fan Starting L. Unoccupied-Unit Off
D. Supply Fan Starting M. Unoccupied-Heating
E. System On N. Unoccupied-Cooling
F. Defrost Mode Active O. Manual Override!!
G. Sys On-Economizer P. Remote Off
H. Sys On-Heating Q. Press Alarm Button!
I. Sys On-Cooling
On indicates the fan is running. In most modes of operation, both fans will be On. There
are three modes in which one fan may be Off while the other is On. 1) Start-up of the
unit, 2) Timed exhaust frost control, and 3) Unoccupied, 100% return air mode. Other
than these three modes, if one fan is Off and the other is On, there may be a problem.
If the unit does not contain a VFD on the wheel motor, then 0% = OFF; 100% = ON. If
the unit contains a VFD to modulate the wheel speed for frost control or economizer
operation, this screen will display the percentage directly proportional to the 0-10 VDC
signal being sent to the wheel VFD
0 VDC = 000%, 10 VDC = 100%
To override: ‘MANUAL OVERRIDE’ menu >Energy Recovery Wheel Override
THISSCREENDISPLAYSTHECOOLINGCONTROLASAPERCENTAGE.
This screen only appears if a cooling option is provided.
Chilled Water Coil: The Loop Output % is directly proportional to a 0-10 VDC signal
000% = 0 VDC - Full Closed; 100% = 10 VDC - Full Open
000% = 2 VDC - Full Closed; 100% = 10 VDC - Full Open
The cooling control valve can either be 0-10 VDC or 2-10 VDC depending upon the
valve installed. The user may need to adjust the I/O SETUP menu so that 0-100%
cooling correlates with a 2-10 VDC signal (0-10 VDC is default).
To adjust: ‘I/O SETUP’ menu> Analog Output Y3
DX Coil: Cooling Control displays compressor engagement as a percent
• 000% Compressors OFF (1 or 2 compressor system)
• 050% First compressor ON (2 compressor system)
• 100% First & second compressor ON (2 compressor system)
First compressor ON (1 compressor system)
5
Page 6
UNIT STATUS MENU - continued
“STATUS LINE”
Cooling Control:000%
Compressor: ##
“STATUS LINE”
Hot Gas Reheat:000%
Heater Control:000%
The Compressor line indicates which compressor is ON
1 First compressor
2 Second compressor
1 2 Both compressors
To override: ‘MANUAL OVERRIDE’ menu >Cooling Loop Override
Hot Gas Reheat only appears if provided with unit.
Hot Gas Reheat operation is on/off control displayed as a percent.
100% is ON and 000% is OFF
To override: ‘MANUAL OVERRIDE’ menu >Hot Gas Reheat Override
For Modulating Hot Gas Reheat Control:
000% is OFF and 001% HGRH is ON and the airflow damper is modulating
between 4 VDC and 10 VDC.
Heater Control displays the real-time percent heater output and is directly proportional
to a 0-10 VDC signal provided by the discharge temperature sensor.
To override: ‘MANUAL OVERRIDE’ menu >Heating Loop Override
Electric Heater: The Heater Control % is directly proportional to a 0-10 VDC signal
being sent to the SCR controller in the electric heater’s control center.
000% = 0 VDC = 0 kW output
100% = 10 VDC = Maximum kW output
Indirect Gas Furnace: The Heater Control % is directly proportional to a 0-10 VDC
signal being sent to the indirect gas furnace control board. The first stage is full ON at a
1% Heater Control. Once the Heater Control reaches 50%, the second stage modulates
between 50% and 100% output.
001 – 049% First stage: ON, Second stage: OFF
050 – 100% First stage: ON, Second stage: Modulating between
50% and 100% output
Hot Water Heater: The heating control valve (supplied by others) can either be 0-10 VDC
or 2-10 VDC depending upon what valve is installed. The user may have to adjust the
‘I/O SETUP’ menu so that a 0-100% heating correlates with a 2-10 VDC signal (0-10 VDC
is default).
“STATUS LINE”
Energy recovery
wheel differential
pressure is: Normal
This screen only appears if Electric Preheat frost control was provided.
To override: ‘MANUAL OVERRIDE’ menu >Energy Recover y Wheel Preheater
Page 7
Outdoor Air Reset Function
55°
57°
59°
61°
63°
65°
67°
69°
71°
73°
55°60°6 5°70°75°
Outside Air Temperature (°F)
Discharge Temperature (°F)
SET POINTS MENU
Access the SET POINTS menu through the Main Menu. Scroll through the menu screens using the keys.
***ACCESS DENIED***
Enter Password:0000
WRONG PASSWORD
Unit Set Points
Supply set pt
is currently=###.#ºF
This set pt is reset
up/down by the DDC.
THISSCREENCANBELOCKEDTOPREVENTTAMP ERI NGWITHTHESETTINGS.
FROMTHEFACTORY, ACCESSISNOTPASSWORDPROTECTEDTOALLOWQUICKER
START-UP.
To set the password, go to the ‘PROGRAM’ menu by pressing the button. Once
there, scroll down until you arrive at the Change Password screen. The ‘Level 1’
password protects the ‘SET POINTS’ menu.
If there is no room temperature sensor (nothing wired to terminals B4 and BC4 on
controller), the controller changes the supply air discharge temperature of the unit
based on the outdoor air temperature (refer to outdoor air reset function below). With
no room temperature sensor, a BMS can override the controller and input directly the
desired supply temperature for the unit.
If a room temperature sensor is connected to terminals B4 and BC4 on the DDC
controller, then the supply temperature of the unit is adjusted based on the difference
between the actual room temperature (reading from the room temperature sensor) and
the desired room temperature which is programmed into the controller (refer to Room Set Point screen below). With a room temperature sensor connected to the controller, a
BMS can override the controller and input directly the desired room set point. This new
desired room set point will be used for comparing with the actual room temperature.
To activate the BMS override temperatures, refer to the Program Menu and change the
Set Point Source screen to BMS Interface.
This screen does not appear when the room supply temp sensor is wired into
terminals B4 and BC4 on the controller.
The unit monitors the outdoor air temperature and adjusts the desired supply
temperature accordingly. For example, when the outdoor air is below 60.0ºF, the
controller will change the Supply set pt to 72.0ºF. If the outdoor air is above 70.0ºF, the
controller would change the Supply set pt to 60.0ºF. If the outdoor air temperature is
between 60.0ºF and 70.0ºF, the Supply discharge temperature changes according to
the outdoor air reset function. A visual representation of the outdoor air reset function
is shown.
Cold coil set point
Normal Mode:55.0ºF
Dehumidify:50.0ºF
Active set pt:55.0ºF
THISSCREENDISPLAYSTHESPACETEMPERATURESETPOINT.
This screen only appears if the room supply temp sensor is wired into terminals B4
and BC4 on the controller.
The unit will reset the unit discharge temperature up and down to maintain the local
set point. If a BMS is interfaced with the controller, the user has the capability to
dictate the desired Room set point through the BMS. The screen will show a BMS
set point and an Active set point. The Active set point is the room temperature the
controller is currently tr ying to maintain.
This screen only appears if the room supply temp sensor is wired into terminals B4
and BC4 on the controller.
The supply air temp will integrate SLOWLY down (Pl loop) towards this minimum set
point to maintain room temperature. The supply air temp will integrate SLOWLY up (PI
loop) towards this maximum set point to maintain room temperature.
This screen only appears if a Cooling option was provided with the unit.
The Normal Mode set point is the after coil temperature the unit will maintain under
standard operation. If a Humidistat was provided with the unit, the Dehumidify set
point is the temperature the cooling coil will discharge on a call for dehumidification
from a humidistat.
The Active set pt is the temperature that the unit is currently trying to maintain off the coil.
Unit will energize
to maintain unocc
room set points.
Differential:5.0ºF
Unoccupied room set
point
Heating:65.0ºF
Cooling:85.0ºF
This screen only appears if the 7th character in the DDC Code is set to 1, meaning
the “Cycle on Room” unoccupied mode was chosen. Operation in “Cycle on Room”
unoccupied mode requires the room sensor be wired into terminals B4 and BC4 , and
a night setback damper in the unit.
This differential acts as a hysteresis to keep the heating and cooling from cycling too
often. For example, on a call for heating (room temp. set point - differential, 65.0ºF-
5.0ºF=60.0ºF) supply fan cycles on. Unit cycles off when the room temperature reaches
the Unoccupied room set point (65.0ºF, adjustable). For cooling, the differential is
added to the Unoccupied room set point (85.0ºF+5.0ºF=90.0ºF) to cycle supply fan
on. Unit cycles off when the room temperature reaches Unoccupied room set point
(85.0ºF).
This screen only appears if the “Cycle on Room” unoccupied mode was chosen
for the unit. A room sensor temp. must be wired into terminals B4 and BC4 on the
controller, and the unit must have a night setback damper.
In Unoccupied Mode when the temperature falls below the room Heating set point
(hysteresis = 5ºF), the supply fan and unit heating will turn on. Unit will discharge the
Supply Max temperature per the ‘Supply Reset Limits’ screen above until the room set
point is satisfied. Unit will then shut down. In Unoccupied Mode when the temperature
rises above the Cooling set point (hysteresis = 5ºF), the supply fan and unit cooling will
turn on. Unit will discharge the Supply Min temperature per the ‘Supply Reset Limits’
screen above until the room temperature set point is satisfied. Unit will then shut down.
Heater Lockout
Lockout heater when
outside air >:70.0ºF
Hysteresis=02.0ºF
This screen only appears if a Heating option was provided with the unit.
A Hysteresis of 2ºF helps to avoid short cycling of the heater. The hysteresis is similar
to a deadband above and below the Lockout heater set point.
(Example: If Lockout = 70ºF, heating is locked out for outside air conditions above 72ºF
and enabled below 68ºF).
Page 9
SET POINTS MENU - continued
Cooling Lockout
Lockout cooling when
outside air <:55.0ºF
Hysteresis=02.0ºF
Lockout dehumidification until outside
air is:10.0ºF above
cold coil set point
Economizer Lockout
Lockout econo when
outside air <:40.0ºF
Hysteresis=02.0ºF
This screen will only appear if Cooling was provided with the unit.
There is a built in hysteresis of 2ºF which prevents the compressors from short cycling.
The hysteresis is similar to a deadband above and below the lockout set point.
(Example: If Lockout = 55ºF, cooling is locked out below 53ºF and end enabled above
57ºF outside air temp).
This screen will only appear if cooling was provided with the unit.
This setting prevents the unit from operating in dehumidification mode when outdoor
air conditions are relatively cool. For example, if the cold coil set point is 55ºF,
dehumidification mode cannot operate until the outdoor air is at least 65ºF.
This screen only appears if economizer was provided with the unit.
The lockout prevents outdoor air from 1) entering the space at too cold of a
temperature or 2) entering heating and cooling coils at conditions that could freeze
the coils. Built-in hysteresis of 2ºF. The hysteresis is similar to a deadband above and
below the lockout set point.
(Example: If Lockout = 40ºF, economizer is locked out below 38ºF and enabled above
42ºF outside air temp)
Supply air low limit
alarm when supply is
less than: 35.0ºF
Alarm delay:300s
Defrost
Allow wheel defrost
mode when outside
is less than: 05.0ºF
If the unit supply discharge temperature falls below Supply Air Low Limit set point
(factory default 35F) for a period of time (factory default 300 sec) the unit will shut down
and an alarm will be signaled. The purpose of the Discharge Freeze Protection is to
protect the building and contents from low temperature supply air. It is NOT designed
to protect the Energy Recovery unit.
If the Energy Recovery unit does not have CW or HW coils (has only no heat, IG heat,
electric heat, no cooling, or Dx cooling) it should not need additional protection from
freezing. If the Energy Recovery unit does have CW or HW coils, please contact the
factory for more details.
This screen only appears if a frost control method was provided with the unit.
The energy wheel transfers both latent and sensible energy at relatively similar
efficiencies. Therefore, in most applications where indoor mositure levels are
below 35% RH, frost typically will not occur on the energy wheel until outdoor air
temperatures are below 5ºF. Consult the factory if you have any concerns regarding
your specific application.
9
Page 10
MANUAL OVERRIDE MENU
Access the OVERRIDES menu through the Main Menu. Scroll through the menu screens using the keys.
***ACCESS DENIED***
Enter Password:0000
WRONG PASSWORD
Manual override of
control loops
(Unit must be ON)
Energy recovery
wheel override
Wheel:AUTO
Wheel:OFF
Energy recovery
wheel override
Wheel:AUTO
% Speed:000%
THISSCREENCANBELOCKEDTOPREVENTTAMP ERI NGWITHTHESETTINGS.
FROMTHEFACTORY, ACCESSISNOTPASSWORDPROTECTEDTOALLOWQUICKER
START-UP.
To set the password, go to the ‘PROGRAM’ menu by pressing the button. Once
there, scroll down until you arrive at the Change Password screen. The ‘Level 1’
password protects the ‘OVERRIDES’ Menu.
THE OVERRIDE MENUISUSEDFORMANUALOVERRIDEOFTHECONTROLLOOP.
To manualy override a function, change the status “AUTO” to “MANUAL”.
This screen only appears if the Modulating Wheel Frost Control or Modulating Wheel
Economizer was provided with the unit.
When the wheel is in MANUAL mode, use the arrow buttons to change the % Speed to
vary the wheel rotational speed. The % Speed is directly proportional to a 0-10V signal
being sent to the energy wheel VFD.
This screen only appears if a cooling option was provided with the unit.
When the cooling loop override is in MANUAL mode, use the arrow buttons to vary the
% output.
Chilled Water Coil: Loop Output % is directly proportional to a 0-10 VDC or 2-10 VDC
signal.
000% = 0 VDC = Full Closed; 100% = 10 VCD = Full Open
000% = 2 VDC = Full Closed; 100% = 10 VCD = Full Open
2 Stage DX Coil: Loop Output displays compressor engagement as a percent.
000% Compressor OFF
050% First Compressor ON
100% First & Second Compressor ON
Second stage will NOT disengage until Loop Output is below 50%
First stage will NOT disengage until Loop Output is 0%
1 Stage DX Coil: Loop Output displays compressor engagement as a percent.
000% Compressor OFF
100% Compres sor ON
In a single stage DX cooling system, the compressor engages when the Loop Output is
100%. Once the compressor is engaged, it will not disengage until the Loop Output is
0%.
Note: Damage can occur to compressors from short-cycling, therefore the controller
has built-in time delays which are effective upon each engagement of a compressor.
Hot gas reheat loop
override
Hot gas: AUTO
Hot gas: OFF
THEUSERCANOVERRIDETHEHEATINGOPERATION.
This screen only appears if a Heating option was provided with the unit.
To manually override the heating, adjust the Heating status from AUTO to MANUAL.
When the Heating loop override is in MANUAL mode, use the arrow buttons to vary the
% output.
Hot Water Coil: The Loop Output % is directly proportional to a 0-10 VDC or 2-10 VDC
signal being set to the hot water valve.
000% = 0 VDC = Full Closed; 100% = 10 VDC = Full Open
000% = 2 VDC = Full Closed; 100% = 10 VDC = Full Open
Electric Heater: The Loop Output % is directly proportional to a 0-10 VDC signal being
sent to the SCR controller in the electric heater’s control center.
000% = 0 VDC = 0 kW output
100% = 10 VDC = Maximum kW output
Indirect Gas Furnace: The Heater Control % is directly proportional to a 0-10 VDC
signal being sent to the indirect gas furnace control board. Where the first stage is full
ON at a 1% Heater Control. Once the Heater Control reaches 50%, the second stage
modulates between 50% and 100% output.
001% - 049%: First stage: ON, Second stage: OFF
050% - 100% First stage: ON, Second stage: Modulating between 50%
and 100% output
THEUSERCANOVERRIDETHEHOTGASREHEATOPERATION.
This screen only appears if the On/Off Hot Gas Reheat option was provided with the
unit.
To manually override the Hot gas reheat loop, adjust the Hot gas status from AUTO to
MANUAL. When the Hot Gas Reheat loop is in MANUAL mode, use the arrow buttons
to open or close the HGRH valve (ON = Open, OFF = Closed).
Hot gas reheat loop
override
Hot gas: AUTO
Loop output:000%
Energy recovery wheel
preheater
Preheater:AUTO
Preheater:OFF
End of manual
overrides
THEUSERCANOVERRIDETHEHOTGASREHEATOPERATION.
This screen only appears if the Modulating Hot Gas Reheat option was selected with
the unit.
To manually override the Hot gas reheat loop, adjust the Hot gas status from AUTO to
MANUAL. When the Hot Gas Reheat loop is in MANUAL mode, press the up and down
arrow to vary the Loop output %. The Loop output % is directly proportional to a 0-10
VDC signal being sent to the HGRH controller.
000% = 0 VDC = Full Closed
100% = 10 VDC = Full Open
This screen only appears if the Electric Preheat Frost Control option was provided
with the unit.
To manually override the Electric Preheater, adjust the Preheater status from AUTO to
MANUAL. When the Energy Recovery wheel preheater is in MANUAL mode, use the
arrow buttons to turn the Electric Preheater ON or OFF.
11
Page 12
I/O SETUP MENU
Access the I/O SETUP menu through the Main Menu. Scroll through the menu screens using the keys.
Sensor Calibration: Measure the actual temperature and find the difference from the Sensor Temp
(uncalibrated). This difference becomes the Offset and once the Offset is input to the
controller, the Actual Temp should match the actual measured temperature.
To set the password, go to the ‘PROGRAM’ menu by pressing the button.
Once there, scroll down until you arrive at the Change Password screen. The ‘Level 2’
password protects the
‘I/O SETUP’ menu.
THE ‘I/O SETUP’ MENUISUSEDTOSETUPTHEANALOG & DIGITAL
INPUT/OUTPUTS.
NOTE: The wiring terminal for each I/O is displayed in the respective screens.
Sensor Temp is the sensor’s uncalibrated output.
Offset is for calibrating the sensor.
Actual Temp is the new calibrated sensor output.
This screen only appears if the room supply sensor is NOT wired between B4 and
BC4 on the controller.
When the Input Status is Open, the unit will operate normally and adjust the discharge
temperature based on outdoor air temperature. When the Input Status is Closed (in the
case of a digital input, ie. Thermostat), this indicates that a digital call for cool is being
received by the controller. The controller then overrides the outdoor air temperature
discharge control and sends the supply temperature set point to the supply reset
minimum temperature (Max cooling: 55
ºF,adj. in ‘SET POINTS’ menu).
12
Page 13
I/O SETUP MENU - continued
B5 Dehumidify:ON/OFF
Input Status:Open
ANALOG OUTPUTS - PARAMETERS
The Analog Output screens allow the user to adjust the analog outputs for the energy recovery wheel, heating, cooling, and
hot gas reheat operation. The factory defaults are provided in the screens shown and are designed to operate with any
factory supplied components. Chilled water valves, hot water valves, DX distributors, or HGRH valves provided by others
may require adjustments to the following screens to properly operate the components.
Analog output Y1
Energy Recovery Wheel
Output 0% --> 100%
SIGNAL 00.0V 10.0V
This screen only appears if there is a humidistat wired to terminals B5 and BC5 on
the controller.
When the Input Status is Open, there is no call for dehumidification. When the Input
Status is Closed, the cold-coil set point is reset for fur ther dehumidification.
This screen may relate to on/off or modulating control depending upon what
accessories were ordered with the unit. The energy recovery wheel is factory-installed
and programmed.
This screen only appears if Heating was provided with the unit.
The Output and SIGNAL will provide the appropriate control of a hot water coil, electric
heater, or indirect gas furnace. User can change the SIGNAL range if required. Factory
defaults are 0-10 VDC.
NOTE: This is where the user would adjust for a Heating Control Valve that is
2-10 VDC rather than 0-10 VDC.
Analog output Y3
Cooling
Output 0% --> 100%
SIGNAL 00.0V 10.0V
Analog output Y4
Hot Gas Reheat
Output 0% --> 100%
SIGNAL 00.0V 10.0V
This screen only appears if Chilled Water was provided with the unit.
The Output and SIGNAL will provide the appropriate control of a chilled water coil.
User can change the SIGNAL range if required. Factory defaults are 0-10 VDC.
NOTE: This is where the user would adjust for a Cooling Control Valve that is
2-10 VDC rather than 0-10 VDC.
This screen only appears if HGRH was provided with the unit.
The Output and SIGNAL will provide the appropriate control of a on/off or modulating
hot gas reheat coil. User can change the SIGNAL range if required. Factor y defaults are
0-10 VDC.
WARNING!
The following screens show the factory defaults for each parameter. Do NOT change parameters unless you are
absolutely certain the parameter needs to be modified. Unit will not function properly and damage may occur
to the unit if the parameters do not match the contact requirements of the components.
Digital Input (ID1)
Supply proving switch
Alarm: Open
Status:Closed
When the Supply proving switch alarm is triggered, the fan is not seeing airflow and the
unit will shutdown and alarm. The Alarm parameter allows the user to select Open or
Closed for the contact position that will trigger the alarm. Status displays the real time
status (Open/Closed) of the digital input.
NOTE: The controller is only monitoring the contact position -- Not the actual
operation of the fan.
13
Page 14
I/O SETUP MENU - continued
Digital Input (ID2)
Wheel pressure switch
High pressure=Closed
Status:Open
Digital Input (ID3)
Wheel rotation alarm
Alarm:Closed
Status:Open
Digital Input (ID4)
Unit ON/OFF control
Unit ON when:Closed
Status:Open
Digital Input (ID5)
Exhaust proving switch
Alarm:Open
Status:Closed
When the Wheel pressure switch alarm is triggered, the wheel has excessive frost or
dirt build-up. The High pressure parameter allows the user to select Open or Closed
for the contact position that will trigger the alarm. Status displays the real time status
(open/closed) of the digital input.
When the Wheel rotation alarm is triggered, the wheel has stopped rotating. Refer to
‘PROGRAM’ menu for wheel rotation alarm delay. Status displays the real time status
(open/closed) of the digital input.
The Unit ON when parameter allows the user to select Open or Closed for the contact
position that will energize the unit. Status displays the real time status (open/closed) of
the digital input.
When the Exhaust proving switch alarm is triggered, the fan is not seeing airflow and
the unit will shutdown and alarm. The Alarm parameter allows the user to select Open
or Closed for the contact position that will trigger the alarm. Status displays the real
time status (open/closed) of the digital input.
Digital Input (ID6)
Occupied/Unoccupied
Occupied when:Open
Status:Closed
Digital Input (ID7)
Dirty filter switch
Alarm:Closed
Status:Open
Digital Input (ID8)
Compressor limits
Alarm:Open
Status:Closed
While in Input ID6 mode, (refer to ‘PROGRAM’ menu) the input from ID6 will send the
unit into occupied or unoccupied mode. If in BMS or Time Clock mode, a 24 VDC input
from ID6 will override the system operation from unoccupied (refer to ‘TIME CLOCK’
menu for actual override time period) to occupied (but not occupied to unoccupied)
mode for a specific override. The Occupied when parameter allows the user to select
Open or Closed for the contact position that will indicate Occupied operation. Status
displays the real time status (open/closed) of the digital input.
The Alarm parameter allows the user to select Open or Closed for the contact position
that will trigger the alarm. Status displays the real time status (open/closed) of the
digital input.
This screen only appears if DX cooling was provided in the unit.
The Alarm parameter allows the user to select Open or Closed for the contact position
that will trigger the alarm. Status displays the real time status (open/closed) of the
digital input. Based on factory defaults, the DX staging will lockout and alarm when the
Status is Open.
14
End of I/O setups
Page 15
TIME CLOCK MENU
Access the
CLOCK SETUP menu through the Main Menu. Scroll through the menu screens using the keys.
***ACCESS DENIED***
Enter Password:0000
WRONG PASSWORD
CLOCK
hr:min:sec
(Day of week)
mm/dd/yyyy
Time/Date/Day Setup
Press ENTER to reset
the internal clocks
time, date & day
IMPORTANT! User must select one of the three options for the Source in the
Unoccupied mode setup screen in the ‘PROGRAM’ menu. The Source represents the
means by which Occupied and Unoccupied modes are determined.
Option 1: Input ID6 – typically used with a remote time clock (Default)
Option 2: BMS – can be overridden by a separate input to ID6
Option 3: Internal Time Clock – can be overridden by a momentary input to ID6
THISSCREENCANBELOCKEDTOPREVENTTAMP ERI NGWITHTHESETTINGS.
FROMTHEFACTORY, ACCESSISNOTPASSWO RDPROTECTEDTOALLOWQUICKER
START-UP.
To set the password, go to the ‘PROGRAM’ menu by pressing the button. Once
there, scroll down until you arrive at the Change Password screen. The ‘Level 1’
password protects the ‘TIME CLOCK’ menu.
THE CLOCKSETUPMENUALLOWSTHEUSERTOADJUSTTHETIME, DATE, AND
OCCUPIED/UNOCCUPIEDMODESETTINGS.
User can also override the current occupied/unoccupied mode for a designated period
of time.
Set the time, date & day here. All three must be
set/reset at the same time. When the cursor is in the
upper left corner, press up or down to return to the
clock menu.
Occ-Unocc Override
Current Mode:Occ
Override Time:060min
Override:No
The following screens only appear if Option 3, the Internal Time Clock function, has been enabled in the Program
Menu.
This screen will only appear if the Occupied/Unoccupied ID6 function has been set
to ‘ON’ in the PROGRAM menu under Binary Input Enables.
The controller will allow the user to override from Unoccupied to Occupied mode, but
not vice versa. This can be performed by changing this screen to Yes, or it can also
be done through a momentary 24 VDC input to terminal ID6. After the Override Time
expires, the clock returns to the 7-day schedule.
Selecting ‘No’ means the unit will operate in an Occupied mode only.
Selecting ‘Yes’ means the unit will operate in an Occupied mode and an Unoccupied
mode.
Enter the desired Occupied/Unoccupied star t times for each day (24 hour time scale).
Enter the desired Occupied/Unoccupied star t times for each day (24 hour time scale).
15
Page 16
TIME CLOCK MENU - continued
Occupied Unoccup
Sat 06:00 18:00
Sun 06:00 18:00
Holidays
Holiday = unoccupied
mode for 24 hrs.
# of holidays:00
Holiday #1
Month:01
Day:01
Unoccupied for 24hrs
End of Clock setup
Enter the desired Occupied/Unoccupied star t times for each day (24 hour time scale).
Enter the number of holidays you wish to schedule (up to 15 days can be entered).
Holidays must be updated every year!
The internal clock will index into unoccupied mode as long as the date is equal to a
date entered as a holiday (always a 24 hour period).
Example: New Years Day, January 1
MISC INFO MENU
Access the MISC INFO menu through the Main Menu. Scroll through the menu screens using the keys.
Greenheck Fan Corp.
ER DDC1 v3.00
DDC Code: GY2A211X
The DDC was supplied with
a user manual - if missing,
visit www.greenheck.com
If contacting the factory for assistance, record the version of the program and the DDC
Code displayed on this screen.
UNIT ON/OFF MENU
Access the UNIT ON/OFF menu through the Main Menu. Scroll through the menu screens using the keys.
Press (ESC) to exit
Command unit on or
off below.
Command Unit:ON
THE ‘UNIT ON/OFF’ MENUALLOWSTHEUSERTOTURNTHEUNITONANDOFF
FROMTHECONTROLLER, PROVIDEDTHE R TO G CONTACTINTHEUNITCONTROL
CENTERISCLOSED.
Press Enter to highlight ON/Off in the lower right corner.
Press the the
A remote ON/OFF switch may also be wired into ID4
buttons to turn unit ON or OFF.
16
End of Information
menu
Page 17
PROGRAM MENU
Access the PROGRAM menu by pressing key. Scroll through the menu screens using the keys.
The program button is used to setup the control loops for economizer, defrost, heating, cooling, and reheat
along with defaults for staging, supply reset, time delays, occupied mode, communications, set point source,
temperature scale, and changing passwords. Adjustments to these parameters should be performed by a
qualified technician. (A Level 2 password must be entered to alter any of the factory programming; factory
default is 9998).
***ACCESS DENIED***
Enter Password:0000
WRONG PASSWORD
Factory Setup
Consult factory
before altering
Economizer Controller
Integration:300s
Control Band:20ºF
THISSCREENCANBELOCKEDTOPREVENTTAMP ERI NGWITHTHESETTINGS.
FROMTHEFACTORY, ACCESSISNOTPASSWORDPROTECTEDTOALLOWQUICKER
START-UP.
To set the password, go to the ‘PROGRAM’ menu by pressing the button. Once
there, scroll down until you arrive at the Change Password screen. The ‘Level 2’
password protects the ‘Program’ menu.
This screen will only appear if an Economizer mode was selected with the unit.
This controller uses a Proportional + Integral type control. The integration time
programmed into the controller is to provide a smooth reaction to conditions, allowing
for less sporadic changes in discharge temperature. To speed up reaction time,
decrease the integration time. For slower reaction time, increase the integration time.
When making adjustments, make them in small increments, and test the system to
determine if the new setting is adequate prior to further adjustment. The band is the
range that the integration will occur between.
Range of Integration = Supply set pt ± Band. ie: 50° F ± 20° F
Economizer Setup
Econo on/off times
Minimum ON:300s
Minimum OFF:300s
Supply fan cycling
defrost setup.
Fan off time:005min
Fan on time:030min
This screen only appears if a Cooling option was provided with the unit.
This controller uses a Proportional + Integral type control. The integration time
programmed into the controller is to provide a smooth reaction to conditions, allowing
for less sporadic changes in discharge temperature. To speed up reaction time,
decrease the integration time. For slower reaction time, increase the integration time.
When making adjustments, make them in small increments, and test the system to
determine if the new setting is adequate prior to further adjustment. The band is the
range that the integration will occur between.
Range of Integration = Supply set pt ± Band. ie: 50° F ± 20° F
17
Page 18
PROGRAM MENU - continued
Compressor Setup
# of stages:2
Minimum ON:030s
Minimum OFF:180s
Compressor Setup
Between stages:240s
Lead-Lag:YES
Lead-Lag Time:100hrs
This screen only appears if 2-stage DX cooling (2 compressors) was provided with
the unit.
Between Stages is the time delay (in seconds) between the first and second
compressors engaging. Lead-Lag governs whether the stages will reverse operation
order after some period of time designated by the Lead-Lag Time setting (Factory
Default: YES, 100hrs.). The Lead-Lag Time is the duration of time the unit will operate
before reversing the DX staging. In other words, based on the factory default,
Compressor 1 will engage before Compressor 2 for 100 hours of operation. After 100
hours, the order reverses and Compressor 2 will engage first. This cycle will continue
indefinitely.
This screen only appears if DX cooling was provided with the unit.
Each compressor will engage and disengage based upon the percentage of
cooling that the user inputs (refer to Cooling Loop Override screen on the ‘MANUAL
OVERRIDE’ menu).
This screen only appears if 2-stage DX cooling was provided with the unit.
This screen shows the order in which the compressors will engage when operating in
the lead-lag setup.
IFTHECONTROLLERDETECTSTHREE (3) ALARMSINTHETIMEPERIODSHOWN, IT
WILLSHUTOFFTHECOMPRESSORSASASAFETYMEASURE.
This screen only appears if DX cooling was provided with the unit.
The safety lockout screen monitors the safety loop of the DX system, including high
limit, low limit, and ambient temps. If the controller detects three (3) trips within 120
minutes, the controller will shut down the DX system. (Example: If the low limit switch
trips, automatically resets, and then trips two more times within 120 minutes, the DX
system will shut down). If there is a fatal trip, such as a high limit pressure switch trip,
the DX system will not run and the controller will signal an alarm after trying three times
unsucessfully to start the DX cooling process.
THISSCREENDISPLAYSTHEINTEGRATIONTIMEFORTHE PI CONTROLOFTHE
This screen only appears if a Heating option was provided with the unit.
This controller uses a Proportional + Integral type control. The integration time
programmed into the controller is to provide a smooth reaction to conditions, allowing
for less sporadic changes in discharge temperature. To speed up reaction time,
decrease the integration time. For slower reaction time, increase the integration time.
When making adjustments, make them in small increments, and test the system to
determine if the new setting is adequate prior to further adjustment. The band is the
range that the integration will occur between.
Range of Integration = Supply set pt ± Band. ie: 50° F ± 20° F
18
Page 19
PROGRAM MENU - continued
Will heater be used
for reheat during
dehumidification?
Reheat:Enable
Will heater be used for
reheat along
with the hot gas?
Heater:Disable
This screen only appears if a Heating option was provided with the unit and the unit
does NOT have hot gas reheat.
If it is desired that the heater be used to reheat the air off the cooling coil when in
dehumidification, adjust this screen so the Enable is displayed.
This screen only appears if Hot Gas Reheat and a Heating option was provided with
the unit.
Setting the Heater parameter to Enable allows the Heating option to provide additional
reheat above and beyond what the Hot Gas Reheat can provide. This would typically
only be used if the discharge temperature off the Hot Gas Reheat coil was too cold for
the space.
THISSCREENDISPLAYSTHEINTEGRATIONTIMEFORTHE PI CONTROLOFTHEHOT
These parameters may be adjusted if necessary. This screen only appears if a Hot
Gas Reheat option was provided with the unit.
This controller uses a Proportional + Integral type control. The integration time
programmed into the controller is to provide a smooth reaction to conditions, allowing
for less sporadic changes in discharge temperature. To speed up reaction time,
decrease the integration time. For slower reaction time, increase the integration time.
When making adjustments, make them in small increments, and test the system to
determine if the new setting is adequate prior to further adjustment. The band is the
range that the integration will occur between.
Range of Integration = Supply set pt ± Band. ie: 50° F ± 20° F
Hot Gas reheat coil
minimum on/off
time 10 minutes
This screen only appears if ON/OFF Hot Gas Reheat was provided with the unit.
This is the minimum on/off time operation for the Hot Gas Reheat coil. The factory
programmed time prevents short-cycling of the coil, which allows for better oil
distribution through the DX system.
Use caution when altering the on/off time as damage may occur to the system
if set too low. Consult the factory for information.
These parameters may be adjusted if necessary. This screen only appears if a Room
Supply Temp sensor is wired between B4 and BC4 on the controller.
This controller uses a Proportional + Integral type control. The integration time
programmed into the controller is to provide a smooth reaction to conditions, allowing
for less sporadic changes in discharge temperature. To speed up reaction time,
decrease the integration time. For slower reaction time, increase the integration time.
When making adjustments, make them in small increments, and test the system to
determine if the new setting is adequate prior to further adjustment. The band is the
range that the integration will occur between.
Range of Integration = Room set pt ± Band. ie: 72° F ± 20° F
19
Page 20
PROGRAM MENU - continued
Time delay between
heating, cooling, &/or
economizer modes.
Delay:600s
Unoccupied mode
setup.
Type:Cycle Supply Fan
Source: Input ID6
Allow the dampers to
open for:10 seconds
before starting the
fans.
Setting the Type to Cycle Supply Fan will engage the unit to maintain space
temperature. However, the room suppy temp sensor must be wired between B4 and
BC4 on the controller. If desired, the Source offers three options that can be used to
operate unoccupied/occupied modes:
Option 1: Input ID6 – typically used with a remote time clock (Default)
Option 2: BMS – can be overridden by a separate input to ID6
Option 3: Internal Time Clock – can be overridden by a separate input to ID6
Without the room supply temp sensor, the Type will say Unit Off, and thus the unit will
be off during unoccupied mode.
This allows for a smoother startup of the system and prevents the fans from having
to overcome the higher pressures when dampers are just beginning to open. Since
dampers have a slow reaction time, the default is 10 seconds which allows enough time
for them to fully open.
Fan/airflow proving
alarm delay:030s
(inputs ID1 & ID5)
Time delay between
starting of supply
& exhaust fans.
Fan delay:005s
Since the unit is only part of a complete system, the airflows may momentarily change
(ie. If a downstream damper closes). This delay is intended to prevent false alarms (the
factory recommends that at least 30 seconds be programmed into the controller).
Also, the exhaust fan engages first, allowing the wheel to see space temperature
conditions prior to the supply fan engaging. This allows the energy recovery wheel
the opportunity to provide maximum preconditioning of the outdoor air. This also
minimizes the potential of extreme outdoor air temperatures being supplied to the
space prior to the cooling and or heating sections engaging.
20
Page 21
PROGRAM MENU - continued
Wheel rotation alarm
delay:030s
(input ID3)
Communications Setup
Press ENTER to setup the
communication parameters
This screen appears whether the wheel rotation alarm was provided or not. If
provided, there will be a wire in ID3 on the controller.
Similar to the Fan/airflow proving switch alarm, the Wheel rotation alarm delay allows
time to elapse prior to the controller showing an alarm. The delay prevents a false
alarm from occurring if the sensor does not pickup the wheel rotation for a second or
two.
The communications setup allows the user to program the type of BMS system
(BACnet, LonWorks, pcoWEB, or MODBUS), and where required, the Identification
# and Baud numbers needed to operate the controller. Screens displaying the
communication options available with this unit are shown.
Communications Setup
Comm Type:LonWorks
Communications Setup
Comm Type:pcoWEB
Communications Setup
Comm Type:PlantVisor
Identification #:001
Communications Setup
Comm Type:Modem
Identification #:001
Communications Setup
Comm Type:MODBUS
Identification #:001
Baud:9600
21
Page 22
PROGRAM MENU - continued
--Set Point Source-Use local set point,
or BMS interface set
point?:Local
Temperature Scale
Select:Fahrenheit
Display Buzzer
Select:Enable
This screen only appears if a BMS is wired into the controller.
Local means the controller set point will be used during operation, and BMS Interface
means that Supply Discharge set point can be inputted to the controller from the BMS.
The temperature can be either Fahrenheit or Celsius. The buzzer is only applicable
when there is a remote interface panel attached to the controller. If an alarm were to
occur, the remote display panel would begin buzzing loudly (if the buzzer was enabled)
and it would show the alarm status.
This code is set from the factory to operate the components selected with the unit.
Refer to front page for code description. When troubleshooting, be sure to verify that
the code matches the components provided with the unit.
If the code needs to be modified, press Enter
first character. Use the
character. To finish, press Enter
the screen.
keys to adjust. Press Enter to move to the next
until the cursor moves to the upper left corner of
Note: 1) Unit status index: 0=system off; 1=initial delay; 2=opening dampers;
23
Page 24
DateTimeNotes:
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one
year from the purchase date. The energy recovery wheel is warranted to be free from defects in material
and workmanshipfor a period of five years from the purchase date. Any units or parts which prove defective
during the warranty period will be replaced at our option when returned to our factory, transportation
prepaid.
Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by
Greenheck prove defective during this period, they should be returned to the nearest authorized motor
service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.