TSD-SEQ6
Sequencer Controller
Owner’s Manual
Description
The AtlasIED TSD-SEQ6 Sequencer Controller features 6 outputs that are configurable individually
to be either a 24VDC output or Hard Switch Contact Closure (CC). There are two separate output
sequence time delay trimmers ranging from 1 second to 10 minutes. Activation can be done via the
front panel or remotely via Hard Switch CC, Momentary Switch or DC Voltage. The TSD-SEQ6 also
incorporates an Emergency Power Down (EPD) port for local fire codes. You can link two
TSD-SEQ6 units together giving you 12 sequenced outputs.
The TSD-SEQ6 is part of a full line of AtlasIED Time Saving Devices. These compact
(1.5" x 4" x 2.75") units are designed to solve some of the common audio system problems in the
easiest, most efficient, and cost-effective way. All models are made from high quality components
and include removable individual I/O connectors for quick and precise wiring, separate ground
terminals for all I/Os assuring secured connections, and removable level controls that can be
replaced with tamper-resistant security covers. The TSDs are highly efficient and meet most energy
standards as one 24V DC power supply (available separately) can power multiple Atlas Time Saving
Devices.
Features
• 6 Sequenced Outputs
• Assignable 24VDC or Hard Switch
Contact Closure (CC) per Output
• Sequence 1 is Adjustable: Delay Time
1 Second to 10 Minutes
• Sequences 2 - 6 are Adjustable: Delay Time
1 Second to 1 Minute
• Remote Activation via 5-24VDC,
Momentary Contacts, Hard Switch Contacts
• Status Indicator for Each Output
• Emergency Power Down “EPD” Port
• Link Out for Two TSD-SEQ6 Controllers
• Voltage Output for Remote
LED Status Display
• Separate Wiring Port for Each I/O
• Cable Management System
• Multiple Mounting Congurations
• Removable Phoenix Style I/O Connectors
• Meets Most Energy Standards
• Compact Chassis Design
Interfaceable Atlas Products
• ECM-20
• ECM-20M
• ECM-15SH
• ECM-20SH
• ECM-30
• ECM-2063
Installation
• Churches
• Restaurants
• Sports Bars
• Schools
• Industrial Facilities
• House of Worship
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
AtlasIED.com – 2 –
Specifications are subject to change without notice.
Page 3
Owner’s Manual
TSD-SEQ6
Sequencer Controller
Front Panel Description
2
3
145
1. System Activation Switch - Press to activate the ON or OFF sequence.
2. System Activation Switch Security Cover - If you do not want to use the Front Panel Activation
Switch, place the security cover over the switch and secure using the retainer screw.
3. Power LED - Illuminates Blue when 24VDC power is present.
4. System Status/Ready LED - Flashes Green during a sequence and will illuminate steadily when
sequence is complete indicating the system is powered up. When the LED is Off, it indicates the
system is in the Off mode.
5. Channel Output LED - Each of the 6 outputs have their own LED which illuminates Red when the
specic channel / output is active.
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
AtlasIED.com – 3 –
Specifications are subject to change without notice.
Page 4
TSD-SEQ6
Sequencer Controller
Owner’s Manual
Rear Panel Description
2
1111
1111
1345768
TSD Input/Output connections are removable for easy system wiring. The connectors have a 3.5mm
pitch between pins.
1. DC Power Input - Each TSD that requires DC power comes with a 2 position connector for an
external 24VDC power supply (sold separately). Because of the TSD’s low power consumption, a
single external power supply may power more than one TSD. Please refer to the specications
on current requirements in milliamps to match with the appropriate power supply. Please observe
the polarity of the wiring to this connector. Note: It is acceptable to exceed the current
requirements of the TSDs but NOT safe to use a power supply that is below the current
requirement of the device. Use a power supply with a 500mA capacity (Atlas TSD-PS24V500MA).
2. Channel Output - There are 6 channel output control ports. Each output can be assigned to provide
a 24VDC output or a Hard Switch Contact Closure (CC). See the Function Settings for Output
conguration below.
3. Remote Activation Momentary Switch Port - Remote System activation can be done several
hundred feet away via a momentary contact closure type switch.
4. Remote Activation Hard Switch Contact Closure (CC) Port - Remote System activation can be
done several hundred feet away via a Hard Contact closure type switch.
5. Remote Activation 5 - 24VDC Port - Remote System activation can be done several hundred feet
away by applying 5 - 24VDC. Only a few milliamps of current is required.
6. Panel LED Port - This port can be used to power an LED on a remote panel for system status
indication. The 24VDC Output will pulsate during a sequence and remain at a steady state when
the sequence is completed and all outputs are on.
910
7. Link Control Port - You can combine two TSD-SEQ6 units together to make a 12 step sequence
system. Note: Pay special attention to the Input and Output terminals. Connect the Output from
unit 1 (Master) to the Input of unit 2 (Slave). Connect the Output from unit 2 (Slave) to the Input of
unit 1 (Master). Pay close attention to this or the Link Out will not work. See the Function Settings
for the Master/Slave conguration below.
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
AtlasIED.com – 4 –
Specifications are subject to change without notice.
Page 5
Owner’s Manual
8. EPD “Emergency Power Down” Port - When an urgent system shut down is required, short the
two pins together and the sequence portion will be bypassed and turn Off all outputs at the same
time. This EPD feature is commonly used with re control systems.
9. Delay Pot for Sequence 1 Output - The time between Sequence 1 Output and Sequence 2
Output can be set by rotating the pot following the indicators on the panel. In X1 mode the delay
time adjustment is from 1 second to 60 seconds. In X10 mode the delay time adjustment is from
10 seconds to 600 seconds, or 10 minutes. See the Function Settings below for Sequence 1 Output
X1 or X10 conguration.
10. Delay Pot for Sequences 2-6 - The time between Sequence 2 Output and Sequence 6 Output can
be set by rotating the pot following the indicators on the panel. Whatever the time is set to will be
the time between Sequenced outputs.
11. Cable Management Retainer Points - Each TSD includes two cable retainer straps for securing
the included cable management retainers. Remove one of the rear panel screws, align the
panel hole with a retainer and rmly tighten the screws.
TSD-SEQ6
Sequencer Controller
Dip Switch Function Identication
SWITCH FUNCTIONS
Switch Position
• DIP SW # 1-6 - Channel Output Assignment - Each output can be assigned to deliver a Hard
Switch Contact Closure (CC) or +24VDC output when activated by the Sequence for Output
Channels 1-6.
• DIP SW # 7 - Link Assignment Conguration - This switch determines if the unit is to be a
Master or a Slave unit. The Master unit is always the rst in line of the sequence.
• DIP SW # 8 - Sequence Output 1 Time Delay - In the X1 setting the adjustable time delay setting
is from 1s to 60s and in the X10 position the time delay setting is from 10s to 600s, or 10 minutes.
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
AtlasIED.com – 5 –
Specifications are subject to change without notice.
Page 6
TSD-SEQ6
Sequencer Controller
Owner’s Manual
Cable Management
Knob and Security Cover
All front panel level controls feature a removable knob that can be replaced with an included security
cover. Follow these steps to prevent potentiometer damage or unwanted changes.
1. Knob Installation - Turn the potentiometer shaft fully counter-clockwise. Align the knob indicator
to the lowest setting on the panel and the potentiometer shaft slot. Carefully press the knob onto
the potentiometer shaft. Do not force or damage may occur to the potentiometer.
2. Security Cover Installation - Remove the knob from the panel and insert the cover. Small pliers may
be required to remove the knobs. Align the security cover to the level control panel hole. Push the
cover into the hole until it snaps into place. Do not force or damage may occur to the potentiometer.
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
AtlasIED.com – 6 –
Specifications are subject to change without notice.
Page 7
Owner’s Manual
TSD-SEQ6
Sequencer Controller
Mounting
Listed below are the ways to mount the TSD and the optional accessories that can be purchased.
1. Velcro™ - Each unit includes two 2" x 2" pieces of industrial-grade Velcro™ with adhesive backing
to adhere to any at surface. Clean all surfaces before applying the adhesive side of the Velcro™.
2. Multi Mount Plate - Each TSD includes a versatile multi-position mounting plate. This plate
allows the TSD to be mounted to any surface; but is ideal for use with rear rack rails or side rack
hat channels. Use the included M3 x 4mm screws to install the plate on the TSD. Note: Only use
the included M3 x 4mm screws as other screws may be too long and will cause internal damage
to the TSD. The multi-position mounting plate is a new addition being included with TSDs. If the
TSD being used did not include the mounting plate, contact AtlasIED customer service at
1-800-876-3333.
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
AtlasIED.com – 7 –
Specifications are subject to change without notice.
(M3 x 4mm)
(M3 x 4mm)
Page 8
TSD-SEQ6
Sequencer Controller
Owner’s Manual
Optional Mounting Accessories
1. TSD-RMK 19" Width Rack Mount Kit - For 19" rack mounting, AtlasIED offers an optional rack
mount kit, the TSD-RMK. This rack mount kit can support up to four TSD units. The kit includes
three blank panels designed to ll any unused slots. Use the included hardware to mount the TSD
into the rack mount kit using the top mount screw holes on the TSD.
2. TSD-RMKHR Half Width Rack Mount Kit - AtlasIED offers an optional rack mount kit that can
be used in half width rack applications including the AtlasIED WMA-HR and AWR-HR models.
The TSD-RMKHR can support up to two TSDs. Included is an extra blank panel to ll one of the
spaces if only one TSD is being used.
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
AtlasIED.com – 8 –
Specifications are subject to change without notice.
Page 9
Owner’s Manual
3. TSD-RRMK Rear Rack Mounting Kit - For complete exibility in mounting a TSD or TSD external
power supplies the optional TSD-RRMK is available. The TSD-RRMK can support mounting of
either two larger TSDs with external power supplies or up to 4 TSD models. Note: Only use the
included M3 x 4mm screws as other screws may be too long and will cause internal damage to
the TSD.
TSD-SEQ6
Sequencer Controller
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
AtlasIED.com – 9 –
Specifications are subject to change without notice.
Page 10
TSD-SEQ6
Sequencer Controller
Owner’s Manual
Specications
Description Sequence Controller
Chassis Color Black
Chassis Material Aluminum
Outputs
Type Qty 6, Sequenced Channel Output, Selectable 24VDC or CC
Connection Removable 3 Position Captive Screw 3.5mm Spacing
Type Qty 1, Link Input/Output
Connection Removable 3 Position Captive Screw 3.5mm Spacing
Type Qty 1, Output 24VDC for Remote Panel LED Indicator
Connection Removable 2 Position Captive Screw 3.5mm Spacing
Sequence Activation Controls
Type Qty 1, Momentary Switch Front Panel
Type Qty 1, Momentary Switch Port
Connection Removable 2 Position Captive Screw 3.5mm Spacing
Type Qty 1, Hard Switch Contact Closure (CC) Port
Connection Removable 2 Position Captive Screw 3.5mm Spacing
Type Qty 1, DC Voltage Port
Connection Removable 2 Position Captive Screw 3.5mm Spacing
Type Qty 1, Emergency Power Down (EPD)
Connection Removable 2 Position Captive Screw 3.5mm Spacing
Controls
Dip Switch Function • Output 1-6, Assign 24VDC or Contact Closure (CC)
• Link Assignment
• Sequence Output 1 Time Setting: X1 or X10
Output 1 Sequence Delay Trim Pot, 1 sec - 60 sec or 10 sec - 10 min (Selectable)
Indicators
Sequence Status Green, Qty 1
Output Sequence Status Red, Qty 6
Power Blue
Power Requirements
Voltage 24VDC, 500mA
Power Consumption Current 100mA
Power Consumption VA Watts 2.4W
Dimensions H 1.5" (39mm) x W 4" (101mm) x D 2.75" (70mm)
Weight 6oz, .165kg
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
AtlasIED.com – 10 –
Specifications are subject to change without notice.
Page 11
Owner’s Manual
Included Accessories
Velcro™ Industrial-Grade
Multi-Mount Plate Qty 1, Includes Two (2) M3 x 4mm Screws
Cable Retainers Qty 2
System Switch Security Cover Qty 1
Safety and Certifications
External Power Supply cUL, CE, RoHS, TUV
TSD-SEQ6
Sequencer Controller
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
AtlasIED.com – 11 –
Specifications are subject to change without notice.
Page 12
TSD-SEQ6
Sequencer Controller
Owner’s Manual
Limited Warranty
All products manufactured by AtlasIED are warranted to the original dealer/installer, industrial or
commercial purchaser to be free from defects in material and workmanship and to be in compliance
with our published specifications, if any. This warranty shall extend from the date of purchase for
a period of three years on all AtlasIED products, including SOUNDOLIER brand, and ATLAS SOUND
brand products except as follows: one year on electronics and control systems; one year on
replacement parts; and one year on Musician Series stands and related accessories. Additionally,
fuses and lamps carry no warranty. AtlasIED will solely at its discretion, replace at no charge or
repair free of charge defective parts or products when the product has been applied and used in
accordance with our published operation and installation instructions. We will not be responsible
for defects caused by improper storage, misuse (including failure to provide reasonable and
necessary maintenance), accident, abnormal atmospheres, water immersion, lightning discharge,
or malfunctions when products have been modified or operated in excess of rated power, altered,
serviced or installed in other than a workman like manner. The original sales invoice should be
retained as evidence of purchase under the terms of this warranty. All warranty returns must comply
with our returns policy set forth below. When products returned to AtlasIED do not qualify for repair
or replacement under our warranty, repairs may be performed at prevailing costs for material and
labor unless there is included with the returned product(s) a written request for an estimate of repair
costs before any nonwarranty work is performed. In the event of replacement or upon completion of
repairs, return shipment will be made with the transportation charges collect.
EXCEPT TO THE EXTENT THAT APPLICABLE LAW PREVENTS THE LIMITATION OF CONSEQUENTIAL
DAMAGES FOR PERSONAL INJURY, ATLASIED SHALL NOT BE LIABLE IN TORT OR CONTRACT
FOR ANY DIRECT, CONSEQUENTIAL OR INCIDENTAL LOSS OR DAMAGE ARISING OUT OF THE
INSTALLATION, USE OR INABILITY TO USE THE PRODUCTS. THE ABOVE WARRANTY IS IN LIEU OF
ALL OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE.
AtlasIED does not assume, or does it authorize any other person to assume or extend on its behalf,
any other warranty, obligation, or liability. This warranty gives you specific legal rights and you may
have other rights which vary from state to state.
Service
Should your Atlas TSD require service, please contact the AtlasIED
warranty department at 1-877-689-8055, ext. 277 to obtain an RA number.
AtlasIED Tech Support can be reached at 1-800-876-3333 or support.atlasied.com.
Visit our website at www.AtlasIED.com to see other Atlas products.