ECM-20, ECM-20M
Electical Control Modules
ECM-20
ECM-20M
Features
ECM-20 / ECM-20M
• Manual/Auto ON/Off switch
• Incoming AC present LED
• Active LED
• AC Fault LED (ECM-20M Only)
• Clamping Spike & Surge Suppression EVS Circuitry
• AC Mains Voltage & Current monitoring (Voltage only for ECM-20)
• EMI & RFI Filtering (ECM-20M Only)
General Description
The Atlas Power ECM-20 is a 20A Power Conditioner and AC Spike
Suppressor that is designed to be used as a standalone unit or in
conjunction with an ECS unit up to 1000ft away. The ECM-20 features
AC Spike and Surge Suppression, AC Mains Voltage monitoring,
EVS circuitry, and Remote Activation. The ECM-20 is designed to be
conveniently housed in the ECM-RACEWY6 for the addition of multiple
outlets directly connected to the AC mains from the electrical panel.
The Atlas Power ECM-20M is a 20A Power Conditioner and AC Spike
Suppressor that is designed to be used as a standalone unit or in
conjunction with an ECS unit up to 1000ft away. The ECM-20M features
AC Spike and Surge Suppression, AC Mains Voltage monitoring, EVS
circuitry, and Remote Activation. In addition, the ECM-20M features
noise filtering for removing unwanted Radio Frequency Interference
(RFI) and EMI filters to reduce noise from Electromagnetic Interference
(EMI) caused by items such as electric motors or switching power
supplies. The ECM-20M is designed to be conveniently housed in the
ECM-RACEWY6 for the addition of multiple outlets directly connected to
the AC mains from the electrical panel.
©2011 Atlas Sound L.P. All rights reserved. Atlas Sound and Strategy Series are trademarks of Atlas Sound L.P. All other trademarks are the property of their respective owners. ATS004188 RevA 9/11
Specifications
ECM-20
Current Rating 20 Amps
Operating Voltage 102-132VAC
Minimum Spike
Clamping Voltage 460 VRMS @ 3000A
Maximum Spike
Clamping Voltage 6,000V
Power Consumption .5 Watts
Power Requirements 120V 60Hz
Height 3.0" (76.2mm)
Width 8.5" (215.9mm)
Depth 3.5" (88.9mm)
Weight 1.25 lbs. (.68 kg)
Certifications MET (UL 1449)
ECM-20M
Current Rating 20 Amps
Operating Voltage 102-132VAC
Minimum Spike
Clamping Voltage 460 VRMS @ 3000A
Maximum Spike
Clamping Voltage 6,000V
Power Consumption .5 Watts
Power Requirements 120V 60Hz
Height 3.0" (76.2mm)
Width 8.5" (215.9mm)
Depth 3.5" (88.9mm)
Weight 1.75 lbs. (.80 kg)
Certifications MET (UL 1449)
Architect and Engineer Specifications
Sequencing power module shall be Atlas Sound model ECM-20 or
ECM-20M. Sequencing power module shall have 2, 20A outlets.
Sequencing power module shall include Radio Frequency and
Electromagnetic filtering to reduce noise in AC lines where required
(EC M20-M) and AC surge and spike protection technology (ECM-20/M).
Sequencing power module shall have a manual bypass switch and
LEDs indicating Incoming AC (ECM-20/M), Active (ECM-20/M),
and AC Fault (ECM-20M). Units shall be designed to work with
Atlas Power raceway units: ECM-RACEWY6, ECM-RACEWY3, or
ECM-RACEWY1 for connecting to AC Mains power. Finish shall be
textured black epoxy and dimensions shall be 8.5"W x 3.5"D x 3"H
(215.9mm x 88.9mm x 76.2mm).
1601 JACK MCKAY BLVD. ENNIS, TEXAS 75119 U.S.A.