Atlantis Land A03-OP6000 User Manual

ISO 9001:2000 Company Cer tified
where solutions begin
True On Line Sinewave Double Conversion UPS
Powerful CPU integrates and True online architecture (pure sine-wave)
Very wide input range (160-280V) application without using battery power
The high crest factor of the inverter handles all high­inrush current loads without power rating upgrading
Smart Battery Management enhances battery utilization and life
SNMP Card embedded
Dual Input (Inverter e Bypass)
A03-OP6000
Product line “On-Power” is able to protect even the most sophisticated
electric devices thanks to the On-Line technology where the charge is
always powered by the UPS, granting reliable voltage and frequency
in every condition. No transfer time: On line UPS is always feeding the
load attached.
Built-in microprocessor controls continuosly UPS and battery functioning
granting their efficiency.
Crest factor allows the UPS functioning (without any power rating
increasing) with any power supply, especially for Computer Systems.
Smart Battery Management controls battery performance continuously
and it charges them only when they need it and only for the necessary
time.
Automatically corrects either under-voltage or over-voltage condition
without unnecessary battery drain and extend the battery’s life. Optional
interfaces AS-400, Relay (with dry contacts) andSNMPallowto place
thoseUPSboth in office and factory. In case of black out or overload,
also when mains is damaged, the UPS turns on the Protection System
for the users and for himself aswell.
Metal chassis guarantees higher protection from electromagnetic
disturbs.
The easy going installation and the intuitive usage make this product
suitable for any kind of user.
The built-in microprocessor allows the UPS (UPSilon2000 software is
included in all models) to communicate with your Personal Computer
thanks to the serial interface Rs232, making you able to check its
performances and planning its shut down and data savings every-
time.
On Power
ATLANTI S LAND S.p.A. - Viale De Gasperi 122 - 20017 Mazzo di Rho - Milano - ITALY Phone: +39 - (0)2 - 93.90.60.85 Fax: +39 - (0)2 - 93.90.61.61 - Web: www.atlantis-land.com - E-Mail: info@atlantis-land.com
Subject to change without notice
True On Line Sinewave Double Conversion UPS
A03 -OP 600 0_ SE_ 06 3
TECHNICAL FEATURES
MODEL
A03-OP6000
Power Rating
6000 VA - 4200 W
INPUT
Voltage (Vac) 160-280
Frequency (Hz) 50 ± 5% (Auto Sensing)
Phase SingleLine+Neutral+Ground
Input Power Factor > 0.99 (Full Load)
OUTPUT
Voltage (Vac) 220/230/240
Voltage Regulation ± 2%
Voltage Adjustement ± 0%; ± 1%; ± 2%; ± 3%
Frequency Stability ±0.2% (Free Running)
Frequency Regulation ± 1%; ± 3%
Wave Form Sine Wave, THD<4%
(no load to full load)
Rated Power Factor 0.7
Transfer Time 0 ms
Crest Factor 3:1
Efficiency (AC to AC) >90% (Normal)
Efficiency
(AC to AC, ECO)
>98% (ECO)
Run Time (Full Load) > 8 min
DC Start Yes
BATTERY
Type Maintenance Free Sealed
Lead Acid
Quantity (pcs) 20
Voltage (Vdc) 240
Recharge Time 4 Hours to 90%
Supplem. Charger Optional 1000W Isolated
chargers
PROTECTION
Short Circuit Hold Whole System
OverHeat Switch to Bypass
High Voltage Trip Switch to Backup Mode
Battery Low Alarm and Switch Off
Noise Suppression Complies with EN50091-2
Spike Suppression Complies with EN610000-4-5
OverLoad AC Mode:
1) <105% continuously Alarm
2) 105%-150% delay 40
seconds before switching to bypass
4) >150% immediately
switching to bypass
Backup Mode: Same Delay
Time as AC Mode, then
completely shutdown
MODEL
A03-OP6000
ALARMS
Audible and Visual Line Failure, Battery Low, Tranfer to Bypass,
System Fault Conditions
DISPLAY
Self Diagnostics Push Button (On Demand)
LED+LCD Utility, Battery, Inverter, Bypass, Self-Test,
OverLoad, Load/Battery Level and Fault
PHYSICAL
Dim (WxDxH) 290 x 645 x 748 mm
Outlets Terminal Block
Net Weights (Kgs) 80
ENVIRONMENTAL
Operating
Temperature
0-40o C
Temperature Warning The battery design life is based on a
temperature of 25o°C. Ambient temperature
above this range will reduce battery life
Altitude / Humidity 0-2000m up to 40°C, 3000m up to 35°C /
90% RH Humidity max (non-condensing)
Noise < 45 dB (at 1 metere)
COMPUTER
INTERFACE
Interface Type Standard RS232 Interface / SNMP
Protocol MEGATEC Protocol
AS 400 Interface Optional As400/ Basic Photo Contact
Interface Board provides Utility Failure,
Battery Low, Bypass Active, UPS
Shutdown functions
SNMP Adaptability Slot for Standard SNMP Card
Compatibility of
Bundled Software
UPSilon2000 for: Novell NetWare,
Windows95/98, Windows NT, Windows ME,
Windows 2000 and XP, Linux and FREE BSD
Optional Software UPSilion for UNIX, SNMP Adapter, USBMate
SAFETY
CONFORMANCE
Quality Assurance ISO9001 Certified Company
Marks CE
On Power