Atlantis Land A03-HP1000, A03-HP1500, A03-HP2000, A03-HP3000 User Manual

HOST POWER Series
SineWave Line-Interactive Technology
UPS
where solutions begin
PLUS
Powerful CPU integrates and True online architecture Expanded input voltage working range (±23%)minimizes battery usage User-friendly “hot swap” battery replacement Compact dimensions and Metal case Extensive front-panel diagnostic LED Display UPSilon2000 for real-time power & UPS status monitoring, automatic shutdown, schedule ON/OFF and many other advanced power
The Host Power series has been designed and constructed to protect your assets from the wide range of power aberrations experienced on Utility power lines today . It is your insurance for reliable, clean and stable volt age supply. It is worth taking care to install the system correctly and to have it maintained correctly by your local distributor. The main characteristics of this UPS line are:
-Nearly Zero Transfer (<3ms)
-Pure Sine-wave Inverter good for almost every kinds of load
-Powerful microprocessor design integrates all power stages as well as control and communication functions that strongly enhanced the functionality and reliability of Host Power series
-Batteries easy to be substituted by the user (hot swap)
-Should the output becomes short-circuited, the UPS holds the system and cuts the output automatically till the short circuit situation is removed
- True RS232 interface with dry contact signal for Novell/AS400 application
-Metal Case The easy installation and use make this product suitable for any kind of user.
The integrated microprocessor allows the UPS (the UPSilon2000 software is included in any model) to communicate, thanks to the serial interface RS232, with your Personal Computer , making you able to verify ,at any time, its functioning and to plan its switch-off and data savings.
HOST POWER Series
SineWave Line-Interactive Technology
UPS
TECHNICAL FEATURES
MODEL
Power Rating Power Rating
VOLTAGE
INPUT
OUTPUT
TRANSFER Line/Battery
BATTERY
PROTECTION
CONNECTIONS DISPLAY & DIAGNOSTICS
LCD Display
LED Display
RANGE Hz VOLTAGE WAVEFORM Hz
Half-load runtime Capacity Quantity Recharge Time Type Over/Under Volt. Overload &
Shot Circuit Low Battery
EMI/RFI Surge Protection Modem/Network Energy Rating Attenuation Noise Filtering
Output Computer
where solutions begin
A03-HP1000 A03-HP1500 A03-HP2000 A03-HP3000
1000 VA
600 W
Single Phase; 200/220/230/240V selectable by DIP Switch
Normal Mode: 10% of rated voltage; Inverter mode: 3%±±
Pure Sine-Wave with THD 5% at linear load
Inverter mode: 50Hz or 60Hz 0.1Hz±
9Ah 7Ah 7Ah 7Ah
2 3 4 6
<8hrs <5hrs <2hrs <2hrs
Sealed Maintenance Free Lead Acid VRLA Type
Switch to Battery Output whrn the Utility over regulation range
Current-limiting & NFB (No Fuse Breaker) protection for both Utility & Battery mode
Two stages, no battery drain after cut-off
Meet with IEEE 587 cat. A&B Standard
Better than 45dB @1Mhz for Normal/Common mode
4*IEC(Battery Power Supply) + 1*Schuko
Status:
Data:
Normal, AC Input High, AC Input Low, On Battery, Battery Low, Battery Bad, Overload, Fault, Phase error, Ground Fault Utility Voltage, Ouput Voltage, Output Hz, Load%, UPS Temperature, Battery Voltage, Runtime Timer(HH:MM)
Green=Normal, Amber=Warning, Red=Critical LCD shows detalis in respect to the lighting indication of LED
1500 VA
900 W
2000 VA 1200 W
±23% of nominal input voltage
50Hz/60Hz Auto-Select as Input Hz
Nearly Zero Transfer (<3ms)
8-12 min
Full time suppression
RJ11 / RJ45
960 Joules instantaneous response
EN50991-1
RS232(DB9)
With LCD & LED Display
3000 VA 1800 W
Beeping Alarm
Advanced Mode Communication Port
Environmental Condition SAFETY APPROVAL DIMENSION (W*H*D cm) Weight (N.W/ G.W) Kg
ATLANTIS LAND S.p.A. via De Gasperi, 122 - 20017 Mazzo di Rho (MI) Tel. 02 9390.6085 - Fax 02 9390.6161 - www.atlantis-land.com - info@atlantis-land.com
Società Certificata ISO 9001:2000
Overload, Fault, High Temperature, Battery On, Battery Low, Battery Bad, Over/Under Voltage, Frequency Error
Self-diagnostic; Direct Time-based readout of battery remained runtime
DB9 port with TRUE RS232 serial signal plus dry contact signals
0-37°C; 0-90% Non Condensing Humidity
CE/UL
17*24*37
14/16 22/24 26/28 34/36
Loading...