Atlantic Boilers Multi-Elec Compacte, Multi-Elec Compacte 36, Multi-Elec Compacte 48, Multi-Elec Compacte 72, Multi-Elec Compacte 60 Technical Manual

Multi-Elec
COMPACTE BOILER
TECHNICAL MANUAL
CE Directive 2006/95/CEE British Standard EN 60335-1 (C 73800)
FOR TECHNICAL HELP/ADVICE Call 0161 621 5960
or email info@atlanticboilers.com
FOR FULL PRODUCT RANGE & LITERATURE
Visit www.atlanticboilers.com
ATLANTIC BOILERS, PO BOX 11, ASHTON UNDER LYNE, OL6 7TR T: 0161 621 5960 E: info@atlanticboilers.com www.atlanticboilers.com
CONTENTS
1) INTRODUCTION
1.1) Description 3
1.2) Dimensions & connections 4
2) INSTALLATION
2.1) Procedure 5
2.2) Arrangement 5
2.3) Essential accessories 6
2.4) Precautions 7
2.5) Boiler room arrangements 7
2.6) Commissioning 7
3) ELECTRICAL ARRANGEMENTS
3.1) Control panel arrangement 8
3.2) Control circuitry 9
3.3) Electrical power circuitry 10
3.4) Fuse and overload protection 11-12
3.5) Operation of the digital controller 13
3.6) Alarm signals 14
4) DELIVERY and OFF-LOADING 14
5) MAINTENANCE 15
6) GUARANTEE 16
7) IDENTIFICATION OF SPARE PARTS 17
8) FAULT DETECTION 17
2
1) INTRODUCTION
1.1) Description
The COMPACTE electric boiler is suitable for a variety of types of space heating and indirect domestic hot water – covering sealed circuits from 0.5BARS to 7.0BARS working pressure.
The COMPACTE electric boiler always requires earthing, under protection index IP21/1K 08.
The COMPACTE electric boiler is designed and manufactured according to the following :-
EN Decree 95-1081control of boiler materials and electrical supply voltage used in
order to conserve the safety of persons and animals which might be in the vicinity
European Directive 2006/95/CEE covering low voltage system application BS EN 60335-1 class C73800, part 1, general rules
3
Model
Maximum
Amps
Weight
Footprint
Depth mm
Width mm
Height
36 36 56 120
400 x 600
690 500 1240
48 48 75
122
400 x 600
690 500 1240
60 60
9
4 124
400 x 600
690 500 1240
72 72
124 126
400 x 600
690 500 1240
Access mm: One side: 500 Other side: 100 Front: 1000 Rear: 500 Height: 1240 + 700
1.2) Dimensions and connections
Output
kW
Access to remove immersion heater elements
The COMPACTE electric boiler range covers from 36kW to 72kW and is complete with pre­wired electrical controls. Generally, it requires an unvented circuit containing clean water and without inhibitor or other water treatment. The main boiler body is manufactured from S235JR 10025-2:2004 quality carbon steel without internal coating.
Data for 36kW to 72kW models Water content – 70l Maximum working pressure – 4BARS Test pressure – 6BARS Dry weight – 110kgs Maximum working temperature – 99degC Limit temperature – 110degC Maximum water flow rate–3.0l/sec Pressure drop–4kPA Minimum water flow rate-0.8l/sec Glass wool thermal insulation – 50mm thick
per
phase
kg
mm
mm
4
Expansion
Pressure &
Auto air
Non return
Pressure relief
Isolating
Fill Loop
2) INSTALLATION
2.1) Procedure
* Position the boiler squarely on the prepared base * Fit the correct accessories to the boiler connections * Connect the boiler to the pipework system * Connect the boiler to the isolated electrical supply * Fill the boiler with fresh, clean water * Check that the immersion heaters are electrically isolated from the boiler. If the isolation is less than 2mega-ohms, the bridge must be
found and rectified. * Check the operation of the main control panel isolator, and of the overloads serving the immersion heaters * Check the operation and the correct direction of rotation of the circulating pump * Check, with the circulation pump stopped, that the water flow switch over-rides the immersion heaters through their relays and also brings on the relevant alarm light * Check the setting and operation of the immersion heater step controls * Switch off the immersion heaters using the main control panel isolator * Check that all the cartridge fuses are sound * Double check that all the immersion heaters receive the common voltage. Repeat the check after several hours run. Any defect in
voltage can destroy the heaters and invalidate the guarantee.
2.2) Basic heating arrangement
Auto top-up system
vessel
vent
valve
temperature relief valve
3 port valve
Pump
valve
ball valve
Radiators
5
2.3) Essential accessories
The following items are required :­A. One 4-bar safety valve and one 7bar temperature and pressure relief valve B. One shunt pump
– protected by overloads (0.37A to 1.4A adjustable) and run + fault lamps
C. One water flow switch
- Recommended water flow settings in litres per second Pipeline sizes 32mm 40mm 50mm 65mm
Minimum range 0.35-0.47 0.53-0.72 0.61-0.83 1.0-1.4
Maximum setting 1.0 1.6 1.9 3.2
D. One automatic air vent with isolating valve E. One drain ball valve
6
2.4) Precautions
The Multi-elec Compacte requires an installation conforming to
89.336/EEC Directive (electromagnetic compatibility)73/23/EEC Directive (low voltage)92/42/EEC Directive (performance)
2.5) Boiler room arrangements
The Multi-elec Compacte must be installed  In an adequately-ventilated boiler room with ambient temperature below 30degC
And relative humidity maintained between 30% and 80% and where condensation does not occur
In a non-corrosive atmosphere In a non-explosive atmosphere Where there is good access to the boiler position for installation and maintenance Where there is good access for delivery, off-loading and positioning Using similar materials in the pipework, and avoiding materials leading to electrolytic
action and system deterioration
The Multi-elec Compacte is not suitable for external installation
2.6) Commissioning
The boiler must be completely full of water before the heating elements are switched
on. To ensure 100% filling, manual and automatic vents must be in effective positions where complete air clearance can be guaranteed.
The boiler can be filled with water by connecting a fill hose to the boiler drain valve
and partly opening the valve.
The boiler safety valve can also be used firstly to vent the boiler at filling and,
secondly, ensuring the blow-down facility of the valve is clear in case of use.
Commissioning is recommended by Atlantic 2000 or an authorised engineer for
Atlantic equipment.
7
3) ELECTRICAL ARRANGEMENTS
3.1) Control panel arrangement
Photograph of control panel with identification of components
8
External Controls
9
3.3) Electrical power circuitry
10
Km2 12kW 24kW 24kW 36kW
3.4) Fuse and overload protection
Fuse ratings and type Fuses F1 – F2 cartridge F1 – 1A type aM, cartridge F2 – 1A type gG Fuses F3 – F4 cartridge F3 & F4 type 10 x 38 to 22 x 58
Amperage requirement
415V 3ph 36kW 48kW 60kW 72kW
Step 1 F3 40A (14x51) 40A (14x51) 63A (22x58) 63A (22x58) Km1 24kW 24kW 36kW 36kW Step2 F4 20A (10x38) 40A (14x51) 40A (14x51) 63A (22x58)
ELECTRICAL CIRCUIT
The Compacte electric boiler must be provided with 415volts and
without neutral wiring
The electrical wiring cables must be sized by a qualified electrician in
order to conform to BS C 15100 and satisfying load, length of run and prevention of short circuit.
The installation must be tested for automatic power failure in the
event of emergency power cut, heater lock-out or error in the neutral layout.
All electrical equipment shall satisfy IP21/IK08 Class 1 The immersion heaters shall only receive electrical power if they are
fully immersed in water; otherwise the guarantee on the heaters will not apply
ALL ELECTRICAL WIRING MUST BE CORRECTLY EARTHED
11
12
3.5) Operation of the digital controller
Sous Tension – Alive Step 1 Limit thermostat 110degC Arret – stop Marche – run Step 2 Secure Factory settings – Step 1 – 80degC; Step 2 – 75degC 1 – digital numbers or message 2 – touch settings 3 – touch raise settings 4 – touch lower settings 5 – controller action Light out – none, light on – in action 6 - controller reading 7 - error/lockout
Adjusting temperatures a) SET 1 – step 1 SET 2 – step 2 b) SET 1 is always higher than SET 2 c) Minimum temperature setting +20degC d) Maximum temperature setting +99degC e) Set SET 1 to 3degC below factory setting and allow 3 minutes to reach the setting f) Set SET 2 to 2degC below factory setting and allow 3 minutes to reach the setting g) Replace SET 1 and SET 2 at the factory settings
AFTER THE WAITING PERIOD OF 3 MINUTES A) Touch (2) SET 1 for 5 seconds – reading (6) shows B) Make adjustments to (6), touching (3) and (4) C) Confirm the setting SET 1 by touching (2)
Indicator (1) flashes, indicating that Step One is confirmed Setting (6) fades out and after several seconds, the actual temperature is shown
D) Touch (2) SET 2 for 5 seconds – reading (6) shows E) Make adjustments to (6), touching (3) and (4) F) Confirm the setting SET 2 by touching (2)
Indicator (1) flashes, indicating that Step One is confirmed Setting (6) fades out and after several seconds, the actual temperature is shown
13
Lifting eyes
3.6) Alarm Signals
On Alarm, light (7) shows and the following messages appear on (1) < PFO > Lock-out or power cut < HA > High temperature lock-out < LA > Low temperature alarm
4) DELIVERY and OFF-LOADING
It is recommended that the COMPACTE electric boiler is transported and, if necessary, stored on the pallet on which it is delivered from the factory. If temporarily stored, the surroundings should be maintained at temperatures below 80degC, and without condensation at relative humidities between 30% and 80%
Manhandling the COMPACTE electric boiler into position requires :-
(a) Qualified, skilled manpower (b) Use of a pallet trolley or a fork lift truck (c) Use of the lifting eyes provided on the boiler and tested lifting beams
14
5) MAINTENANCE
Effective maintenance must aim at preventinga). a reduction in the movement of water circulation through the boiler
- this can result in the formation of sediment or limescale on the boiler immersion heater elements b). pockets of high temperature water across the boiler immersion heater elements – resulting in their destruction by overheating c). accumulation of sediment or limescale within the boiler, particularly on or around the boiler immersion heater elements – overcoming these developments by the introduction of fresh, clean water without any inhibitor or de-scaling agent
Minimum maintenance periods
A). Monthly maintenance i). Check operation of the automatic air vent ii). Check operation of the water flow switch iii). Check operation of the safety valve
B). Annual maintenance i). Carry out the monthly checks ii). Check all the electric control functions iii). Check all pipework joints are water-tight iv). Drain off small amount of boiler water content and check for condition
C). 3-yearly maintenance i). Carry out the annual maintenance ii). Isolate the boiler safely from all services iii). Drain the boiler of water and open up for inspection iv). Check for all maintenance requirements and remedy as necessary v). Close and seal the boiler, fill with fresh clear water through drain outlet vi). Pressure test, then repeat annual maintenance procedure
15
6). GUARANTEE
16
7). IDENTIFICATION OF SPARE PARTS
Controller XT120C (5 COPU) 583042 Flow sensor PTC 583024 240V lamp bulb 587215 12kW immersion heater 2412 Limit thermostat 581104 Water flow switch 480230
8). FAULT DETECTION
Before making any physical check, switch off the power
FAULT CHECK The ‘alive’ light is out Check for incoming power Check fuses F1 and F2 Check the ‘alive’ bulb ……………………………………………………………………………………………………………………….. The controller screen is out Check fuse F3 …………………………………………………………………………………………………………………………. Step 1 or Step 2 light is out Change the bulb …………………………………………………………………………………………………………………………. The ‘red’ light is lit Check the limit thermostat Check the water flow switch action Check the circulating pump overload ………………………………………………………………………………………………………………………….. If the fault remains Call in a qualified service engineer
17
Loading...