Environmental & Safety
• Storage Temperature: -20ºC to 50ºC
(-4F-122F)
• Operating Temperature: 0ºC to 40ºC
(32F-104F)
• Max Changes per hour temp: 30ºC
• Operating Humidity: 80% Max
Non-Condensing
• Conforms to IEC61010 CAT III 600V
• Operating environment: Indoors
The Cx Monitor® is a power quality monitor adapted
specifi cally for the needs of a commissioning agent.
The monitor gathers all of the voltage and current
data required for all of the commissioning tests as well as
provides a means for gathering wireless T&H or DC voltage
data for over one hundred (100) locations! The Cx Monitor®
is equipped to simultaneously monitor in real time, voltage on
ten (10) separate channels and current on fi ve (5) separate
channels. This is ideal for documenting the testing of generators, UPS’s and transfer switches.
General Specifi cations:
• Clock: Leap Year, 24-Hour, with time zone info
• Real-time Clock Accuracy: +/- 1 sec / day max.
• Internal Memory: Minimum 512Mbytes high speed
NAND Flash
• Wireless 802.11g Integration (Ad-hoc mode)
• 10/100Mbit Ethernet; FTP, SMTP, H P, H PS, SSL, SSH.
• USB Mass storage class support
• Remote access though secure remote Ethernet tunneling
• Max number of events: Only limited by internal memory
• Power Requirements: 100V-240V ACrms +/-10% 47-63 Hz
10Wa s 24Vdc 0.5Arms Center Barrel positive
• UPS standby time: Programmable Max time 10 Minute
• Dimensions: 11.5 x 10.25 x 4 Inches.
(Height x Width x Depth)
• Weight: 5.55lb
Synchronization & Sampling:
Low Frequency:
• Sampling Frequency: 256 samples/cycle
• A/D Resolution: 16 bit oversampled
voltage 2X ; current 4X
• Auto 50/60 Hz ; or locked to input
• Voltage & Current RMS triggers ; Cross
triggering
• Adaptable trigger thresholds
High Frequency:
• 1.666Msample/sec per channel.
• A/D Resolution: 12 bit
©2013 Rx Monitoring Services Inc.
Voltage and Current Measurement:
Low Frequency
• Voltage Measurement Range: 0-600Vrms
• Voltage input impedance: 1.2Mohm
High Frequency
• Voltage Measurement Range: 0-2,500V
• Measurement type: AC coupled digital threshold trigger
500 sample buff er per channel
• Voltage input impedance: 1.2Mohm
Current Measurement Range (Probe dependant)
• Current input type: AC/DC +/- 6Vdc Input impedance
120K, 1M to gnd.
Specifi cations are subject to change without notice.
Log Types & Rates:
RMS Voltage / Current:
1 Second to 30 Minutes
10 Voltage Channels Ph-Ph, Ph-G, Ph-N & N-G
5 Current Channels { L1, L2, L3, N & G}
1 Residual Current {L1+L2+L3+N}
RMS Voltage Imbalance
Frequency:
10 Seconds to 30 Minutes
3 Voltage {L1-G, L2-G, L3-G}
Peripherals:
4 Seconds to 30 Minutes
Up to 100 Probes
Wireless DC Voltage +/- 0-600V AutoRanging
Wireless DCx Voltage {10Ch - 60dc}
Wireless DC Current {2,000A, 4,000A}
Wireless Temperature / Humidity
Wired Temperature / Humidity
Power:
10 Seconds to 30 Minutes
3 Phase Delta
{Min/Max/Average} Apparent Power(KVA), Real
power(KW), Reactive (KVAR) Power Factor (PF). Total KVA,
Total KW, Total KVAR, Total PF, Total KVAH, Total KWH, Total
KVARH, Total Demand(KVA) and Total Demand(KW)
3 Phase Wye - Split Phase - Single Pole Single Phase
{Min/Max/Average} Apparent Power(KVA), Real
power(KW), Reactive (KVAR) Power Factor (PF). Total KVA,
Total KW, Total KVAR, Total PF, Total KVAH, Total KWH, Total
KVARH, Total Demand(KVA) and Total Demand(KW)
2 Pole Single Phase
{Min/Max/Average} Apparent Power(KVA), Real
power(KW), Reactive (KVAR) Power Factor (PF). Total KVA,
Total KW, Total KVAR, Total PF, Total KVAH, Total KWH, Total
KVARH, Total Demand(KVA) and Total Demand(KW)
Harmonics:
10 Seconds to 30 Minutes
3 Ph-Ph, 3 Ph-G & 3 Current channels to the 31st.
THD:
10 Seconds to 30 Minutes
3 Ph-Ph, 3 Ph-G & 3 Current{Odd, Even, Total & Max}
Phase Angle:
10 Seconds to 30 Minutes
3 Ph-Ph, 3 Ph-G
Symmetrical Components:
10 Seconds to 30 Minutes
Voltage & Current : Magnitude, Angle & Imbalance
Voltage and Current Accuracy:
Low Frequency
• A/D Measurement type: True RMS calculated every half cycle
• A/D Measurement Uncertainty: AC +/- 0.1% reading +/- 0.1% full scale above 50Vrms
DC +/- 0.1% reading +/- 0.1% full scale above 50V dc Off set Error: AC/DC: 0.05Vrms
High Frequency
• A/D Measurement type: Sampled reshold cross 500 sample buff er per channel
• A/D Measurement Uncertainty: AC +/- 5% reading Off set Error: AC: 5V
Current:
• A/D Measurement type: True RMS calculated every cycle
• A/D Measurement Uncertainty System:
• AC +/- 0.1% reading +/- 0.1% full scale above 50Arms
• DC +/- 0.1% reading +/- 0.1% full scale above 50Adc
Off set Error: AC/DC: 1Arms