Atec Rx-Cx-Monitor User Manual

Environmental & Safety
• Storage Temperature: -20ºC to 50ºC (-4F-122F)
• Operating Temperature: 0ºC to 40ºC (32F-104F)
• Max Changes per hour temp: 30ºC
• Operating Humidity: 80% Max Non-Condensing
• Conforms to IEC61010 CAT III 600V
• Operating environment: Indoors
The Cx Monitor® is a power quality monitor adapted
specifi cally for the needs of a commissioning agent.
The monitor gathers all of the voltage and current data required for all of the commissioning tests as well as provides a means for gathering wireless T&H or DC voltage data for over one hundred (100) locations! The Cx Monitor® is equipped to simultaneously monitor in real time, voltage on ten (10) separate channels and current on fi ve (5) separate channels. This is ideal for documenting the testing of genera­tors, UPS’s and transfer switches.
General Specifi cations:
• Clock: Leap Year, 24-Hour, with time zone info
• Real-time Clock Accuracy: +/- 1 sec / day max.
• Internal Memory: Minimum 512Mbytes high speed NAND Flash
• Wireless 802.11g Integration (Ad-hoc mode)
• 10/100Mbit Ethernet; FTP, SMTP, H P, H PS, SSL, SSH.
• USB Mass storage class support
• Remote access though secure remote Ethernet tunneling
• Max number of events: Only limited by internal memory
• Power Requirements: 100V-240V ACrms +/-10% 47-63 Hz 10Wa s 24Vdc 0.5Arms Center Barrel positive
• UPS standby time: Programmable Max time 10 Minute
• Dimensions: 11.5 x 10.25 x 4 Inches. (Height x Width x Depth)
• Weight: 5.55lb
Synchronization & Sampling:
Low Frequency:
• Sampling Frequency: 256 samples/cycle
• A/D Resolution: 16 bit oversampled voltage 2X ; current 4X
• Auto 50/60 Hz ; or locked to input
• Voltage & Current RMS triggers ; Cross triggering
• Adaptable trigger thresholds High Frequency:
• 1.666Msample/sec per channel.
• A/D Resolution: 12 bit
©2013 Rx Monitoring Services Inc.
Voltage and Current Measurement:
Low Frequency
• Voltage Measurement Range: 0-600Vrms
• Voltage input impedance: 1.2Mohm
High Frequency
• Voltage Measurement Range: 0-2,500V
• Measurement type: AC coupled digital threshold trigger 500 sample buff er per channel
• Voltage input impedance: 1.2Mohm
Current Measurement Range (Probe dependant)
• Current input type: AC/DC +/- 6Vdc Input impedance 120K, 1M to gnd.
Specifi cations are subject to change without notice.
Log Types & Rates:
RMS Voltage / Current: 1 Second to 30 Minutes
10 Voltage Channels Ph-Ph, Ph-G, Ph-N & N-G 5 Current Channels { L1, L2, L3, N & G} 1 Residual Current {L1+L2+L3+N} RMS Voltage Imbalance
Frequency: 10 Seconds to 30 Minutes
3 Voltage {L1-G, L2-G, L3-G}
Peripherals:
4 Seconds to 30 Minutes Up to 100 Probes Wireless DC Voltage +/- 0-600V AutoRanging Wireless DCx Voltage {10Ch - 60dc} Wireless DC Current {2,000A, 4,000A} Wireless Temperature / Humidity Wired Temperature / Humidity
Power:
10 Seconds to 30 Minutes
3 Phase Delta
{Min/Max/Average} Apparent Power(KVA), Real power(KW), Reactive (KVAR) Power Factor (PF). Total KVA, Total KW, Total KVAR, Total PF, Total KVAH, Total KWH, Total KVARH, Total Demand(KVA) and Total Demand(KW)
3 Phase Wye - Split Phase - Single Pole Single Phase
{Min/Max/Average} Apparent Power(KVA), Real power(KW), Reactive (KVAR) Power Factor (PF). Total KVA, Total KW, Total KVAR, Total PF, Total KVAH, Total KWH, Total KVARH, Total Demand(KVA) and Total Demand(KW)
2 Pole Single Phase
{Min/Max/Average} Apparent Power(KVA), Real power(KW), Reactive (KVAR) Power Factor (PF). Total KVA, Total KW, Total KVAR, Total PF, Total KVAH, Total KWH, Total KVARH, Total Demand(KVA) and Total Demand(KW)
Harmonics:
10 Seconds to 30 Minutes
3 Ph-Ph, 3 Ph-G & 3 Current channels to the 31st.
THD:
10 Seconds to 30 Minutes
3 Ph-Ph, 3 Ph-G & 3 Current{Odd, Even, Total & Max}
Phase Angle:
10 Seconds to 30 Minutes
3 Ph-Ph, 3 Ph-G
Symmetrical Components:
10 Seconds to 30 Minutes
Voltage & Current : Magnitude, Angle & Imbalance
Voltage and Current Accuracy:
Low Frequency
• A/D Measurement type: True RMS calculated every half cycle
• A/D Measurement Uncertainty: AC +/- 0.1% reading +/- 0.1% full scale above 50Vrms DC +/- 0.1% reading +/- 0.1% full scale above 50V dc Off set Error: AC/DC: 0.05Vrms
High Frequency
• A/D Measurement type: Sampled  reshold cross 500 sample buff er per channel
• A/D Measurement Uncertainty: AC +/- 5% reading Off set Error: AC: 5V
Current:
• A/D Measurement type: True RMS calculated every cycle
• A/D Measurement Uncertainty System:
• AC +/- 0.1% reading +/- 0.1% full scale above 50Arms
• DC +/- 0.1% reading +/- 0.1% full scale above 50Adc Off set Error: AC/DC: 1Arms
©2013 Rx Monitoring Services Inc.
Specifi cations are subject to change without notice.