Portable AC Hipot Test Sets
0-10 kVac, 0-30 kVac, 0-50 kVac and 0-100 kVac
Description
The PFT Series of portable AC hipot test sets are ideal for a variety of eld
and repair shop testing applications. These inexpensive, compact and light
weight units are rugged and reliable. Our 3 kVA models feature capacitive
load compensation enabling full load testing with a power draw of 1.5 kVA
while operating from a conventional line input.*
Applications
Model PFT-503CM
(0-50 kVac)
Model PFT-301CM
(0-30 kVac)
Model PFT-1003CM
(0-100 kVac)
These units are well suited for testing overhead apparatus, vacuum bottles
and interrupters, switch gear, bus duct, motorized vacuum switches,
reclosers, bushings, fuses and arrestors, linemans safety products, small
transformers, electrical components and motors.
For AC cable testing, we offer a variety of Very Low Frequency AC
hipots that are well suited for testing long cable lengths. Please contact our
sales ofce for more information on cable testing applications.
Control Features
Control features on our 3 kVA models include a dual range kilovoltmeter
and triple range output current meter. All of our units feature continuously
adjustable output voltage control, external safety interlock, zero start safety
interlock, self resetting over current protection, guard/ground return mode,
HV on/off and main power pushbuttons and ruggedized meters with glass
windows that eliminate static buildup.
An optional fault burning mode is available for our 3 kVA models and for
increased portability, a hand cart option is available for the PFT-1003CM.
Advantages
We offer four single piece, shielded output cable models: PFT-103CM,
PFT-301CM, PFT-303CM and PFT-503CM. A two piece 100kV model
PFT-1003CM with a top toroid termination (no output cable) is also
available. In addition, we offer an ALT-120/60 that is specialized for Aerial
Lift and Bucket Truck testing applications and suitable for general AC high
voltage testing applications. Custom models are available from 10kVac to
300kVac output.
HIGH VOLTAGE, INC.
High Voltage, Inc. designs and manufactures high voltage test equipment for utility and industrial applications. Also available are Very Low
Frequency (VLF) high voltage AC test sets, oil dielectric test sets, AC and DC instrumented test sets, cable fault locators and other products.
31 County Rt. 7A • Copake, NY 12516 • (518) 329-3275 • Fax: (518) 329-3271
E-Mail: sales@hvinc.com • Web: www.hvinc.com
Input
HV Output
PFT Model Specifications
Advantages
PFT-103CM
PFT-303CM
PFT-503CM
PFT-1003CM
120 V, 60 Hz, 15A, or 230 V, 50/60 Hz, 8A
0-10 kVac, 1kVA resistive load
3 kVA capacitive load
Up to 300 mA current
0-100 kVac, 1 kVA resistive load
3 kVA capacitive load
Up to 30 mA current
0-50 kVac, 1kVA resistive load
3 kVA capacitive load
Up to 60 mA current
0-30 kVac, 1kVA resistive load
3 kVA capacitive load
Up to 100 mA current
20 ft. (6m) long shielded output cable
with alligator clamp and hook for test connections
3kVA: 1 hour ON, 1 hour OFF
1kVA: continuous
<5%
2% F.S.
3.5 inch
Scaled 0-5/10 kVac
3.5 inch
Scaled 0-50/100 kVac
3.5 inch
Scaled 0-25/50 kVac
3.5 inch
Scaled 0-12/30 kVac
3.5 inch
Scaled 0-40 mAac
3.5 inch
Scaled 0-1.0
mAac, with x1, x10, x100 Range Multiplier
Top Toroid
(No output cable)
21È w x 11.25È d x 15.25È h
533 mm w x 286 mm d x 387 mm h
High Voltage Tank included in controls
13È w x 13È d x 22È h
330 mm w x 330 mm d x 559 mm h
62 lbs. (28kg)
75 lbs. (34kg)
75 lbs. (34kg)
Control–35 lbs. (16kg)
HV Tank–85 lbs. (39kg)
Models below 100 kVac are single piece units with a shielded cable output for fast and easy test setup. The
PFT-103CM, PFT-303CM, PFT-503CM, and PFT-1003CM are compensated enabling testing of 3 kVA loads with a
power draw of 1.5 kVA and operate from a conventional electrical source*. In addition, these units include a dual range
kilovolt meter, triple range output current meter and a guard/ground return mode enabling the operator to measure the
total current to ground or only the current flowing through the sample under test.
Portable AC Hipot Test Sets
Note: For 230 volt line input, an F is suffixed to the model number.
PFT-301CM
0-30 kVac, 1kVA resistive load
33 mA current
120V, 60 Hz, 10A
or 230V, 50/60 Hz, 5A
1kVA, 1 hour ON,
1 hour OFF
700VA: continuous
3.5 inch
Scaled 0-30 kVac
3.5 inch
Scaled 0-3.0 mAac
with x1, x10 x100 Range
Multiplier
17È w x 11.5È d x 14È h
431 mm w x 292 mm d
x 365 mm h
45 lbs. (20kg)
PFT-301CM Control Layout
PFT-503CM Control Layout
*3 kVA output power is only available with a capacitive load sized to draw 3 kVA at full rated output.
Available output current decreases with other loads.
at full output voltage in ground
mode but not guard mode
Output
Termination
Duty
Distortion
Meter Accuracy
Kilovolt Meter
Current Meter
Control
Dimensions
H.V. Tank
Dimensions
Weight
2.5 mA
1.0 mA 14 mA
20 mA
2.0 mA
No Load Current:
HIGH VOLTAGE, INC.
31 County Rt. 7A • Copake, NY 12516 • (518) 329-3275 • Fax: (518) 329-3271
E-Mail: sales@hvinc.com • Web: www.hvinc.com
Revised 10/18/07
High Voltage, Inc. designs and manufactures high voltage test equipment for utility and industrial applications. Also available are Very Low
Frequency (VLF) high voltage AC test sets, oil dielectric test sets, AC and DC instrumented test sets, cable fault locators and other products.