Eagle Eye LB-75-200-3-5-400 Portable Resistive Load Bank Specifications
Rating: 75 kW, 94 kVA at 200 Volts AC, 3 Phase, 400 Hertz, 217 Amps per Phase
Tolerance: 3%
Power Factor: 1.0
Duty Cycle: Rated for continuous generator test operation.
Load Connections: Quick disconnect power connections 3 Phase 4 Wire “wye” (A,B,C,N)
Load Steps: 5, 10, 10, 25, & 25 kW each at 200 Volts AC 3 phase (75 kW total)
Easy to use operator control panel with:
Air-flow indicating red and green lights
Over-temperature red light Master on/off switch Fan on/off switch Master Load switch Individual load step switches
Safety Features: Fast acting branch circuit fuse protection on all 3 phases of all load steps Fused 120V control circuit Air pressure switch to prevent load from being applied if loss of cooling air is detected Over-temperature sensor automatically removes load if an over-temperature condi Blower Motor circuit is protected by current overload protection. Operator warning and caution statements are located on appropriate access panels and doors.
Control Power:
110-120 VAC, 1 Phase, 50/60 Hz, required for control circuit operation. Line cord provided.
Cooling System: Integrally mounted, high velocity, low noise, 110-120V AC 1 phase 50/60 Hz. fans provide the necessary cooling air for the resistor load elements.
Construction: Rugged construction all metal frame Durable powder coat fin
ish Lifting handles Stainless steel exterior fasteners Horizontal Airflow Front control guards / handles
Unit Dimensions: 14" wide x 26" long x 22" tall
Weight: Approx. 75 lbs.
Optional Features Available:
Mating Anderson plug set Cable set Storage cover Wheel kit Padded hard case with wheels and telescoping handle
tion is detected