LB-Series DC Load Banks
Model # LB-SERIES
DC Load Banks LB-SERIES
Data Acquisition Case (DAC):
Eagle Eye’s SMART Load Banks come standard
with monitoring of the system during discharge as well as four (4) conditions to automatically stop
the test. An optional DAC package allows the voltage of EACH CELL to be wirelessly recorded and
displayed during discharge. The DAC package
allows the user to evaluate the health of each cell
and replace only the cells that require replace-
ment-savingtimeandmoneybysignicantly
reducing labor hours and replacement costs.
LB-Series DC Load Bank
To Order Call Toll Free:
1-877-805-3377
Product Overview
Eagle Eye’s SMART DC Load Banks are designed for discharge testing, battery capacity testing, acceptance testing, battery maintenance
and other testing for DC power with a load. The LB-Series load
banks are portable, economic, easy-to-use and come complete with
DataView Software for data management and analysis. With over
35 standard models, the LB-Series is used in a variety of industries
including utilities, telecommunications, UPS, motive power/forklifts,
transportation, CATV and many more. Custom Solutions are available. Eagle Eye load banks are designed to make discharge testing
convenient and easy for any application.
LB-Series Features
• SMART Load Banks with system monitoring and cell monitoring
• Powerful management software for data analyzing and report
building
• Rugged, compact and portable units
• PTC Ceramic resistor for safe discharging
• Four settings for auto shut-down of discharge: discharge
time, discharged capacity, cell cut-off voltage and total cut-off
voltage
• Parallel connection of two units for mass discharge testing
• Thermal cut-off and automatic overload protection
• Safe circuits avoid damage to battery when testing
• Optional Real-time display of voltage for each cell with DAC
package
• Optional: Optional DAC Package for 12v Only for Real-Time
Wireless Monitoring Per Cell
22
Data Acquisition Case (DAC)
DAC Connection to 48V System (2V Cells)
www.eepowersolutions.com | p: +1-414-962-3377 | toll free: +1-877-805-3377 | fax: +1-414-962-3660
Discharge Dataview
Software
The included Dataview
software allows the user to
create customized reports with company name,
contact, testing location,
battery manufacturer, model
number, number of cells,
and much more. DataView
reports provide the test
criteria, list of weakest cells,
graph of weakest cells, string
information, individual cell
information, time stamping,
discharging graphs and an
area to add notes.
TechnicalSpecications
To Order Call Toll Free:
1-877-805-3377
Carrying CaseLive Monitoring of Discharge Test
Cell Voltage:
Standard DAC: 1.2V*, 2V, 6V, 12V / Optional: Custom
DACcongurationsavailableuponrequest
Discharge Current Range: Single Load: 12 – 600A / Parallel Load: 24 – 1200A
Range: 10 – 576V (Max)
Discharge Voltage Range:
Voltage Steps: 12V, 24V, 36V, 48V, 80V, 125V, 240V,
380V, 480V
Accuracy: Discharge Current: 1% / Voltage: 0.5% – 0.8%
Resolution: Discharge Current: 0.1 A or 0.5% / Voltage: 0.001 V
Sampling Interval: 5 seconds – 1 minute
Data Transfer: USB, Wireless (466 MHz)
Display: Backlit LCD
Operating Environment: 0 – 40 °C (32 – 104 °F)
Power Requirements: 110/220 VAC 50/60 Hz / DC (from connected batteries)
Small: 400 x 177 x 288 mm (15.7 x 7 x 11.3 in)
Medium: 520 x 202 x 355 mm (20.5 x 8 x 14 in)
Dimensions:
Large: 555 x 225 x 435 mm (22.5 x 8.9 x 17.2 in)
X-Large: 603 x 400 x 740 mm (23.7 x 15.7 x 29 in)
XX-Large: 762 x 406 x 737 mm (30 x 16 x 29 in)
Small: 11 kg (24 lbs) Medium: 16 kg (36 lbs) Large: 21
Weight:
kg (47 lbs) X-Large: 42 kg (93 lbs) XX-Large: 55 kg (122
lbs)
Safety Standard: CE Market, EMC Standard
*The standard DAC package includes the adequate amount of DAC’s & cabling for testing 2V/6V/12V batteries.
If testing 1.2V NiCad’s batteries, please advise your sales representative to ensure you receive the additional
DAC’s and cabling that will be required.
Kit Includes:
• LB-Series Load Bank
Unit
• Dataview Management Software
• Carrying Case (with
Small & Medium
models)
• Set of 10’ Red/Black
Load Cables
• Set of 10’ Red/Black
Voltage Cables
• Data Comm Terminal
• USB-RS232 Cable
• Grounding Cable
• AC Power Cord
• 1GB USB (with Firm-
ware, User Manual,
Software)
• (2) Antenna
• LB-Series User
Manual
• Optional: Standard
DAC Package
• Optional: Current
Clamp for Assisted
Load Testing
DC Load Banks LB-SERIES
Ordering Information
No. Model # Description
1 LB-Series*
www.eepowersolutions.com | p: +1-414-962-3377 | toll free: +1-877-805-3377 | fax: +1-414-962-3660
SMART DC Load Bank with Monitoring (12-480V, 100-600A)
*See next page for listing of model numbers
*Add “DAC” after model number for wireless monitoring per cell
23