Atec DELTA3000 User Manual

10 kV Automated Insulation Power Factor Test Set
DELTA3000
10 kV Automated Insulation Power Factor Test Set with “PowerDB OnBoard”
Integrated PowerDB software package allows for automated control without the use of a laptop
Rugged, portable unit for field/shop use and designed to work in high interference switchyards of up to 765 kV
Built-in capability for storing, printing and downloading test results
Optional module for LV 3-phase TTR testing and excitation current up to 500 mA
DELTA3000
DESCRIPTION
The DELTA3000 is a fully automatic 10 kV insulation power factor test set designed for condition assessment of electrical insulation in high voltage apparatus such as transformers, bushings, circuit breakers, cables, lightning arresters and rotating machinery. In addition to performing insulation power factor tests, the DELTA3000 can be used for measuring the excitation current of transformer windings.
The DELTA3000 allows for direct data feed into PowerDB for automatically generating test reports such as table of contents, data sheets, deficiency and comments r data can be saved in an XML file with all historical data. This allows the user to view the previous year’s test sheet or to trend specific test points. If a user also has a full license of PowerDB, test sheets can be modified and downloaded to the instrument to customize the instrument’s personality and procedures in order to meet customer needs.
The unit’s intuitive and easy-to-use interface allows the user to configur QWERTY keyboard makes it simple for entering all nameplate and location infor also included in the unit with two exposed USB ports.
The test set is designed to provide a comprehensive AC insulation diagnostic test. Measurements are performed automatically by the DEL on a large 8.4” full VGA bright color display. Measured
e test sheets and pop-up test pr
mation. USB drive support is
A3000, and results are displayed
T
eports. All
ocedures. A
Optional HV reference capacitors (100 pF, 1000 pF) with 2% dissipation factor, and a 10 nF HV TTR capacitor
Optional Priority Access package offering exclusive 24/7 service and support (US market only)
quantities include voltage, current, power (loss), power factor and capacitance. The operator has the option of correcting the current and loss readings to their 2.5 kV or 10 kV equivalents. Information can be downloaded directly to a PC or USB flash device, allowing the user to
e up to 100,000 data sets. Printing is done via a
stor second USB port directly to a USB thermal paper printer (included) allowing the user to print full-size test for in either 8.5” x 11” or A4 size, without the use of an
nal laptop.
exter
DELTA3000 shown testing a pad mount transformer
ms
Two optional high-voltage reference capacitors are available to allow the user to perform a quick field check to ensure the DELTA3000 has maintained its calibration. In
ddition, an optional 10 nF TTR capacitor is available to
a allow the user to perform high-voltage Transformer Turns Ratio measurements with the DELTA3000.
The built-in tracking automatic interference suppression circuit ensures accurate and reliable test results under severe electrostatic and electromagnetic interference conditions. This feature allows the performance of test measurements in energized switchyards of up to 765 kV.
he Priority Access program provides specific support to
T assure full utilization of the Megger DELTA3000. The purchase of the program entitles the user to 24/7 support services at an economical cost, with the first year provided at no charge. (Applies to US market only.)
FEATURES AND BENEFITS
Fully automatic operation (stand-alone or r
emote­control) with user interface via on-screen customizable test forms.
Integrated PowerDB ONBOARD allows for data analysis
and trending while in the field without the use of an external computer.
Built-in USB port and included USB printer allows for
8.5”x 11” or A4 test forms printing without the use of a laptop.
Built-in capability for storing test results, in an open
XML format, to either internal memory or to an external USB storage device.
Large 8.4” full VGA bright color display.
Performs all standard ungrounded-specimen tests (UST) and grounded-specimen tests (GST), with or without a guard circuit.
Built-in self diagnostic and calibration check.
Optional module to perform LV three-phase transformer turns ratio testing and excitation current up to 500 mA in accordance with Megger TTR330 pr
oduct specifications.
DELTA3000
0 kV Automated Insulation Power Factor Test Set
1
tilizing the automatic suppression circuitry achieves
U high accuracy measurement under severe electrostatic and electromagnetic interference conditions.
Two-piece design reduces size and weight of the system and provides easier transportation.
The operator has the option of measuring either the power factor or dissipation factor (tan ).
Open-ground detector ensures proper grounding before test.
Interlock switches provide operator safety.
High accuracy SF6 gas-filled capacitor as internal reference.
Built-in interface to the optional Resonating Inductor (Cat. No. 670600) to extend the capacitance measuring range to 1.1
Optional HV TTR capacitor (10 nF) in addition to two HV reference capacitors (100 pF and 1000 pF) with a 2% dissipation factor.
Optional USB bar code scanner to record and alphanumeric test identification in the field.
Optional Priority Access package with exclusive services (US market only).
Optional Oil Test Cell for testing insulating fluids up to 10 kV.
Optional Calibration Standard verifies proper operation and accuracy of the test results.
µF at 10 kV.
Close-up of DELTA3000 panel
A3000, available in either 120 or 240 V ac/50 or 60 Hz,
T
The DEL includes the Control Unit (top) and High Voltage Unit (bottom)