Atec DELTA2000 User Manual

10 kV Automated Insulation Power Factor Test Set
DELTA2000
10 kV Automated Insulation Power Factor Test Set
n
Designed to work in high interference
switchyards of up to 765 kV
n
Built-in capability for storing, printing and
downloading test results
n
shop use with automated control via the PowerDB™ software package
n
Optional module for LV 3-phase TTR testing
and excitation current up to 500 mA (via PowerDB)
n
Optional HV reference capacitors
(100 pF, 1000 pF) with 2% dissipation fac­tor, and a 10 nF HV TTR capacitor
n
Optional Priority Access package offering
exclusive services/support (US market only)
DELTA2000
DESCRIPTION
The DELTA2000 is a fully automatic 10 kV insulation power factor test set designed for condition assessment of electrical insulation in high voltage apparatus such as transformers, bushings, circuit breakers, cables, lightning arresters and rotating machinery.
This set has been designed to provide a comprehensive AC insulation diagnostic test. Measurements are performed au­tomatically by the DELTA2000, and results are displayed on a large graphical LCD. Measured quantities include voltage, current, power (loss), power factor and capacitance. The operator has the option of correcting the current and loss readings to their 2.5 kV or 10 kV equivalents.
The built-in tracking automatic interference suppression circuit ensures accurate and reliable test results under severe electrostatic and electromagnetic interference condi­tions. This feature allows the performance of test measure­ments in energized switchyards of up to 765 kV.
The operator has the option of storing the test results on the provided data key, or download directly to a PC or the included thermal printer. A small printer mounting can be installed inside the unit’s lid in lieu of the standard printer that is included. The data key has storage capacity for 127 sets of test results. Information stored on the data key can be easily retrieved on a PC using the provided software program and interface box.
In addition to performing insulation power factor tests, the DELTA2000 can be used for measuring the excitation cur­rent of transformer windings.
The Priority Access program provides specific guaranteed support to assure full utilization of the Megger DELTA2000. The purchase of the program entitles the user free services for one year from receipt of the unit.
FEATURES AND BENEFITS
n
Fully automatic operation eliminates operator error and
reduces testing time.
n
Simplified operation procedure eliminates the need for
extensive software or hardware setups.
n
Performs all standard ungrounded-specimen tests (UST)
and grounded-specimen tests (GST), with or without a guard circuit.
n
Utilizing the automatic suppression circuitry achieves
high accuracy measurement under severe electrostatic and electromagnetic interference conditions.
n
Two-piece design reduces size and weight of the system
and provides easier transportation.
n
Built-in self diagnostic and calibration check.
n
The operator has the option of measuring either the
power factor or dissipation factor (tan ).
DELTA2000
10 kV Automated Insulation Power Factor Test Set
n
Open-ground detector ensures proper grounding before
test.
n
Interlock switches provide operator safety.
n
High accuracy SF6 gas-filled capacitor as internal refer-
ence.
n
Built-in interface to the optional Resonating Inductor
(Cat. No. 670600) to extend the capacitance measuring range to 1.1µF at 10 kV.
n
Data key stores 127 sets of test results for retrieval and
analysis. Stored results can be easily transferred to a PC using the provided interface box.
n
Optional printer mounting inside unit’s lid instead of
standard thermal printer.
n
Optional HV TTR capacitor (10 nF) in addition to two HV
reference capacitors (100 pF and 1000 pF) with a 2% dissipation factor.
n
Optional module to perform LV three-phase transformer
turns ratio testing and excitation current up to 500 mA in accordance with Megger TTR300 product specifications (via PowerDB software).
n
RS-232 serial interface for downloading the test results to a PC.
n
Includes a battery/line operated printer for a hard copy
of the test results which are date and time stamped.
n
Optional bar code wand and PC software for recording
an alphanumeric test identification in the field.
n
Optional Priority Access package with exclusive services
(US market only).
n
Optional Oil Test Cell for testing insulating fluids up
to 10 kV.
n
Optional Calibration Standard verifies proper operation
and accuracy of the test results.
n
Interfaces with a PowerDB software package that per-
forms extensive information processing, data trending and report generation.
The DELTA2000, available in either 120 or 240 V ac/50 or 60 Hz, includes the Control Unit (top) and High Voltage Unit (bottom)
Close-up of DELTA2000 panel
DELTA2000
10 kV Automated Insulation Power Factor Test Set
SPECIFICATIONS
Input
120/230 V ±10%, 1φ, 50/60 Hz, 1440 VA
Output
0 to 12 kV, continuously adjustable, 200 mA continuous; 310 mA maximum for up to 5 minutes. The power supply capacity can be expanded to 4 Amps using the optional Resonating Inductor, catalog number 670600.
Accuracy
Voltage
(RMS) ±(1% of reading + 1 digit)
Current
(RMS) ±(1% of reading + 1 digit)
Capacitance
±(0.5% of reading + 2 pF) in UST mode ±(0.5% of reading + 6 pF) in GST mode
Power Factor
±2% of reading + 0.05% (up to 90%)
Dissipation Factor
±2% of reading + 0.05% (up to 200%)
Watt Loss
±(2% of reading + 1mW)
Measuring Ranges
Voltage
250 V to 12 kV, 10 V resolution. Minimum recommended voltage is 500 V.
Current
0 to 5 Amps, 1µA maximum resolution. The measurement can be corrected to either 2.5 kV or 10 kV equivalents.
Capacitance
1 pF to 1.1 µF, 0.01 pF maximum resolution on low ranges.
Power Factor
0 to 100%, 0.01% maximum resolution.
Dissipation Factor
0 to 1000%, 0.01% maximum resolution.
Watt Loss
0 to 2 kW, actual power, 0 to 100 kW when corrected to 10 kV equivalent. 0.1 mW maximum resolution. The measurement can be corrected to either 2.5 kV or 10 kV equivalents.
Measurement
The following seven test modes are available, using the blue and red measuring leads, and can be selected by the operator:
UST: Ground Red, Measure Blue UST: Ground Blue, Measure Red UST: No Ground, Measure to both Red and Blue GST: No Guard GST: Guard Blue, Ground Red GST: Guard Red, Ground Blue GST: Guard Red, and Blue, No Grounding UST: Ungrounded Specimen Testing GST: Grounded Specimen Testing
Test Frequency
Same as line frequency
Interference Suppression
Available Suppression Methods
1. Operator selectable automatic forward/reverse measurement averaging.
2. Operator selectable automatic tracking interference cancellation.
Safety Qualifications
The test set meets the requirements of both the IEC-1010 and the CE mark specifications. The test set also meets the shock and vibration requirements of the ASTM D999.75 standard.
Environment
Temperature
Operating: 32 to 122° F ( 0 to 50° C), Storage: -58 to +140° F (-50 to +60° C)
Relative Humidity
Operating: 0 to 90% non-condensing Storage: 0 to 95% non-condensing
Dimensions
Control Unit
16 H x 22 W x 16 D in. (406 H x 559 W x 406 D mm)
High Voltage Unit
16 H x 22 W x 16 D in. (406 H x 559 W x 406 D mm)
Weight
Control Unit: 74 lb (33kg) High Voltage unit: 63 lb (29 kg) Cables: 35 lb (16 kg)
Data Keys with PC interface box and standard thermal printer
OPTIONAL ACCESSORIES
Optional capacitor kit includes carry case, TTR capacitor (left), and 2 reference capacitors (center). Also shown are 2 connectors (right) that will work with the capacitors and are supplied with the DELTA2000 unit
DELTA2000
10 kV Automated Insulation Power Factor Test Set
The optional Resonating Inductor expands the capacitance range of the DELTA2000
The optional accessory kit, C/N 670501 includes mini bushing tap connec­tors, hot collar straps, temperature/humidity meter, .75” bushing tap con­nector, 1” bushing tap connector, “J” probe bushing tap connector, 3-ft non-insulating shorting leads, 6-ft non-insulating shorting leads
Optional TTR300D module, for LV three-phase TTR testing, installed inside DELTA HV cabinet. (Lid not shown for clarity.) Via PowerDB software, TTR testing is in accordance with Megger TTR300 product specifications. External laptop is easily placed on top surface of module for added convenience.
The optional Oil Test Cell, C/N 670511, is used for testing insulating fluids up to 10 kV
DELTA2000
10 kV Automated Insulation Power Factor Test Set
OPTIONAL ACCESSORIES (Continued)
Optional bar code wand for re­cording an alphanumeric test identification
The optional Calibration Stan­dard traceable to the NIST for quick operating or calibration checks of test set bridges calibrated in watts loss or in dissipation factor
PowerDB™ Acceptance & Maintenance Test Data Management Software
The DELTA2000 is controlled and automated by the PowerDB management system, a powerful software package providing data management for acceptance and maintenance testing jobs. Customer/contract information is quickly sorted and searched. Opening a specific record shows detailed information such as type of service, order date, sales contact, and invoice information. Job informa­tion can be transferred between field-use databases and a master database. Job/Device Productivity Reports aid in bidding future jobs as well as personnel evaluation.
Electrical utilities who have invested in sophisticated Com­puterized Maintenance Management Systems (CMMS) can easily link with the PowerDB software because it works with a number of systems.
The package also provides test documentation and trend­ing, report generation and a number of other optional add­ons that are described in the Megger PowerDB data sheet available on our website www.megger.com.
Data entry and automated control of Megger DELTA2000
ORDERING INFORMATION
Item [Qty] Cat. No.
DELTA2000, 10 kV Automated Insulation Test Set 120 Vac, 60 Hz 672001 120 Vac, 50 Hz 672001-44 240 Vac, 60 Hz 672001-45 240 Vac, 50 Hz 672001-47
Included Accessories
High voltage lead: 70 ft (21.4 m), double shielded, interchangeable hook or clip termination 30012-5
Low voltage leads: 70 ft (21.4 m), shielded Color-coded Red 25572-1 Color-coded Blue 25572-2 Ground lead: 15 ft (4.6 m) 4702-7 120 volt Power cord: [1] 8 ft (2.5 m) 17032-4 240 volt Power cord: [1] 8 ft (2.5 m) 17032-2 Safety hand switch, Interlock #1: 70 ft (21.4 m) 34460-021 Safety hand switch, Interlock #2: 8 ft (2.5 m) 34460-020 Interconnect cables: For connecting the control
and high voltage units, two 5 ft (1.5 m) 27978, 27979 Foam transit case: two, foam padded, heavy-duty
cases for control and high voltage unit 35582 Programmed battery/line power serial thermal printer 33842 AC 120 V adapter 33841-2 AC 230 V adapter 33841-3 Data keys [2] 30603 Data key interface box, 120 volt 30606 Data key interface box, 240 volt 30606-1 Data key download software 35227 PowerDB LITE software RS-232 cable 34675-1 Instruction and application manual AVTM672001A
DELTA2000
10 kV Automated Insulation Power Factor Test Set
Item [Qty] Cat. No.
Optional Accessories
PowerDB software, 1st machine license, soft key DB1001 PowerDB software, 1st machine license, USB dongle DB1001S Printer mounted in lid (in lieu of std. printer) Add -39 HV TTR capacitor (10 nF, 10 kV) 36610 HV reference capacitor (100 pF, 10 kV) 36610-1 HV reference capacitor (1000 pF, 10 kV) 36610-2 **LV three-phase TTR field upgrade kit
(for upgrading DELTA2000 to DELTA2100) TTR300D Carry case for capacitors 36610-CC Capacitor kit (HV TTR cap, 2 ref caps, carry case) 36610-KIT Resonating inductor 670600 Calibration standard 670500-1 Oil test cell 670511 Hot collar belts [3] 670505 Bushing tap connectors [2] 670506 Transit cases for calibration standard
(heavy-duty, foam-padded) 670635 Bar code wand and software 34705 High voltage lead, 25 ft (7.6 m) 30012-8 Accessory kit: mini bushing tap connectors [2],
hot collar straps [3], temperature/humidity meter [1], .75” bushing tap connector [1], 1” bushing tap connector [1], “J” probe bushing tap connector [1], 3-ft non-insulating shorting lead [3], 6-ft non-insulating shorting lead [3] 670501
Priority Access package (US market only) D2K-P-ACCESS
**C/N TTR300D converts a DELTA2000 to a DELTA2100 and includes all LV 3-phase TTR included accessories as listed in the Ordering Information on DELTA2100 data sheet.
UK
Archcliffe Road, Dover CT17 9EN England T +44 (0) 1 304 502101 F +44 (0) 1 304 207342 UKsales@megger.com
UNITED STATES
4271 Bronze Way Dallas, TX 75237-1019 USA T 1 800 723 2861 (USA only) T +1 214 333 3201 F +1 214 331 7399 USsales@megger.com
OTHER TECHNICAL SALES OFFICES
Valley Forge USA, College Station USA, Sydney AUSTRALIA, Täby SWEDEN, Ontario CANADA, Trappes FRANCE, Oberursel GERMANY, Aargau SWITZERLAND, Kingdom of BAHRAIN, Mumbai INDIA, Johannesburg SOUTH AFRICA, and Chonburi THAILAND
ISO STATEMENT
Registered to ISO 9001:2000 Cert. no. 10006.01
DELTA2000_DS_en_V20
www.megger.com Megger is a registered trademark
Loading...