Atec Amp-MS-2 User Manual

MS-2
Circuit Breaker and Overload Relay Test Set
Digital memory ammeter
Digital, multirange timer
High-current output
Solid-state output initiate circuit
MS-2
Circuit Breaker and Overload Relay Test Set
DESCRIPTION
The MS-2 test set is used around the world by several thousand utility companies, industrial plants and electrical service organizations.
Using the latest technology, Model MS-2 is a self-contained test set that incorporates a variable high-current output and appropriate control circuitry and instrumentation for testing thermal, magnetic or solid-state motor overload relays; molded-case circuit breakers; and ground-fault trip devices.
APPLICATIONS
Model MS-2 is capable of testing the time-delay characteristics of motor overload relays and molded-case circuit breakers rated up to 125 amperes, when following the recommended test procedure of testing the time delay of these devices at three times their rating.
Higher currents are available for the short durations required to test an instantaneous trip element. For example, the test set will provide a maximum short­duration output of 750 amperes through a typical, 125 ampere, molded-case circuit breaker.
Additional applications include verifying the ratio of current transformers and testing panelboard ammeters and voltmeters.
FEATURES AND BENEFITS
Digital memory ammeter: High-accuracy, direct­reading instrument has read-and-hold memory for measurement of short-duration currents.
Digital, multirange timer: Crystal-controlled, high­accuracy instrument with autoranging measures operating time to 1 millisecond.
High-current output: Provides instantaneous currents up to 750 amperes through a 125 ampere breaker.
Rugged and lightweight: Unit weighs only 33 lb (15 kg) and is tough enough to withstand daily field or plant use.
Solid-state output initiate circuit: Solid-state circuit eliminates need for contact maintenance.
SPECIFICATIONS
Input
Input Voltage (specify one): 120 V OR 240 V, 50/60 Hz, 1f
Output
Output Ranges: The output is continuously adjustable in four ranges to accommodate a variety of test-circuit impedances: 0 to 5 A at 120 V max. 0 to 25 A at 24 V max. 0 to 120 A at 6 V max. 0 to 240 A at 3 V max. Output Capacity: The output circuit is designed to permit shor t­duration overloads and the output ranges will provide several times their current rating, provided the output voltage is sufficient to push the desired current through the impedance of the test circuit.
MS-2
Circuit Breaker and Overload Relay Test Set
The test set is capable of testing the time-delay characteristics of devices rated up to 125 A using a test current of three times their rating (375 A). Additionally, to perform an instantaneous trip test, it will provide 750 A through a typical, 125 A, molded-case circuit breaker connected with the test leads provided with the test set. Overload Capability: To increase use of the test set, it is designed so that the current ratings may be exceeded for short durations. Because the magnitude of the output current is determined by the impedance of the load circuit, the voltage rating must be sufficient to push the desired current through the device under test and the connecting test leads.
Percent Rated Maximum Minimum
Current Time On Time Off
100 (1x) 30 min 30 min 200 (2x) 3 min 8 min 300 (3x) 30 s 4 min
400 (4x) 7 s 2 min Output Initiate Circuit: The test set uses a solid-state output initiating circuit. To increase reliability and eliminate contact maintenance, this circuit uses a triac instead of a contactor to initiate the output. The initiating circuit provides momentary and maintained modes to control output duration. The momentary mode is used whenever the output is to be on for a short duration, such as when performing instantaneous trip tests, or to avoid damage or overheating of the device under test while setting the test current. In the maintained mode, the output remains energized until manually turned off or, when performing timing tests, until the device under test operates — which both stops the timer and de-energizes the output.
INSTRUMENTATION Ammeter
Operating Modes (switch-selected)
Memory Normal
Display
3
1
/
2
digit, extra-bright LED display with 0.3 in. (7.62mm) numerals
Ranges (switch-selected)
0 to 1.999/19.99/199.9/750 A
ContinousAccuracy (overall ammeter system)
±1% of reading, ±1 digit on three high ranges Regulating: ±1% of range, ±1 digit on low range
Timer
Display
5-digit, extra-bright, LED display with 0.3 in. (7.62mm) numerals
Ranges (switch-selected)
0 to 99.999 s 0 to 999.99 s 0 to 99999 cycles
Accuracy
±0.005% of reading, ±1 digit
Timer Control Circuit
This circuit automatically starts the timer when the output is energized and automatically stops the timer and de-energizes the output when the device under test operates. This circuit accommodates the following test conditions by simple switch selection of the appropriate mode: Current Actuated: Used to test a device that has no auxiliar y contacts to monitor, such as a single-pole circuit breaker. The timer stops when the output current is interrupted. Normally Closed: Used to test a device with nor mally closed contacts. The timer stops and the output is de-energized when the contacts open. Normally Open: Used to test a device with nor mally open contacts. The timer stops and the output is de-energized when the contacts close.
Enclosure
The test set is housed in a high strength, molded, suitcase-type enclosure with carrying handle and removable cover. Storage space is provided for test leads.
Dimensions
9.9 H x 14 W x 11 D in. (25 H x 35 W x 28 D cm)
Weight
33 lb (15 kg)
Item (Qty) Cat. No.
Model MS-2 115 volt input MS-2-115 230 volt input MS-2-230
Included Accessories
Timer control circuit leads, 5 ft (1.5 m) [2] 1282 Test and maintenance record cards
Green [50] 2239 Buff [50] 2238
ORDERING INFORMATION
Item (Qty) Cat. No.
No. 4 high-current leads, 5 ft (1.5 m) [2] 2265 Fuses
5 A, 250 V, MDA [5] 952
0.125 A, 250 V, MDL [5] 981 10 A, 250 V, MDA [5] 984
0.0625 A, 250 V, MDL [5] 987
Instruction manual [1] 8470
UK
Archcliffe Road Dover CT17 9EN England T +44 (0) 1304 502101 F +44 (0) 1304 207342
UNITED STATES
4271 Bronze Way Dallas TX75237-1088 USA T 800 723 2861 (USA only) T +1 214 330 3203 F +1 214 337 3038
OTHER TECHNICAL SALES OFFICES
Valley Forge USA, Toronto CANADA, Mumbai INDIA, Trappes FRANCE, Sydney AUSTRALIA, Madrid SPAIN and the Kingdom of BAHRAIN.
Registered to ISO 9001:2000 Reg no. Q 09290 Registered to ISO 14001 Reg no. EMS 61597
MS2_DS_en_V10
www.megger.com Megger is a registered trademark