MULTI-FUNCTION GROUND
Now measure ground
resistance, soil resistivity
RESISTANCE SOIL
and bonding resistance
with one instrument!
RESISTIVITY TESTER
Model 6470-B
► 2- and 4-Wire Bond Resistance/Continuity Measurement (DC Resistance) with automatic polarity reversal
► 3-Pole (3-Point) Fall-of-Potential measurement with manual or automatic frequency selection
► 4-Pole (4-Point) Fall-of-Potential measurement for very low resistance measurements with manual or
automatic frequency selection and automatic lead compensation
► 4-Pole (4-Point) Soil Resistivity measurement with automatic calculation of Rho (r) and user selection of
the Wenner or Schlumberger test method
► 3-Pole (3-Point) Earth Coupling measurement
► Manual and automatic frequency scan from 40 to 513Hz for optimum test accuracy in electrically
noisy environments
► Selectable test voltage of 16 or 32V up to 250mA of test current
► Auto-off power management
► Automatic recognition of all electrode connections and their resistance value
► Stores up to 512 complete test results in internal memory
► Optically isolated USB communication
► Remote set up and operation of all measurements using DataView
► Automatic report generation
► Rechargeable NiMH batteries from wall charger or vehicle power
► Rugged dustproof and rainproof field case – IP54 rated in closed positione
► Grounding standards IEC 61557 parts 4 and 5 compliant
► Includes DataView
and system configuration
®
software for data storage, real-time display, analysis, report generation
®
software supplied
Model 6470-B quickly checks ground rod resistance with its Connect - Press - Read approach
The Digital Ground Resistance Tester Model 6470-B is a portable
measurement instrument designed to measure Ground Resistance, Soil
Resistivity (two methods – Wenner and Schlumberger), Bonding Resistance
(DC Resistance 2-Wire and 4-Wire Kelvin sensing) and Earth Coupling
resistance. This direct reading tester measures from 0.01 to 99.99kΩ and is
auto-ranging, automatically seeking out the optimum measurement range and
test current.
Easy-to-use – simply connect the leads, select the test mode, press Start and
read the results. Up to 512 test results can be stored in internal memory for
later recall to the display or downloaded to a PC via DataView® software.
The large LCD is easy-to-read and indicates ground electrode resistance,
test voltage, current and frequency as well as individual electrode resistance,
battery status and more.
The Model 6470-B is Cat IV rated to 50V and is over voltage protected to
more than 250VAC against accidental connection to live circuits. The voltage
is also displayed on screen. In the event of a system fault, the Model 6470-B
can withstand 250VAC.
Additional features of the Model 6470-B include a heavy-duty field case
sealed against dust and water when closed (the test button is also sealed
against the elements); manual and automatic test frequency selection from 40
to 513Hz; user selectable 3-Pole (3-Point) Fall of Potential or 4-Pole (4-Point)
Soil Resistivity test methods and user selectable 2-Wire or 4-Wire Bond
Resistance test method.
The Model 6470-B is powered by 9.6V, 3.5 Ah NiMH rechargeable batteries.
An external recharger powered from 120/230V 50/60Hz is included and
provides for testing while recharging. The Model 6470-B can also be vehicle
powered from an optional 12V battery adapter.
The Ground Resistance Tester Model 6470-B is rugged, easy-to-use
and ideal for maintenance crews performing numerous tests. It exceeds
mechanical and safety specifications for shock, vibration and drop tests per
IEC standards. The adjustable test frequency provides for rejection of high
levels of interference, allowing it to be used under difficult conditions such as
high stray currents that normally affect accuracy.
Features
► 2- and 4-Wire Bond Resistance/Continuity
Measurement (DC Resistance) with automatic
polarity reversal
► 3-Pole (3-Point) Fall-of-Potential measurement
with manual or automatic frequency selection
► 4-Pole (4-Point) Fall-of-Potential measurement
for very low resistance measurements with
manual and automatic frequency selection and
automatic lead compensation
► 4-Pole (4-Point) Soil Resistivity measurement
with automatic calculation of Rho (r) and user
selection of the Wenner or Schlumberger test
method
► 3-Pole (3-Point) Earth Coupling measurement
► Manual and automatic frequency scan from
40 to 513Hz for optimum test accuracy in
electrically noisy environments
► Selectable test voltage of 16 or 32V up to
250mA of test current
► Auto-off power management
► Automatic recognition of all electrode
connections and their resistance value
► Stores up to 512 complete test results in
internal memory
► Optically isolated USB communication
► Remote set up and operation of all
measurements using DataView® software
supplied
► Automatic report generation
► Rechargeable NiMH batteries from wall charger
or vehicle power
► Rugged dustproof and rainproof field case –
IP54 rated in closed position
► Grounding standards IEC 61557 parts 4 and 5
compliant
► Includes DataView® software for data storage,
real-time display, analysis, report generation and
system configuration
applications
► 3-Point measurements of resistance to
ground of ground rods and grids. 3-Point
measurements are generally used when the
electrode or grid can be easily disconnected.
► 4-Point tests or soil resistivity
measurements. Locating areas of lowest
soil resistivity is essential for achieving an
economical grounding installation.
► Touch and step potential testing
measurements. These tests are
recommended when the ground cannot be
disconnected, where ground faults are highly
likely to occur, or when the “footprint” of
grounded equipment (the outline of the part
of equipment in contact with the earth) is
comparable to the size of the ground
to be tested.
► 2- or 4-Wire tests for continuity
tests on bonding or on grounding systems.
This test is a DC resistive test using 250mA
or more and is used to check bonding of all
connection points on the ground system.
► Earth coupling measurement and display.
Used to estimate the influence of two earth
resistance systems that are not connected to
each other.
2
www.aemc.com
Technical Assistance (800) 343-1391
speciFications
MODEL 6470-B
ELECTRICAL
3-Point Measurement
Range (Auto-Ranging) 0.01Ω to 99.99kΩ
Resolution 0.01Ω to 100Ω
Test Voltage Nominal 16 or 32VRMS user selectable
Resistance Measurement Frequency 41 to 513Hz user selectable or automatic selection
Test Current Up to 250mA
Accuracy ±2% of Reading + 1ct
Earth Coupling Measurement Yes
Soil Resistivity 4-Point Measurement
Test Method Wenner or Schlumberger selectable with automatic calculation of test results in Ω-meters, Ω-cm or Ω-feet
Range (Auto-Ranging) 0.01 to 99.99kΩ
Resolution 0.01 to 100Ω
Test Voltage 16 or 32V user selectable
Frequency From 41 to 128Hz selectable
External Voltage Measurement
Range (Auto-Ranging) 0.1 to 65.0V — DC to 450Hz
Accuracy 2% of Reading + 3cts
Resistance Measurement (Bond Testing)
Measurement Type 2-Point (with lead resistance compensation) or 4-Point (Kelvin sensing) user selectable
Range (Auto-Ranging) 2-Point 0.01Ω to 99.9kΩ; 4-Point 0.001Ω to 99.99kΩ
Accuracy ±2% of Reading + 2cts
Test Voltage 16V
Test Current Up to 250mA max
Data Storage
Memory Capacity 512 test results
Communication Optically isolated USB
Automatic Report Generation Yes — tabular listings and Fall-of-Potential plots
Power Source 9.6V rechargeable battery pack
Recharging Source 110/220 50/60Hz external charger with 18V
MECHANICAL
Test Lead Connection 4mm recessed banana jacks
Mechanical Shock Per EN 61557
Vibration Test Per EN 61557
Drop Test Per EN 61557
Dielectric Test 3kV 50/60Hz
Dimensions 10.7 x 9.76 x 5.12" (272 x 248 x 130mm)
Weight 7.5 lbs (3.5kg)
Case Polypropylene
Index of Protection IP53 with cover closed
DISPLAY
Display Type Custom 256 segment multi-line LCD
Backlight Blue electroluminescent
COMMUNICATION
Software
ENVIRONMENTAL
Operating Temperature 14° to 122 °F (-10° to 55°C)
Storage Temperature -40° to 158°F (-40° to 70°C)
SAFETY
Safety Rating EN 61010-1 50V Cat IV, Pollution Degree 2
Double Insulation Yes
CE Mark Yes
DataView® graphing, analysis and reporting software
d c (+, — or auto polarity)
d c , 1.9A output or 12 Vd c vehicle power
Technical Assistance (800) 343-1391 www.aemc.com 3