Atec AEMC-6416, AEMC-6417 User Manual

Clamp-On
Provides an extra
level of safety with
Ground Tester
Models 6416 & 6417
new Touch Voltage
indication feature
Simple and fast clamp-on
operation - no leads, no auxiliary rods or spacing requirements
Selectable test frequency
Differentiates between
loop and ground resistance measurements
Android™ application
provides real-time data review, geolocation and e-mailing of test results
IP 40
Rated
Automatic Hold function
Displays stored
measurements visible in direct sunlight and in dark areas
Storage of measurements
(, A, V, alarms, test frequency with time-stamping)
Our products are backed by over 100 years of experience in test and measurement
Technical Hotline: (800) 343-1391
www.aemc.com
Test multi-grounded systems without disconnecting
the ground system under test!
The Ground Resistance Tester Models 6416 and 6417 measure ground rod and
grid resistance without the use of auxiliary rods. Clamp-on ground resistance testers
can be used in multi-grounded systems without disconnecting the ground system
under test or de-energizing them. Models 6416 and 6417 simply clamp around the
ground conductor or rod and measure the resistance to ground. By performing
measurements on intact ground systems, the user also verifies the quality of the
grounding connections and bonds. Resistance and continuity of grounding loops
around pads and buildings may also be measured.
Two new features unique to AEMC voltage indication. The ability to select the test frequency provides more accurate
results in inductive environments. Displaying voltage derived from current and
resistance measurements provides an extra level of safety for the user, indicating
a potential dangerous touch condition. Both models include a current measurement
function. The probe’s high sensitivity enables measurement of leakage current
flowing to ground or circulating in ground loops from 0.2mA to 40A and resistances
from 0.01 to 1500Ω.
Both models offer battery life information at power-up and Auto-Off for power
management. Additional features are also displayed on the large OLED display to
ensure precise measurements. The Buzzer and Auto Power Off features may be
disabled from the push-buttons at any time.
Both offer an alarm function and a data storage function. In the Alarm mode, the probe will audibly and visually indicate if the reading is beyond the user programmed set point. The user may have the alarm activate above or below the
set point. This alarm feature permits quick field checks where only “pass”
or “fail” readings are required.
®
are test frequency selection and touch
IP 40
Rated
* *
*Model 6417 only
The data storage function enables the user to conduct field surveys, and to retrieve and analyze the readings at a later time. The alarm settings and stored data are saved
when the ground tester is turned off. When using the FREE DataView 6417 provides Bluetooth transmission to a PC for analysis and report generation.
®
software, the
Now a simple solution to
read your measurements
Results, on the Go!
Model 6417 is available with an Android™
application for easy data programming, downloading, printing and e-mailing test results from your mobile device.
With its mobile GPS capability, users are now able to easily locate the site associated with the measurements.
2
www.aemc.com
Technical Assistance (800) 343-1391
SPECIFICATIONS
Models 6416 & 6417
FEATURES
Touch voltage is displayed to alert user to potential unsafe conditions
Large multi-function, bright yellow organic display (OLED) usable in all lighting conditions
Display in Standard mode (1 screen) or Advanced mode (3 screens)
Selectable test frequency improves accuracy in inductive environments
Differentiates between loop and ground resistance measurements
Data storage ( and/or A, with time-stamping)
Model 6416: stores up to 300 measurements Model 6417: stores up to 2000 measurements
Displays stored measurements on the OLED display or by Bluetooth to a PC or the Android based mobile application. (Model 6417)
Easy clamp opening by a force compensation trigger system
Large jaw design, 1.38" (35mm) accommodating up to 1000kcmil cables
Alarm function with adjustable set point and buzzer for quick field checks
Rugged Lexan® head and body construction resists breakage
Alarm settings and stored memory information saved during shutdown (Model 6417)
NOISE icon and buzzer alert user to presence of dangerous voltage and current levels
Automatic Hold of measurement when jaw is opened
Disturbance indicator (current) in the loop
Hold function
Buzzer is displayed when active
Measurement date/time display
Advanced Mode selection
Indicates when the inductive component is negligible in Advanced Mode
Symbols identify the value displayed in Advanced Mode
Main display
Data Storage indicator
Memory Recall indicator
Memory Index display
Bluetooth
connection
indicator
Incorrect jaw closing indicator
Auto Power Off indicator
Battery charge indicator
4000-count upper
measurement
display
Upper display
measurement unit
Main display
measurement unit
Signal for
hazardous
voltage
Alarm
measurement
display unit
Alarm threshold
display
Alarm threshold
indicator
ELECTRICAL
Ground Resistance
Auto-Ranging
0.01 to 1500
Current Measurement
Auto-Ranging
0.2mA to 40A
Resistance Measurement Frequency
Current Measurement Frequency
Touch Voltage Display
Power Source
Data Storage
Measurement
Range
0.010 to 0.099 0.001Ω ±1.5% ±0.01
0.10 to 0.99 0.01Ω ±1.5% ±0.01
1.0 to 49.9 0.1Ω ±1.5% ±0.1
50.0 to 99.5 0.5Ω ±2% ±0.5 100 to 199 1Ω ±3% ±1 200 to 395 5Ω ±5% ±5 400 to 590 10Ω ±10% ±10
600 to 1150 50Ω 20% approx
1200 to 1500 50Ω 25% approx
0.200 to 0.999mA 1µA ±2% ±50µA
1.000 to 2.990mA
3.00 to 9.99mA
10.00 to 29.90mA
30.0 to 99.9mA
100.0 to 299.0mA
0.300 to 0.990A
1.000 to 2.990A
3.00 to 39.99A
50, 60, 128 or 2083Hz (user selectable)
4x1.5V LR6 (AA) Alkaline batteries or 4 NiMH batteries;
Battery life: 12 hours, or 14,400 30-second
Model 6416: 300 measurements;
Model 6417: 2000 measurements
Resolution
10µA ±2% ±50µA
100µA ±2% ±100µA
1mA ±2% ±1mA
10mA ±2% ±10mA
47 to 800Hz
0.1 to 75.0V
measurements approx
ac
MECHANICAL
Dimensions Weight Jaw Opening Display
2.16 x 3.74 x 10.31” (55 x 9 x 262mm)
2.06 lbs (935g) approx. with batteries
1.38” (35mm) max
Multi-function, bright yellow organic display (OLED)
ENVIRONMENTAL
Operating Temperature Operating Humidity
-4° to 131°F (-20° to 55°C) 10% to 90% RH
SAFETY
Safety Rating
EN 61010-1 (Ed. 2 of 2001); 600V CAT IV
PRODUCT INCLUDES
Hard carrying case, calibration loop, four 1.5V AA batteries, and USB stick supplied with ground tester workbook and user manual. Model 6417 also includes DataView
®
software on USB sitck.
Accuracy
(% of Reading)
ORDERING INFORMATION CATALOG NO.
Ground Resistance Tester Model 6416 (Clamp-On, Alarm, Memory) Cat. #2141.01
®
Ground Resistance Tester Model 6417 (Clamp-On, Bluetooth, Alarm, Memory, DataView
Technical Assistance (800) 343-1391
www.aemc.com
software) Cat. #2141.02
3
www.aemc.com
United States & Canada
Chauvin Arnoux®, Inc. d.b.a. AEMC
200 Foxborough Blvd. Foxborough, MA 02035 USA (508) 698-2115 • Fax (508) 698-2118
Customer Support
for placing an order, obtaining price & delivery
customerservice@aemc.com
Sales & Marketing Department
for general sales and marketing information
sales@aemc.com marketing@aemc.com
Repair & Calibration Service
for information on repair & calibration
repair@aemc.com
®
Instruments
United States & Canada (continued)
Technical & Product Application Support for technical and application support
techinfo@aemc.com
Webmaster
for information regarding www.aemc.com
webmaster@aemc.com
South America, Central America, Mexico & the Caribbean
Chauvin Arnoux®, Inc. d.b.a. AEMC
15 Faraday Drive Dover, NH 03820 USA
export@aemc.com
®
Instruments
Australia & New Zealand
Chauvin Arnoux®, Inc. d.b.a. AEMC
15 Faraday Drive Dover, NH 03820 USA
international@aemc.com
®
Instruments
All other countries
Chauvin Arnoux® SCA
190, rue Championnet 75876 Paris Cedex 18, France Tel 33 1 44 85 45 28 Fax 33 1 46 27 73 89
info@chauvin-arnoux.com www.chauvin-arnoux.com
Visit our website at www.aemc.com
Call the AEMC® Instruments Technical Assistance Hotline for immediate consultation with an applications engineer: (800) 343-1391
Chauvin Arnoux®, Inc. d.b.a AEMC® Instruments • 200 Foxborough Blvd. • Foxborough, MA 02035 USA • (800) 343-1391 • (508) 698-2115 • Fax (508) 698-2118
© 2014 Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments 950.BR-6416-6417_01/14Rev01 Printed in the USA
Export Department: (603) 749-6434 (x520) • Fax (603) 742-2346 • E-mail: export@aemc.com