Field and Lab AC Dielectric Test Sets
15-200 kV
➤ A premier line of AC Dielectric Test Sets with ratings
from 15 to 200 kVAC
➤ Lightweightandruggedlyconstructedforyearsofelduse
➤ Units feature easy to read digital instrumentation
andclean,efcientcontrols
➤ Simple set-up and operation
➤ Low partial discharge output
Model 6CP200/100-10
TESTING APPLICATIONS
Suitable for dielectric testing a
wide range of electrical apparatus
CABLE
SWITCHGEAR
Specications are subject to change without notice.
Brochure No. 60700
MOTOR
Model 6CP30/15-3
GENERATOR
G
INSULATION
Model 6CP120/60-7.5
RECLOSER
PROTECTIVE
EQUIPMENT
SAFETY & DESIGN FEATURES DESCRIPTION
• 2 or 3 piece designs
• Circuit breaker protection
• External interlock provision
• High voltage On/Off pushbuttons
with indicator
• Zero Start interlock
• Manual control of output voltage
• Adjustable overload circuit
• Slow and fast-acting transient
protection on all meters and relays
• Digital timer with audible alarm
• Digital multi range metering
• Emergency Off pushbutton with
key lockout
• Guard mode for accurate current
measurements
• Output overload indicator with
reset switch
• All interconnect control and power
cables are included
• Cable storage provision
• Two copies of operation/
maintenance manual
This portable rugged line of AC high voltage test equipment is
ideally suited for use in the eld or in the laboratory. The 6CP line
offers a complete test system in a mobile package. All units in the
6CP line use a combination control and regulator enclosure and
a separate high voltage section. The system is equipped with
advanced digital metering, and control and protection devices
which are easy to use and provide the operator with all necessary
information to safely operate the system. The Metering Guard Mode
allows accurate measurements of the high voltage test specimen
leakage current by bypassing stray capacitive currents. The high
voltage section consists of a specially designed oil insulated high
voltage transformer characterized by use of an isolating cylindrical
housing mounted on a rugged steel base. The high voltage output
is equipped with a corona free aluminum shielding electrode. The
high quality design and construction is key to the superior partial
discharge performance of the 6CP line. The system arrives ready
to use with all power and interconnect cables included; the simple
setup allows this 6CP to be ready for testing in minutes. The rugged
construction and dependability, backed by long-term warranty
makes the 6CP line an ideal choice for your high voltage testing
requirements.
110-120 V, 16 A 110-120 V, 16 A 110-120 V, 30 A 110-120 V, 30 A
220-240 V, 8 A 220-240 V, 8 A 220-240 V, 15 A 220-240 V, 15 A
INPUT
Frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
≈ 0-30 kV, 100 mA ≈ 0-50 kV, 60 mA ≈ 0-100 kV, 75 mA
OUTPUTFEATURESPD
S
5 min ON/15 min OFF 3 kVA 7.5 kVA 10 kVA
15 min ON/1 hr OFF 2 kVA 5 kVA 7.5 kVA
DUTY
CYCLE
1 hr ON/1 hr OFF 1.5 kVA 3 kVA 5 kVA
66% Inductive + Selectable
Capacitive Preload
Metering Accuracy 0.8% Reading +.2% Full Scale
Voltmeter Range(s) 0-15/30 kV 0-10/50 kV 0-50/100 kV 0-60/120 kV 0-50/100 kV 0-60/120 kV 0-100/200 kV
Output HV Electrode
PD level <10 pC
Optional up to 100kV <3 pC
Power Cable 10’(3048 mm) 30’(9144 mm)
Power Interconnect 10’(3048 mm) 20’(6096 mm)
Meter Interconnect 10’(3048 mm) 20’(6096 mm)
Ground 10’(3048 mm) (2) 20’(6096 mm) each
CABLES
Return 10’(3048 mm) 20’(6096 mm) 10’(3048 mm)
INCLUDED
Divider Metering n/a n/a 30’(9144 mm)
Paralleling n/a n/a 10’(3048 mm)
MODEL 6CP30/15-3 6CP50/10-3 6CP100/50-7.5 6CP120/60-7.5 6CP100/50-10 6CP120/60-10 6CP200/100-10
Voltage/Current
Voltage/Current
Compensation
Currentmeter Range(s)
≈ 0-15 kV, 200 mA ≈ 0-10 kV, 300 mA ≈ 0-50 kV, 150 mA ≈ 0-60 kV, 125 mA ≈ 0-50 kV, 200 mA ≈ 0-60 kV, 167 mA ≈ 0-100 kV, 100 mA
≈ 0-120 kV, 62.5 mA
50% Inductive Reactive 50% Inductive Reactive
0-200 µA/2 mA/ 0-200 µA/2 mA/
20 mA/200 mA 20 mA/300 mA
220-240 V, 30 A 220-240 V, 30 A 220-240 V, 25 A
≈ 0-100 kV, 100 mA ≈ 0-120 kV, 83 mA ≈ 0-200 kV, 5
0-200
µ
A/ 2 mA/ 20 mA/ 200 mA
(3) 30’(9144 mm) ea
0 mA
ENVIRONMENTAL CONDITIONS
• 10-40°C, indoor/outdoor in fair weather
R
www.phenixtech.com
• Humidity <95% non-condensing
• Altitude <3000 ft (1000 meters)