Three-Phase TTR
®
Transformer Turns Ratio Test Set
The new TTR applies voltage to the high voltage winding
of a transformer and accurately measures the resulting
voltage from the low voltage winding. In addition to turns
ratio, the unit measures excitation current, phase angle
deviation between the high and low voltage windings and
percent ratio error.
Transformer Turns Ratio
Transformer Turns Ratio is the ratio of the number of turns
in the high voltage winding to that in the low voltage
winding. A Transformer Turns Ratio Test Set such as the
Three-phase Automatic TTR can directly measure the ratio
of most types of transformers. Transfor mer ratio can
change due to several factors, including physical damage
from faults, deteriorated insulation, contamination and
shipping damage. If a transformer ratio changes more
than 0.5 percent from the rated voltage ratio, it may not
operate reliably. To measure small ratio changes such as
this, the accuracy of a Biddle TTR is needed.
Exciting Current
The exciting current is the current that maintains the
magnetic flux excitation in the core of a transformer.
A Transformer Turns Ratio Test Set such as the
Three-phase Automatic TTR is capable of measuring
exciting current because they apply voltage to one of the
transformers windings. An accurate measurement of
exciting current can provide information about the
condition of a transformer’s core. Unwanted circulating
currents or unintentional grounds can affect the exciting
current and indicate a problem.
Phase Angle Deviation
The phase angle deviation is the relationship between the
voltage signal applied to the high voltage winding and the
voltage signal extracted from the low voltage winding.
The phase deviation between the high and low side of a
transformer is generally very small. If there is deterioration
or damage in the transformer core, however, the phase
deviation can change significantly. The Three-phase T TR
can measure this phase relationship with the resolution
necessary to detect a problem.
More information about a transformer’s electrical proper ties
can be found in the IEEE Standard Test Code for
Transformers, C57.12.90, or by contacting Megger.
FEATURES AND BENEFITS
■
Measures the widest turns ratio range in the industry
(10,000:1) and also provides the highest accuracy (0.1%).
■
Enables the operator to enter the ratio of the transformer
and all of it’s taps. This allows the operator to know
immediately when a tap is outside the acceptable limits.
Also allows for a pass/fail limit so problem taps can be
easily flagged.
■
Comes equipped with “remote-control” switch for single
person testing. This allows the operator to test
transformers with “LTCs” very quickly.
■
Records ratio errors for bushing CTs to an accuracy of
±0.1% nameplate. This reduces the need for additional
test equipment and improves set-up time.
■
Measures the phase deviation (in minutes) of the
transformer primary versus secondary. This quickly
indicates problems in the transformer such as partial
shorted turns and core faults. This measurement is also
useful in verifying phase errors in all types of PTs and
CTs.
■
Perfect for meter shops, the TTR can be used for
inspection purposes by using it to determine the no-load
accuracy of most CTs and PTs. Also, it can be used to
determine the need to further test potentially faulty CTs
and PTs.
■
This instrument is also ideal for use by power
transformer manufacturers. Its unique testing
procedures and storage capability allows an operator to
set up and test difficult three-phase transformers (with
multiple tap changers and bushing CTs) in a quarter of
the time than it used to take with the former Biddle
TTR. This test also includes a pass/fail limit of
individual ratios.
■
A “Quick Test” Mode provides a fast determination of
the turns ratio for single and three-phase transformers,
thus saving time.
■
Displays all values for each test including measured and
calculated ratio, exciting current, ratio error, and phase
angle deviation, thus providing comprehensive and
conclusive data.
■
Automatic self-calibration for each test.
■
Rugged, lightweight design ideally suited for a harsh
field and substation environment.
■
Three user selectable standards: ANSI, IEC, and
Australian. Also meets IEC 1010 as well as other safety
standards such as CSA and UL.
■
Six user selectable languages: French, German, Italian,
Portuguese, Spanish and English.
Example of the TTR LCD screen which shows test data
from a three-phase transformer test.
THREE PHASE TRANSFORMER TEST
TEST: 105 ID: A13579CV0246 DIAG: 31 Yzn11
TAPS TESTED: 3 - 16 R
H VOLTAGE: 25000 X VOLTAGE: 5000
CALCULATED TURNS RATIO: 5.000
TEST VOLTAGE: 80 V
ABC
RATIO 5.102 5.015 4.986
% DEVIATION 2.04 0.30 -0.28
PHASE (min.) 1.2 2.4 1.8
lexc (mA) 20.6 10.5 7.78
SELECT: 1 - PRINT 2 - STORE 3 - NEXT TEST
4 - PRINT TEST 5 - MAIN MENU