Models 360ASX-360ASXT
6,000VA
15-1,200 Hz
1, 2 , or 3Ø – High Performance AC Power Source
1Ø4 0-330V
2Ø4 0-600V
3Ø4 0-330/572V
L-N
L1-L
2
L-L
Standard Features:
• 1 phase / 3 phase Selectable Output
from front panel or bus command.15 to
1,200 Hz. Operation – 5,000 Hz small
signal bandwidth.
• Precision Voltage Programming – 0.05%
with Continuous Self-Calibration (CSC)
engaged.
• True-RMS metering of volts, amps, and
power.
• GPIB (IEEE-488.2) or RS-232 Interface.
• Waveform Library – Arbitrary Waveform
Generator.
• 99 stored programs with associated
transients for static and dynamic test
applications.
• UPC Studio Software Suite.
• UPC Interactive LabVIEWTM Libraries .
Available options:
• Rack enclosures with caster base.
• Programmable Output Impedance.
• Harmonic Analysis and Waveform
Synthesis.
• Peak Inrush Capture and Waveform
Analysis.
• UPC Test Manager Software Application.
• Wide range of Output transformer
options for world-wide testing.
UPC Manager Software Suite
Master the Power of the Wave!
UPC Manager
Software gives you
the tools necessary
to quickly and eas-
ily operate your AC
Power Source. With
our graphical interface control all areas
of your AC Power
Source testing with
simple presets, user
prompts, test sequences, test plans
and custom reports.
Model 360-ASX
As a member of Pacic's ASX-Series family of high performance AC Power Sources,
the 360ASX oers the low acoustic noise, ease of installation, and maximum power
density found in all of Pacic's high frequency, pulse width modulated AC Power
Sources. Control and operational features provide a high degree of versatility and
ease for applications ranging from simple, manually controlled frequency conversion
to harmonic testing and sophisticated bus programmable transient simulation.
AC TEST POWER
The 360-ASX is equipped with a powerful micro-controller with the ability to
operate as a fully integrated test system. It supplies a variety of power conditions
and transients to the device under test while metering and analyzing all output
performance parameters.
FREQUENCY/ VOLTAGE CONVERSION
The 360-ASX is an excellent source of stable AC Voltage over the frequency range
of 15 to 1,200 Hz. The output frequency is quartz-crystal stabilized. Output
voltages up to 600V are available.
PHASE CONVERSION
With the ability to provide single, two, and three-phase outputs, the 360ASX is an
ideal choice to convert three-phase line voltage into precisely controlled split (twophase) or single-phase output power.
UPC SERIES CONTROLLER
Three controller models are available oering both manual and programmable
control. All controllers provide manual operation from the front panel.
Programmable Controllers may be operated from the front panel or from a remote
interface via RS 232 or GPIB.
The Leader in AC Power Technology
An early pioneer in the development solid-state power conversion equipment,
Pacic Power Source continues to develop, manufacture, and market both linear
and high-performance PWM AC Power Sources. Pacic's reputation as a market
and technology leader is best demonstrated by its continuing investments in both
research and development and world-wide customer support. With corporate
owned oces in the United States, Germany, the United Kingdom, and China, local
personalized support is always available.
THE POWER OF EXPERTISE
FREQUENCY CONVERSION R & D MANUFACTURINGAEROSPACE MILITARY CUSTOM
360ASX-360ASXT
OUTPUT CURRENT - AC AMPS RMS
OUTPUT VOLTAGE - AC VOLTS RMS
150 140 130 120 110 100 90 80 70 60 50 40 30 300
150
280
140
260
130
240
120
220
110
200
100
1809016080140701206010050804060-2 Phase Mode
30-3 Phase Mode
84
72
60
48
36
24
12
0
28
24
20
16
12
8
4
0
OUTPUT VOLTAGE - AC VOLTS RMS
OUTPUT CURRENT - AC AMPS RMS
0.00 PF
1.00 PF
1.00 PF
0.00 PF
3 Phase
2 Phase
Single Phase Mode Split and Three Phase Mode
Short term overloads to 60A are permitted. Operating time before thermal
shutdown or circuit breaker trip varies from seconds to several minutes
depending upon line and temperature conditions.
Short term overloads to 20A are permitted. Operating time before thermal
shutdown or circuit breaker trip varies from seconds to several minutes
depending upon line and temperature conditions.
Output Ratings
360ASX
Rated Power (VA)
5
6000
1
Coupling Mode
Direct 1Ø/2Ø
Form
3Ø
2
V
Max
rms
(L-N/L-L)
132/264
132/228
Output Voltage3
360ASXT
Output Voltage3
1
Rated Power (VA)
5
6000
Coupling Mode
Direct
Transformer 1.5:1
Transformer 2.0:1
Transformer 2.5:1
NOTES:
1. Rated output power is based on a combination of nominal output voltage, rated current and load power factor. Values stated represent the maximum capabilites of a given model. Consult factory for assistance in determining specic unit
capabilities as they might apply to your application.
2. Unit is operable as single phase with dual range capability or as a three phase. Output voltage range and 1/3 conversions are selected by front panel or bus commands.
3. Vmax is output voltage with nominal input and full rated load applied.
4. Available current will vary with output voltage and power factor.
5. Source rated at 4kVA in 2Ø mode.
ASX Power Source Specications (PF = 1.0, V
Output
Frequency
Full Power
15-1,200Hz Direct Coupled
45-1,200 Hz Transformer Coupled
Line Regulation
0.1% max for a
±10% line
change
2
Form
1Ø/2Ø
3Ø
1Ø/2Ø
3Ø
1Ø/2Ø
3Ø
1Ø/2Ø
3Ø
V
Max
rms
(L-N/L-L)
132/264
132/228
198/396
198/343
264/528
264/457
330/600
330/572
> 25% F.S.)
out
Load Regulation
(Typ. 3 Phase)
3Ø direct coupled: 0.25% 15 to 400 Hz.,
0.50% 400 to 1,200 Hz.
3Ø transformer coupled: 2 to 5% depending on ratio
Improves to less than 0.1% with external sense and
CSC enabled
Current
(A
rms
48/16
16/Ø
Current
(A
rms
48/16
16/Ø
32/11
11/Ø
24/8
8/Ø
19/6
6/Ø
4
)
Frequency
Range
15-1200
15-1200
4
)
Frequency
Range
15-1200
15-1200
45-1200
45-1200
Input
Power
3Ø
47-63Hz
Input
Power
3Ø
47-63Hz
Unit Height
In/mm/U
8.75/222/5U
Unit Height
In/mm/U
360ASX
8.75/222/5U
Transformer Module
5.25/133/3U
Unit Weight
(Lbs/Kg)
145 Lbs/66 kgs
Unit Weight
(Lbs/Kg)
360ASX
145 Lbs/66 Kgs
Transformer Module
125 Lbs/56.8 Kgs
45-1200
45-1200
45-1200
45-1200
Output Distortion
0.25% THD
1.25% THD
15 to 200 Hz
AVG
200 to 1,200 Hz
AVG
Ripple
and Noise
-66dB
Response Time
60 µsec typical,
10-90% load step
Input Power Requirements (47-63 Hz)
Input Voltage
Input Current
Recommended
Input service
208V 3ØΔ
±10%
20A
rms
30A
220V 3ØΔ
±10%
18A
rms
30A
240V 3ØΔ
±10%
16A
rms
25A
220/380V 3ØΔ
±10%
11A
rms
15A
* Power Source equipped with soft start feature. In-rush current at application of input power will not exceed recommended input service.
230/400V
±10%
11A
rms
15A
Power Factor Rating Curves
Rated Continuous load current as a function of Power Factor and Output Voltage-Nominal Input Line
240/416V
±10%
10A
rms
15A
277/480V
±10%
Cost Option