Atec 3060MS User Manual

Model 3060-MS
62.5kVA
50, 60, 400 or 47-500 Hz
Solid State Frequency Converter
Direct Coupled Output (3Ø): 0-120
Output Transformer options available for higher voltage ranges.
/ 0-208V
L-N
System Summary:
• Power: 50kV/62.5kVA per Chassis
• Output Voltage 0-120V
or Delta. Optional External Output Transformers
Available to meet higher voltage range
requirements.
• Single or Split Phase Output Configurations
Available.
• Current: Paralled Systems to 1750A/Phase
• Frequency Range: 50, 60 or 400Hz fixed , 47-
500Hz Variable or 20-1000Hz Variable with SCU/
UPC32 Option.
/0-208V
L-N
3 Phase Wye
L-L
L-L
The Model 3060-MS is a high power solid state frequency converter consisting of one to ten 50 kW/62.5 kVA, 3 phase AC Power Sources. The MS Series oers reliable voltage and frequency conversion and power monitoring for facilities power and/or AC power test applications. By adding the external SCU/UPC-32 Universal Programmable Controller, the MS Series can be operated as a fully featured programmable AC Power Source complete with arbitrary waveform generation and AC transient programming.
System Features:
• Voltage and Frequency Conversion.
• Highly Flexible and Expandable Power
Architecture with Unique Master/Slave
Configuration up to 625 kVA.
• Very High Current Capability.
• Low Voltage Distortion.
Included with Standard Delivery:
• 3060-MS Solid State Frequency Converter.
• User Manuals.
Optional SCU/UPC32 M993235 Remote Controller
Maximum System Flexibility and Reliability
Capable of operating as either the master or slave in a multi-cabinet parallel system. Easy to recongure to meet changing test needs.
Control and Monitor Panel
The 3060-MS is equipped with simple to use front panel controls for set­ting output voltage and frequency. This panel also provides read back on both AC input and AC output Frequency, Voltage, Current and Power as well as diagnostic information on system status and operation. For general frequency conversion facility power applications, the front pan­el controls provide all necessary setting and monitoring capabilities. For AC power test and development applications, the external SCU/UPC-32 programmable controller may be added as an option.
THE POWER OF EXPERTISE
FREQUENCY CONVERSION R & D MANUFACTURINGAEROSPACE MILITARY CUSTOM
True Advantages
Solid State Technology
3060-MS
Rugged, Powerful Output
•
350 Amps of Pulse Current
per phase is delivered by
each 3060-MS for driving non-linear loads. This elimi­nates the need to oversize facility power as is common for rotary or low quality PWM power systems.
•
Load Power Factor
is not an issue. The 3060-MS will
drive virtually any load without damage or risk.
Excellent Regulation
•
and response time eliminates load “cross talk.” Voltage sags common to other conversion methods are eliminated with 150 microsecond re­sponse time to a 50% load step. The output recovers to ± 3% of nominal within less than 1/10th of a cycle at 400 Hz.
Maximum Reliability
•
Each 3060-MS
is capable of operating as either the mas­ter or slave in a multi-cabinet parallel system providing conguration exibility.
•
Mission Reliability
is ensured. The parallel system ar-
chitecture is such that a failed slave unit automatically removes itself from the power grid. Should the master unit fail, the operator can select any other paralleled unit as the new master from the front panel and restore system operation.
Simple / Informative Display
Measures
•
output phase.
•
Eciency
performance verication.
• Internal Diagnostics assist in quickly locating failed components, resulting in extremely low MTTR.
•
Power Generation
diagnostics. A failure in the display logic will not aect output power quality. Output power cannot be inter­rupted by system interrogation.
•
Audible and Visual Alarms
ditions requiring attention.
volts, amps, watts and kVA for each input and
is continuously monitored, allowing system
circuits are separate from display and
alert the operator to any con-
Low Cost of Ownership
•
Lower Maintenance Costs
are achieved through built-in diagnostics that minimize MTTR. Quick and easy repair is facilitated with a small complement of local spares.
•
Input Power Factor
is a constant 0.9 lagging, regard­less of load. The MS Series actually corrects PF re­ected back to the utility, eliminating PF penalties.
•
Low Installation Cost
. The MS Series ts through
standard doorways. Audible noise is limited to cool­ing fans. There is no 400 Hz whine that requires noise isolation. Solid state design with a forklift base eliminates the need for concrete pads and vibration isolators common to rotary installations. Casters are optional if desired.
Facility/Test Power Flexibility
•
Power Levels Grow
ed or removed from the power grid as required.
•
Variable Frequency
switch selectable xed frequency operation of 50, 60 or 400 Hz, is standard on every model.
•
External Input
allows operation as a variable frequency test power amplier.
•
UPC-32 Programmable Controller Option
able to provide steady state and transient control of output power from the RS-232 or GPIB bus.
36"/ 914
mm
with demand. Units may be add-
range of 47–500 Hz, as well as
is provided as a standard feature. This
Input
TOP
Knockouts for
mm
Output
Conduit
30"
762 mm
Conduit
Paralleling and Options
12"/ 305
is avail-
Exhaust Air
© 2012 Pacic Power Source, Inc. Specications subject to change without notice.
72"
1829
DS#43060MS122012
FRONT
SIDE
Air Intake
Input Circuit
Air Intake
Page 2 of 4
3060-MS
AC Output Specications
POWER 62.5kVA/50kW for each 3060-MS
VOLTAGE
(Nominal)
CURRENT RMS 175 A
OVERLOAD (KW) 110% for 1 hour, 125% for 10 minutes, 150% for 10
FREQUENCY 50Hz, 60Hz or 400Hz Fixed settings
VOLTAGE THD < 1% max. Vthd at 50 or 60Hz
LOAD REGULATION ±1% @ 50/60Hz, ±2% @ 400Hz with Automatic Gain
LINE REGULATION ±1% maximum for ±10% line voltage change
LOAD TRANSIENT
RESPONSE AND RECOVERY TIME
LOAD POWER
FAC TOR
LOAD BALANCE
RESTRICTION
ISOLATION An input transformer with an electrostatic shield
OVER CURRENT
PROTECTION
Direct Coupled: 0-120/208 V, 3-phase External
Transformer
Options:
/Phase continuous
RMS
Pf < 0.8=175A Pf 1.0=140A
seconds
47 - 500 Hz Variable
< 2% max. Vthd at 400Hz
Control (AGC) enabled
150 microseconds for 50% load step and 300 microseconds for 100% load step.
Delivers full rated kVA into any Power Factor load.
None. Each phase is independently regulated
provides isolation between the input and output of the system.
Integral electronic current limiting with auto recovery. Output Circuit Breaker is optional.
Consult factory for details.
/Phase
RMS
/Phase
RMS
Measurements (with optional SCU/UPC32)
VOLTAGE
(True RMS)
CURRENT
(True RMS)
POWER/CREST
FREQUENCY Range 20 to 1000 Hz
VOLTAGE Range 0 to VMAX
CURRENT LIMIT Range 0 to I
PROGRAMMABLE
OUTPUT IMPEDANCE
Range 0-354V Resolution 0.1 VAC to front panel.
Accuracy ±0.2% of range +cal.ref.
Range 4,000Apk Resolution 0.01A to front panel.
Accuracy ±0.2% of range +cal.ref.
POWER Measures True Power (kW), Apparent Power (kVA)
Power Factor and Crest Factor.
1.4MW / 1.4MVA
Range Resolution
Calculated and displayed to three signicant digits.
FAC TOR
1.0 Watt
Parameter Settings
Resolution 4 signicant digits, e.g. 400.0 Accuracy ±0.01%,
Resolution 0.1 VAC steps. Accuracy ±0.2% of range +cal.ref.
Resolution ±0.05% Accuracy ±3%, FS
Dynamic output impedance (Zo) is programmable, ± Zo, MAX in 0.1% steps. Zo value in milliohms and typically results in a ±10% change in output voltage at maximum rated load current.
, 0-708V
L-N
L-L
0.001 VAC to remote interface.
0.001A to remote interface.
(with optional SCU/UPC32)
max
RMS
Input Power Requirements
208
240
380
400
INPUT
VAC∆
VAC∆
VAC∆
VOLTAGE
RECOMMENDED
SERVICE CURRENT
INPUT FREQUENCY 47–63 Hz
POWER FACTOR 0.85 lagging typical
PROTECTION Input CB Standard. Slow Turn-On Circuit is provided to
±10%
±10%
175 A
175 A
RMS
RMS
limit inrush current
100 A
±10%
VAC∆ ±10%
100 A
RMS
416 VAC∆ ±10%
100 A
RMS
RMS
Mechanical Specications
HEIGHT 72" / 1829 mm
WIDTH 36" / 914 mm
DEPTH 30" / 762 mm
WEIGHT 1,557 lbs. / 715 kg
INSTALLATION
CLEARANCE
36" at front of cabinet for service, 12" top, 0" side and rear
General Specications
OPERATING TEMP Operating: 0º to +40ºC (32º to 104ºF) – Storage: -10º to
RELATIVE HUMIDITY 0 to 95% non-condensing
NOISE LEVEL 65 dbA at 3 feet
EFFICIENCY 85 % typical at full load
COOLING/
VENTILATION
HEAT DISSIPATION AT
FULL LOAD
SERVICE ACCESS Unit is designed for front access. Power Cabling is routed
CERTIFICATION CE, ETL (Optional)
ALTITUDE Operating 6000 Ft. Storage 40,000 Ft.
+70ºC (+14º to +158ºF)
Self-Contained fans; bottom intake, top exhaust, 1200 CFM.
20 kBTU/HR (6 kW/HR)
through either top or bottom knock-outs.
Protection and Safety
AC Power Source is protected against Overcurrent, Short Circuit, and Overtemperature.
AUDIBLE & VISUAL
ALARMS
Alter operator to any conditions requiring attention.
Typical MS Options
/CE CE Mark. Includes Output Circuit Breaker (/OCB)
/CSTB Casters
/OCB
Output Circuit Breaker
/M99575
/M99583
Split Phase Output Congurations (50 kw)
Split Phase Output Congurations (32 kw)
Options for SCU/UPC32 Equipped MS Systems
/G GPIB Inter face, SCPI Commands & IEEE488.2 (standard)
/S RS232 Inter face. SCPI Commands, Baudrate up to 38.4
kBps. (Replaces GPIB, no cost option)
UPC-Studio Windows AC Power Source control Software (no cost
ABD0100 License for Avionics Test Sequences according to norm
IEC-AC-4XX IEC 61000-4 AC Immunity Test Sequences. Includes 4-11,
SCU/UPC32-413 IEC 61000-4-13 Inter Harmonic Generator. Required to
DRIVERS LabView
option) UPC Test Manager License (cost option) required for
Avionics or IEC test options listed below:
ABD0100.8.1. Requires UPC-Test Manager Option.
A350 License for Avionics Test Sequences according to norm
Airbus A350. Requires UPC-Test Manager Option.
DO160 License for Avionics Test Sequences according to norm
DO160 Version E - Requires UPC-Test Manager Option.
4-14, 4-27, 4-28 and 4-34. Excludes 4-13 Option.
run 4-13 tests. Includes 4-13 software.
and LabWindows™ drivers available
Only
VAC∆ ±10%
80 A
480
RMS
© 2012 Pacic Power Source, Inc. Specications subject to change without notice.
DS#43060MS122012
Page 3 of 4
3060-MS
UMS Option
MS Series Battery Support Systems
With the addition of the UMS Battery Backup option, the 3060-MS can be converted to an uninterruptable Power Source (UPS). The UMS battery support system for a single cabinet UMS installation (62.5 kVA, 50 kW) consists of 30 sealed, maintenance free, im­mobilized electrolyte batteries installed in a Zone 4 cabinet. The UMS system DC voltage regulator provides for automatic charging of the battery system to maintain the proper oat voltage.
The Leader in AC Power Technology
As a privately held, leading manufacturer of high-quality AC Power Conversion Equipment, Pacic Power Source, Inc. oers standard catalog products that range in power from 500 VA to >625 kVA. Low-power products include frequency converters and Programmable AC Power Sources. High­power systems include programmable power test equipment, frequency converters and uninterruptible AC Power Sources.
Founded in 1971, the Irvine, California, company was an early pioneer in the development of linear solid-state power conversion for use in high-reliability applications. The company now manufactures both advanced linear and broadband switching types of AC Power Sources.
A battery disconnect is located in the center of the battery cabinet front door. Battery support time at full load (50 kW) is approximately 15 minutes. The waveform quality at the end of the battery support time meets the requirements of MIL-STD 1399, section 300A, Types I, II and III power forms.
On-Line, No-Risk Battery Test
This feature of the UMS system provides the ability to perform a battery test on com­mand from the front panel or RS-232 serial port. Test results are displayed on the front panel and are available over the serial port as a part of the system diagnostics. A battery failure during the test will not cause the system to drop the load or distort the output waveform.
UPC Manager Software Suite
Master the Power of the Wave!
UPC Manager Software gives you the tools necessary to quickly and easily operate your AC Power Source. With our complete, graphical interface, control all areas of your AC Power Source testing with simple presets, user prompts, test sequences, test plans and custom reports.
UPC Features
•SimpleandComprehensiveprogramming
•Executeand Monitor the output values using theinternal power
analyser
•Create arbitrary waveforms, import waveforms captured on
external instruments, freehand draw, enter harmonic and phase angle content, create ringwaves, random noise, clipping and other custom waveshapes.
SCU-UPC32 Programmable Controller
12-bit A/D converter. This technique provides exceptional metering accuracy and resolution (20 bits), and delivers a high-delity waveform back to a host computer for analysis. The UPC includes
a remote GPIB interface compatible with IEEE488.2 and SCPI.
© 2012 Pacic Power Source, Inc. Specications subject to change without notice.
The UPC controller is a 3-Phase AC arbitrary waveform generator and precision AC metering system. Each waveform stored in the UPC is encoded with 12-bit amplitude and 10-bit time resolution for each cycle. The waveform for each phase may be independently selected and varied in amplitude and phase angle with respect to phase A. The UPC output metering samples the output volts and amps at 512 samples per measurement using a