Model 5597
OPERATING INSTRUCTIONS
1000A DC/AC CLAMP METER
Safety
International Safety Symbols
This symbol, adjacent to another symbol or terminal, indicates the user must refer
to the manual for further information.
This symbol, adjacent to a terminal, indicates that, under normal use, hazardous
voltages may be present
Double insulation
SAFETY NOTES
• Do not exceed the maximum allowable input range of any function
• Do not apply voltage to meter when resistance function is selected.
• Set the function switch OFF when the meter is not in use.
WARNINGS
• Set function switch to the appropriate position before measuring.
• When measuring volts do not switch to current/resistance modes.
• Do not measure current on a circuit whose voltage exceeds 240V.
• When changing ranges using the selector switch always disconnect the test leads from
the circuit under test.
• Do not exceed the maximum rated input limits.
CAUTIONS
Improper use of this meter can cause damage, shock, injury or death. Read and
understand this user manual before operating the meter.
Always remove the test leads before replacing the battery.
Inspect the condition of the test leads and the meter itself for any damage before operating
the meter. Repair or replace any damage before use.
Use great care when making measurements if the voltages are greater than 25VAC rms or
35VDC. These voltages are considered a shock hazard.
Remove the battery if the meter is to be stored for long periods.
Always discharge capacitors and remove power from the device under test before
performing Diode, Resistance or Continuity tests.
• Voltage checks on electrical outlets can be difficult and misleading because of the
uncertainty of connection to the recessed electrical contacts. Other means should be used
to ensure that the terminals are not "live".
• If the equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Input Limits
Function Maximum Input
A AC 1000A
V DC, V AC 600V DC/AC
Resistance, Diode, Continuity, Capacitance,
250V DC/AC
Frequency, Duty Cycle, Test
Temperature (℃/℉)
60V DC/24V AC
Meter Description
1. Current clamp
2. Clamp trigger
3. Data Hold and Backlight button
4. Mode select button
1
5. Hz/% button
6. LCD display
7. COM input jack
8. Rotary Function swith
9. ZERO button
10. Range select button
11. V Ω℃/℉ jack
12. Battery compartment on rear
A
400A
40A
2
3
4
5
6
7
Hz%
DC
AC
8
9
C
¡ã¡ãF
A
mV
kM
12
1.
AC DC
2. Minus sign
AC (alternating current)
and DC (direct currrent)
n
u
3. 8.8.8.8 4000 count (0 to 3999)
measurement reading
4. AUTO AutoRange mode
5. Diode test mode
6. •))) Audible Continuity
7.
9.℃,℉, µ
Data Hold mode
HOLD
,m,V,A,K,M,Ω,
Units of measure list

Specifications
Function Range & Resolution Accuracy (% of reading)
DC Current
AC Current
DC Voltage
AC Voltage
Resistance
Capacitance
Frequency
Duty Cycle
Temp (type-K)
(probe accuracy
not included)
Note: No Autoranging & 400mV AC Voltage Range
Clamp size Opening 1.2" (30mm) approx
40.00 AAC ± (2.8% + 10 digits)
400.0 AAC ± (2.8 % + 5 digits)
1000 AAC
40.00 AAC ± (3.0% + 10 digits)
400.0 AAC ± (3.0 % + 5 digits)
1000 AAC
400.0 mVDC ± (0.8% + 3 digits)
4.000 VDC
40.00 VDC
400.0 VDC
600 VDC ± (2.0% + 3 digits)
400.0 mVAC ± (0.8% + 20 digits)
4.000 VAC
40.00 VAC
400.0 VAC
600 VAC ± (2.5% + 5 digits)
400.0 Ω ± (1.0% + 4 digits)
4.000KΩ
40.00KΩ
400.0KΩ
4.000MΩ ± (2.5% + 3 digits)
40.00MΩ ± (3.5% + 5 digits)
40.00nF
400.0nF ±(3.0% reading + 5 digits)
4.000μF
40.00μF
100.0μF
5.000Hz
50.00Hz
500.0Hz
5.000kHz
50.00kHz
100.0kHz
±(5.0% reading + 5 digits)
0.5 to 99.0%
Pulse width: 100µs - 100ms, Frequency: 5.000Hz ~ 100.0kHz
-20 to 1000 °C ±(3.0% reading + 5°C)
-4 to 1832 °F
± (3.0 % + 5 digits)
± (3.0 % + 5 digits)
± (1.5% + 3 digits)
± (1.8% + 5 digits)
± (1.5% + 2 digits)
±(5.0% reading + 100 digits)
±(3.5% reading + 5 digits)
±(1.5% reading + 5 digits)
±(1.2% reading + 2 digits)
Sensitivity: 10Vrms min.
±(1.2% reading + 2 digits)
±
(3.0% reading + 7°F)
Diode Test
Test current of 0.3mA typical; Open circuit voltage 1.5V DC
typical.
Continuity Check
Threshold <100Ω; Test current < 1mA
Low Battery Indication “ BAT ” is displayed
Overrange Indication “OL” is displayed
Measurements Rate 2 per second, nominal
Input Impedance 7.8MΩ (VDC and VAC)
Display 4000 counts LCD
AC Current
AC Voltage bandwidth
Operating Temperature 14 to 122
Storage Temperature -14 to 140
Relative Humidity 90%(0
Altitude
Over voltage
Category III 600V
50/60Hz (AAC)
50/60Hz (VAC)
o
F (-10 to 50oC)
o
F (-30 to 60oC)
o
C to 30oC); 75%(30oC to 40oC); 45%(40oC to 50oC)
Operating: 3000m; Storage 10,000m
Battery One “9V” Battery
Auto OFF approx. 35 minutes
Dimensions/Weight 229x80x49mm/303g
Safety
For indoor use and in accordance with Overvoltage Category
II, Pollution Degree 2. Category II includes local level,
appliance, portable equipment, etc., with transient
overvoltages less than Overvoltage Cat. III
Operation
NOTICES: Read and understand all warning and precaution statements listed in the
safety section of this operation manual prior to using this meter. Set the function
select switch to the OFF position when the meter is not in use.
DC/AC Current Measurements
WARNING: Ensure that the test leads are
disconnected from the meter before making current
clamp measurements.
1. Set the Function switch to the 1000A or400A or
40A range. If the range of the measured is not known,
select the higher range first then move to the lower
range if necessary.
2. Select AC or DC with the
MODE
button.
3. Press the trigger to open jaw. Fully enclose over one
conductor wire to be measured.
4. The clamp meter LCD will display the reading.
DC/AC Voltage Measurements
1. Insert the black test lead into the negative
red test lead into the positive V terminal.
terminal and the
COM
2. Set the function switch to the V position.
3. Select AC or DC with the MODE button.
4. Connect the test leads in parallel to the circuit under test.
5. Read the voltage measurement on the LCD display.