ATD Tools ATD3698 User Manual

WARRANTY POLICY
The ATD3698 Refrigerant Gas Leak Detector is warranted to be free of defects in materials and workmanship for a period of two years from the date of purchase including an industry first two year warranty on the sensor. This warranty applies to all repairable instruments that have not been tampered with or damaged through improper use including unauthorized opening of the unit. Please ship warranty units that require repair freight prepaid to Service Center along with proof of purchase, return address, phone number and/or email address.
Model ATD3698
Refrigerant Gas Leak Detector
User Manual
Detects all CFC, HFC, HCFC
Refrigerants including blends
J2791
INTRODUCTION
T
he ATD3698 features a long life heated sensor technology that is designed to detect the more current and difficult HFC refrigerants such as R-134a in addition to all HCFC (R22) and CFC (R12) refrigerants including SNAP approved hydrocarbon blends. The ATD3698 does not require rechargeable batteries.
FEATURES
Unique numeric leak size Indicator
Long life, stable sensor
R134a sensitivity .05 oz/yr R22 sensitivity .025 oz/yr
Designed certified SAE
2791
standard
Automatic calibration and reset to ambient
Low battery indicator 3 adjustable sensitivity levels
2- year warranty including 2
years for the sensor
True mechanical pump
Uses 4 AA alkaline batteries CE Certified
Made in USA
1
Replacement Parts
Item Part Number
Sensor with Filter
PRT3700-01
Filter Kit
PRT3700-02
Test Vial
PRT3700-03
Product Specifications
Model # ATD3698
Name
Leak Detector, Refrigerant Gas
Sensitivity
.05 oz/yr R134a .025 oz/yr R22
Sensor Life > 300 hours
Response Time Instantaneous
Power Supply 4 AA Alkaline batteries
Battery Life 8 hours continuous
Warm up time < 20 seconds
Probe length 17 inches
Weight, lbs 1.5 lbs
Warranty 2 years (2 yrs for sensor)
6
Maintenance
Polarity Mark
Filter
Keyway
alignment
Pull straight out (do not
Unscrew tip to
replace filter
Push straight on (do not
twist) to install sensor
Batteries:
Install Batteries
: Remove screw located at rear end of unit and
pull down hinged battery door to open as shown.
Always insert all
4 batteries into the compartment in the same direction. Note the
polarity mark on the inside of the battery door for proper battery
installation.
Sensor:
Replace Filter: Unscrew sensor tip as shown to repl
ace filter.
Replace filter whenever it becomes visibly dirty or every 2 to 3
months depending on use.
Replace Sensor: Remove sensor by pulling out of socket.
Install
the new sensor by aligning the
notch in sensor cover with the raised
keyway on sensor socket holder (see figure below).
Note: Do not force sensor into socket
. Misalignment can
damage the sensor pins.
5
ATD3698 Control Panel
Operating Instructions
1. TURN ON:
Press the ON/OFF button once to turn on and again
to turn off.
2. WARM UP: The detector automatically start
s heating the sensor.
During the heating cycle, the detector will sound a slow “beep”.
Warm up is usually less than 20 seconds.
3. READY
: The detector is ready to begin searching for leaks when
the green sensitivity LED turns on. The audio “beep” increa
ses in
frequency.
Low Battery
Indicator
Sensitivity Level
Sensitivity Level
Selectors
Power
On/Off
2
L
ow Battery Indicator
Replace the 4 AA Alkaline batteries when the red LED on the control panel is lit. Follow battery installation instructions under Maintenance section.
Adjusting Sensitivity Levels
The Leak Detector will default to the NORM sensitivity level automatically once the unit comes out of the warm up cycle and the green LED will turn on.
To change sensitivity levels, press the SENS once for HI sensitivity (red LED will turn on) and again for LO sensitivity (yellow LED will turn on).
3
Leak Test Vial
The leak detector comes with a Leak Test Vial that allows the user to make sure the detector is performing properly. To test:
1. Remove the plastic seal cap on top of the Leak Test Vial by pulling it off (see fig. below).
2. Turn on the detector and allow the unit to complete the warm up cycle.
3. Place the sensor close to the small hole in the top of the Leak Test Vial. The beep rate should increase and the Digital Leak Size Indicator should display a number from 4-6 indicating that the sensor and electronics are working properly.
NOTE: Always remember to replace plastic seal cap after leak test is completed. Replace Test Vial when the green color is no longer visible.
Remove
Seal Cap
To test
Leak Test Vial
4
Loading...