SPECIFICATIONS
\\\
CONTROL VOLTAGE
PICK UP VOLTAGE
DROP OUT VOLTAGE
MAXIMUM VOLTAGE
RESPONSE TIMES
TEMPERATURE RATING
POWER (NOMINAL VOLTAGE)
DUTY CYCLE INSULATION
RESISTANCE DIELECTRIC STRENGTH CONTACT MATERIAL
CONTACT ARRANGEMENTS
OUTPUT RATINGS AGENCY
APPROVALS WEIGHT
WIRING
\\\
Automatic Timing & Controls
12 to 240 VAC 12 to 110 VDC, See Table 1
AC Coils 80% of Nominal DC Coils 80% of Nominal AC Coils 30% of Nominal DC Coils 10% of Nominal
110% of Nominal
Pick-up 30 mSEC, maximum
Drop-out 20 mSEC, maximum
Operate –10°C to +40°C
Storage –45°C to +85°C AC Coils 2.1 VA DC Coils 1.2 Watts
Continuous
100 Meg ohms, minimum
1500 VAC, 50/60 Hz. for 1 minute
Silver cadmium oxide
DPDT 8-Pin plug in
3PDT 11-Pin plug in
See Table 2
Consult factory
3 oz.
M
e
d
i
u
Low Cost
Rugged Design
10 Amp Output
High Reliability
8 pin or 11 pin Track Mountable Plug-in base
COIL RATINGS (TABLE 1)
\\\
Nominal Voltage
12 199 168
AC
DC
24 99 84 120 20.5 17.5 240 10.2 8.8
12 100 120
24 51 472 110 11.5 10,000
KAA Series
P
o
w
e
r
P
l
u
g
-
I
DPDT & 3PDT Arrangements
12, 24, 120, & 240 volts operation
Rated current (mA)
50 Hz 60 Hz
Coil resistance
n
(ohms)
s
y
a
l
e
R
// KAA Series
Powered by TCPDF (www.tcpdf.org)
DIMENSIONS (INCHES)
\\\
TOP
SOCKET
OUTPUT CONTACT RATINGS (TABLE 2)
\\\
Specifications
Rated load
Carry current 10A Max. operating voltage 250 VAC 250 VDC Max. operating current 10A
Max. switching capacity
Minimum permissible load 5 VDC 100mA
MODEL NUMBER >>>>>> KAA X
Example: KAA-120-ADX
Resistive load
(p.f. = 1)
230 VAC 10A
28 VDC 10A
2300VA
280W
Coil Voltage
110 Volts 110 120 Volts 120
240 Volts (AC only) 240
Type of Voltage
Contact Arrangement
Inductive load
(p.f. = 0.4; L/R = 7msec)
230 VAC 6A
28 VDC 7.5A
1400VA
210W
12 Volts 24 Volts 24
12
AC
DC D
DPDT
3PDT T