ATC550
OperatingInstruction
SPECIFICATIONS
Display
4 + 4 digit, 7 segment digital display
LED Indications
1 : Output 1 ON
2 : Output 2 ON
S : Dwell timer
Keys
3 keys for digital setting
INPUT SPECIFICATIONS
Input Signal
Sampling time
250 ms
Input Filter(FTC)
0.2 to 10.0 sec
Resolution
o
C / °F selectable
Indication Accuracy
(20 min of warm up time for TC input)
Control Method
1) PID control with auto tuning
2) ON-OFF control
3) Heat-Cool (with auto-tuning)
Proportional Band (P)
1.0 to 400.0°
0 to 9999 sec
0 to 9999 sec
0.1 to 99.9 sec
Hysteresis Width
0.1 to 99.9°
0-9999min
Manual Reset Value
-19.9 to 19.9°
Control Method
PID
Proportional Band-Cool
0.0 to 400.0°
0.1 to 99.9 sec
Dead Band
SPLL to SPHL (Programmable)
OUTPUT
Control Output
Relay Contact (SPDT)
(Relay or SSR user selectable) :
5Aresistive@250VAC/30VDCSPSTRLY
12V DC, 50 mA
Auxiliary Output :
Relay Contact
5Aresistive@250VAC/30VDCSPSTRLY
SSR Drive Output(Voltage Pulse)
12V DC, 50 mA
(SPDT)
POWER SUPPLY
85 to 270V AC/DC (AC: 50 or 60 Hz )
Optional - 24V AC/DC
Power Consumption
Operating 0 to 50°C:
Storage -20 to 75°C:
Humidity(non-condensing)
95% RH
Weight
ATC550 : 142 gms
SAFETY PRECAUTIONS
that appear in this operating manual or on the equipment must
be strictly followed to ensure the safety of the operating
personnel as well as the instrument.
the manufacturer it might impair the protection provided by the
equipment.
Read complete instructions prior to installation and
operation of the unit.
WARNING :Risk of electric shock.
WIRING GUIDELINES
WARNING:
1. To prevent the risk of electric shock power supply to the
equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is
being supplied.
2. To eliminate electromagnetic interference use short wire
with adequate ratings; twists of the same in equal size shall
be made. For the input and output signal lines, be sure to
use shielded wires and keep them away from each other.
3. Cable used for connection to power source, must have a
insulation capacity made of at least 1.5kV.
4. When extending the thermocouple lead wires, always
use thermocouple compensation wires for wiring. For the
RTD type, use a wiring material with a small lead resistance
three wires.
2
have
5.
standard power supply cable for the instrument.
MAINTENANCE
1. The equipment should be cleaned regularly to avoid
blockage of ventilating parts.
2. Clean the equipment with a clean soft cloth. Do not use
Isopropyl alcohol or any other cleaning agent.
INSTALLATION GUIDELINES
1. This equipment, being built-in-type, normally becomes a
part of main control panel and in such case the terminals do
not remain accessible to the end user after installation and
Internal wiring.
2.
it may lead to a safety hazard that may in turn endanger life
or cause electrical shock to the operator.
3. Circuit breaker or mains switch must be installed between
power source and supply terminals to facilitate power 'ON'
or ‘OFF’ function. However this switch or breaker must be
installed in a convenient position normally accessible to the
operator.
4. Use and store the temperature controller within the
mentioned in this manual.
CAUTION
1.
output connections.
2.
power switch and fuses. Make wiring so that the fuse is
placed between the mains power supply switch and the
controller. (2 pole breaker fuse- rating: 275V AC,1A for
electrical circuitry is highly recommended)
3.
control panel), its output terminals get connected to host
equipment. Such equipment shall also comply with basic
EMI/EMC and other safety requirements like BSEN61326-1
and BSEN 61010 respectively.
4. Thermal dissipation of equipment is met through
ventilation holes provided on chassis of equipment. Such
ventilation holes shall not be obstructed else it can lead to a
safety hazard.
5. The output terminals shall be strictly loaded to the
MECHANICAL INSTALLATION
Outline Dimensions Panel Cutout
NEW
G
F
46G46
12T
B
S
MODELS
ATC550
A
D
C
E
DIM
A52B
C
D45E4F
94
52
ProtectionLevelIP65forFaceplate
1.Prepare the panel cutout with proper dimensions as shown
above.
2.Fit the unit into the panel with the help of clamp given.
3. The equipment in its installed state must not come in
close proximity to any heating sources, caustic vapors,
oils, steam, or other unwanted process by-products.
4.
terminal block using the tightening torque within the
range of 1.2 N.m.
5. Do not connect anything to unused terminals.
EMC GUIDELINES
1. Use proper input power cables with shortest
connections and twisted type.
2. Layout of connecting cables shall be away from any
internal EMI source.
LOAD CONNECTIONS
1. The service life of the output relays depends on the
switching capacity and switching conditions. Consider
the actual application conditions and use the product
within the rated load and electrical service life.
2. Although the relay output is rated at 5 amps it is
always necessary to use an interposing relay or
the controller in the event of a fault short developing on
the power output circuit.
3. Always use a separate fused supply for the “power
load circuit”and do not take this from the live and neutral
terminals supplying power to the controller.
For load current less than 0.5A
L
TC
C NO
MOV
TC
LOAD
R C
Snubber
N
For bigger loads, use interposing relay / contactor
L
TC
C NO
MOV
C
TC
Contactor
R C
Snubber
LOAD
N
Electrical noise generated by switching of inductive
loads can create momentary disruption, erratic
display, latch up, data loss or permanent damage to
the instrument.
a) Use of snubber circuits across loads as shown
above, is recommended.
b) Use separate shielded wires for inputs.
Document name : Operating instruction ATC550

TERMINAL CONNECTIONS
+
( )
L
+
SSR1
( )
N
ATC550
NO2
COM2
NO1
+
-
SSR1
SSR2
Use only the correct thermocouple wire or
compensating cable from the probe to
instrument terminals avoiding joints in the
cable if possible.
Failure to use the correct wire type will lead to
inaccurate readings.
Ensure that the input sensor connected at the
terminals and the input type set in the
same.
+
TC /RTD1
TC /RTD2
RTD3
COM1
FRONT PANEL DESCRIPTION
ATC
1
3
1 T
4
5
6
Process-value (PV) /
1
Parameter name
display
Parameter setting
2
display
Control output 1
3
indication
Control output 2
4
indication
5
Tune
6
Dwell timer
S
2
1) Displays a process value (PV).
2) Displays the parameter symbols
3) Displays PV error conditions.
1) Displays the parameter settings
The LED is lit when the control
output 1 is ON
The LED is lit when the control
output 2 is ON
Auto tune : Blinking
Blinking: Dwell timer is in progress.
Continuous ON : Time over.
2
FRONT KEYS DESCRIPTION
FUNCTIONS
ONLINE
Press key for 3 seconds.
Press key for 3 seconds.
Press + keys for 3 seconds.
Lower display selectable between
parameters
NOTE :Elapsed time / Remaining time dependent on the
selection of ONL parameter in level1.
SET1/SET2/TIME using key.
INPUT RANGES (Table 1)
FOR RTD
Input
Resolution
Pt100
Ranges
1 0.1
-150 to 850 -150 to 850
°C
-238 to 1562 -199 to 999
°F
FOR THERMOCOUPLE
Input Ranges
Resolution
J
K
T
R & S
1 0.1
-199 to 750 -199 to 750
°C
-328 to 1382 -199 to 999
°F
-199 to 1350
°C
-328 to 2462
°F
-199 to 400
°C
-328 to 750
°F
0 to 1750
°C
32 to 3182
°F
-199 to 999
-199 to 999
-199 to 400
-199 to 750
N/A
N/A
ERROR DISPLAY (Table 2)
When an error has occured, the upper display indicates error
codes as given below.
Error
Sensor break / over
range condition
Sensor reverse /
under range condition
Meaning
Control Output
Status
OFF
OFF
ATC550
Programming online parameters
Setpoint 1
Range : SPLL to SPHL
If upper display is selected as then,
Pressing key will show on Upper display :
Lower display : <50>
Press keys to increment/decrement+ /
value.
Setpoint 2 / Dead band
Range : SPLL to SPHL
If upper display is selected as / then,
Pressing key will show on Upper display : /
Lower display: <0>
Press keys to increment/decrement+ /
/ value.
Range : OFF, 1 to 9999 min
If upper display is selected as / then,
Pressing key will show on Upper display :
Lower display : <OFF>
Press keys to increment/decrement+ /
time value.
Default : 50
Default : 0
Default : OFF
Display selectable between SET1/
SET2 using key.
parameters
parameter values
Note :Display shows parameter
SET1/ SET2 for 1sec.
Press + / to change
parameter value.
PROGRAMMING MODE
or key once to view the next
the same level.
the value of a particular
parameter.
NOTE : The unit will auto exit programming mode after 30
By pressing the
OR
or previous function in operational
menu.
+ to increase and + to
decrease the function value.
Note:Parameter value will not alter
when respective level is locked.
or or + keys for 3 seconds.
CALIBRATION CERTIFICATE
Product is tested & calibrated by automatic technique.
The calibration of this instrument is done as per
following accuracy :
(20 min of warm up time for TC input)

CONFIGURATION INSTRUCTIONS
+ or +
Press once to view online parameters
Press for 3 sec to enter Level 1
Allows the user to increase or decrease associated parameter value
Press for 3 sec to enter Level 2
OPERTAIONAL MENU
Press key for 3sec.
Press key for 3sec.
Level 1 Level 2
Description
Display DisplayDefault
Input type
Display Resolution Proportional band
Temperature unit
Set point low limit
Set point high limit
Filter time constant
Control action for
relay 1
Control logic
Control Output selection
Dwell mode enable
Heat-cool mode
selection
Control action for
relay 2
Relay 2 type
Online menu for timer
Anti-reset windup %
Factory default
(Reset all)
J/K/T/R/S/RTD OFF/ON
1/0.1 1.0 to 400.0°
°C/°F
Min range of sensor
selected to SPHL
SPLL to Max range
of sensor selected
0.2 to10.0 sec
RE/FD
PID/ONF
NO/YES
NO/YES
RE/FD/TIME
DEV/ABS
REMN/ELPS
1.0 to 100.0%
NO/YES
Display
Condition
Not prompted
for R & S type
Not prompted
for HC=YES
When HC=NO.
TIME prompted
when DWEL
=YES
When
ACT2=RE/FD
When DWEL
=YES
When CNTL
=PID
Description
Tune
Integral time
Derivative time
Cycle time mode
Cycle time
Hysteresis 1
Manual reset
Proportional
band-cool
Cycle time-cool
Hysteresis 2
Dwell time
Display bias
POWER ON
ATC
1 T
S
2
DefaultRange Range
or or
0 to 9999 sec
0 to 9999 sec
0.1 to 99.9 sec
0.1 to 99.9°
-19.9 to +19.9°
1.0 to 400.0°
0.1 to 99.9 sec
0.1 to 99.9°
OFF, 1 to 9999 min
-19.9 to 19.9°
+
Note : At power ON lower display shows (momentary) input type selected in Level 1.
Display
Condition
For CNTL=PID
For CNTL=PID
For CNTL=PID
For CNTL=PID
For CNTL=PID
For CNTL=PID
For CNTL=ONF
For CNTL=PID
& I=0
For CNTL=PID
& HC=YES
For CNTL=PID
& HC=YES
For HC=NO or
HC=YES &
CNTL=ONF
When DWEL
=YES
+
Description
Display Default
Lock setpoint 1
Lock setpoint 2
Lock level 1
Lock level 2
Lock dwell time
Note
change in the value of respective level parameters.
in protection level.
makes update speed faster in 3 stages after 3 sec.
Press for 3 sec to enter protection Level
Press + keys for 3sec.
Protection Level
Range
UNLK/LOCK
UNLK/LOCK
UNLK/LOCK
UNLK/LOCK
UNLK/LOCK
continuous process )
Display
Condition
Prompted when
DWEL=YES