![](/html/89/8980/898076aebd0080ccfe2aef560e1b2133ff8f6b0e495f39d5a9dfef94ade0fece/bg1.png)
417 Series
r
e
m
i
T
r
u
e
O
F
• True OFF-Delay mode of
operation
• Output contacts rated 10A
at 120/240 VAC
• Three timing ranges in a
single unit:
10 SEC, 1 MIN, 10 MIN
5 SEC, 0.5 MIN, 5 MIN
• Universal power operation:
24 VAC to 240 VAC
& 24 VDC
TYPICAL APPLICATIONS
Whenever main
power is interrupted, the 417B
// 417 Series
(adjustable from
0.1 SEC to 10
MIN), enables an
emergency backup power source.
e
D
F
-
1/16 DIN Timers
Controlled by a PLC, the 417B timing cycle can be aborted by
using the remote reset terminals.
The 417B Directly Replaces 417A.
30
T
y
a
l
• 8-Pin or 11-Pin mounting.
• Remote reset models.
2
• 48mm
• Watertight when panelmounted
• Range selection is tamperproof when panel-mounted.
DIN standard housing
Automatic Timing & Controls automatictiming.com 800.727.5646
The 417B True OFF-Delay Timer is designed for the most rugged industrial
environments. It offers exceptional electrical noise immunity, with excellent
setting and repeat accuracy.
Each 417B can be powered from 24 VAC to 240 VAC and 24 VDC, greatly
simplifying ordering and inventory management.
2
The 48mm
panel-mounted. The 417B is mounted in an 8-pin octal or 11-pin round
socket. The 417B can be panel-mounted with an optional mounting clip.
A large time-setting knob is provided for easy adjustment by operator.
The range select switch is located on the side of the unit; therefore, once
panel-mounted, the switch is not accessible to the operator. This tamper-proof
feature prevents unauthorized or hazardous changes to the timing range.
The 417’s high intensity LED turns on when power is applied to the timer and
turns off during timing.
(1/16 DIN) housing is compact and watertight when
SPECIFICATIONS
\\\
MODELS
RANGE
CONTACT
RATING
TEMPERATURE
RATING
NOISE
IMMUNITY
MOUNTING
POWER
REQUIREMENTS
LOAD RELAY
REPEAT
ACCURACY
MINIMUM
SETTING
SETTING
ACCURACY
REMOTE
RESET
POWER ON
TIME
INDICATOR Power on LED
HOUSING
WEIGHT NET: 5 oz. SHIPPING: 1 lb.
Choice of eight multi-range units.
Each model has three timing ranges.
Model 417B100 (10 SEC, 1 MIN, 10 MIN)
Model 417B500 (5 SEC, 0.5 MIN, 5 MIN)
10 AMPS (Resistive @ 250 VAC)
1/3 HP @ 120 VAC
0° to 104°F (-18° to 40°C)
Showering Arc per NEMA 2-230, the 417 will
withstand a voltage surge of 4500 volts for 50
micro seconds without damage.
Plug in base available in 8-Pin Octal or
11-Pin Round Base
OPTIONS: Surface Mounting Socket
24 to 240 VAC & 24 VDC, 50 or 60 Hz,
(+10%, -20%) 24 to 240 VAC.
(+20%, -20%) 24 VDC
DC MAXIMUM RIPPLE AT 60 Hz-5%
+/-5%*
*variation from avg. actual time
2% of range
+/-10%
50 mSEC minimum (remote reset models)
1.0 SEC minimum
48mm2(1/16 DIN) housing is watertight when
panel mounted
DIN Rail Mounting Socket
Panel Mounting Kit
Plug-in Socket Kit
TYPE
LIFE
DPDT, Standard Models
SPDT, Remote Reset Models
10,000,000 operations (no load)
100,000 operations with
5 AMPS at 30 VDC (or less) or
5 AMPS at 250 VAC (or less)
![](/html/89/8980/898076aebd0080ccfe2aef560e1b2133ff8f6b0e495f39d5a9dfef94ade0fece/bg2.png)
800.727.5646 automatictiming.com Automatic Timing & Controls
417 Series
DIMENSIONS (INCHES/MILLIMETERS)
\\\
HOLD DOWN CLIP
ATC P/N 0407-025-13-00
PANEL MOUNTING
BRACKET
ATC P/N 0405-320-02-00
PANEL MOUNTING (UP TO .188 THICK)
OPERATIONS
\\\
When power is applied to the timer, the relay energizes and the
indicating LED turns on. Timing starts when power is removed,
and the LED turns off. The output relay remains energized until
the end of the cycle, or by connecting terminals 1 to 4 when
using the Remote Reset Model.
Model
417...F.X
Standard unit
with DPDT
relay contacts
MODEL NUMBER >>>>>> 417B F
Range
10 SEC, 1 MIN, 10 MIN
5 SEC, 0.5 MIN, 5 MIN 500
Voltage & Frequency
24 to 240 VAC & 24 VDC
Accessories-8 Pin
8-Pin surface/DIN rail socket 0000-825-85-00
Hold down for above socket 0407-025-13-00
Panel mounting bracket 0405-320-02-00
Plug-in socket kit (8-pin) 0319-261-45-00
8-Pin panel socket with rear facing
terminals
Accessories-11 Pin
11-Pin surface/DIN rail socket 0000-825-86-00
Hold down clips for above socket 0407-025-13-00
Panel mounting bracket 0405-320-02-00
Plug-in socket kit (11-pin) 0314-260-07-00
11-Pin panel socket w/rear facing
terminals
WIRING
\\\
TERMINAL WIRING
600-3-0011
600-3-0012
100
F
Arrangement
8 Pin Base
11 Pin Base
Features
Standard
Remote
Special
2
4
X
R
K
Model
417...F.R
Same as standard unit
except with
SPDT relay
contacts and
ability to reset
from an
externally
located
remote reset
switch
SETTING THE RANGE
Refer to the drawing. Using a small screwdriver
inserted into the adjusting slot as shown (fig. 1),
rotate the range switch. The selected range will
appear through the window of the dial face.
417 Series
//
1/16 DIN Timers
31