ATC-Automatic Timing & Control 417B Series Data Sheet

The 417 True Off-Delay Timer is designed for the most rugged industrial environments. It offers exceptional electrical noise immunity, with excel- lent setting and repeat accuracy.
Each 417 can be powered from 24 VAC to 240 VAC and 24 VDC, greatly simplifying ordering and inventory management.
The 48mm2 (1/16 DIN) housing is compact. The 417 is mounted in an 8-pin octal or 11-pin round socket. The 417 can be panel-mounted with an optional mounting clip.
A large time-setting knob is provided for easy adjustment by operator.
The range select switch is located on the side of the unit; therefore, once panel-mounted, the switch is not accessible to the operator. This tamper-proof feature prevents unauthorized or hazardous changes to the timing range.
The 417’s high intensity LED turns on when power is applied to the timer and turns off during timing.
E48329
True OFF-Delay Timer
SPECIFICATIONS
MODELS Choice of eight multi-range units.
Each model has three timing ranges.
RANGE Model 417B100 (10 SEC, 1 MIN, 10 MIN) Model 417B500 (5 SEC, 0.5 MIN, 5 MIN)
CONTACT RATING 10 AMPS (Resistive @ 250 VAC) 1/3 HP @ 120 VAC
TEMPERATURE 0° to 104°F (-18° to 40°C) RATING
NOISE Showering Arc per NEMA 2-230, the 417 IMMUNITY will withstand a voltage surge of 4500 volts
for 50 µsec without damage.
MOUNTING Plug in base available in 8-Pin Octal or 11-Pin Round Base. Options: Surface mounting socket DIN rail mounting socket Panel mounting adapter kit Plug-in socket kit
POWER 24 to 240 VAC & 24 VDC, 50 or 60 Hz, REQUIREMENTS (+10%, -20%) 24 to 240 VAC.
(+20%, -20%) 24 VDC DC MAXIMUM RIPPLE AT 60 Hz -5%
LOAD RELAY TYPE DPDT, Standard Models SPDT, Remote Reset Models LIFE 10,000,000 operations (no load 100,000 operations with 5 AMPS at 30 VDC (or less) or 5 AMPS at 250 VAC (or less)
REPEAT ± 5%* ACCURACY *Variation from average actual time.
MINIMUM SETTING 2% of range
SETTING ACCURACY ± 10%
REMOTE RESET 50 mSEC minimum (remote reset models)
POWER ON TIME 1.0 SEC minimum
INDICATOR Power on LED
2
HOUSING 48mm
WEIGHT 5 oz. (140 g)
(1/16 DIN)
True Off-Delay mode of operation
Output contacts rated 10A at 120/240 VAC
Three timing ranges in a single unit: 10 SEC, 1 MIN, 10 MIN 5 SEC, 0.5 MIN, 5 MIN
Universal power operation: 24 VAC to 240 VAC & 24 VDC
8-Pin or 11-Pin mounting.
Remote reset models.
2
• 48mm
Range selection is tamper-proof when panel-mounted.
TYPICAL APPLICATIONS
Whenever main power is interrupted, the 417 (adjustable from
0.1 SEC to 10 MIN), enables an emergency backup power source.
Controlled by a PLC, the 417 timing cycle can be aborted by using the remote reset terminal.
DIN standard housing
The 417B Directly Replaces 417A
1/16 DIN TIMERS 417B Series
Automatic Timing & Controls
HOLD DOWN CLIP ATC P/N 407-026-13-00
PANEL MOUNTING BRACKET ATC P/N 406-320-02-00
PANEL MOUNTING (UP TO 0188 THICK)
1/16 DIN TIMERS 417B Series
OPERATIONS
When power is applied to the timer, the relay energizes and the indicating LED turns on. Timing starts when power is removed, and the LED turns off. The output relay remains energized until the end of the cycle, or by connecting terminals 1 to 4 when using the Remote Reset Model. During time delay, power on will RESET Delay Time.
MODEL NUMBERDIMENSIONS (INCHES/MILLIMETERS)
MODEL NUMBER 417B F
RANGE
10 SEC, 1 MIN, 10 MIN 100 5 SEC, 0.5 MIN, 5 MIN 500
VOLTAGE & FREQUENCY 24 to 240 VAC & 24 VDC F
ARRANGEMENT 8-Pin Base 2 11-Pin Base 4
FEATURES Standard X Remote R Special K
ACCESSORIES 8-PIN 8-Pin surface/DIN rail socket 000-825-85-00 Hold down for above socket 407-025-13-00 (Requires two per unit) Panel mounting bracket 405-320-02-00 Plug-in socket kit (8-pin) 319-261-45-00 8-Pin panel socket w/rear 000-825-90-00 facing terminals
ACCESSORIES 11-PIN 11-Pin surface/DIN rail socket 000-825-86-00 Hold down for above socket 407-025-13-00 (Requires two per unit) Panel mounting bracket 405-320-02-00 Plug-in socket kit (11-pin) 319-260-07-00
MODEL 417...F.X
Standard unit with DPDT relay contacts
MODEL 417...F.R
Same as standard unit except with SPDT relay contacts and ability to reset from an externally located remote reset switch
SETTING THE RANGE
Refer to the drawing. Using a small screwdriver inser ted into the adjusting slot as shown (fig. 1), rotate the range switch. The selected range will appear through the window of the dial face.
WIRING
TERMINAL WIRING
Powered by TCPDF (www.tcpdf.org)
Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)
Automatic Timing & Controls
Loading...