ATC-Automatic Timing & Control 405AR Series Data Sheet

ON DELAY / TIMING MODES:
Dip switch settings for time range selection
The 405AR has a selectable ON-Delay or Interval Mode of operation. The unit has a DPDT 10A contact output. When in the On-Delay mode, the contacts transfer at time out. When in the Interval mode, the contacts transfer when power is applied and released at time out.
1/16 DIN HOUSING: The 48mm2 housing is compact and IP40 rated front cover. The 405AR is mounted in an 8-pin round socket (PF083A or OT-08). The 405AR can also be panel mounted.
The MODE/Range select dip switches are located on the front under a clear cover.
UNIVERSAL POWER: The 405AR is universal powered and can be powered by 20 to 240 VAC or 12 to 240 VDC, greatly reducing inventory management of replacement units.
E339488
1/16 DIN ON Delay/Interval Timer
ON Delay / Interval Mode of Operation
12 Timing Ranges
Universal Supply Voltage
LED Status Indicator Power ON, Relay ON
Compact Size
Face Plate IP40
1/16 DIN TIMERS 405AR Series
MODE AND RANGE SELECTION
RANGE
1 SEC
3 SEC
10 SEC
30 SEC
1 MIN
3 MIN
10 MIN
30 MIN
1 HR
3 HR
10 HR
30 HR
Dip switch settings for mode selection
MODE
ON DELAY
INTERVAL
Switch setting example:
ON
Sw1 Sw2
Sw3
SW 1
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
Sw4
SW 5
OFF
ON
Mode
SW 2
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Range: 30sec Mode :On delay
SW 3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
SW 4
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF/ON
OFF/ON
OFF/ON
OFF/ON
SPECIFICATIONS
OUTPUT CONTACT DPDT
DELAY MODES ON Delay / Interval
TIME RANGES 1 / 3 / 10 / 30 SEC / MIN / HR
Model S2X 10A @ 230 VAC/24 VDC, resistive Model S5TX 5A @ 230 VAC/24 VDC, resistive
ACCURACY Setting: ± 5% of full scale. Repeat: ±0.5% or 50 msec (whichever is greater).
RESET On interruption of power.
OPERATING 32° to 122°F TEMPERATURE (0° to 50°C)
STORAGE -4° to 167°F TEMPERATURE (-20° to 75°C)
Automatic Timing & Controls
DIMENSIONS (MILLIMETERS)
1/16 DIN TIMERS 405AR Series
Terminal type
48
7
70.5
OPERATING MODE
Plug type
79
Panel cutout
46
45
46
LOAD CONNECTIONS
8-PIN PLUG-IN TYPE TERMINAL TYPE
NC1
4
3
NO1
2
1
COM1 COM2
LN
5
8
NC2
6
NO2
7
1
NC1
11
6
L
3
2
NO1
COM1
8
7
+
-
N
4
NC2 COM2
9
5
12
10
ORDERING CODE
MODEL NUMBER DESCRIPTION
405AR100S2X 8-PIN socket with 10 amp relay
405AR100S5TX Terminal with 5 amp relay