ATC-Automatic Timing & Control 322B Series Data Sheet

A Dial-Adjustable TDR with cycle progress indication, the ATC 322 can also be used as a low-cost automatic reset timer for a wide range of interval, delay and pulse timing functions, in either ON-delay or OFF-delay operation.
PRICE/PERFORMANCE VALUE: Although it is priced like a TDR, the 322 provides the versatile timing functions and features of much more expensive automatic reset timers.
INSTANTANEOUS AND DELAYED LOAD SWITCHES: Because the standard 322 includes an instantaneous switch as well as two delayed switches, it can be used in the On-Delay mode for interval and/or delayed control, with either a momentary or sustained start signal. All three switches are mounted on a sliding deck which facilitates replacement and maintenance.
SURFACE OR FLUSH MOUNT: The 322 is provided with hardware for surface mounting or, if desired, flush mounting through a single 15/16" OD cutout in a 1/8" panel.
CYCLE PROGRESS INDICATION: A pointer in the dial knob rotates during the cycle, continuously showing the time remaining until time-out.
OPERATION
The 322 is a synchronous motor-driven timer with an electrically- operated clutch equipped either for On-Delay or Off-Delay operation.
ON-DELAY: When power is applied (start signal sustained on), the clutch engages, the motor begins to drive a cam toward its zero position, and the instantaneous switch transfers from one set of con- tacts to the other. At the end of the timed period, the cam trips one of the delayed switches, but the motor continues to run. A brief time later (about 2-1/2% to 5% of full scale), the cam trips the second delayed switch, stopping the motor but leaving the clutch engaged. The 322 resets when power is removed from the clutch.
OFF-DELAY: Timing begins when power is removed (start signal off) from the spring-loaded, normally-engaged clutch. The timer resets when power is restored to the clutch, thus disengaging it and transfer- ring the instantaneous switch from one set of contacts to the other. Action of the delayed contacts is the same as with the On-Delay timer. A power outage stops the motor but does not reset the Off-Delay 322; the timer completes the interrupted cycle when power is restored.
WIRING
E24305
Motor-Driven Cycle Progress Timer
SPECIFICATIONS
MODEL Choice of ON-Delay or OFF-Delay
operation (not field-convertible)
RANGES 11 standard ranges, from 5 SEC to 5 HRS at 60Hz (6 SEC to 6 HRS at 50 Hz)
RESET TIME 150 ms.
MIN. SETTING 5% of dial range.
LIFE MECHANICAL: 2,500,000 cycles (average) EXPECTANCY CONTACTS: 2,500,000 operations under
resistive or inductive load of 1A
TIMING SINGLE CYCLE: interval, delay or pulse. MODES
LOAD INSTANTANEOUS: one, SPDT, precision type. SWITCHES DELAYED: two, SPDT, precision type.
CONTACT RATINGS (non-inductive): 10 A at 120 VAC 5 A at 240V A C
TERMINALS 11-point terminal block on side of housing; all terminals accept .250" push-on connectors. Terminals 1, 2, 4, 9 and 11 are split connectors for use with either one .250" or two .110" push-on connectors.
POWER 120 or 240V, 50 or 60 Hz. (±10%, - 15%) REQUIREMENTS Running Current 121 mA (14.5 VA)
at 120V Inrush Current 157 mA (18.9 VA) at 120V
TEMPERATURE 32° to 120°F (0° to 50°C) RATING
WEIGHT NET: 1 lb. 8 oz SHIPPING: 2 lbs.
ELECTROMECHANICAL TIMER 322B Series
Automatic Timing & Controls
RANGE - 60HZ- 120 VAC
5 SEC 114 10 SEC 003 20 SEC 005 40 SEC 115 60 SEC 007 150 SEC 009 5 MIN 012 10 MIN 014 40 MIN 056 60 MIN 017 5 HR 113
RANGE - 50 HZ - 120 VAC 6 SEC 101
12 SEC 116 24 SEC 117 48 SEC 118 72 SEC 073 180 SEC 119 6 MIN 029 12 MIN 047 48 MIN 058 72 MIN 061 6 HR 030 Special 000
ELECTROMECHANICAL TIMER 322B Series
VOLTAGE FREQUENCY
120/60 A 240/60 B
120/50 C 240/50 D Special K
MODEL NUMBER
MODEL NUMBER 322B 2
RANGE
VOLTAGE & FREQUENCY
ARRANGEMENTS
ON-DELAY (reset on power interruption) 1 OFF-DELAY (non-reset on power interruption) 2 Special 0
SWITCH DIFFERENTIAL
2-1/2% - 5% of dial range 2
FEATURES
STANDARD surface mounting unit, clutch contact CS SPECIAL CK
DIMENSIONS (INCHES/MILLIMETERS)
ON DELAY
Timing Sequence**
SWITCH CONTACTS Before During End of Start Cycle Cycle *
Instantaneous 4-5
Delayed (D2) 11-7
Delayed (D1) 9-8
* D2 trips approximately 2-1/2% of range after end of cycle.
** Assumes a sustained closed start signal (i.e. longer than the dial set time).
OFF DELAY
Timing Sequence**
SWITCH CONTACTS Before During End of Start Cycle Cycle *
Instantaneous 4-5
Delayed (D2) 11-7
Delayed (D1) 9-8
* D2 trips approximately 2-1/2% to 5% of range after end of cycle.
** Assumes a sustained closed start signal (i.e. longer than the dial set time).
4-3
11-6
9-10
4-3
11-6
9-10
*
*
BLACK Circuit Closed
GRAY Circuit Open