
Features
Real time detect, transmit and control indoor air quality
3-color TFT screen display and warning indoor CO2, TVOC, temperature and
relative humidity
Four buttons for operation conveniently
Two power supply optional for different application
Provide up to 3 analogs + 1 relay outputs or 3 relays + 1 analog outputs
Optional Modbus RS485 interface, to connect PC, realize remote control
Specification
±50ppm + 3% reading or ±75ppm (whichever is greater)
<2% of FS over lifetime (15 years) of sensor
ABC Logic self-calibration
Lifetime of NDIR CO2 sensor
<2 minutes for 90% step change
2 hours (first time or using again after power off for a long time)
2 min (operation)
0~2000ppm (default)
0~5000ppm (selected in the advanced setup)
Japan Figaro semi-conductor mixed gas sensor
Temperature & Relative Humidity
Temperature sensor (selectable)
High precision digital integrated temperature and humidity sensor SHT,
or NTC thermistor
-20~60℃/-4~140F (default) 0~100%RH
Temp.: <±0.5℃@25℃ RH: <±3.0%RH (20%~80%RH)
Electrical Specification and Functions
3-color TFT screen, with 4 buttons for operation
Up to 3× analog + 1× relay outputs or 3× relay + 1× analog outputs
Analog: 0~10V or 4~20mA or PID
Relay: rated current: 5A, resistance load
CO2 Transmitter/Controller
Model: AT-VLX series

0~50℃; 0~95%RH, non-condensing
150mm(L)×90mm(W)×42mm(H)/280g
Wall type (65mm×65mm or 2”×4” wire box)
Mounting and Wire Connection
Notice the power supply of the monitor is 24VAC/VDC or 100~240VDC. Do not install the monitor on voltages higher
than marked on the monitor. Always turn off power before operating as follow steps.
Open the cover: push the both clips at the bottom of the unit, to remove the front cover from the back cover. Please
operate gently to avoid damaging of the clips.
Fix back cover: fix the back cover on the wall according to the dimension and position, see Fig. 1.
Connect wires: connect wires according to Fig.2 and press the wires under the terminals of back cover.
Close the cover: align the top clip of the unit firstly, then close the front cover and back cover by pressing the bottom
clips, to finish the installation.

TFT Display & Buttons
There are TFT screen and 4 buttons on the cover, they are SET, ▲, ▼, and .
Power: used to turn on/off the transmitter/controller by each pressing. Under turning off station, OFF
displays on the right bottom corner, and under this station, all outputs are ineffective.
TFT display: CO2, temperature and humidity measuring value display on first line, second line and bottom line
respectively. If the output is linear, when customer press any key among SET, ▲, and ▼, it will display “Linear”
to indicate, the keys are in-effective, see below Fig. 3. TFT 3-color screen is controlled by CO2 measuring value,
with below default setpoint. End user can adjust the setpoint via Advanced Setup parameter P8 & P9.
│ Green: CO2 < 800ppm │ Yellow: 800ppm ≤ CO2 < 1200ppm │ Red: CO2 ≥ 1200ppm │
SET button: be used to switch parameter items and PID/relay set points. The parameter item switches to next by
each pressing, and will switch quickly by continuous pressing.
▲ & ▼: be used to adjust the setpoint/target value. The setpoint/target value only changes one by each pressing,
and will switch quickly by continuous pressing.
Lock/Unlock the buttons: Please refer to Advanced Parameter P72.
Table 1 - DIPs setting
DIPs Setting
End user can enter Advanced Setup by adjusting DIP1=ON and return to normal suing by adjusting DIP1=OFF.
DIP2 is used to adjust analog 3, when DIP2= ON, analog 3 is for TVOC, when DIP2=OFF, analog is for RH. See
above Table1.
Analog Output Setting
The default analog output is PID before leaving factory, unless otherwise stated by customers. End user can reset the
analog output as linear by Advanced Setup P20 according to below table 2. Voltage output or current output can be
selected by connecting/disconnecting the jumpers, as shown on table 3 and Fig 4. End user also may get 2~10V or
4~20mA by adjusting parameters P22, P24, P26, P28, P30, P32, P34, P36 in Advanced Setup.
Table 2 – Analog linear/PID output instruction
Advanced
parameter
setting
P20 value

Table 3 - Voltage output or current output selection via jumpers
Upper jumpers connect DC1=0~10V
Upper jumpers connect DC2=0~10V
Upper jumpers connect DC3=0~10V
Lower jumpers connect DC1=0~20mA
Lower jumpers connect DC2=0~20mA
Lower jumpers connect DC3=0~20mA
voltage output
0-10V
current output
0-20mA
Relay Control Mode
End user may adjust CO2 relay 1 control mode by Advanced Setup P12 as instructed by below table 4, adjust
temperature relay 2 control mode by Advanced Setup P13 as instructed by table5, adjust humidity relay 3 control
mode (DIP2=OFF) by Advanced Setup P14 as instructed by table 6, adjust TVOC relay 3 control mode (DIP2=ON) by
Advanced Setup P15 as instructed by table 7.
Table 4 CO2 relay 1 control mode
Advanced parameter
P12 value
Auto control
ON1- decrease CO2
Auto control
ON1- increase CO2
Table 5 Temperature relay 2 control mode
Advanced parameter
P13 value
Table 6 Humidity relay 3 control mode (DIP2=OFF)
Advanced parameter
P14 value
Auto control
ON3- dehumidifying
Auto control
ON3- humidifying

Table 7 TVOC relay 3 control mode (DIP2=ON)
Advanced parameter
P15 value
Auto control
ON3- decrease TVOC
Auto control
ON3- increase TVOC
For example, End user may adjust the CO2 relay offset by Advanced Setup parameters P16. The relay 1 auto control
logic is as below instructed:
a. under decrease CO2 mode, when CO2 measuring > CO2 setpoint, relay 1 = ON, when CO2 measuring ≤ CO2
setpoint – CO2 offset, relay 1 = OFF
b. under increase CO2 mode, when CO2 measuring < CO2 setpoint, relay 1 = ON, when CO2 measuring ≥ CO2
setpoint + CO2 offset, relay 1 = OFF
c. under CO2 manual control-OFF, relay 2 = OFF
d. under CO2 manual control-ON, relay 2 = ON
Advanced Setup
After power off and remove the back cover, there is a set of DIPs on the middle part of PCB. Put the DIP1 to ON to
enter Advanced Setup interface, and put the DIP1 back to OFF, it will return back to normal using interface. Using SET
button to switch the parameter items from P1 to P75, and using ▲ & ▼ buttons to adjust the target values.
Wait 6 seconds for the new value to set!
Note: Please read the below parameters firstly, any of modification do not be recommended if not necessary.
4800 9600 14400 19200 38400 56000 57600 115200
RS485 parities and stops
choice
1-1stop bit None;2-2stop bit None;3-1stop bit ODD;
4-1stop bit EVEN
Humidity correction value
TVOC correction target value
CO2 green to yellow setpoint
CO2 yellow to red setpoint
TVOC green to yellow setpoint
TVOC yellow to red setpoint
CO2 offset for relay control
Temp offset for relay control
Humi offset for relay control
TVOC control relay offset
0.000 ~ 10.000V, configure current output by current
value/2
0.000 ~ 10.000V, configure current output by current

0.000 ~ 10.000, configure current output by current
value/2
0.000 ~ 10.000V, configure current output by current
value/2
0.000 ~ 10.000V, configure current output by current
value/2
0.000 ~ 10.000V, configure current output by current
value/2
0.000 ~ 10.000V, configure current output by current
value/2
0.000 ~ 10.000V, configure current output by current
value/2
0 ~ 100 % 0~10v/0~20mA percent
0 ~ 100 % 0~10v/0~20mA percent
0 ~ 100 % 0~10v/0~20mA percent
0 ~ 100 % 0~10V/0~20mA percent
1- Run CO2 control PID self-tuning
0- stop PID self-tuning
1- Run temp. control PID self-tuning
0- stop PID self-tuning
1- Run humi. control PID self-tuning
0- stop PID self-tuning

1- Run TVOC control PID self-tuning
0- stop PID self-tuning
1- turn off
2-turn on after power up again
3- hold the mode before the power failure
1- Degree Celsius; 2- Fahrenheit
1- ABC Logic ON;
2- ABC Logic OFF; (T67X3 only can set, cannot
read)
CO2 single-point calibration
target
0 ~ 5000ppm S8 does not support this command
CO2 single-point calibration
on/off
0- do not run single calibrate
1- start to run single calibrate
-500 ~ 500 (TVOC AD calibration value)
1- all buttons are usable; 2- ON/OFF button disable;
3- set, ▲,▼buttons disable; 4- all buttons disable
relay and analog output test
0- DC1 DC2 DC3 ON1 ON2 ON3 run normally
1- DC1=0V/0mA DC2=0V/0mA DC3=0V/0mA
ON1=OFF ON2=OFF ON3=OFF
2- DC1=2V/4mA DC2=2V/4mA DC3=2V/4mA
ON1=OFF ON2=OFF ON3=OFF
3- DC1=10V/20mA DC2=10V/20mA DC3=10V/20mA
ON1=ON ON2=ON ON3=ON
Modbus Parameters
Mode: RTU (MSB First)
Baud Rate: 9600,14400,19200,38400,56000,57600,76800,115200bps default: 9600
Start Bits: 1
Data Bits: 8
Stop Bits: 1 / 2 default : 1
Parity: None / Odd / Even default: None
Register Map Support Function: 3 4 6 16
Starting
Register
Decimal
Address
(Base 0)
Correspond
LCD
Parameter
0

DC1 0-10v
4-20mA
analog output
DC2 0-10v
4-20mA
analog output
DC3 0-10v
4-20mA
analog output
2-9600bps; 3-14400bps
4-19200bps; 5-38400bps
6-56000bps; 7-57600bps
8-76800bps; 9-115200bps
P-2 2 RS485 parities
and stops
choice
1-None 1Stop Bit;
2-None 2Stop Bit;
3-Odd 1Stop Bit;
4-Even 1Stop Bit
P-3 4 All button lock
choice
1- all buttons are usable
2- ON/OFF button disable
3- set, ▲,▼buttons disable
4- all buttons disable
TVOC adjust
target setpoint