Explanations of symbols and signs on the Control Tower display.
Operation indication
(in the first display position of technical read out)
0
No heat requirement
1
Ventilation phase
2
Ignition phase
3
Burner active on central heating
Burner active on hot water
4
Fan check
5
6
Burner off when room thermostat is demanding
Pump overrun phase for central heating
7
Pump overrun phase for hot water
8
9
Burner off because of too high flow water temperature
Automatic venting program
A
display
Central heatingon / off
Domestic hot water (DHW) on / off
Pump programon / off
From "Good" read-out to Technical read out (and vice versa):
- Press STEP key for 5 sec.
Step key Selecting chapters
Mode keySelecting chapters
Reset keyUnlocking the boiler
in case of error
Water pressure is to low (<0,7 bar), FILL
indication remains continuously visible,
the boiler is taken out of operation. The
installation needs to be topped up.
Water pressure is to low (<1,0 bar),
flashing FILL will alternate with indication
of water pressure, boiler power of 50% is
possible. The installation needs to be
Water pressure is to high (>2,8 bar), if
HIGH indication remains continuously
visible, the boiler is taken out of operation.
The installation pressure needs to be
decreased by draining water.
The appliance should only be installed by a Competent Gas Installer.
Work on the boiler must be carried out by a competent person, (Ref: Gas
Safety Installation and Use Regulations) using correctly calibrated
instruments with current test certification.
These instructions describe the functioning, installation, use and primary maintenance
of ATAG central heating boilers for the United Kingdom and Ireland. Where necessary the
different regulations for each country are separately described.
These instructions are intended for the use by Corgi registered installers or registered
Bord Gais installers in connection with the installation and putting into operation of ATAG
boilers. It is advisable to read these instructions thoroughly, well in advance of installation.
Separate instructions for use are supplied with the boiler for users of ATAG central heating
boilers. ATAG is not liable for the consequences of mistakes or shortcomings which have
found their way into the installation instructions or user’s manual. Further, ATAG
reserves the right to alter its products without prior notification.
When delivering the boiler, give the customer clear instructions concerning its
use; present the customer with the user’s manual and card.
Each boiler is fitted with an identification plate. Consult the details on this plate to verify
whether the boiler is compliant with its intended location, e.g.: gas type, power source
and exhaust classification.
On completion of the installation the installer or commissioning engineer must fill out and
complete the Benchmark commission section of the boiler log book and hand to customer
or end user for future record keeping. The Benchmark log book must also be filled out and
completed by the service agent following each service call, and returned to the customer.
A copy of the Benchmark commissioning certificate must be returned to ATAG Heating UK
Ltd along with the warranty registration card to register the appliance for the standard
warranty benefits
Relevant Installation, Service and User manuals:
-ATAG MonopassFlue system guide
-ATAG BrainQDigital room thermostat
-ATAG MadQCascade-/Zone controller
2Regulations
The following regulations apply to installation of ATAG central heating boilers:
Legislation and Regulations.
Gas Safety (Installation and Use). All gas appliances must by law, be installed by a
competent person, eg. Members of CORGI and in accordance with the current Gas Safety
Regulation. Failure to install appliance correctly could lead to prosecution.
In addition to the above regulations this appliance must be installed in compliance with the
current IEE Regulations, the Building Standards (Scotland Consolidation) Regulations.
Regulations and bye laws of the Local Water Authority and the Current Health and Safety
Regulation.
The current, Electricity at Work Regulation must be complied with and also be in
accordance with the relevant and current editions of the British Standards.
The ATAG E boiler is a certified appliance and must not be modified or installed in any
way contrary to this Installation Manual.
Manufacturers instructions must not be taken in any way as overriding statutory
obligations.
The ATAG E is a central heating boiler with an optional integrated hot water function.
These boilers must be connected according to these instructions and all installation
norms in respect of the part of the boiler to be connected.
Observe the following rules of safety:
-All work on the boiler must take place in a dry environment.
-ATAG boilers may never be in operation without their housing, except in connection
with maintenance or adjustments (see Chapter 13 and 14).
-Never allow electrical or electronic components to come into contact with water.
Carry out the following tasks in connection with maintenance, etc. to an already-
installed boiler:
-Shut down all programs
-Close the gas tap
-Remove the plug from the wall socket
-Close the stop cock of the boiler’s intake connection
Take note of the following when maintenance or adjustments are needed:
-The boiler must be able to function during these activities; for this reason, the boiler’s
supply voltage, gas pressure and water pressure must be maintained. Ensure that
there is not a source of potential danger during these activities.
Following maintenance or other activities; always check the installation of all
parts through which gas flows (using leak-search spray).
Following maintenance or other activities, always replace the housing and
secure it with the screw behind the door at the front of the casing.
The following (safety) symbols may be encountered in these installation instructions
and on the boiler:
This symbol indicates that the boiler must be stored away from frost.
This symbol indicates that the packaging and/or contents can be damaged as
a result of insufficient care taken during transport.
This symbol indicates that, whilst still in its packaging, the boiler must be
protected from weather conditions during transport and storage.
KEY-symbol. This symbol indicates that assembly or dismantling, must be
carried out.
ATTENTION symbol. This symbol indicates that extra attention must be paid
in connection with a particular operation.
The boiler is supplied ready for use. The supply kit is composed as follows:
•Boiler with casing;•Template;
•Automatic vent (inside the boiler);•Installation instructions
•Safety valve (inside the boiler);•Operating manual;
•Suspension bracket•Warranty card;
•Expansion vessel (inside the boiler)•Benchmark logbook.
•Fixing material consisting of plugs and
screws;
4Description of the boiler
Room sealed boiler
The boiler retrieves its
combustion air from the
outside then discharges
the flue gasses to the
outside.
Condensing
Retrieves heat from the
flue gasses. Water
condensates on the
heat exchanger.
Modulating
Higher or lower burning
according to the heat
demand.
Stainless Steel
Super solid kind of
steel which keeps its
quality for life. It will not
rust or erode in contrast to composition
materials, like aluminium.
The ATAG E boiler is a room sealed, condensing, modulating central heating boiler, with
or without an integrated hot water facility.
The boiler is provided with a compact stainless steel heat exchanger with smooth
tubes. A well thought out principal using durable materials.
The boiler burns gas for supplying warmth. The heat is transferred in the heat
exchanger to the water in the central heating system. By cooling down the flue gasses
condensate is formed. This results in high efficiency. The condensate, which has no
effect on the heat exchanger and the function of the boiler, is drained through an
internal siphon.
The boiler is provided with an intelligent control system (CMS Control Management
System). The boiler anticipates the heat demand of the central heating system or the hot
water facility.
When an outside sensor is connected, the boiler works weather dependantly. This
means that the boiler control measures the outside temperature and flow temperature.
With this data the boiler calculates the optimal flow temperature for the installation.
Explanation of the type indication:ATAG E 22C
E = Type
22 = Nominal load in kW
C = Combi (S = Solo)
The boiler has been tested according to valid CE* standards and has a CE* certificate
and SEDBUK A-rating.
Statement: No banned materials including asbestos, mercury, CFC's have or will not be
included in the product.
The room where the boiler will be placed must always be frost free. The boiler casing is
splash water tight (IPX4D) and is suitable to be installed in e.g. a bathroom.
It is NOT necessary to have a purpose provided air vent in the room or internal space in
which the boiler is installed. Neither is it necessary to ventilate a cupboard or
compartment in which the boiler is installed, due to the extremely low surface
temperature of the boiler casing during operation. Therefore the requirements of BS 6798,
Clause 12, and BS5440:2 may be disregarded.
The boiler can be mounted practically to any wall with the suspension bracket and the
enclosed fixing equipment. The wall must be flat and of sufficient strength in order to be able
to carry the boiler weight with its water content.
Above the boiler there must be at least 250 mm working space in order to be able to fit
a coaxial flue system or a twin supply. On the left side of the boiler at least 50 mm and
on the right side 10 mm must be reserved to allow fitting or removing of casing. The
location of the boiler can be determined by using the template.
Remove the casing of the boiler. The casing is also the airbox of the boiler and is secured
with a screw behind the door at the front. Also the four quick-release fasteners (2 at the
top and 2 at the bottom) should be secured with a screw.
First remove the screws before loosening the quick-release fasteners.
Tighten the screws again when replacing the housing.
Removing the casing figure 1
Lift the boiler only by the boilers rear wall.
Lifting and carrying precautions:
-Lift only a manageable weight, or ask for help.
-When lifting the boiler, bend the knees, and keep the back straight and feet apart.
-Do not lift and twist at the same time.
-Lift and carry the boiler close to the body.
-Wear protective clothing and gloves to protect from any sharp edges.
A height
B height with expansion vessel
C width
Ddepth
E left side / flue gas exhaust
F centre to centre / flue - airintake
G back / flue gas exhaust
H left side / gas pipe
J left side / flow pipe
K left side / return pipe
L left side / condensation pipe
N left side / cold water pipe
P left side / hot water pipe
Q pipe lenght of g*
R pipe lenght of c*
S pipe lenght of c and f;r; k and w *
T back / centre of pipe c;k and w*
U back / centre of pipe f;g and r*
mm 650650650650
mm--870870
mm 500500500500
mm 395395395395
mm 335335335335
mm 120120120120
mm 270270270270
mm 250250250250
mm 150150150150
mm 350350350350
mm 405405405405
mm285285
mm215215
mm1919215215
mm40404040
mm5050160160
mm26262626
mm50505050
dimensions table 1
type of unitE22SE22CE 32SE32C
air supply / flue gas system
gas pipe - g
central heating flow pipe - f
central heating return pipe - r
condensation discharge pipe - c
cold water pipe - k
hot water pipe - w
mm 60 / 100 60 / 100 60 / 100 60 / 100
½"
female½"female½"female½"female
22 mm 22 mm ¾" ext. ¾" ext.
22 mm 22 mm ¾" ext. ¾" ext.
22 mm 22 mm 22 mm 22 mm
These can be connected to the installation by means of compression fittings /
adapter fittings;
-The gas pipe.
It is provided with a female thread into which the tail piece of the gas valve can be
screwed;
-The condensation drain pipe.
It consists of a 22mm plastic pipe. The drain pipe can be connected to this by means
of an open connection. If the open connection is fitted in a different location, then the
pipe can be lengthened by means of a 32 mm PVC sleeve;
-The flue gas exhaust system and air supply system.
It consists of a concentric connection 60/100 mm.
-Cold and hot water pipes.Only Combi boilers: These consist of 15 mm copper pipe and can be connected
to the installation by means of compression fittings / adapter fittings.
It is recommended that isolation valves are fitted to all heating and hot water
connections to facilitate ease of future maintenance.
It is advisable to spray-clean all of the boiler’s connecting pipes and/or to
spray-clean/blow-clean the installation before connecting it to the boiler.
6.1Central heating system
Connect the central heating system according to the actual regulations.
The boiler pipes can be connected to the installation by means of compression fittings.
Reducers should be used for connecting to thick-walled pipe (welded or threaded).
When removing the plastic sealing caps from the pipes, contaminated testing
water may be released.
The boiler has a self-adjusting and self-protecting control system for the load. By this means
the temperature difference between the flow and return water is checked. Table 3 shows the
water displacement which supplies the circulation pump at certain installation resistance.
type of unit
E22S
E32S
E22C
E32C
Installation resistance table 3
Pump
type
UPS 20-5014,385628280
UP 20-6020.7124417170
UPS 20-5014,385627270
UP 20-6020.7124315150
wa ter flo w rate
'
'T 20°C
''
l/minl/hkPambar
permi ssi bl e
installation
resistance
If the installation resistance is higher than the stated value the load will be adjusted until
an acceptable temperature difference between flow and return water has been obtained.
If, after this, the temperature difference remains too much then the boiler will switch itself
off and wait until an acceptable temperature has been reached.
If an unacceptable temperature is detected, then the control will repeatedly try to achieve
water flow, and if this does not work then the boiler will switch off.
If the capacity of the boiler pump is insufficient, an extra external pump can be installed
in combination with a low velocity header in series with the boiler. The electrical side of
this external circulation pump can be connected in the Control Tower, by means of an
optional cable tree, which can be ordered seperately (art.nr. S4643900). The external
pump will switch at the same times as the boiler pump.
The maximum absorbed current consumption of the external circulation pump may be
230 W (1 Amp). The extra external pump must be selected according to the installation
resistance and the required flow.
H(m)
UP 20-60
E22S, E32C
UPS 20-50
E22C, E32S
Q(m³/h)
pump index lines graph 1
As standard the boiler is provided with a water filter in the return pipe of the boiler. With
this, possible contamination of the central heating water is prevented from ending up in
the boiler. The boiler is also provided with an internal safety valve set at 3 bar. This is
connected to the waste discharge together with the condensation discharge.
If all, or a large part of the radiators are provided with thermostatic radiator valves it is
advisable to use a pressure difference control (bypass) in order to prevent flow problems
in the installation.
The boiler is designed to be used on a sealed system only.
Additives in the installation water are only permitted in consultation with the
country distributor. ATAG Heating UK Ltd recommend the use of either
Fernox or Sentinel products.
All ATAG E-Series boilers are provided with an internal expansion vessel.
The vessel of the E22S and E22C is positioned inside the boiler casing. This expansion
vessel has a pre-charge pressure of 1 bar and a capacity of 8 litres.
The vessel of the E32S and E32C is positioned directly beneath the boiler and together
with the casing forms a single entity with the boiler.
The expansion vessel is located vertically behind the casing, which can be removed by
pulling forwards. The expansion vessel has a pre-charge pressure of 1 bar and a capacity
of 12 litres.
If a larger capacity expansion vessel is needed for the installation a standard expansion
vessel should be fitted additionally.
If the internal expansion vessel is not sufficient, choose an expansion vessel volume, of
which the summary is geared to the installation’s water capacity. The pre-charge pressure
depends on the installation height above the expansion vessel (Table 4). Fit the expansion
vessel into the return pipe as close as possible to the boiler.
When connecting or using an underfloor heating system, designed with plastic pipes, or
plastic pipes are used elsewhere in the installation,one should ensure that the plastic
pipes used comply with the DIN 4726/4729 standard. It is set out in this standard that
the pipes may not have oxygen permeability higher than 0.1 g/m³.d at 40°C. If the system
does not comply with this DIN standard, the underfloor heating component will have to
be separated from the central heating appliance by means of a plate exchanger.
No recourse can be made to the terms of the warranty in the event of failure
to observe the regulations pertaining to plastic underfloor heating pipes.
6.4Gas connection
The appliance pipe is fitted with an internal thread, into which the tail piece of the gas tap
can be screwed.
United Kingdom:
The gas supply must comply to the current Gas Safety, Installation & Use Regulations.
Ireland:
-Irish standard 813
-Domestic gas installations
The connection to the appliance must include a suitable method of disconnection and a
gas control cock must be installed adjacent to the appliance for isolation purposes. The
nominal inlet working gas pressure measured at the appliance should be 20 mbar for Nat
gas (G20).
Make sure that the gas pipe work does not contain dirt, particularly with new
pipes.
When the boiler has to be converted from natural gas to LPG, ATAG provides special
kits for this purpose. Special instructions are supplied with the kit.
Always check the installation of all of the parts through which gas flows
(using leak-search spray)
Connection of the drinking water installation should be done according to the national
water laws.
The ATAG E combination boilers are fitted with a stainless steel plate heat exchanger
for producing domestic hot water. The boiler does not have a hot water store and in case
of a demand for hot water the boiler will heat the domestic water flowing through the plate
heat exchanger up to 60°C instantaneous.
The water mains installation must comply with the British water regulations.
In regions with a water hardness value higher than 267ppm (2,67 mmol/l),
calcium deposits should be removed from the plate heat exchanger on a
regular basis. If problems occur when using sanitary water with a chlorine
content higher than 150 mg/l, no recourse can be made to the terms of the
warranty.
The hardness of the water is variable in Great Brittain and Ireland. The water company
can provide exact information about this.
The domestic water pipes can be connected to the installation by means of compression
fittings / adapter fittings. The cold water inlet on the Combi boilers must be provided with
the following (counted in the water flow direction):
-Dosing valve (supplied),
-Safety group,
-Expansion vessel 6bar (potable water, blue).
A dosing valve must be fitted in the cold water pipe. The dosing valve ensures that a
quantity of water is supplied which has a guaranteed outlet temperature of 60°C
(assuming a cold water temperature of 10°C). The quantity of water is virtually unaffected
by the water pressure.
With a water pressure lower than 1.5 bar it is advisable to remove the inside mechanism
of the dosing valve.
6.6Condensation drain pipe
ATAG boilers produce condensate. This condensate must be drained otherwise the
boiler will not function.
The common condensation drain pipe should be connected to the drain by means of an
tundish break connection. By this means the possibility of drain gases ending up in the
boiler is prevented. The drain connection should have a minimum diameter of 32mm.
Connect the condensation drain pipe according to the actual regulations.
The following components are connected to the collective condensation drain pipe:
-Condensation discharge;
-Safety valve;
Draining of the condensation water to the external rain guttering is not
permitted in view of the danger of freezing.
Before putting the boiler into operation fill the siphon with 300 ml of water.
The condensate pipe must be run using suitable corrosion resistant materials (eg.
plastic).
The appliance concentric connection diameter is 60/100 mm, to which the flue gas outlet
and air supply system can be fitted, with or without elbow pieces. The maximum
permissible pipe length is set out in Table 5.
It is also possible to use a parallel pipe connection of 2x 80mm. In this case the adapter
60/100 should be removed and a seperate 125mm cover should be ordered. Art.nr.
S4323410.
We suggest you design a simple flue gas system and air supply system using table 6.
For further information about the available components of the flue gas and air supply
system we recommend you consult the Monopass Flue system literature.
The ATAG flue gas system is meant and designed solely for the use on ATAG central
heating boilers adjusted to Nat gas or LPG. The maximum flue gas temperatures are
below 70°C (full load 80/60°C)
The proper operation can be influenced harmfully by changes of or adjustments to the
correct set up.
Possible warranty claims will not be honoured if incorrect changes result in non
compliance with the installation manual or local rules and regulations.
The flue gas systems described in this document are solely suited for ATAG central
heating boilers of the ATAG boiler range. For this purpose the CE Certificate has been
supplemented under the Gastec nr: 0063BR3405, 0063BQ3021, 0063AS3538 and
0063AU3110.
The flue gas system should be built up using only ATAG program products.
Combinations with other brands or systems are without written permission from ATAG
Heating is not permitted.
The terminal should be located where dispersal of combustion products is not unimpeded
and with due regard for the damage or discolouration that might occur to parts of the
building in the vicinity (see fig 9).
minimum
distance
mm300
mm75
mm200
mm200
mm75
mm300
mm300
mm600
mm1200
mm1200
mm1500
mm300
mm300
figure 9
terminal position for fan assisted boiler
directly below an open window or other opening
A
(e.g. air brick)
B below gutters, soil pipes or drain pipes
C below eaves
D below balconies or car port roof
E from vertical drain pipes and soil pipes
F from internal or external corners
G above ground or below balcony level
H from a surface facing a terminal
I from a terminal facing a terminal
from an opening in the car port (e.g. door
J
window) into dwelling
K vertically from a terminal on the same w all
L h oriz o ntally from a terminal on the same wall
In certain weather conditions condensation may also accumulate on the outside of the
air inlet pipe. Such conditions must be considered and where necessary insulation of the
inlet pipe may be required.
In cold and/or humid weather water vapour may condense on leaving the flue terminal.
The effect of such ‘plumeing’ must be considered.
The terminal must not be located in a place where it is likely to cause a nuisance.
For protection of combustibles, refer to IS 813 section 9.10.1. where the terminal is less
than 2m (6.6ft) above a pavement or platform to which people have access (including) any
balcony or flat roof. The terminal must be protected by a guard of durable material.
A suitable guard is available from the country distributor.
Where a terminal is fitted below a window which is hinged at the top, and
where the hinge axis is horizontal, and the window opens outwards, the
terminal shall be 1m below the bottom of the window opening.
If the boiler is to be located under stairs, a smoke alarm meeting the
requirements of I.S. 409 or equivalent must be fitted.
The flue must be terminated in a place not likely to cause a nuisance.
For horizontal sections, the outlet system should always be fitted on an incline (50 mm/
m) sloping down towards the appliance so that no condensation water is able to
accumulate in the outlet system. The chances of icicles forming on the roof outlet is
minimised by causing the condensation water to run back towards the appliance. In the
case of horizontal outlets the inlet system should be fitted on an incline sloping down
towards the outside to prevent rainwater from coming in.
The appliance produces a white wisp of condensation (plumeing). This wisp of
condensation is harmless, but can be unattractive, particularly in the case of outlets in
outside walls.
At this time there are 2 different ways of connecting the flue gas/air intake system. The
flue gas duct for the 60/100, 80/125 and 100/150 are push fit connections, see figure 10.
The air intake for the 60/100 is a clamp ring connection.
These two types are not interchangeable.
Cutting the pipe goes as follows:
-Take out the inner tube by turning it until it releases from its security position;
-Cut just as much from the air intake part as from the flue gas part;
-Take off the burrs from the cutting edge to prevent cutting the seals;
-Click the pipes back together again.
Use special grease to simplify the fitting
When mounting the flue gas system, pay attention to the flow direction. An arrow on the
product points this out. It is not permitted to mount a system upside down and will lead
to complaints.
6.7.1Dimensioning of the flue gas and air intake duct
A
Example:
A 22kW with a
concentric flue gas system
ø60/100mm has according
to the table a maximum flue
straight length of 12m In the
system that is going to be
put in there are 2 x 45°
bends, so the maximum flue
gas length is
12 – ( 2 x -1 ) = 10 meters.
The flue diameter is determined by the total length of the run, including for the connection
pipe, elbows fittings and terminal covers etc and the type and number of boilers installed
into the system.
An undersized flue pipe can lead to disorders. Look at table 1 for the choice of the system
and the correct diameter. The table below shows the maximum flue lengths with the
different boiler outputs. A longer flue gas length can be achieved by increasing the
diameter to ø 100mm.
Explanation table 1:
Two pipe flue gas system:maximum noted length = distance between boiler and
roof terminal A
Concentric flue gas system: maximum noted length = distance between boiler and
roof terminal B
When using bends the noted value behind every bend should be deducted from the
maximum straight length.
Two pipe flue system + chimney lining
ø80mm
E22SMaximum straight lenth 8030
E22C87° bend resistance length -1,5
45° bend resistance length -0,8
E32SMaximum straight lenth 8024
E32C87° bend resistance length -1,5
45° bend resistance length -0,8
in m
Concentric flue system
B
ø60/100mm
E22SMaximum straight lenth 60/10012 Maximum straight lenth 80/12530
E22C87° bend resistance length -1 87° bend resistance length 6
45° bend resistance length -1 45° bend resistance length -2,8
E32SMaximum straight lenth 60/1008 Maximum straight lenth 80/12524
E32C87° bend resistance length -1 87° bend resistance length 0
45° bend resistance length -1 45° bend resistance length 0
Dimensions flue gas system and air supply system Table 5
Depending of the comfort preferences different external hot water cylinders can be
connected to the boiler. The choice of the cylinder depends on the coil output. The coil
output must comply with the boiler output.
The E-Series are provided with an internal DHW control. The electrical connection can
be made on the connection terminal in the Control Tower. See the wiring diagram on page
19 and 20.
The appliance complies with the CE Machinery Directive 89/392/EEC. The EC Low Voltage
Directive 72/23/EEC and the EC EMC Directive 89/336/EEC.
A 230V -50Hz mains electrical supply is required fused externally at 5A.
The installation must continue to comply with:
United Kingdom:
-the national rules for electrical installations.
Ireland:
-the ECTI national rules for electrical installations
The appliance must be connected to an earthed socket. this must be visible and within
reach.
The following general stipulations also apply:
-No changes may be made to the wiring of the appliance;
-All connections should be designed in accordance with the enclosed regulations.;
-Should it be necessary to change it, the mains power supply cable may only be
replaced with an ATAG mains power supply cable (item No. S4477300).
The ATAG room thermostat and controls must be connected to their allocated
connections. All other types or makes of room thermostats or controls which are
used must have a Volt free contact.
When using an on/off thermostat or control, it is possible that an anticipating resistance
must be installed in order to prevent too high temperature fluctuations. As a standard
rule this means mercury thermostats. This resistance wire can be ordered by your
supplier and must be connected to clamps 23 and 27. The anticipating resistance in the
room thermostat has to be set at 0.11 A.
For more detailed questions regarding the components which are not supplied, the
country distributor should be contacted.
The boiler is provided with a fully automatic microprocessor control, called CMS
Control Management System. This system simplifies operation by undertaking all major
control functions. Initially when power to the boiler is switched on it will remain on
standby. There is no indication Led on, untill one of the programme keys is pressed. The
control panel display will show the relevant state. When the installation is empty the
display will show FILL.
The various parameters can be called up in two ways:
The Good-state or standard read out
The first way shows a simple display read out.
The boiler in operation will always show 'Good'. When a message is necessary this will
be shown instead of Good.
Technical read out
The second way is a technical read out. In normal situations the following will be shown:
•on the left the status in which the boiler is active;
•on the right the flow temperature;
•the water pressure in the installation.
When a message (error or blocking code) is necessary this will be shown instead of
the technical read out..
To switch over from the Good-state to the Technical read out (and vice versa):
- Press the STEP-key for 5 sec.
When the system has been filled the automatic venting program starts, when a program has
been selected, by pressing the key for Central Heating, DHW or pump program (,
of ). The program takes 17 minutes and stops automatically. After this the boiler will
function normally. (See also 'Filling and venting the boiler and installation).
During this 17 minute program, the boiler will not operate for Central Heating or DHW. The
display will show A and the boilers current flow temperature.
On a call for heating or hot water the control system will select the required water control
temperature. This water temperature is called the T-set value. On a call for central heating
the boiler ignites first at low output. The output is then changed slowly to match the load
required. The boiler operates in this way to avoid excessive installation noises and
temperature overshoot. On a call for hot water supply the T-set value of central heating return
water temperature is monitored. Depending on the amount of sanitary water which is
withdrawn from the plate heat exchanger, the central heating return water temperature,
from which the input is adjusted, will vary.
-Central Heating program key.
Switching the Central Heating on or off (Led on/off);
- Hot Water program key.
Switching the Domestig Hot Water (DHW) facility on or off (Led on/off);
-PC program key.
adjusts the pump to continuous water circulation in the central heating system (Led
on), or according to the pump overrun times on the relevant programs (Led off);
When the pump is
switched on continuously
it can lead to undesired
heating up of the central
heating system during
the summer.
•Mode-key.
After briefly pressing, a selection of the data chapters can be retrieved.
After pressing for 5 seconds it is possible to enter the code as described in chapter
11.3;
•Step-key.
After briefly pressing, the water pressure can be retrieved and pages per chapter
can be retrieved.
After pressing for 5 seconds it switches from the Good-state to technical read out
and vice versa;
•Reset-key.
After briefly pressing, for:
- unlocking errors;
- ending the access code;
After pressing for 5 seconds an operating stop is made, for example, for activating
the automatic venting program.
Some keys have other functions.These functions are only active when according to the
procedure described in chapter 11.3, adjustment has to be changed or data must be
retreived from the CMS.
The other functions are:
- Central Heating program key :+ function;
- Hot Water program key:- function;
- PC program key : store-function, which means that by means
The central heating installation needs to be filled with potable water. For filling or
topping up the installation you use the filling loop according to the following procedure:
1 Switch on the power supply;
2 The diplay will show FILL;
3 All functions off (heating, DHW and pump);
4 Push briefly the 'STEP'-button: P x.x = water pressure in bar;
5 Open the filling loop (Indication on display increases);
6 Fill up slowly to 1.5 to 1.7 bar;
7 STOP appears on the display;
8 Close the filling loop;
9 De-aerate the complete installation, start at the lowest point;
10 Check the water pressure and if necessary top it up;
11 Close the filling loop;
12 Activate the functions in use (heating , DHW and/or pump );
13 If A xx appears on the display, wait for 17 minutes;
1 4 Check the water pressure and if necessary top it up to 1,5 to 1,7 bar
15 Close the filling loop;
16 Press the ‘STEP’-button;
17 Be sure that the filling loop is closed.
1 8 After the automatic de-aeration program (A xx) is finished the boiler will return to
the Good state or Technical read out.
Check the water pressure regularly and top up the installation when necessary.
The working pressure of the installation should be between 1.5 and 1.7 bar when the
installation is cold.
It can take a while before all air has disappeared from a filled installation.
Especially in the first week noises may be heard which indicate the presence
of air. The automatic air vent in the boiler will make this air disappear, which
means the water pressure can reduce during this period and therefore topping up with water will have to be done.
10.1Hot water supply
Apply the water pressure to the DHW(open main valve and/or stop valve of the safety
group).
Vent the DHW facility and the hot water installation by opening a hot water tap. Leave
the tap open for as long as required until all air has disappeared from the DHW installation
and only water is flowing from the tap.
Before the boiler is fired, ensure that the boiler and the system are well vented and free
of air. Purge the gas line between the gas meter and the boiler and carry out a gas
soundness test as specified in the current Gas Safety, Installation & Use Regulations.
The boiler does not require adjustment of the burner pressure and air quantity because
it is self adjusting and is factory set at the correct value.
11.1Central Heating system
Provided there is a heat requirement from the thermostat or control, the central heating
program will be put into operation by means of the key (central heating program).
The circulation pump will start circulating and the boiler will start the burner.
11.2Hot water supply
Provided there is a heat requirement from the cylinder the hot water program will be put
into operation by means of the key (hot water program).
When the boiler is installed it is in principal ready for use. All adjustments of the boiler
control are already pre-programmed for a heating system with radiators/convectors
with a flow temperature of 85°C. The adjustments are described in the Parameter
chapter on page 28.
In certain cases adjustment have to be altered in case of :
-Lower flow temperature
Read through the Parameter chapter to adjust the boiler to its installation.
Contact ATAG Heating in case of doubt.
Please follow next procudere to alter adjustments:
Altering adjustments
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
Press the Mode-key for 5 secondss.
The display shows COdE followed by an arbitrary number;
Press by means of the + or the - key until the code C123 is shown;
Press the STORE-key to confirm the code (code blinks1 x).
Now you have acces to the installer level. There are 4 chapters:
•PARAParameters
•INFOInformation chapter (no adjustments possible)
•SERVService chapter
•ERROError-chapter (no adjustments possible)
The content of the chapters is described on the following pages.
Press briefly the MODE-key to select one of the 4 chapters, i.e. PARA;
Press once or more briefly on the STEP-key to select a Parameter
(parameter visible on the left, value on the right) ;
STEP 6
STEP 7
STEP 8
Alter the value, if necessary/possible, by means of the + or the - key
Press briefly on the STORE-key to confirm the alteration.
When you have to change more values, repeat from step 5.
Press once or more on the MODE-key until StBY or Good is shown:
After a few seconds the text StBY will be replaced by the technical read-out
or Good-state (Depending from the position the acces code is keyed in)
When you want to return from an arbitrary position to the original read out
press once or more on the MODE-key until StBY is shown.
When during 20 minutes no single key is used the display will return automatically to
its original read-out (Good state or technical read out)
185°Cmaximum flow temperature CH20 - 90°C
2*01type of CH installation:
3max.maximum power CH in kWmin-max
4*00control principal with on / off thermostat:
5*2.3heating line K-factor (see also heating line graph)0.2 - 3.5
6*1.4heating line exponent (see also heating line graph)1.1 - 1.4
7*-10heating line climate zone (see also heating line graph)-20 - 0
10*0°Cfine adjustment heating line day temperature-5 until 5°C
11*0°Cfine adjustment heating line night temperature-5 until 5°C
147gradient speed0 - 15
15*0booster after night reduction:
23-3°Cfrost safety temperature-20 until 10°C
3163°Cswitch-off temperature of additional cylinder with E boiler40 - 80°C
360type of three-way valve
43max.maximum power DHW in kWmin-max
450Not applicable00 - 01
8900address setting interface:
FactoryDescriptionRange
radiators; air heating; convectors:
T max. flow 85°C; K factor heating line 2.3; gradient 5°C/min; gear differential 6°C
radiators with large surface areas or underfloor heating as additional heating:
T max. flow 70°C; K factor heating line 1.8; gradient 5°C/min; gear differential 5°C
under floor heating with radiators as additional heating:
T max. flow 60°C; K factor heating line 1.5; gradient 4°C/min; gear differential 4°C
full under floor heating:
T max. flow 50°C; K factor heating line 1.0; gradient 3°C/min; gear differential 3°C
01
02
03
04
100 % on / off thermostat00
100 % on / off weather dependant01
Spare-01
ATAG Bus thermostat (BrainQ, Smart)00
boiler 1 - 8 in cascade00 - 07
Information chapter
INFOValueDescription
1°Cflow water temperature T1
4°Creturn water temperature T2
5°CDHW temperature T3
7°Coutside temperature T4
8°Cflue gas temperature T5
16%actual power in %
17kWactual power in kW
18kWactual load in kW
20indication bus communication
21GJconsumption total in GJ (.. x 33 = .. m3)
22GJconsumption CH in GJ (.. x 33 = .. m3)
23GJconsumption DHW in GJ (.. x 33 = .. m3)
24hourtotal number of burner run hours
25hournumber of burner run hours CH
26hournumber of burner run hours DHW
32hourtotal number of hours counter
37hourtotal number of run hours pump CH and DHW
46hourwithin how many hours is service required
1OFFboiler in operation with burner function onOFF - max.
2OFFfan adjustable and burner offOFF - max.
3OFFpump adjustable with burner onOFF - max.
4OFFshowroom position ON = active and OFF = non activeON - OFF
ValueDescriptionRange
Error chapter
ERROValueDescription
Err.L - Err.5Last saved error until 5 last predecessing errors
1error code
2operation status boiler
3°Cflow water temperature T1
4°Creturn water temperature T2
5kWload
6%pump capacity
Parameter-, Info-, Service- and Error-chaptersTable 6
* Most of the data in this table can be requested by the BrainQ. Most of the adjustments which are stated
in this table are unnecessary when in combination with the ATAG BrainQ thermostat and will be taken care
of by the BrainQ itself and do not have to be adjusted. For further information regarding to the BrainQ
thermostat, please refer to the ATAG BrainQ installation manual.
flow water temperature in °C
outside temperature in °C
heating line adjustments Parameter Step 6 and 7graph 2
In some situations it may be that the entire boiler must be switched off. By switching
off the three keys with the lamps for central heating, hot water and pump program ( ,
or ), the boiler is switched off. Leave the plug in the wall socket, which means
the circulation pump and the three-way valve are activated once every 24 hours in order
to prevent jamming.
In the event of frost danger it is advisable to drain the boiler and/or the
installation.
13Commissioning
Work on the boiler must be carried out by a competent person, (Ref: Gas
Safety, Installation & Use Regulations ) using correctly calibrated instruments
with current test certification.
To commission the boiler the casing has to be removed.
Remove the lower part of the casing which covers the expansion vessel (if present)
forward. The casing is fixed by 4 quick release clamps and 5 screws (4x 1 clamp and 1
behind door). After removing the screws, unlock the clamps, now the casing can be
removed forward.
The boiler settings, such as burner pressure and adjustment of the air quantity are
unnecessary, due to the fact that the boiler operates with a so-called zero pressure
control. This means the correct gas quantity is controlled by the suction operation of the
fan. The fine adjustment which is carried out at the factory is one off, which means that
adjusting of these values is unnecessary. Only when replacing the gas valve, venturi and/
or the fan, does the zero pressure and the incorrect CO2 adjustment have to be checked
and, if necessary, adjusted to the correct value.
Always check the installation of all parts through which gas flows (using
leak-search spray)
13.1Checking for contamination
In order to be able to check the boiler for contamination in the following running years
it is advisable to measure the maximum air displacement in the boiler when putting the
boiler into operation. This value can be different with each type of boiler.
In order to be able to measure this value follow the next procedure:
-Press the Central Heating and DHW buttons once to ensure that the boiler is OFF
and not firing.
-The diplay will show COdE followed by an arbitrary number;
-Select by means of the + or the - key the code C123;
-Press the Store-key to confirm the code (code blinks 1 x);
-Press the MODE-key until SERV is shown;
28
-Press the STEP-key until 2 is shown;
alternately 2 and OFF will be shown.
-Undo the upper measuring nipple on the gas valve open (fig. 12);
-Connect the hose of the digital pressure gauge to the upper measuring nipple of the
gas valve
-Press the + key until the maximum value is achieved;
The fan will function to its maximum revolutions (burner stays off)
-Measure the under pressure and write down this value.
At the next commissioning visit this value may drop 20% of its original value on the
moment of intallation. When this value is dropped more than 20% the boiler needs
maintanance.
-Press the - key until OFF is shown (keep key pressed)
With this the procedure is finished.
13.2Checking of the zero pressure control
The zero pressure control is set at the factory. To measure this value you need a
difference pressure gauge with a range of +0,2 to -0,8 mbar. Follow the next
procedure:
Check point contamination
figure 13
-Turn the boiler on so that the boiler is alight.
-Press the MODE-key for 5 seconds.
-The diplay will show COdE followed by an arbitrary number;
-Select by means of the + or the - key the code C123;
-Press the Store-key to confirm the code (code blinks 1 x);
-Press the MODE-key until SERV is shown;
-Press the STEP-key once until 1 is shown;
alternately 1 and OFF will be shown.
-Undo the upper measuring nipple on the gas valve open (fig. 13);
-Connect the hose of the digital pressure gauge to the upper measuring nipple of the
gas valve
-Press the - key until the minimum value is achieved;
The fan will function to its minimum revolutions (burner is active)
-Measure the negative pressure. Value should be +/- 0 to -4Pa (+/- 0 to -0,04 mbar).
Adjustment zero pressure
figure 14
-If the zero pressure deviates too much:
-Remove black cover of the gas valve
-Remove cap with Torx key (fig. 14)
-Turn slightly the Torx screw behind the cap:
Turn left is positive pressure deviation
Turn right is negative pressure deviation
-Ending this procedure is done by pressing the Reset key.
-Proceed by checking the CO2 value and correct it if necessary.
The CO2 percentage is factory-set. This has to be checked at commissioning,
maintance and faults.
This can be checked by means of the following procedure:
-Remove the black cover of the gas valve by unscrewing the sealed screw.
-Put the boiler into operation and take care that it can deliver its heat;
Tip: If there is no demand for heat on CH, turn the hot water tap completely open and
measure the CO
-Press the MODE-key for 5 seconds.
-The diplay will show COdE followed by an arbitrary number;
-Select by means of the + or the - key the code C123;
-Press the Store-key to confirm the code (code blinks 1 x);
-Press the MODE-key until SERV is shown;
2
.
2
checkpoint CO
adjustment screw CO
figure 16
2
figure 15
2
-Press the STEP-key once until 1 is shown;
alternately 1 and OFF will be shown.
-Calibrate the CO2 meter ;
-Place the lance of the CO2 meter into the check point (see fig. 15);
-Press the + key until the maximum value (in kW) is achieved;
The boiler will burn on full load (value on display in kW)
-Check Table 7 for the correct CO2 percentage (page 33)
-Let the CO2 meter do its measuring procedure.
-Adjust, if necessary, the adjustment screw to correct the CO2 value ( see fig. 16).
Ending the CO2 measuring procedure:
-Press the - key until OFF is shown (keep key pressed).
With this the procedure has ended..
-Replace the black cover on the gas valve and fix it with the screw.
Maintenance or changes to the boiler may only be carried out by an authorised
technician.
14.1The frequency of maintenance
We advise that an inspection is carried out every year with an overhaul every three years.
When doing this the circumstances of the boiler’s location must be taken into account.
From this one can determine whether to deviate from this advice.
Please contact the country distributor for further guidance on the frequency and
service requirements.
14.2Maintenance activities
To carry out the maintenance activities please follow the next procedure:
-switch off the power supply;
-remove the four screws out of the quick release fasteners;
-remove the screw behind the door on the front of the casing;
-remove the casing towards the front.
The air box
-the casing is also the airbox
-clean the casing with a cloth with a simple (non-abrasive) cleaning agent;
The fan unit and burner cassette
-remove the electrical connection plug from the gas valve and fan motor;
-loosen the nut of the gas pipe under the gas valve;
-replace the gasket with a new one;
-loosen the front cross head screw of the black plastic silencer;
-after this turn the two clamping rods ¼ turn and remove them by pulling them forward.
Note the right turning direction (red indicator);
-slightly lift the fan unit and remove it towards the front of the heat exchanger;
-remove the burner cassette out of the fan unit;
-check the burner cassette for wear, pollution and possible cracks. Clean the burner
cassette with a soft brush and vacuum cleaner. If burners are cracked replace the
complete burner cassette;
-replace the gaskets between burner and fan unit and the gasket between fan unit and
heat exchanger;
-check the venturi and the gas-air distribution plate for pollution and clean this part, if
necessary with a soft brush and vacuum cleaner. If the air box contains a lot of dirt
it is plausible that the fan itself is dirty as well. To clean this, the fan has to be removed
from the hood and the venturi. Clean the fan with a soft brush and a vacuum cleaner.
Replace the gasket and ensure that all gaskets of the fan parts are mounted correctly.
Heat exchanger
-check the heat exchanger for contamination. Clean this if necessary with a soft brush
and a vacuum cleaner. Prevent dirt falling down into the heat exchanger.
Flushing the heat exchanger from the top down is not permitted
Refitting of the components is done in reverse order.
Make sure that during refitting the clamping rods they are put in the right
position. They should be turned vertical.
Ignition electrode
The replacement of the electrode is only necessary when the electrode is worn off. This
can be checked by measuring the ionisation current. The minimum ionisation current has
to be higher the 4µA on full load.
If the viewing glass is damaged the complete electrode must be replaced.
Replacement goes as follows:
-remove the electrical connections of the electrode;
-press the clips on both sides of the electrode to both sides and remove the complete
electrode;
-remove and replace the gasket;
Refitting of the components is done in reverse order.
Siphon and condensate tray
-first remove the condensate cup;
Check this for pollution. If there is no sign of strong pollution it is not necessary to clean
the condense tray. If there is a strong pollution in the cup it is necessary to remove
and clean the condensate tray;
-check the O-rings of the cup as well as those from the pipe and replace if necessary;
-clean both part by flushing it with clean water;
-grease the O-rings again with acid free O-ring grease to make fitting easier;
-if there is a leak at the siphon cup or tray the complete siphon unit has to be replaced
by S4421200;
-remove the plug from the flue gas sensor if present;
-turn the two short clamping rods ¼ turn and remove them by pulling them forward; Note
the right turning direction (red indicator);
-lift the flue gas pipe out of the condensate tray;
-press the condensate tray carefully downwards and remove it by pulling it forward;
-replace the gasket between condensate tray and heat exchanger by a new one;
-clean the condensate tray with water and a hard brush;
-check the condensate tray for leaks.
Refitting is done in reverse order.
Note thate the gasket of the condensate tray seals completely.
Make sure that during refitting of the clamping rods they are put in the right
position. They should be turned vertically.
Alway replace all removed gaskets of dismantled parts during the
maintenance activities.
Put the boiler into
operation and check
the CO2 (see page 30).
Replace the secure
screws A, B, C, D
and E in the quickrelease fasteners
after the
maintenance
activities.
For warranty conditions we refer to the warranty card supplied with the boiler.
32
15Technical specifications
ATAG E-Serie
CombiSolo
Boiler typeE22CE32CE22SE32S
Input Hs CHkW22322232
Q
Output Hi CH
n
Input Hs DHW
Q
nw
Efficiency class according BED
Efficiency according EN677
(36/30°C part load, Hi)
Efficiency according EN677
(80/60°C full load, Hi)
Modulation range CH
(capacity 80/60°C)
Modulation range CH
(capacity 50/30°C)
Nox class EN483
CO
2
Temperature class for PP flue
Appliance type
Flue gas temp. CH
(80/60°C on full load)
Flue gas temp. CH
(50/30°C on low load)
Categories
Gas consumption G20 CH (DHW)
(at 1013 mbar/15°C)
Electr. power consumption max.W
Electr. power consumption stand byW
CurrentV/Hz
Fuse ratingA
Degree of protection acc. EN 60529
Weight (empty)kg39403740
Widthmm
Heightmm
Depthmm
Water content CHl3,553,55
Water content DHWl0,50,7
After run time pump CHmin
After run time pump DHWmin11
P
Water pressure min./max.
MS
Water pressure DHW max.
P
MW
Flow temperature max.°C
Pump typeUPS20-50UP20-60UPS20-50UP20-60
Available pump height CHkPa28172715
Label
DHW flow (at 38°C)l/min10,717,5
DHW flow (at 35°C 'T)l/min8,614,0
A detected error is indicated on the display by means of a blocking or error messages.
A distinction should be made between these two messages due to the fact that blocking
can be of a temporary nature, however, error messages are fixed lockings. The control
will try its utmost to prevent locking and will temporarily switch off the boiler by blocking
it. Below is a list of some of the messages.
Blocks with a number in the last 2 positions.
Block 60:
Incorrect parameter setting of the minimum or maximum power.
Block 67:
A 'T has been detected between flow and return sensor whereas the burner is not in operation. After
the 'T has disappeared the block will disappear.
Block 80:
Maximum flue gas temperature has been exceeded (if present). The block will not be cancelled until
the flue gas temperature has lowered to a correct figure.
Block 81:
The flue gas sensor is not connected although it was connected to the control. The burner is blocked
until the flue gas sensor is reconnected.
Block 82:
The flue gas sensor has short-circuited, heat requirement blocked and pump capacity at minimum.
Block 85:
The control has not detected a water flow. The venting cycle is started. If during this cycle water
flow is detected, the venting cycle is ended and the burner is released.
Block 86:
The frequence of the power supply deviates more than 2,5Hz (<47,5Hz, >52,5Hz)
Error with a number in the last two positions.
Error 00:Poor flame-forming
Error 01:short-circuit of 24 volt circuit
Error 02:no flame-forming
Error 04:the control unit has detected an error
Error 05:fault control unit
Error 12:fuse 24 volt/3AT faulty
Error 19:fault control
Error 28:number of revolutions not reported back from fan
Hereby declares ATAG V erwarming Nederland BV that,
the condensing boiler types: A T AG
E22SE22C
E32SE32C
are in conformity with the provisions of the following EC Directives, including all amendments, and
with national legislation implementing these directives:
DirectiveUsed standards
Gas Appliance Directive90/396/EECEN483: 1999
EN50165: 1997
Efficiency Directive92/42/EECEN677: 1998
Low V oltage Directive73/23/EECEN50165: 1997
ATAG Heating UK Ltd. • Unit 3 • Beaver Trade Park • Quarry Lane Chichester West Sussex PO19 8NY
Phone: 01243 815 770 • Fax 01243 839 596 • E-mail: info@atagheating.co.uk • Internet: www.atagheating.co.uk
Ditributor for Ireland
Total Energy Management Ltd. • Unit 9 • Ballybritt Industrial Estate • Monivea Road Galway Ireland
Phone: 091 769174 • Fax 091 769485 • E-mail: info@tem.ie • Internet: www.tem.ie
E. & O. E.
This renewed publication cancels all previous installation instructions. The company reserves the right to change the specifications and dimensions without prior notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.