Astria fireplaces GEMINICD40DEN, GEMINI40DEN, GEMINICD35DEN, GEMINI45DEP, GEMINI45DMP User Manual

...
Installation and Operation Instructions
CUS
P900285-01
Gemini™ Direct-Vent Gas Fireplaces
P/N 900285-01 REV. H 01/2017
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 900285-03.
Report No. F13-094
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
Models
Gemini33TMN Gemini33TMP
Gemini33TEN Gemini33TEP
Gemini33RMN Gemini33RMP
Gemini33REN Gemini33REP
GeminiCD35DEN
Gemini35DMN Gemini35DMP
Gemini35DEN Gemini35DEP
Gemini40DMN Gemini40DMP
Gemini40DEN Gemini40DEP
GeminiCD40DEN
Installateur : Laissez cette notice avec l’appareil. Consommateur : Conservez cette notice pour consultation ultérieure.
Gemini45DMN Gemini45DMP
Gemini45DEN Gemini45DEP
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil peut installé dans une maison préfabriquée (mobile) déjà installée à demeure, si les réglements locaux le permettent. Ce appareil doit être utilisé uniquement avec le type de gaz indiqué sure la plaque signalétique. Cet appareil ne peut être converti à d’autres gaz, sauf si une trousse de conversion est utilsée.
WARNING:
FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• If you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
AVERTISSEMENT: RISQUED’INDENDIE OU D’EXPLOSION
Le non-respect Des avertissements de sécurité pourrait d’entraîner des blessures graves, la mort ou des dommages matériels.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des téléphones se trouvant dans le bâtiment où vous trouvez.
• Sortez immédiatement de bâtiment.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
SAFETY AND YOUR FIREPLACE
See attached color flyer for proper color representation
General Information
900285-01 01/2017
DANGER
A barrier designed to reduce the risk of burns from the hot viewing glass is pro­vided with this appliance and shall be installed for the protection of children and other at-risk individuals.
Voir ci-joint tract pour une bonne représentation de la couleur
DANGER
L’écran pare-étincelles fourni avec ce foyer réduit le risque de brûlure en cas de contact accidentel avec la vitre chaude et doit être installé pour la protection Des enfants et Des personnes à risques.
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
VITRE CHAUDE
RISQUE DE BRÛLURES.
NE TOUCHEZ PAS UNE VITRE
NON REFROIDIE.
NE LAISSEZ JAMAIS UN ENFANT
DE TOUCHER LA VITRE.
Vea el volante adjunto para la representación de color adecuado
PELIGRO
CAUSARÁ QUEMADURAS.
TOCAR EL VIDRIO CALIENTE.
LOS NIÑOS DEBEN NUNCA
Una barrera diseñada para reducir el riesgo de quemaduras desde la mirilla (vidrio) caliente es proveida con este aparato y deberá instalarse para la protección de los niños y otros individuos en riesgo.
2
EL VIDRIO CALIENTE
USTED DEBE NUNCA
TOCAR EL VIDRIO.
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
General Information
900285-01 01/2017
Safety and Your
Fireplace
All parts of your
IHP fireplace get
EXTREMELY HOT!
To prevent severe burns
and injuries, do Not remove the barrier on the appliance which prevents direct contact with the glass.
Follow the safety instructions below
and be sure everyone in your household understands this burn hazard:
• The surfaces on your fireplace get EXTREMELY HOT!
• The glass on the front of the fireplace reaches EXTREMELY HIGH temperatures and can cause severe burns if touched.
• Keep children away from an operating fireplace. Closely supervise children in any room where a fireplace is operating to prevent contact with glass.
• Keep clothing, furniture, gasoline, and other flammable liquids away from the fireplace.
• Even after the gas is turned off, fireplace surfaces remain extremely hot.
Be sure to attach the enclosed Safety-
in-Operation Warnings where you
turn on your fireplace, to help remind everyone of the dangers associated with high temperatures
Read Important Safety Information
(Page 5)
.
(Page 47)
.
La sécurité et
votre foyer
Toutes les parties de votre
foyer IHP deviennent
EXTRÊMEMENT CHAUDES !
Afin d’éviter les brûlures
graves ou les blessures, ne pas retirer l’écran de protection de la foyer qui empêche tout contact direct avec la vitre.
Suivez les instructions de sécurité
ci-dessous et veillez à ce que tous les membres de votre famille soient conscients du danger de brûlure encouru :
• Les surfaces de votre foyer deviennent EXTRÊMEMENT CHAUDES !
• La vitre située à l'avant du foyer atteint des températures EXTRÊMEMENT ÉLEVÉES et peut causer de graves blessures en cas de contact.
• Tenez les enfants à l'écart du foyer lorsqu'il fonctionne. Surveillez attentivement les enfants dans les pièces où un foyer est utilisé afin d'éviter qu'ils ne soient en contact avec la vitre.
• Tenez tous les vêtements, les meubles, l'essence et tout autre liquide inflammable à l'écart du foyer.
• Même après fermeture du gaz, les surfaces du foyer restent extrêmement chaudes.
Veillez à coller les Étiquettes de mise
en garde relatives à la sécurité d'utilisation à l'endroit où vous
utilisez le foyer, pour rappeler à tous les utilisateurs les dangers liés aux
températures élevées
Lisez L’information de sûreté
importante (Page 5)
(Page 47)
.
.
Seguridad y su
chimenea
¡Todas las partes de la
chimenea IHP se ponen
MUY CALIENTES!
Para evitar quemaduras y lesiones
graves, no quite el protector de malla o guardia de seguridad que evita el contacto directo con el vidrio.
Siga las instrucciones de seguridad
a continuación y asegúrese de que todos en su hogar sepan acerca de este peligro de quemadura:
• ¡Las superficies de la chimenea se ponen MUY CALIENTES!
• El vidrio delante de la chimenea alcanza temperaturas EXTREMADAMENTE ALTAS y puede causar quemaduras graves si se toca.
• Mantenga a los niños alejados de la chimenea en funcionamiento. Supervise en forma cercana a los niños en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio.
• Mantenga la ropa, mobiliario, gasolina y otros líquidos inflamables alejados de la chimenea.
• Aún después de haber apagado el gas, las superficies de la chimenea permanecen extremadamente calientes.
Asegúrese de colocar las Etiquetas de
advertencia de seguridad de operación
en el lugar donde enciende la chimenea, para que todos recuerden los peligros asociados con las altas temperaturas
(Página 47)
Lea Información importante de
seguridad (Página 5).
.
[FRENCH][ENGLISH]
[SPANISH]
3
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
General Information
900285-01 01/2017
Traditional - Driftwood Logs
THANK YOU FOR YOUR PURCHASE. WE APPRECIATE YOUR BUSINESS!
Please carefully read and follow all instructions in this manual. Pay special attention to all warnings and safety information. Following these safety, care, and operation instructions will help ensure many years of dependable and enjoyable service from your fireplace.
Please read and understand these instructions before installing, operating, or servicing this product.
General Information
Safety and Your Fireplace...................................................................2
Important Safety Information ............................................................5
Fireplace Installation, Operation, and Maintenance Notices ............... 6
Packaging List ................................................................................... 8
Introduction ....................................................................................... 8
Gas Pressure ..................................................................................... 9
Requirements for the Commonwealth of Massachusetts ................10
Cold Climate Insulation .................................................................... 10
Manufactured Home Requirements ................................................. 11
Location ...........................................................................................11
Vent Termination Clearances ...........................................................12
Minimum Clearances to Combustibles ............................................14
Wall Finishes / Surrounds / Mantels ................................................15
Installation Preparation ....................................................................15
Installation
Installation Sequence ......................................................................16
Construct the Fireplace Framing ...................................................... 16
Prepare the Fireplace Top Spacers ...................................................18
Route the Gas Supply Line to the Fireplace .....................................18
Vent System Preparation .................................................................21
Install the Vent System ....................................................................25
Complete the Field Wiring ................................................................37
4
Contemporary
We recommend that our gas hearth products be installed and serviced by professionals who are certied in the U.S. by the National Fireplace Institute® (NFI) as NFI Gas Specialists.
Install the [Optional] Blower Kit after Installation in the Framing ..... 39
Connect the Gas Line ....................................................................... 40
Verify Proper Fireplace Operation ....................................................41
Optional: Install the Firebox Liners ..................................................42
Install the Logs, Volcanic Stone, and Glowing Embers or Glass
Media ..........................................................................................42
Install the Glass Door ......................................................................42
Adjust the Air Shutter to Ensure Proper Flame Appearance ............. 42
Install the Hood ...............................................................................43
Install the Finishing Materials .......................................................... 44
Attach the Safety-in-Operation Warnings.........................................44
Installing Batteries for Backup and Wall Switch ...............................44
Installation Accessories ................................................................... 48
Gas Conversion Kits ........................................................................50
Operation
Operation ......................................................................................... 51
Maintenance .................................................................................... 60
Accessory Components ................................................................... 63
Lighting Instructions .......................................................................67
Troubleshooting ...............................................................................73
Replacement Parts ..........................................................................75
Warranty ..........................................................................................79
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
IMPORTANT SAFETY INFORMATION
General Information
900285-01 01/2017
Important Safety Informa­tion
1. WARNING: Do not operate appliance with the glass front removed, cracked or broken.
2. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to in­spect the appliance and to replace any part of the control system and any gas control which has been under water.
3. Due to high temperatures, the appli­ance should be located out of traffic and away from furniture and draperies.
4. Children and adults should be alerted to the hazards of high surface tem­perature and should stay away to avoid burns or clothing ignition.
5. Clothing or other flammable material should not be placed on or near the appliance.
6. Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children, and others may be sus­ceptible to accidental contact burns. A physical barrier is recommended if there are at-risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children, and other at-risk individuals out of the room and away from hot surfaces.
7. Any safety screen, guard or barrier removed for servicing an appliance must be replaced prior to operating the appliance.
8. Installation and repair should be done by a qualified service person. The ap­pliance should be inspected before use and at least annually by a professional service person. More frequent clean­ing may be required due to excessive lint from carpeting, bedding material, et cetera. It is imperative that control compartments, burners, and circulat­ing air passageways of the appliance be kept clean. See maintenance in­structions on Page 60.
L’information de sûreté importante
1. AVERTISSEMENT. Ne pas utiliser l’appareil si le panneau frontal en verre n’est pas en place, est craqué ou brisé.
2. Ne pas se servir de cet appareil s’il a été plongé dans l’eau, même partiellement. Faire inspecter l'appareil par un technicien qualifié et remplacer toute partie du systéme de contrôle et toute commande qui ont été plongées dans l'eau.
3. En raison des températures élevées, l’appareil devrait être installé dans un en droit où il y a peu de circulation et loin du mobilier et des tentures.
4. Les enfants et les adultes devraient être informés des dangers que posent les tem pératures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
5. On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
6. Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la surface chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habitent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécurité ; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
7. Tout écran ou protecteur retiré pour per mettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
8. L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres. Voyez les instructions d’entretien à la Page 60.
-
-
-
-
Información importante de seguridad
1. ADVERTENCIA: No opere el artefacto con el frente de vidrio quitado, agrietado o roto.
2. No use este artefacto si alguna de sus partes ha estado bajo agua. Llame de inmediato a un técnico de servicio calificado para que inspeccione el artefacto y reemplace cualquier parte del sistema de control y cualquier control de gas que haya estado bajo agua.
3. Debido a las altas temperaturas, el artefacto debe situarse fuera de las áreas de tráfico y lejos del mobiliario y cortinas.
4. Se debe alertar a los niños y adultos sobre los peligros de las altas temperaturas en la superficie y que se mantengan alejados para evitar quemaduras o ignición de la ropa.
5. No debe colocarse ropa u otros materiales inflamables sobre y cerca del artefacto.
6. Se debe supervisar de cerca a los niños cuando estén en el mismo cuarto que el artefacto. Los niños pequeños, los jóvenes y otras personas pueden ser susceptibles a quemaduras por contacto accidental. Se recomienda instalar una barrera física si hay personas en riesgo en la casa. Para restringir el acceso a una chimenea o estufa, instale una puerta de seguridad ajustable para mantener a los niños pequeños, jóvenes y otras personas en riesgo fuera del cuarto y lejos de las superficies calientes.
7. Cualquier malla o resguardo de seguridad quitado para dar servicio a un artefacto, debe reinstalarse antes de operar el artefacto.
8. Una persona de servicio competente debe realizar la instalación y reparación. Una persona de servicio profesional debe inspeccionar el artefacto antes de usar al menos una vez por año. Se puede requerir limpieza más frecuente debido a la pelusa excesiva del alfombrado, del material de cobijas, etc. Es imprescindible mantener limpios los compartimientos de control, los quemadores y los pasajes de circulación del aire del artefacto. Ver las instrucciones de mantenimiento en la página 60.
[English]
[French]
[Spanish]
5
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
APPLIANCE INSTALLATION, SERVICE, AND MAINTENANCE NOTICES
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
AVERTISSEMENT
Une installation, un réglage,une modification, une réparation ou un entretien mal effectué peut causer des dommages matériels ou des blessures. Voir la notice de l’utilisateur qui accompagne l’appareil. Pour de l’aide ou des renseignements supplémentaires, consultez un installateur, un technicien agréé ou le fournisseur de gaz.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this fireplace.
Seules des portes certifiées pour cet appareil doivent être utilisées.
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
General Information
900285-01 01/2017
Any change to this appliance and/or its operating controls is dangerous. Improper installation or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon monoxide poisoning.
CARBON MONOXIDE POISONING: Early signs of carbon monoxide poisoning are similar to the flu with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immediately. Turn off the gas supply to the appliance and have it serviced by a qualified professional, as it may not be operating correctly. Some people are more affected by carbon monoxide than others, including pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Turn off gas and electrical power to the appliance and allow it to cool before cleaning or servicing the appliance.
If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this appliance.
Si l’écran est endommagé, il doit être remplacé par celui fournit par le fabricant de cet appareil.
For use with barrier(s) Part No(s). F1902 (33” Models), F1839 (35” Models), F1840 (40” Models), and F1903 (45” Models). Follow installation instructions.
Reinstall any barrier removed before operating the appliance. The barrier is designed to reduce the risk of burns from hot glass. Do not operate the appliance without the barrier installed.
6
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
APPLIANCE OPERATION NOTICES
These fireplaces are vented gas appliances. Do not burn wood or other material in these appliances.
These appliances are designed to operate on natural gas or propane gas only. The use of other fuels or combinations of fuels will degrade the performance of this system and may be dangerous.
Provide adequate clearances around air openings and adequate accessibility clearance for service and proper operation. Never obstruct the front openings of the appliance.
These appliances are designed as supplemental heaters. Therefore, it is advisable to have an alternate primary heat source when installed in a dwelling.
WARRANTY INFORMATION
Your gas appliance is covered by a limited lifetime warranty. You will find a copy of the warranty accompanying this manual. Please read the warranty to be familiar with its coverage.
General Information
900285-01 01/2017
Retain this manual. File it with your other documents for future reference.
Failure to comply with the installation and operating instructions provided will result in an improperly installed and operating appliance, voiding its warranty.
Do not attempt to alter or modify the construction of the appliance or its components. Any modification or alteration may void the warranty, certification, and listings of this unit.
IMPORTANT SAFETY AND WARNING INFORMATION
Hot while in operation. Do not touch. Severe Burns may result. Keep children, clothing furniture, gasoline and other liquids having flammable vapors away.
L’appareil est chaud lorsqu’il fonctionne. Ne pas toucher l’appareil. Risque de brûlures graves. Surveiller les enfants. Garder les vêtements, les meubles, l’essence ou autres liquides produisant des vapeur inflammables loin de l’appareil.
CAUTION
ATTENTION
7
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
INSTALLATION
PACKAGING
All models include
The assembled vented gas fireplace heater is packaged with:
Literature Kit (envelope in bottom compartment containing Installation and Operation Instructions (this manual), Hot Glass Safety Flyer, and Safety-In-Operation Warning Labels)
U-Shaped Vent Restrictor (attached to Literature Kit envelope)
Hood (Inside firebox, Traditional Models)
Log Set (Traditional Fireplaces, in firebox) or Glass Media (Contemporary Fireplaces)
Volcanic Stone—1 bag (in bottom compartment, Traditional Models)
Glowing Embers—1 bag (in bottom compartment, Traditional Models)
1 Non-combustible board, 2 side brackets and 1 center bracket
INTRODUCTION
These vented gas fireplace heaters are sealed combustion, air-circulating gas fireplaces designed for residential and commercial applications.
Millivolt fireplaces have a millivolt gas control valve with piezo ignition system. If a blower will be installed, electrical power must be provided at the time of fireplace installation.
Electronic fireplaces are designed with an electronic intermittent pilot ignition system. External electrical power is required to operate these units. In the event of a power outage, four (4) AA batteries (in battery holder) provide backup power for fireplace operation. Battery backup will not operate optional/standard blower. Traditional units require an additional four (4) AA batteries to provide power to the split-flow system.
General Information
900285-01 01/2017
NOTE: Installation and repair should be done by a qualified service person. The fireplace should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the fireplace be kept clean.
Remarqué : L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
NOTE: Diagrams and illustrations are not necessarily shown to scale.
Approved Vent Components
These fireplaces are designed, tested and listed for operation and installation with the following vent components only:
Secure Vent® Direct-Vent System Components,
Secure Flex® Flexible Vent Components, and
Z-FLEX® Model GA Venting Systems listed to UL1777 and ULCS635 manufactured by Flexmaster Canada Limited.
Use only the correct size venting (4-1/2” inner and 7-1/2” outer). These approved vent system components are labeled for identification. DO NOT use any other manufacturer’s vent
components with these fireplaces.
Codes and Standards
These fireplaces comply with National Safety Standards and are tested and listed by PFS Corporation (Report No. F13-094) to ANSI Z21.88 (in Canada, CSA-2.33), and CAN/CGA-2.17-M91 in both USA and Canada, as vented gas fireplace heaters.
These fireplaces are listed for installation in bedrooms and manufactured homes. The installation must conform to local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54—latest edition (In Canada, the current CAN/CGA-B149.1 installation code). The fireplace, when installed, must be electrically grounded and wired in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70—latest edition, or the Canadian Electrical Code, CSA C22.1—latest edition.
8
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
BTU Input
Table 1 - Input Rate (BTU/HR), Gas Valves
Models
33” Models 14,000 10,500 13,000 9,500 35” Models 16,000 11,000 15,000 11,000 40” Models 20,000 14,000 19,000 14,000† 45” Models 21,500 13,500 21,500 13,500
† 12,000 in Ecoflow Models
Table 2 - Thermal Efficiency (%)
Model
33” Models 61 57 61 60 35” Models 61 58 61 60 40” Models 61 58 61 60 45” Models 66 58 66 60
* AFUE is a measurement of the US Department of Energy, ** P4 (EnerGuide) is a measurement of the Canadian Office of Energy Efficiency. Efficiencies are based on Normal input operation.
General Information
900285-01 01/2017
Natural Gas Propane Gas
High Rate Low Rate High Rate Low Rate
Millivolt Electronic
AFUE * P4 ** AFUE * P4 **
Gas Pressure
Table 3 - Inlet Gas Supply Pressure
Fuel Minimum Maximum
Natural Gas 5” WC / (1.25 kPa) 10.5” WC / (2.61 kPa)
Propane 11.0” WC / (2.74 kPa) 13.0” WC / (3.23 kPa)
Table 4 - Manifold Gas Supply Pressure
Fuel Pressure
Natural Gas 3.5” WC / (0.87 kPa)
Propane 10.0” WC / (2.49 kPa)
Test gauge connections are provided on the front of the millivolt and electronic gas control valve (identified IN for the inlet and OUT for the manifold side). The control valves have a 3/8” (10 mm) NPT thread inlet and outlet side of the valve (Figures 1 and 2).
Figure 1 - Millivolt Gas Valve
Figure 2 - Electronic Gas Valves
SIT
Ecoflow
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down regulators to reduce the pressure to safe levels.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
9
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
Orifice Sizes—Sea Level to High Altitude
These fireplaces are tested and approved for installation at elevations of 0–4500 ft (0–1372 m) above sea level using the standard burner orifice sizes (Table 5). For elevations above 4500 ft, contact your gas supplier or qualified service technician.
Table 5 - Burner Orifice Sizes, Elevation 0–4500 ft ( 0–1372 m)
General Information
900285-01 01/2017
Model
33” Models #49 (0.073”)* #57 (0.043”)* 35” Models #48 (0.076”)* #56 (0.046”)* 40” Models #44 (0.086”)* #55 (0.052”)* 45” Models #43 (0.089”)* #54 (0.055”)*
* Standard size installed at factory
Deration
At elevations above 4500 ft, the amount of BTU fuel value delivered must be reduced by either:
Using gas that has been derated by the gas company.
Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the (USA) National Fuel Gas Code NFPA 54/ANSI Z223.1—latest edition or, in Canada, the CAN/CGA-B149.1 codes— latest edition.
NOTE: Flame breadth, height and width will diminish 4% for every 1,000 ft of altitude.
IN CANADA—CAN/CGA-2.17-M91 (HIGH ALTITUDE): THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE,
IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/ CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS
Natural Gas
drill size
Propane drill size
These appliances are approved for installation in the US state of Massachusetts if the following additional requirements are met:
Install this appliance in accordance with Massachusetts Rules and Regulations 248 C.M.R. Sections 4.00 through 8.00.
Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts.
The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
The individual manual shut-off must be a T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, horizontal terminations installed less than seven (7) feet above the finished grade must comply with the following additional requirements:
A hard wired carbon monoxide detector with an alarm and battery back-up must be installed on the floor level where the gas fireplace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certified.
A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade and be directly in line with the horizontal termination. The sign must read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your fireplace with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which fireplace rests, if floor is above ground level. Gas line holes and other openings should be caulked or stuffed with unfaced fiberglass insulation.
NOTE: Do not use loose, or blown-in insulation in the cavity surrounding the fireplace. If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can
be placed underneath to prevent conduction of cold transferring to the fireplace and into the room. It also helps to seal inside surfaces and tape for maximum air tightness and caulk firestops.
10
Innovative Hearth Products
(Rear Vent Application)
VERTICAL VENT
(Rear Vent Application without a chase)
HORIZONTAL VENT
Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
Cet appareil peut être installé dans une maison préfabriquée (mobile) déjà installée à demeure si les règlements locaux le permettent.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne peut être converti à d’autres gaz, sauf si une trousse de conversion est utilisée.
Ensure that the cross members are not cut or weakened during installation. The structural integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
This appliance must be grounded to the chassis of the manufactured home in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70—latest edition or the Canadian Electrical Code CSA C22.1—latest edition.
General Information
900285-01 01/2017
CAUTION
CAUTION
LOCATION
In selecting the location, the aesthetic and functional use of the fireplace are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important.
Due to high temperatures, the fireplace should be located out of traffic and away from furniture and draperies.
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures.
The location should also be free of electrical, plumbing or other heating/air conditioning ducting. These direct-vent fireplaces are uniquely suited for installations requiring a utility shelf positioned directly above the
fireplace. Utility shelves like these are commonly used for locating television sets and decorative plants.
Be aware that this is a heat producing fireplace. Objects placed above the unit are exposed to elevated temperatures. Do not insulate the space between the fireplace and the area above it.
The minimum height from the base of the fireplace to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Table 9.
Figure 3 - Typical Locations and Venting
Top Vent
Top Vent
Rear Vent
Top Vent
Rear Vent
Horizontal Vent
(Rear Vent with chase)
Horizontal Vent
(Rear Vent without chase)
Recessed
Installation
Top Vent
Top Vent Top Vent
Vertical Vent
(Rear Vent)
Horizontal Vent
(Top Vent)
Vertical Vent
(Top Vent)
11
Innovative Hearth Products
12
X
Roof pitch is X/12
2 ft
minimum
2 ft minimum
Lowest
discharge
opening
H*
*H = minimum height from roof to
lowest discharge opening of vent
Horizontal overhang
Vertical wall
Vent
termination
Storm collar
Concentric
vent pipe
Flashing
1” (26 mm) minimum clearance to combustibles
TERMINATION HEIGHTS FOR VENTS ABOVE
FLAT OR SLOPED ROOFS
Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI Z223.1/NFPA 54) in the USA or the current standards of CAN/CGA-B149.1 in Canada.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according to the installation codes listed above and Figure 4.
Figure 4 - Multiple Terminations
General Information
900285-01 01/2017
12”
(305 mm)
minimum
6”
(153 mm)
Terminate single vent caps relative to building components according to Table 6 and Figure 4.
Table 6 - Termination Heights for Vents above Flat or Sloped Roofs (NFPA 54 / ANSI Z223.1)—Gas Vent Rule
Roof Pitch Termination Height *
Flat to 6/12 1.0 ft (0.3 m) 6/12 to 7/12 1.25 ft (0.38 m) 7/12 to 8/12 1.5 ft (0.46 m) 8/12 to 9/12 2.0 ft (0.61 m)
9/12 to 10/12 2.5 ft (0.76 m) 10/12 to 11/12 3.25 ft (0.99 m) 11/12 to 12/12 4.0 ft (1.22 m) 12/12 to 14/12 5.0 ft (1.52 m) 14/12 to 16/12 6.0 ft (1.83 m) 16/12 to 18/12 7.0 ft (2.13 m) 18/12 to 20/12 7.5 ft (2.29 m) 20/12 to 21/12 8.0 ft (2.44 m)
Horizontal Vent Termination Clearances
12
The horizontal vent termination must have a minimum of 6” (152 mm) clearance to any overhead combustible projection of 2-1/2” (64 mm) or less (Figure 5). For projections exceeding 2-1/2” (64 mm) (Figure 5). For additional vent location restrictions refer to Table 7.
All horizontal terminations may be located as close as 6” (152mm) to any (non-combustible and combustible) exterior sidewall. This distance may be decreased to 2” (51mm) for noncombustible exterior sidewalls with all approved terminations (Pages 48-49).
Figure 5 - Horizontal Vent Termination Clearances
Combustible projection
2-1/2” or less in length
Combustible projection
greater than 2-1/2” in length
Ventilated
soffit - 18”
(457 mm)
Unventilated
soffit - 12”
(305 mm)
Termination kit
6”
(152)
6”
*
Termination kit**
* 10” to center of termination for H1968 ** Use 6-1/2” from center of termination for
all horizontal terminations applicable.
Innovative Hearth Products
(TERMINATION PROHIBITED)
Inside Corner
Balcony with No Side
Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
Table 7 - Horizontal vent termination clearances for buildings with combustible and noncumbustible exteriors
Outside Corner Recessed Location
D
E
V
B
L
C
F
V
B
TERMINATION CAP
V
Fixed
Closed
Openable
V
Openable
V
B
A
AIR SUPPLY INLET
X
Fixed
Closed
J
B
V
B
X
G
GAS METER RESTRICTED AREA
A Clearance above grade, veranda, porch, desk, or balcony 12” (300 mm) ** 12” (300 mm) * B Clearance to window or door that may be opened 6” (150 mm)
C Clearance to permanently closed window 9” (229 mm)
D Vertical clearance to ventilated soffit located above the
termination within a horizontal distance of 18” (458 mm)
E Clearance to unventilated soffit 12” (305 mm) 12” (305 mm)
See Table 6
H
G
V
V
F
I
G
G
M
V
K
V
G
V
X
A
WallVBalcony with Perpendicular Side Wall
M
M
V
U.S. Installation ** Canadian Installation *
6” (150 mm)
for fireplaces < 10,000 Btu/h (3 kW), 9” (230 mm)
for fireplaces > 10,000 Btu/h (3 kW), and < 50,000 Btu/h (15
for fireplaces < 10,000 Btu/h (3 kW), 12” (300 mm)
for fireplaces > 10,000 Btu/h (3 kW)
kW), 12” (300 mm)
for fireplaces > 50,000 Btu/h (15 kW) **
12” (305 mm)
recommended to prevent window condensation
recommended to prevent window condensation
18” (458 mm) 18” (458 mm)
General Information
900285-01 01/2017
P
N
Q
O
V
F Clearance to outside corner 5” (127 mm)
minimum
5” (127 mm) minimum
G Clearance to inside corner 6” (152 mm) minimum 6” (152 mm) minimum H Clearance to each inside of center line extended above
meter / regulator assembly
36” (910 mm) within a height of 15 ft above the meter / regulator assembly **
36” (910 mm) within a height of 15 ft above the meter / regulator assembly *
I Clearance to service regulator vent outlet 36” (910 mm)** 36” (910 mm)*
J Clearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other fireplace
6” (150 mm) for fireplaces < 10,000 Btu/h (3 kW),
9” (230 mm) for fireplaces > 10,000 Btu/h (3 kW) and < 50,000 Btu/h (15 kW),
6” (150 mm) for fireplaces < 10,000 Btu/h (3 kW),
12” (300 mm) for fireplaces > 10,000 Btu/h (3 kW)
12” (300 mm) for fireplaces > 50,000 Btu/h (15 kW)**
K Clearance to a mechanical air supply inlet 36” (910 mm) above if within 10 ft (3 m) horizontally ** 72” (1830 mm) *
L Clearance above paved sidewalk or paved driveway located
84” (2130 mm) ‡ 84” (2130 mm) ‡
on public property
M Clearance under veranda, porch, deck or balcony 12” (300 mm) *‡ 12” (300 mm) *‡
N Depth of alcove (maximum) 72” (1830 mm) ** 72” (1830 mm) * O Clearance to termination (alcove) 6” (15.2 mm) ** 6” (15.2 mm)* P Width of alcove (minimum) 36” (910 mm) ** 36” (910 mm) * Q Clearance to combustible above (alcove) 18” (457 mm) ** 18” (457 mm) *
*
In accordance with the current CAN/CGA-B149.1 National Gas And Propane Installation Code
**
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
*‡
Only permitted if veranda, porch, deck, or balcony is fully-open on a minimum two sides beneath the floor
13
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
MINIMUM CLEARANCES TO COMBUSTIBLES
Fireplace And Vent Clearances
The fireplace is approved with zero clearance to combustible materials on all sides (Table 8), with the following exception: The unit may not be recessed (allowance made for mantel legs / side trim in (Figure 6). When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit (Figure 6).
Table 8 - Minimum Clearances *
From Bottom of Unit to Ceiling 64” (1626 mm)
Front Service Clearance—
clearance immediately in front of viewing area(s)
Back
Sides
Top Standoffs 0” (0 mm) to top standoffs
Floor 0” (0 mm)
Vent
1” (26mm) to wrapper
0” (0 mm) to Spacers
1/2” (13 mm) to wrapper 0” (0 mm) to Spacers **
3” (77 mm)—Top *
1” (26 mm)—Sides and Bottom
36” (914 mm)
General Information
900285-01 01/2017
The fireplace must be mounted on a fully supported base extending the full width and depth of the unit. The fireplace may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
Hearth Extension
A hearth extension is not required with this fireplace. If a hearth extension is used, do not block the lower control compartment door. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.
Shelf Height
To provide for the lowest possible shelf surface, use the rear vent model. For top vent models, the venting attached to the top vent should be routed in a way to minimize obstructions to the space above the fireplace. Do not insulate the space between the fireplace and the area above it (Table 9). The minimum height from the base of the fireplace to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Table 9.
Table 9 - Combustible Shelf Height—Top Vent
* 3” (77 mm) above any horizontal/inclined vent component. ** See Page 21 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it.
Top Vent with one 90° Elbow
Model
Secure Vent
33” Models 44” (1118 mm)* 46” (1168 mm)* 39” (990 mm)** 35” Models 47” (1194 mm)* 49” (1245 mm)* 41” (1042 mm)** 40” Models 52” (1321 mm)* 54” (1372 mm)* 46” (1169 mm)** 45” Models 52” (1321 mm)* 54” (1372 mm)* 46” (1169 mm)**
®
Secure Flex®
(flex elbow)
Alternative Rear Vent
applications
Secure Vent
®
Shelf Height
(see table)
No com­bustibles or insulation in the shaded area between the appliance and the shelf above it.
14
* Includes 3” clearance to combustibles (required above vent components) ** In alternative, Rear Vent applications, Top Vent will be sealed as detailed in the
Installation and Operation manual.
Innovative Hearth Products
mantel legs may
At 6 in. minimu side wall clearance, a combustible wal can project to an length
Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
General Information
900285-01 01/2017
Figure 6 - Combustible Side Clearances
At 6” minimum side wall clearance, a combustible wall can project to any length.
m
Top View of
l
y
.
o
o
45
45
Top View of
3 1/2 in.
3-1/2”
(89 mm)
(89 mm)*
Fireplace
Fireplace
Combustible materials
Combustible Materials
allowed in shaded area
Allowed In Shaded Area
“Safe Zone”.
“Safe Zone
Combustible Walls
Combustible walls
shown in dark gray
shown in dark gray
Combustible
Combustible mantel
project beyond either side
legs may project
of the fireplace opening
beyond either side of
as long as they are kept
the fireplace opening
within the shaded area
as long as they are kept
illustrated here.
within the shaded area illustrated here.
6”
(152 mm) * 6” (152 mm) in 35” and 40” Contemporary units
Wall Finishes / Surrounds / Mantels
NOTE: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the fireplace front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the fireplace face (Figure 40).
Non-combustible materials, such as surrounds and other fireplace trim, may be installed on the fireplace face, but they must not cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel (Figure 7). Mantels constructed of non-combustible materials may be installed at any height above the fireplace opening. However, do not allow anything to hang below the fireplace hood.
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the fireplace.
Figure 7 - Mantel Height
12
(305)
Mantel depth
(203)
10
(254)
8
6
(152)
20 (508)
18 (457)
16 (406)
14 (356)
12 (305)
10 (254)
in. (mm)
Traditional
4
(102)
2
(51)
Hood
Fireplace
25 (635)
23 (584) 21 (533)
19 (483)
17 (432)
15 (381)
12
(305)
10
(254)
Contemporary
Mantel depth
8
(102)
6
(203)
(152)
4
2
(51)
Fireplace Opening
Fireplace
INSTALLATION PREPARATION
NOTE: To avoid heat-related finish damage, we recommend the use of high temperature paint (rated 175° F or higher) on
the underside of the mantel.
The fireplace is shipped with all gas controls and components installed and pre-wired. Before installing the fireplace, follow these steps:
1. Remove the shipping carton, and retain the front of the carton (used to protect the fireplace during construction).
2. Remove the shipping pad, exposing the front glass door.
3. Remove the glass door (Page 58). NOTE: Place the glass door on the shipping carton to protect its surface.
15
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
INSTALLATION SEQUENCE
The typical sequence of installation is outlined below; however, each installation is unique and may result in variations to the steps described.
See the pages referenced in the following steps for detailed instructions.
Framing
1. Construct the Fireplace Framing (Page 16).
2. Prepare the Fireplace Top Spacers (Page 18).
3. Route the Gas Supply Line to the Fireplace (Page 18).
4. Determining Vent Setup in the Combination Venting Unit (Page 19)
5. Installing Metal, Non-Combustible Front Standoff (Page 19)
6. Rough in the Electrical Supply, if Needed (Page 20).
7. Install the [Optional] Blower Kit before Installation in the Framing (Page 20).
Venting
8. Place the Fireplace in the Framing and Secure (Page 21).
9. Select a Horizontal or Vertical Vent System (Page 21).
10. Install the Vent Restrictor (if necessary) (Page 22).
11. Install the Vent System (Page 25).
Electrical Connection
12. Complete the Field Wiring (Page 37).
13. Install the [Optional] Blower Kit after Installation in the Framing (Page 39).
Gas Connection
14. Connect the Gas Line (Page 40).
15. Verify Proper Fireplace Operation (Page 41).
Finishing
16. Optional: Install the Firebox Liners (Page 42).
17. Install the Logs, Volcanic Stone, and Glowing Embers or Glass Media (Page 42).
18. Install the Glass Door (Page 42).
19. Adjust the Air Shutter to Ensure Proper Flame Appearance (Page 42).
20. Install the Hood in Traditional Fireplaces (Page 43).
21. Reinstall the Included Barrier (Page 44).
22. Install the Finishing Materials and Facade in Contemporary Fireplaces (Page 44).
23. Attach the Safety-in-Operation Warning Labels (Page 47).
24. Installing Batteries for Backup and Wall Switch (Page 44).
Installation
900285-01 01/2017
1. Construct the Fireplace Framing
1. Frame the fireplace as illustrated in Table 10. For corner framing installations, use Table 11. All framing details
must allow for a minimum clearance to combustible framing members as shown in Table 8.
2. If the fireplace is to be elevated above floor level, a solid continuous platform must be constructed below the fireplace. NOTE: Headers may be in direct contact with the fireplace top standoff spacers when they are bent up vertically,
maintaining the 4” clearance to the fireplace top, but must not be supported by them or notched to fit around them. All construction above the fireplace must be self-supporting. DO NOT use the fireplace for structural support.
NOTE: For contemporary models, leave a minimum of 6” clearance to any side wall for proper facade installation and fit.
16
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
Installation
900285-01 01/2017
Table 10 - Fireplace Framing Specifications
Model A * B C D E
33” Models
35” Models
40” Models
45” Models
33-3/4
(857)
35-3/8
(899)
40-3/8 (1026)
45-3/8 (1153)
34-1/4
(845)
36-1/4
(895)
41-1/4 (1048)
41-1/4 (1048)
36-7/8
(930)
38-3/4
(984)
43-3/4 (1111)
43-3/4 (1111)
C = Minimum height of top vent installations
14-1/2
(368)
18
(447)
18
(447)
18
(447 )
19-5/8
(499)
23-3/8
(594)
28-1/4
(717)
28-1/4
(717)
NOTE: Dimension “D” is the required framing depth when the finish material (drywall) thickness is 1/2” (13mm).
Vent Framing—Top Vent
with One 90° Elbow
B
E = Minimum height of rear vent installations
* Minimum opening size; additional 1/8” per side is recommended. NOTE: Framing specifications do NOT apply for flexible venting.
When using flexible venting, refer to the kit requirements for framing specifications.
Inches
(millimeters)
Table 11 - Fireplace Framing Specifications—Corner Installation with Horizontal Termination
Model A B C D E F
33”
35”
40”
45”
33-3/4
(857)
35-3/8
(899)
40-3/8 (1025)
45-3/8 (1153)
51-1/4 (1302)
59-1/2 (1511)
63-7/8 (1622)
70-3/8 (1788)
36-1/4
(921)
42-1/8 (1070)
45-3/8 (1153)
49-3/4 (1264)
25-5/8
(651)
30-1/4
(768)
33-1/4
(845)
35-1/4
(895)
12-1/8
(308)
14-1/4
(362)
15-7/8
(403)
17-1/2
(445)
5-1/2 (140)
6-5/8 (168)
8-1/2 (216)
10-1/4
(260)
C
1/2 A
Framing
10-1/2
construction to be
(267)
2 x 4, or larger.
7 (178)
5-1/8 (130)
C
E
D
A
E
F
12-1/8
(308)
D
7 (178)
A
B
Back wall of chase/enclosure (including finishing materials)
Inches (millimeters)
Table 12 - Fireplace Specifications
NOTE: When finishing the area around the hood, 5/8” clearance above hood is required for hood installation.
F
G
I
K
Top View Front View
Model A B C D (door) E F G H I J K
33” Models 30-1/8 (765) 26-1/4 (667) 18-3/8 (467) 30-1/2 (775) 33-5/8 (854) 21-7/8 (556) 11 (279) 31 (787) 5-3/4 (146) 14 (356) 8-1/2 (207)
35” Models 32-1/8 (816) 28-3/4 (730) 22-1/4 (565) 32-3/8 (822) 35-1/4 (895) 25 (635) 12-1/2 (317) 32-7/8 (835) 6-7/8 (175) 17 (432) 10-1/8 (257)
40” Models 37-1/8 (943) 33-1/4 (845) 27-1/4 (692) 37-3/8 (949) 40-1/4 (1022) 30 (762) 15 (381) 37-7/8 (962) 6-7/8 (175) 17 (432) 10-1/8 (257)
45”Models 37-1/8 (943) 33-1/4 (845) 27-1/4 (692) 42-3/8 (1076) 45-1/4 (1149) 35 (889) 17-1/2 (445) 42-7/8 (1089) 6-7/8 (175) 17 (432) 10-1/8 (257)
A
E
C
D
H
B
Blower
access panel
J K
Hood
Junction
box access
Gas line
access
Left Side View Right Side View
17
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
2.
Prepare the Fireplace Top Spacers
1. The two (2) 4” standoff spacers on top of the fireplace cabinet are shipped flat. Remove the screw adjacent to
the detached end (Figure 8).
2. Bend the standoffs as shown (Figure 9):
3. Align the hole in the standoff with the hole in the fireplace top, and secure with the screw that was removed in Step 1 (Figure 9).
Figure 8 - Unassembled standoff
Installation
900285-01 01/2017
Figure 9 - Assembled standoffs
Positioned flat as shipped from the factory
Screw
Fireplace Front
Top Standoff
3. Route the Gas Supply Line to the Fireplace
1. Route a 1/2” (13 mm) gas line to the left side of the fireplace (Figure 10). NOTE: Gas lines must be routed, assembled, and made of materials that are in strict accordance with local codes and
regulations. All fireplaces are factory-equipped with a flexible gas line connector and a 1/2” shutoff valve (Page 40).
Figure 10 - Routing the gas line - 35”, 40”,
45” Models
Left side front corner of fireplace framing
Pipe coupling (recommended)
7-5/8” (195 mm)
3”
(77 mm)
Configuration for 1/2" finish materials
Top Standoff
Fireplace
Front
Configuration for 5/8" finish materials
Figure10a - Routing the Gas Line - 33” Model
Left side front corner of fireplace framing
Pipe coupling (recommended)
5-1/4” (140 mm)
3”
(77 mm)
Top Standoff
Fireplace
Front
18
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code, NFPA 54—latest edition (USA) or CAN/CGA-B149.1—latest edition (Canada).
The gas supply line should not be connected to the appliance until step 14. Connect the Gas Line (Page 40).
NOTE:
All fireplaces are factory-equipped with a flexible gas line connector and 1/2” shutoff valve (Figure 35).
See Massachusetts Horizontal Vent Requirements for additional requirements for installations in the state of
Massachusetts in the USA.
A pipe joint compound rated for gas should be used on the threaded joints. Ensure propane-resistant compounds are used in propane applications. Be very careful that the pipe compound does not get inside the pipe.
A sediment trap in the supply line as close as possible to the fireplace is recommended.
Check with the local building official for local code requirements (e.g., Are below grade penetrations of the gas line allowed?, etc).
CAUTION
If propane is used, be aware that with a tank that is too small (i.e., under 100 lbs, if this is the only gas appliance in the dwelling—see NPFA 58), there may be a loss of pressure. This can result in insufficient fuel delivery that can cause sooting, delayed ignition, or other malfunctions. Any damage resulting from an improper installation is not covered by the limited warranty.
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
Determining Vent Setup in the Combination Venting Unit
4.
900285-01 01/2017
Combination venting units are shipped with rear venting setup nearly ready for install. If this is the type of vent you require, remove all insulation packing and flue plug block off from rear venting and proceed with fireplace installation. If you require a top-vented unit, use the following steps to convert the fireplace before use.
Outside preparation of the fireplace for top-vent conversion
Installation
Step 1: Remove the eight (8) screws holding the top vent cover
Step 2: Remove the round flue cover from the top venting outlet.
plate and gasket. Discard cover plate and reinstall screws.
Step 3: Remove insulation from inside flue pipe. Step 4: Make sure insulation disc is still in the round cover. Re-
move the flue plug from the top flue.
19
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
900285-01 01/2017
Installation
5. Installing Non-Combustible Fireboard Standoff - All Models
A non-combustible standoff board is provided for all model fireplaces to prevent overlap of drywall or other material of portions of the fireplace that may be prone to the buildup of heat. It is supported by a middle bracket and two side brackets.
Separate and note metal side (2) and center (1) brackets.
Step 2: Remove the three screws that align with the clearance screw holes from the top of the unit. Secure the center bracket to the top center of the fireplace.
Rough in the Electrical Supply, if Needed
5.
Step 1: Remove two screws from the top and side of the unit. Bend the side bracket securing tab over the edge of the unit and secure. Secure bracket to the top through the clearance screw hole.
Step 3: Top of front fireboard standoff should be flush with top standoffs (not shown).
As necessary, rough in the fireplace electrical supply per NEC and local codes.
6. Install the [Optional] Blower Kit before Installation in the Framing
1. Remove the left side blower cover panel screw, and blower cover panel (see Table 12, Page 17). Retain the
panel and screw for later reinstallation.
Step 4: Fireboard standoff can be secured to the capture screw holes.
20
2. Slide the blower through the opening and position it with the bracket oriented to the front of the firebox and the
blower discharge to the rear of the firebox. Bend the two tabs in the firebox floor to secure the blower to the floor.
3. Reinstall the blower cover panel and secure with the removed screw.
4. Access the blower supply wiring through the front of the fireplace and plug it into the junction box in the right,
rear of the fireplace (Figure 32).
5. Install the blower control switch according to its included instructions.
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
Place the Fireplace in the Framing and Secure
7.
NOTE: Nailing flanges, combustible members, and screw heads in areas directly adjacent to the nailing flanges are
EXEMPT from the 1/2” clearance to combustible requirements for the firebox outer wrapper. NOTE: Combustible framing may be in direct contact with the nailing flanges and may be located within 1/2” of screw
heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details in this manual.
1. Bend out the appropriate nailing flanges for the drywall / finish material to be used (Figure 11). Nailing flanges are provided for:
flush framing,
1/2”, and
5/8” framing depths.
2. Secure the fireplace to the side framing members using the unit’s nailing flanges—one top and bottom on each side of the fireplace front (Figure 11). Use 8d nails or the equivalent.
Figure 11 - Nailing Flanges
Installation
900285-01 01/2017
Side
framing
Unit nailing flange (no clearance to combustible framing is required)
VENT SYSTEM PREPARATION
8. Select a Horizontal or Vertical Vent System
1. With the fireplace secured in the framing, determine the vent route and identify the exterior termination location.
The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Use only approved vent components (Page 8 and Pages 48-49).
NOTE: This fireplace must be vented directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a flue serving a separate solid fuel burning appliance.
NOTE: The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no requirement for
inspection openings in the enclosing wall at any of the joints in the vent pipe.
WARNING
21
Innovative Hearth Products
2 1/2”
Break-Away
1
3
20
40
6
10
40
25 ft Maximum
horizontal run (flat to near level)
60 ft Maximum vertical run
60
1.9
25
Horizontal Distance (ft)
Vertical Height (ft) from top of unit
Vertical Height (ft)
2
5
Elbow**
5 10
15
3” Base + wing3” Base
6 ft Minimum vertical run
6 ft Minimum vertical run
None
Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
9. Install the Vent Restrictor (if necessary)
1. Use the vent run descriptions in Figure 12 to determine if a vent restrictor is necessary.
2. If necessary, assemble the vent restrictor and wing as detailed in Figures 12 and 15.
3. If necessary, install the appropriate vent restrictor (Figures 13 and 14).
NOTE: If installing the vent restrictor in a rear vent application, ensure the factory-installed intake air baffle is in place (Figure 14). NOTE: The vent restrictor is shipped in the firebox.
Installation
900285-01 01/2017
Figure 12 - When to use a vent restrictor
***
Figure 13 - Vent restrictor installation, Top vent
*
U-Shaped Vent
Restrictor
Inner
Fireplace
Collar
Appliance Top Vent Outlet
Figure 14 - Vent restrictor installation, Rear vent
Inner Fireplace Collar
Appliance Rear
Vent Outlet
U-Shaped Vent
Restrictor
22
* For straight runs or runs with elbows as illustrated in Vertical Vent Figures/Tables
starting on Page 28 ** No rise required. *** On 33” Models, use the 3” base restrictor. Do not raise the break-away tab.
NOTE: When venting Rear Horizontal with slip collar and termination only, install base vent restrictor with the breakaway portion raised.
*
Intake Air Baffle
Figure 15 - Vent restrictor assembly
With break-away raised***
Base Vent Restrictor
Base Vent Restrictor + Wing
Innovative Hearth Products
SV4.5E90
(90
°
Elbow)
8 1/8 in.
(206 mm)
Swivel Joint
(360
°
swivel)
4 13/16 in.
(122 mm)
SV4.5E45
(45
°
Elbow)
Swivel Joint
(360
°
swivel)
Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
Vent Restrictor with Horizontal Terminations
When horizontally terminating a vent system with a vertical vent run up to 4 ft through an exterior wall, no vent restrictor is required.
If installing more than 4 ft of vertical venting, install the restrictor (Figure 14), from inside or outside the unit, in the inner fireplace collar. The vent restrictor is held in place by friction.
Connecting the vent pipe
Secure Vent® SV4.5 direct-vent system components are unitized concentric pipe components featuring positive twist lock connections (Figures 16-17). All of the fireplaces covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the fireplace/vent collar to create the positive twist lock connection.
1. Align the dimpled end over the collar, adjusting the radial alignment until the four (4) locking dimples are aligned
with the inlet of the four (4) inclined channels on the collar (Figure 16).
2. Push the vent component against the collar until it fully engages, then twist the component clockwise, running
the dimples down and along the incline channels until they seat at the end of the channels.
NOTE: The unitized design of the Secure Vent
3. If desired, a #6 x 1/2” screw can be used at the joint, but is not required as the pipe will securely lock when
twisted (Figure 17).
Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer with an option to install in tight and confined spaces, or where the vent run made up of fixed length pieces develops a joint in a undesirable location, or will not build up to the required length. The SV4.5LA Telescopic Vent Section has an effective length of from 1-1/2 to 7” (38 to 191 mm). The SV4.5LA is fitted with a locking inclined channel end (identical to a normal vent section component) and a plain end with three (3) pilot holes. Slip the plain end over the locking channel end of a standard SV4.5 vent component the required distance and secure with three (3) screws.
Installation
900285-01 01/2017
®
components will engage and seal both the inner and outer vent pipe.
Vent elbows
Figure 16 - Connecting vent
components
Arrow
Dimple
Locking Incline Channel
Appliance Collar or Vent Section
Figure 17 - Connected vent
components
Dimple
Locking
Incline
Channel
Arrow
Figure 18 - Elbow Dimensions
4-13/16” (122 mm)
Swivel Joint
(360°)
SV4.5E45
(45° elbow)
Swivel Joint
(360°)
SV4.5E90
(90° elbow)
8-1/8” (206 mm)
Vent elbows are available in 90° and 45° configurations. Refer to Figure 18 for the SV4.5E45 and SV4.5E90 elbow dimensions. The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element.
1. Rotate the elbow in a clockwise direction (to avoid the possibility of unlocking any of the previously connected vent sections) for proper alignment (Figure 18). See Connecting the vent pipe for more information.
Table 13 - Effective Vent Length
Model Effective Length
SV4.5L6 4-1/2” SV4.5L12 10-1/2” SV4.5L24 22-1/2” SV4.5L36 34-1/2” SV4.5L48 46 1/2”
23
Innovative Hearth Products Gemini™ and GeminiCD Series Direct-Vent Gas Fireplaces
Vent section length table
Table 14 will assist calculating how many vent sections are needed for the planned vent configuration. When a vent section is engaged with another section, its effective length will be 1-1/2” shorter.
Table 14 - Vent Section Length
24
Nominal Section
Length (in.)
Net Section Length
(in.)
Height of Vent
in. ft in. ft
4.5 0.375 1 0 0 0 0 1 252 21 0 1 0 7 0 8
9 0.75 2 0 0 0 0 2 276 23 0 0 0 8 0 8
10.5 0.875 0 1 0 0 0 1 279 23.25 0 0 0 0 6 6
15 1.25 1 1 0 0 0 2 280.5 23.375 1 0 0 8 0 9
22.5 1.875 0 0 1 0 0 1 289.5 24.125 0 1 0 0 6 7
31.5 2.625 0 3 0 0 0 3 301.5 25.125 0 0 1 0 6 7
34.5 2.875 0 0 0 1 0 1 310.5 25.875 0 0 0 9 0 9
37.5 3.125 1 1 1 0 0 3 325.5 27.125 0 0 0 0 7 7
43.5 3.625 0 2 1 0 0 3 330 27.5 1 0 0 0 7 8
45 3.75 0 0 2 0 0 2 345 28.75 0 0 0 10 0 10
46.5 3.875 0 0 0 0 1 1 349.5 29.125 1 0 0 10 0 11
51 4.25 1 0 0 0 1 2 372 31 0 0 0 0 8 8
55.5 4.625 0 1 2 0 0 3 379.5 31.625 0 0 0 11 0 11
57 4.75 0 0 1 1 0 2 418.5 34.875 0 0 0 0 9 9
67.5 5.625 0 0 3 0 0 3 465 38.75 0 0 0 0 10 10
69 5.75 0 0 0 2 0 2 475.5 39.625 0 1 0 0 10 11
73.5 6.125 1 0 0 2 0 3 480 40 1 1 0 0 10 12
79.5 6.625 0 1 0 2 0 3 492 41 1 0 1 0 10 12
81 6.75 0 0 0 1 1 2 499.5 41.625 0 0 0 1 10 11
91.5 7.625 0 0 2 0 1 3 504 42 1 0 0 1 10 12
93 7.75 0 0 0 0 2 2 511.5 42.625 0 0 0 0 11 11
97.5 8.125 1 0 0 0 2 3 520.5 43.375 0 2 0 1 11 14
103.5 8.625 0 0 0 3 0 3 531
108 9 1 0 0 3 0 4 538.5 44.875 1 0 0 2 11 14
117 9.75 1 0 5 0 0 6 549 45.75 1 0 2 1 11 15
118.5 9.875 1 1 0 3 0 5 558 46.5 0 0 0 0 12 12
126 10.5 0 0 1 3 0 4 562.5 46.875 1 0 0 0 12 13
130.5 10.875 1 0 1 3 0 5 568.5 47.375 0 1 0 0 12 13
135 11.25 0 0 6 0 0 6 573 47.75 1 1 0 0 12 14
139.5 11.625 0 0 0 0 3 3 580.5 48.375 0 0 1 0 12 13
142.5 11.875 1 0 0 4 0 5 589.5 49.125 0 1 2 2 10 15
144 12 1 0 0 0 3 4 595.5 49.625 1 1 1 0 12 15
154.5 12.875 1 1 0 0 3 5 604.5 50.375 0 0 0 0 13 13
160.5 13.375 0 2 0 0 3 5 615 51.25 0 1 0 0 13 14
172.5 14.375 0 0 0 5 0 5 625.5 52.125 0 2 0 0 13 15
177 14.75 1 0 0 5 0 6 631.5 52.625 1 0 1 0 13 15
186 15.5 0 0 0 0 4 4 637.5 53.125 0 1 1 0 13 15
196.5 16.375 0 1 0 0 4 5 651 54.25 0 0 0 0 14 14
207 17.25 0 0 0 6 0 6 655.5 54.625 1 0 0 0 14 15
211.5 17.625 1 0 0 6 0 7 672 56 0 2 0 0 14 16
217.5 18.125 0 1 0 6 0 7 678 56.5 1 0 1 0 14 16
229.5 19.125 0 0 1 6 0 7 688.5 57.375 1 1 1 0 14 17
232.5 19.375 0 0 0 0 5 5 697.5 58.125 0 0 0 0 15 15
241.5 20.125 0 0 0 7 0 7 702 58.5 1 0 0 0 15 16
246 20.5 1 0 0 7 0 8 712.5 59.375 1 1 0 0 15 17
6 12 24 36 48
4.5 10.5 22.5 34.5 46.5 Net Section Length (in.) 4.5 10.5 22.5 34.5 46.5
Number of Vent Sections
Nominal Section Length
Total Qty
Installation
900285-01 01/2017
(in.)
Height of Vent
44.25 0 2 2 0 11 15
720 60 0 0 1 0 15 16
6 12 24 36 48
Number of Vent Sections
Total Qty
Loading...