This book is valuable. In addition to instructing you on how to install and manintain your appliance, it also contains
information that will enable you to obtain replacement parts or accessory items when needed. Keep it with your other
important papers.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
This wood burning fireplace complies with
UL127 CAN/ULC-S610-M87 standard as a
FACTORY BUILT FIREPLACE.
This fireplace is approved for use as a wood furning fireplace or for use with a vented gas log approved to
ANSI Z21.60 or Z21.84 standards or for use with a vent-free gas log heater approved to ANSI Z21.11.2 standard.
FOR CANADA: The authority having jurisdiction
(such as the municipal building department, fire
department, etc.) should be contacted before
installation to determine the need to obtain a
Installateur : Laissez cette notice avec l’appareil.
Consommateur : Conservez cette notice pour consultation ultérieure.
Ce foyer au bois est conforme aux UL 127 CAN/ULCS610-M87 norme comme une USINE CONSTRUITE
CHEMINÉE.
POUR LE CANADA: L’autorité compétente (comme le
service municipal du bâtiment, les pompiers, etc.) doit
être contacté avant l’installation afin de déterminer la
nécessité d’obtenir un permis.
permit.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only)
or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated
on the rating plate.
WARNING: If the information in these
instructions is not followed exactly, a fire or
explosion may result causing property damage,
personal injury or death.
AVERTISSEMENT : Assurez-vous de bien suivre les
instructions données dans cette notice pour réduire au
minimum le risque d’incindie ou d’explosion ou pour éviter
tout dommage matériel, toute blessure ou la mort.
— Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from
a neighbor’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call
the fire department.
— Installation and service must be performed
by a qualified installer, service agency or the
gas supplier.
— Ne pas entreposer ni utilizer d’essence ni d’autres
vapeurs ou liquides inflammables dans le voisinage
de cet appareil ou de tout autre appareil.
— QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous
servir des téléphones se trouvant dans le bâtiment
où vous trouvez.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions du
fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
— L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualifié ou par
le fournisseur de gaz.
Page 2
OWNER’S OPERATION AND
PFS
USC
INSTALLATION MANUAL
INDOOR/OUTDOOR WOOD
BURNING
ORACLE CAT 42 AND ORACLE
CAT 50
SERIES MASONRY FIREPLACES
WITH INSULATION
®
These models meet the EPA Wood Burning Fireplace
Program Phase 2 emission level. NOTE: To ensure proper
replace operation, the catalyst should be replaced at a
minimum of 3 years and a maximum of 5 years.
SAVE THIS BOOK
This book is valuable. In addition to instructing you
on how to install and maintain your appliance, it also
contains information that will enable you to obtain replacement parts or accessory items when needed. Keep
it with your other important papers.
This replace is approved for use as a wood burning
replace or for use with a vented gas log approved to
ANS Z21.60 and Z21.84 standards.
This wood burning replace complies with UL127-CAN/
ULC-S610-M87 standard as a FACTORY BUILT FIREPLACE.
FOR CANADA: The authority having jurisdiction (such
as the municipal building department, re department,
etc.) should be contacted before installation to determine the need to obtain a permit.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
tion, service or maintenance can cause injury, property
damage or loss of life. Refer to this manual for assistance or additional information. Consult a qualied
installer or local distributor.
IMPORTANT: Check local codes
before installing this replace.
Before beginning the installation of the
fireplace, read these instructions through
completely.
• This INNOVATIVE HEARTH PRODUCTS
fireplace and its components are safe
when installed according to this installation
manual. Unless you use IHP components,
which have been designed and tested for
the replace system, you may cause a re
hazard.
• The INNOVATIVE HEARTH PRODUCTS
warranty will be voided by and IHP disclaims any responsibility for the following
actions.
a. Modification of the fireplace, com-
ponents, doors, air inlet system and
damper control.
b. Use of any component part not manu-
factured or approved by INNOVATIVE
HEARTH PRODUCTS in combination
with a IHP replace system.
Proper installation is the most important step
in ensuring safe and continuous operation
of the replace. Consult the local building
codes as to the particular requirements
concerned with the installation of all factory
built replaces.
Glass Door Installation ...................................... 18
Operation and Maintenance Guidelines ............ 19
PureFire Emissions Control System .................. 20
• Do not store or use gasoline
or any other ammable vapors
or liquids in the vicinity of this
or any other appliance.
• Due to high temperatures, the
appliance should be located
out of trafc and away from
furniture and draperies.
• Do not place clothing or other
ammable materials on or near
the appliance.
• Never leave children unattended when a re is burning
in the replace.
WARNING: Use solid wood
or processed solid fuel relogs
only. When processed wood fuel
re logs are used, do not poke or
stir the logs while they are burning. Use only re logs that have
been evaluated for the application
in replace and refer to re log
warnings and caution markings
on packaging prior to use.
WARNING: Do not install a
replace insert in this box unless
the manufacturer's instructions
with the insert specically state
this replace has been tested for
use with this insert.
This replace is not intended to be
used as a substitute for a furnace
to heat an entire home. Use for
supplemental heat only.
Page 4
42" MODEL
51 1/8"
5/8"
SPECIFICATIONS
30 1/2"
22 3/4"
15 3/4"
17 5/8"
4 3/8"
29"
26 3/8"
3
41
/8"
42" HEARTH
21
23"
3
/4"
(Ref.)
1
/4"
1
67"
61"
58"
49"
11"
30"
OUTSIDE
AIR
ACCESS
GAS LINE
ACCESS
10 1/2"
4 1/2"
9 1/2"
3 1/2"
81/2"
13"
7"
1"
42"
Figure 1 - 42" Model - Oracle Cat 42
www.Astria.US.com
126761-01A4
Page 5
50" MODEL
23"
(Ref.)
SPECIFICATIONS Continued
38 1/2"
24"
19 1/4"
28 1/2"
17 5/8"
43/8"
34 3/8"
49 3/8"
50" HEARTH
21
3
/4"
1
/4"
1
OUTSIDE
4 1/2"
AIR
ACCESS
GAS LINE
ACCESS
10 1/2"
9 1/2"
3 1/2"
8 1/2"
13"
17"
67"
61"
58"
49"
11"
30"
7"
1"
50"
59"
Figure 2 - 50" Models Model - Oracle Cat 50
126761-01A5
www.Astria.US.com
Page 6
FIREPLACE INSTALLATION
Not Required at
Nailing Flanges
SELECTING LOCATION
To determine the safest and most efcient
location for the replace, you must take into
consideration the following guidelines:
1. The location must allow for proper clearances (see Figures 5 and 6).
2. Consider a location where replace will
not be affected by drafts, air conditioning
ducts, windows or doors.
3. A location that avoids cutting of joists or
roof rafters will make installation easier.
4. An outside air kit is available with this
replace (see Optional Outside Air Kit on
page 7).
MINIMUM CLEARANCE TO
COMBUSTIBLES
Back and sides of replace 1 1/2" min.*
Front of replace 48" min.
Floor** 0" min.
Perpendicular wall to opening 18" min.
Top spacers 0" min.
Mantel clearances
Chimney outer pipe surface 2" min.
* Not required at nailing anges
** See step 2 of Framing
see Mantels, page 6
WARNING: Do not pack
required air spaces with insula-
tion or other materials. A restop
thimble (38FST or FST30) is
recommended.
Minimum/Maximum Chimney Height for
Residential Installation
Minimum height of chimney, measured from
base of replace to ue gas outlet of termination, is 16 feet for straight ue or a ue with
one elbow set. Maximum distance between
elbows is 6 feet. For systems with two elbow
sets, minimum height is 22 feet. Maximum
height of any system is 50 feet. This measurement includes replace, chimney sections and
height of termination assembly at level of the
ue gas outlet (see Figure 14, page 10).
Minimum/Maximum Chimney Height for
Outdoor Installation
Minimum height of chimney, measured from
base of replace to ue gas outlet of termination, is 9.5 feet (minimum of 4 feet of chimney
pipe sections required for outdoor installation).
www.Astria.US.com
FRAMING
1. Frame opening for replace using dimensions shown in Figures 2 and 3.
2. If replace is to be installed directly on
carpeting, tile (other than ceramic) or any
combustible material other than wood
ooring, replace must be installed upon
a metal or wood panel extending full width
and depth of replace.
3. Set replace directly in front of this opening and slide unit back until nailing anges
touch side framing.
4. Check level of the replace and shim with
sheet metal if necessary.
5. Before securing fireplace to prepared
framing, ember protector (provided) must
be placed between hearth extension (not
supplied) and under bottom front edge of
replace to protect against glowing embers
falling through. If replace is to be installed
on a raised platform, a Z-type ember protector (not supplied) must be fabricated to
t your required platform height. Ember
protector should extend under replace a
minimum of 1 1/2". Ember protector should
be made of galvanized sheet metal (28
gauge minimum to prevent corrosion.
6. Using screws or nails, secure replace to
framing through anges located on sides
of replace.
Maintain 1
Clearance
at Sides and
Back of Fireplace
1
1
/2" Clearance
126761-01A6
Page 7
FIREPLACE INSTALLATION
Continued
Note: For outdoor installations, fireplace
enclosure must allow for adequate drainage
and fresh air ventilation. It is recommended
that a sealed, corrosion resistant catch pan
with provision for drainage be installed under
replace within replace enclosure.
HEARTH EXTENSION
A hearth extension projecting a minimum of
20" in front of and a minimum of 12" beyond
each side of replace opening is required to
protect combustible oor construction in front
of replace. Fabricate a hearth extension
using a material which meets the following
specications: a layer of noncombustible,
inorganic material having a thermal conductivity of K=0.84 BTU IN/FT, HR. F (or less) at
1" thick. For example, if the material selected
has a K factor of 0.25, such as glass ber, the
following formula would apply:
0.25 x 1.0" = 0.30" thickness required
0.84
Thermal conductivity "K" of materials can be
obtained from manufacturer or supplier of
noncombustible material. If hearth extension
is to be covered, use noncombustible material such as tile, slate, brick, concrete, metal,
glass, marble, stone, etc. Provide a means
to prevent hearth extension from shifting and
seal gap between replace frame and hearth
extension with a noncombustible material
(see Figure 5).
WARNING: Hearth extension
is to be installed only as shown
in Figure 4.
Seal Gap
Fireplace Front
MANTELS
A mantel may be installed if desired (see Figure
6). Woodwork such as wood trims, mantels
or any other combustible material projecting
from front face must not be placed within 18"
of replace opening. Combustible materials
above 18" and projecting more than 1 1/2" from
replace must not be placed less than 21" from
the top opening of the replace (NFPA STD
211, Sec. 7-3.3.3).
Mantels or any other combustible material
also may come up to side edge of black metal
face of replace as long as projections from
front face fall within limit shown in Figure 6.
12 1/4" Ref.
6"
Ref.
Top View of Fireplace
33°
3" Nom.
11/2" Max.
21" Min.
18" Min.
Fireplace Opening
11.5"
Combustible
Material
Safe
Zone for
Projection of
Combustible
Materials
Upper
Section of
Fireplace
FIREBOX
Ember Protector
Fireplace Front
Raised Hearth
Ember Protector
Fireplace Front
Elevated
Ember Protector
Figure 5 - Hearth Extension
126761-01A7
Seal Gap
Hearth
Extension
www.Astria.US.com
33°
SAFE ZONE
18" Min. to
Perpendicular
Side Wall
Figure 6 - Mantel Clearances to
Combustible Material
3" Max.
4.5"
Combustible
Material Must
Not Overlap
Front Face
Page 8
VENTING INSTALLATION
OPTIONAL OUTSIDE AIR KIT
(MODEL AK4/AK4F)
The installation of an outside air kit should
be performed during the rough framing of
the replace due to the nature of it's location.
Outside combustion air is accessed through
a vented crawl space (AK4F) or through a
sidewall (AK4).
CAUTION: Combustion air
inlet ducts shall not terminate
in attic space.
The maximum height for the
air vent can not exceed 3 feet
below the ue gas outlet of the
termination.
Secure to Collars with Metal Tape,
Screws or Straps (Min. of 1/4" x 20"
in size)
Air Inlet
Location
Must Allow
For Bushes
or Snow
Air Inlet
Eyebrow
Vented Crawl Space
(Check Local Codes
Before Installing in a
Vented Crawl Space)
Figure 7 - Outside Air Kit
CHIMNEY PIPE
The INNOVATIVE HEARTH PRODUCTS
chimney system consists of 12", 18", 24",
36" and 48" snap-lock, double-wall pipe segments, planned for maximum adaptability to
individual site requirements. Actual lengths
gained after tting overlaps must be taken
into consideration (lineal gain) and are given
in the lineal gain chart (see Figure 8). Lineal
Gain is the actual measurable length of a part
after two or more parts are connected. For
Canada, use chimney parts designated "HT".
Vent Hood
Required for
Wall Installation
www.Astria.US.com
WARNING: The opening in
the collar around the chimney at
the top of the replace must not
be obstructed. Never use blown
insulation to ll the chimney
enclosure.
PART NO.DESCRIPTIONGAIN
GeorgianFireplace66 1/2"
12-12DM
12-12HT
18-12DM
18-12HT
24-12DM
24-12HT
36-12DM
36-12HT
48-12DM
48-12HT
RLT-12D
RLT-12HT
STL-12D
* The lineal gain for the terminations is measured to the ue gas outlet height.
15 3/8"
Galvanized
Outer Pipe
12"
Stainless
Inner Pipe
ASSEMBLY AND INSTALLATION OF
DOUBLE WALL CHIMNEY SYSTEM
Each double wall chimney section consists of a
galvanized outer pipe, a stainless steel inner ue
pipe and a wire spacer. The pipe sections must
be assembled independently as the chimney is
installed. When connecting chimney directly to
the replace, the inner ue pipe section must
be installed rst with the lanced side up. The
outer pipe section can then be installed over
5 the ue pipe section with the hemmed end
up. Press down on each pipe section until the
lances securely engage the hem on the replace
starter. The wire will assure the proper spacing
between the inner and outer pipe sections.
LINEAL GAIN
Pipe Section10 5/8"
Pipe Section16 5/8"
Pipe Section23 5/8"
Pipe Section34 5/8"
Pipe Section46 5/8"
Round Termination7 3/4"
Square Chase-Top
with Slip Section
Figure 7 - Lineal Gain
*
7" to 15"*
Hemmed
End
126761-01A8
Page 9
VENTING INSTALLATION
Continued
Continue to assemble chimney sections as
outlined above, making sure that both the
inner and outer pipe sections are locked together. When installing double wall snap-lock
chimney together, it is important to assure
the joint between the chimney sections is
locked. Check by pulling chimney upward
after locking. The chimney will not come apart
if properly locked. It is not necessary to add
screws to keep the chimney together (exception, see Figure 9).
USING ELBOW OFFSETS (30E-12DM)
1.
To achieve desired offset, you may install
combinations of 12", 18", 24", 36" and 48"
length of double wall pipe (see offset chart
and Figure 9).
2.
Chimney weight above offset rests on return elbow. Straps must be securely nailed
to rafters or joists (see Figure 9, details A
and B).
3. Maximum length of pipe between supports (return elbow or 12S-12DM) is 6'
of angle run. Maximum of two 6' angle
run sections per chimney system (see
Figure 11, page 9).
4. All pipe connections between the offset
and return must be secured with two
screws on the outer pipe only (see
Figure 9). Do not penetrate the inner
stainless.
Straps
Straps
Straps
Detail B
Angle Firestop
Straps
Detail A
Return Elbow
Figure 11 - Ceiling Support Pipe
12S-12DM
CAUTION: THE STRUCTURAL
INTEGRITY OF THE MANUFACTURED
HOME FLOOR, WALL, AND CEILING/
ROOF MUST BE MAINTAINED.
See Detail A
2" Min.
See Detail B
A
Figure 10 - Elbow Offset
126761-01A9
www.Astria.US.com
WARNING: DO NOT INSTALL IN
SLEEPING ROOM OF MOBILE HOMES.
Page 10
VENTING INSTALLATION
Continued
Return
Elbow
Offset
Elbow
6' Max.
Return
Elbow
6' Max.
Offset
Elbow
ABC
Figure 11 - Typical Offset Terminations
Offset
Elbow
Return
Elbow
Offset
Elbow
FIRESTOP SPACERS (FS-10)
Firestop spacers are required at each point
where the chimney penetrates a oor space.
Their purpose is to establish and maintain
the required clearance between the chimney
and the combustible materials. When the pipe
passes through a framed opening into a living
space above, the restop must be placed onto
the ceiling from below as shown in Figure 12.
They also provide complete separation from
one oor space to another or attic space as
required by most codes. When the double wall
pipe passes through a framed opening into an
attic space, the restop must be placed into an
attic oor as shown in Figure 13.
Existing
Ceiling
Frame
Firestop
Spacer
Screws or
Staples
(Min. of 8)
Figure 12 - Firestop Spacer with Living
Space Above Ceiling
Return
Elbow
6' Max.
Offset
6' Max.
Firestop
Spacer
Elbow
Figure 13 - Firestop Spacer with Attic
Space Above Ceiling
Return
Elbow
Ceiling
Support Pipe
12S-12DM
6' Max.
Screws or Staples
(Min. of 8)
6' Max.
Existing
Ceiling
Frame
PENETRATING ROOF
To maintain a 2" clearance to the pipe on a
roof with a pitch, a rectangular opening must
be cut.
1. Determine center point through which pipe
will penetrate roof.
2. Determine center point of roof. Pitch is
distance the roof drops over a given span,
usually 12". A 6/12 pitch means that roof
drops 6" for each 12" measured horizontally down from roof rafters.
3. Use roof opening chart (Figure 14, page
10) to determine correct opening length
and ashing required.
4. Remove shingles around opening measured. Cut out this section.
www.Astria.US.com
126761-01A10
Page 11
VENTING INSTALLATION
Continued
5. Add next sections of pipe until end
penetrates roof line. Check to see that
proper clearances are maintained. Extend
chimney by adding sections of double wall
pipe until pipe is minimum of 30" above
highest point of roof cutout. Termination
and chimney must extend a minimum of
36" above highest point where it passes
through roof.
19.5" Min.
2" Min.
2" Min.
30" Min.
2" Min.
Opening "A"
Installing Flashing on a Metal Roof
When installing the ashing on a metal roof,
it is required that putty tape be used between
the ashing and the roof. The ashing must be
secured to the roof using #8 x 3/4" screws and
then sealed with roof coating to prevent leakage through the screw holes. A roof coating
must also be applied around the perimeter of
the ashing to provide a proper seal.
Storm Collar
Flashing
Overlap
Shingles Top
and Sides Only
Cone
Nail Only
Outer
Perimeter
of Flashing
PitchSlope Opening
"A" Max.
Flat0°19.5"V6F-10DM
0-6/1226.6°22'V6F-10DM
6/12-12/12 45.0°27"V12F-10DM
Used Flashing
Model No.
Figure 14 - Roof Opening Measurements
FLASHING INSTALLATION (V6F-10DM
OR V12F-10DM)
Determine the ashing to be used with the
roof opening chart. Slide ashing over pipe
until base is at against roof. Replace as
many shingles as needed to cover exposed
area and ashing base. Secure in position by
nailing through shingles (see Figure 15). DO
NOT NAIL THROUGH FLASHING CONE.
Underlap Shingles
at Bottom
Figure 15 - Flashing Installation
Storm Collar Installation (SC2-1)
Place storm collar over pipe and slide down
until it is snug against the open edge of the
ashing (see Figure 16). Apply waterproof
caulk around the perimeter of the collar to
provide a proper seal.
Chimney
Pipe
Waterproof
Caulk
Storm
Collar
Flashing
Figure 16 - Storm Collar
126761-01A11
www.Astria.US.com
Page 12
VENTING INSTALLATION
Continued
Terminations/Spark Arrestor
The replace system must be terminated with
the listed round top or chase terminations. In
any case, refer to the installation instructions
supplied with the termination.
CAUTION: Do not seal open-
ings on the rooftop ashing. Fol-
low the installation instructions
provided with the termination
being used.
Stainless
Inner Flue
Pipe
Secure
Termination
to Outer
Pipe with 3
Screws
Overlap
Shingles (Top
and Sides of
Flashing Base)
Figure 17 - Termination
RLT-12D
Level of
Flue Gas
Outlet
Waterproof
Caulking
Storm
Collar
Flashing
Underlap
Shingles
18"
Min.
Typ.
24" Min.
24" Min.
Figure 18 - Multiple Chase Installation
10 FOOT RULE
All ue gas outlet chimney terminations must
extend a minimum of 3 feet in height above
the highest point where it passes through
the roof and must be at least 2 feet above
the highest point of the roof that is within a
horizontal distance of 10 feet (see Figure 19).
3' Min.
Level of
Flue Gas
Outlet
10'
2' Min.
3' Min.
10'
2' Min.
CHASE INSTALLATIONS
Instructions for chase installations are
included with the chase style termination
chosen. In a multiple chase installation, be
sure to provide adequate distance between
terminations to prevent smoke spillage from
one termination to another. We suggest that
terminations be separated at least 24", center
to center and stacked at a vertical height difference of 18" (see Figure 18).
Note: If a decorative shroud is to be installed,
contact the manufacturer for specications.
www.Astria.US.com
Figure 19 - 10 Foot Rule
FINISHING FIREPLACE
Combustible materials, such as wallboard,
gypsum board, sheet rock, drywall, plywood,
etc. may make direct contact with sides and top
around the replace face. It is important that
combustible materials do not overlap the face
itself. Brick, glass, tile or other noncombustible
materials may overlap the front face provided
they do not obstruct essential openings like
louvered slots or any other opening. When
overlapping with a noncombustible facing
material, use only noncombustible mortar or
adhesive.
126761-01A12
Page 13
FIREBRICK WALL INSTALLATION
IMPORTANT: Installation of brick
should be done after the re-
place is placed in a permanent
location.
1. The replace is shipped with the hearth
preinstalled. It is held in place for shipping with 3 shipping brackets (Figure 20).
Remove these brackets before installing
any of the other rebrick walls.
Shipping
Brackets
Figure 20 - Removing Shipping Brackets
2. Install the left and right rebrick walls.
There is a bracket with 2 tabs on the
bottom of each rebrick wall. Angle the
wall into the replace opening and into
the slots on the side of the hearth (Figure
21), then tilt the top of the panel toward
the rebox surround.
Slot
Hearth
Figure 21 - Slots for Firebrick Walls
3. Secure the rebrick wall using 2 of the
retainers provided. The bracket will slip
underneath the metal lip on the top of the
wall and screw into the inner dome of the
replace (Figure 22).
Right Wall
Right Face
Retaining
Bracket
Leading
Bricks
Figure 22 - Installing Side Walls
126761-01A13
www.Astria.US.com
Page 14
FIREBRICK WALL INSTALLATION
Continued
4. Install the rear rebrick wall last. Place the
wall face side down on the hearth with the
bottom of the wall toward the rear of the
rebox and the top toward the front of the
replace. Tilt the wall up toward the back
of the rebox. Secure with 2 rear retaining
brackets provided (Figure 23).
Retaining
Bracket
Figure 23 - Installing Rear Wall
5. It is recommended that the joints between
all rebrick walls be grouted for a more
nished look. See left for grouting instructions.
For more information and to watch a how to
video go to www.fmiproducts.com and select
Technical Support.
GROUTING INSTRUCTIONS
Material provided:
Bag of cement
Bag of sand
Material required:
Piping bag
Joints striker
Heavy duty mixing bucket
Sponge or Wet Cloth
1. Moisten brick surface with damp sponge
or spray bottle just prior to application.
When bricks are wet, any excess grout
mixture on bricks will easily wipe off.
2. In a heavy duty mixing bucket, add equal
parts cement and sand. Add enough water
and mix together well using a power drill
with mixing wand attachment to a yogurt
like consistency. Not adding enough water
can lead to grout falling out after burning.
3. The overall length of piping bag should be
about 16". If the bag is longer than 16",
cut it down to size by removing end with
larger opening. This will make the bag
easier to handle.
4. Put grout mixture into piping bag making
sure the smaller opening is downward and
over a moist towel to avoid spilling. Place
a wet towel over the bucket making sure it
is directly on the surface of grout mixture.
This will keep the mixture moist and it will
not dry out before use.
5. Grout all joints where two rebrick walls
come together.
6. Using a trowel, remove excess grout mixture by moving trowel in the direction of
the joint. Grout mixture in the joint should
now be ush with brick surface. If not
enough grout is applied into each space,
grout may fall out after burning.
7. Using a joint striker, smooth out grout line.
Allow 72 hours before
operating replace.
www.Astria.US.com
126761-01A14
Page 15
FIREBRICK WALL INSTALLATION
Continued
INSTALLING SCREEN
1. Slide round end of screen rod into rings at
top of screen. Attach one push-on nut to end
of rod before attaching last ring of screen.
2. Insert the round end screen rod into hole
on the left and right side of smoke shelf
(Figure 24).
3. Mount at end of screen rod with #10 x 5/8"
to center of smoke shelf.
4. Install other screen rod in same manner.
Rating
Plate
Figure 24 - Installing Fireplace Screen
Hole for Screen
Rod
Leading
Bricks
INSTALLING GRATE RETAINERS
1. Place the provided grate retainers on the
hearth as shown in Figure 25. The back
of the retainer will be ush with the rear
rebrick wall. Mark the center of the hole
on the hearth with a marker.
2. Drill two holes in the hearth in the marked
locations using a masonry 3/16" drill bit.
3. Secure grate retainer with masonry screws
provided.
WARNING: Risk of re! Re-
place grate with INNOVATIVE
HEARTH PRODUCTS grate only
(see Parts, page 22). This grate
has been designed to keep the
operation of your replace safe
and efcient.
Figure 25 - Installing Grate Retainers
126761-01A15
www.Astria.US.com
Page 16
OPTIONAL GAS LINE INSTALLATION
Gas line hook up should be done by your
supplier or a qualied service person.
Note: Before you proceed, make sure your
gas supply is turned off.
Use only a 1/2" black iron pipe and appropriate ttings.
1. Remove knockout indentation on refractory or rebrick wall located above refractory hearth oor. Knockout indentation
must be rmly tapped with any solid object
such as a 1/2" dowel until it is released.
Remove fragmented portions of refractory
(see Figure 26).
2. Remove gas line cover plate located on
either side of replace and pull out insulation from gas line conduit sleeve. Save
insulation for reuse. Replace screws.
3. Run a 1/2" black iron gas line into replace
through the rear at gas line conduit sleeve (if
using a raised platform, add height). Provide
sufcient gas line into replace chamber for
tting connection (see Figure 27).
Note: Secure incoming gas line to wood
framing to provide rigidity for threaded end.
4. Repack insulation around gas line and into
sleeve opening. Seal any gaps between
gas line and refractory knockout hole with
refractory cement or commercial furnace
cement, Install the gas appliance or cap-off
gas line if desired.
CAUTION: All gas piping
and connections must be tested
for leaks after the installation
is completed. After ensuring
that the gas valve is on, apply
soap and water solution to all
connections and joints. Bubbles
forming show a leak. Correct
all leaks at once. DO NOT USE
AN OPEN FLAME FOR LEAK
TESTING AND DO NOT OPERATE ANY APPLIANCE IF A LEAK
IS DETECTED. LEAK TESTING
SHOULD BE DONE BY A QUALIFIED SERVICE PERSON.
WARNING: Do not operate an
unvented gas log set in this replace with the chimney removed.
Outside of
Fireplace
Gas Line
Conduit
Insulation
Gas
Conduit
Cover
Figure 26 - Gas Line Access
Outside of
Fireplace
Gas Line
Conduit
Repack
Insulation
Figure 27 - Gas Line Installation
A gas line or gas log lighter may be installed
for the purpose of installing a vented or ventfree decorative gas appliance incorporating an
automatic shutoff device and complying with
the Standard for Decorative Gas Appliances for
Installation in Vented Fireplaces, ANSI Z21.60
or American Gas Association draft requirements
for Gas Fired Log Lighters for Wood Burning
Fireplaces, Draft NO. 4 dated August, 1993.
If you install a decorative gas appliance
(vented gas log), the decorative gas appliance
must comply with the Standard for Decorative
Gas Appliance for Installation in Solid Fuel
Burning Fireplaces, ANS Z21.60 or Z21.84
and shall also be installed in accordance with
the National Fuel Gas Code, ANSI 7223NFPA
54 latest edition.
Remove
Knockout
Incoming
1/2" Black
Iron Pipe
Seal
Opening
with
Refractory
Cement
Side
Firebrick
Finished
Side
1/2" Dowel
Brick with
Access
Hole
Side
Firebrick
Finished
Side
Provide Enough
Threaded
End for Fitting
Connection
www.Astria.US.com
126761-01A16
Page 17
OPTIONAL GAS LINE INSTALLATION
Continued
If you wish to install an unvented (vent-free)
gas log set, only unvented gas log sets which
have been found to comply with the standard
for unvented room heaters, ANSI Z21.11.2 are
to be installed in this replace.
WARNING: If the replace
has been used for wood burning,
the rebox and chimney must be
cleaned of soot, creosote and
ashes be a qualied chimney
cleaner. Creosote will ignite if
heavily heated.
PUREFIRE HOOD INSTALLATION
1. The PureFire hood supplied with this replace is packaged in a separate box and
placed in the rebox during shipping.
2. Remove hood from box. Locate brackets
(quantity 2) and screws (quantity 4) for
hood installation in the hardware bag.
3. Using screws provided, secure the bracket
to the inner dome of the replace as shown
in Figure 28. The left and right bracket are
different. The edge that is straight will be
closer to the replace opening.
4. Lift hood up into the replace and place it
on the retaining brackets (Figure 28). The
rear of the hood will touching the rear of
the replace.
WARNING: When using a
decorative vented gas log, the
damper must be removed or
permanently locked in the fully
open position and the glass doors
must be in the fully open position.
Figure 28 - Installing PureFire Hood
NOTICE: THE FIREBOX CANOPY
(HOOD) MUST NOT BE MODIFIED
OR REPLACED WITH A CANOPY
THAT MAY BE PROVIDED WITH
THE UNVENTED DECORATIVE
ROOM HEATER.
AIR DEFLECTOR AND GLASS DOOR INSTALLATION
INSTALLING AIR DEFLECTORS (42''
MODELS ONLY)
Slide air deector in between the front side
face and side brick panel (see Figure 30, page
17). The notched end of the deector sits on
bottom hearth. Air deector does not require
any fastening.
The front side faces and side brick panels
will hold the deector in place (see Figure
30, page 17).
126761-01A17
www.Astria.US.com
DOOR FRAME MODELS
BDMO42/50E/G/C
Installation
1. Remove screws from smoke shelf (see
Figure 29, page 30).
2. Mount top door frame and secure with
screws provided (see Figure 29, page 17).
3. Place bottom door frame on top of ash lip
at front of replace (see Figure 30, page
17).
4. Secure bottom door frame to brick with
two hex screws provided as shown in
Figure 30, page 17 using a 7/16" open
end or adjustable wrench.
Page 18
AIR DEFLECTOR AND GLASS DOOR INSTALLATION
Continued
INSTALLING GLASS DOORS
Top Door
Frame
Smoke
Shelf
Spring clips have been installed but some
adjustments may be needed. Install the doors
using the following steps:
1. With bifold doors completely folded, insert
bottom pivot pin into pivot hole located
near bottom corner of front face opening
and swing door to vertical position making
sure top pins slide into door track. Door
is installed when top door pin snaps into
spring clip.
2. Repeat step 1 for remaining door.
If you nd the doors do not close properly or
do not appear level or straight, proceed with
section on door adjustment,
Figure 29 - Installing Top Door Frame
Air
Deector
Ash Lip
Bottom
Door
Frame
Ash Lip
Hex
Screw
Figure 30 - Installing Bottom Door Frame
and Air Deector
Fold Door
and Slide
Top Pins
Into Track
Figure 31 - Installing Bi-Fold Doors
Spring
Clip
Insert Pin
into Spring
Clip
Insert
Bottom
Pivot Pin
into Hole
Pivot
Hole
DOOR ADJUSTMENT
Remove doors and slightly loosen lower pivot
clips and upper spring clips. Replace doors
and fully close them. Use 1/8" shims (any
material) to level doors. Once proper setting
is achieved, carefully open doors enough so
that you can access spring clips with a phillips
screwdriver. Tighten screws. See Figure 32.
Figure 32 - Adjusting Bi-Fold Doors
www.Astria.US.com
126761-01A18
Page 19
OPERATION AND MAINTENANCE GUIDELINES
GLASS DOORS
Glass doors are optional with the replace.
When replace is in operation, doors must be
fully opened or fully closed position only or a re
hazard may be created (see Figure 33).
A replace equipped with glass doors operates
much differently than a replace with an open
front. A replace with glass doors has a limited
amount of air for combustion.
Excessive heat within the replace can result if
too large a re is built or if combustion air gate
is not completely open. The following tips should
be followed to assure that both the replace
and glass door retain their beauty and function
properly. Both the ue damper and glass doors
must be fully opened before starting re. This will
provide sufcient combustion air and maintain
safe temperatures in rebox.
IMPORTANT: The glass must be allowed to
warm slowly and evenly. The tempered glass will
withstand a gradual temperature rise to 550° F,
which is more than a normal re will generate.
Such materials as pitch/wax laden logs, very dry
mill end lumber and large amounts of paper or
cardboard boxes can create an excessively hot
re and should not be burned in this replace.
Always keep the re well back from the doors
and never allow ames to contact the glass.
WARNING: Fireplaces
equipped with glass doors
should be operated only with
doors fully opened or doors fully
closed. Doors, if left partly open,
may draw gas and ame out of
the replace opening creating
risks of both re and smoke.
Cleaning Glass
Clean glass with any commercial glass cleaner
or soap and water. Do not use any abrasive
material to clean glass. Do not clean glass with
any cool water if glass is still hot from the re
and smoke.
OUTSIDE AIR AND DAMPER
HANDLE OPERATION
The damper handle, which opens and closes
the damper blade, is located in the upper front
face of the replace. Pushing the handle forward and up through the keyway slot will free
damper blade to automatically open. Pushing
the handle forward and down will lock damper
blade closed (see Figure 34).
To Close
Damper
Doors Fully Closed
Fireplace Front
Doors
Fully Opened
Fireplace Front
Figure 33 - Bi-Fold Glass Doors
Damper
Weight
Damper
Weight
To Open
Damper
Figure 34 - Operating Damper Handle
126761-01A19
www.Astria.US.com
Page 20
PUREFIRE EMISSION CONTROL SYSTEM
This replace is equipped with a PureFire
Emission Control System. The Catalytic
Hood system reduces particulates emissions
in a wood burning replace to meet the EPA
Wood-Burning Fireplace Program Phase 2
emission level.
The EPA qualifying label, shown on page 20,
will be afxed to the catalyst. Before lighting
the rst re, remove and maintain this label in
a safe place if needed for permits or building
inspection. Prior to beginning installation, contact your local building ofcial to determine the
need to obtain a permit. For proper operation,
catalyst must be replace every 3 to 5 years.
FUELING GUIDELINES
The replace grate must always be secured to
the retaining brackets provided. The position
of the grate must be centered against the back
wall of the rebox.
Burn only dry, seasoned (cured) wood with
less than 20% moisture. Avoid the use of
treated, painted and laminated wood. Never
burn garbage or other foreign materials. Do
not use articial logs, colored newspaper or
petroleum based re starters. Avoid wood with
high salt content. All of these materials may
contain compounds which can shorten the
life of the catalyst. Wet or unseasoned wood
may lower catalytic temperatures and result
in inefcient operation.
The catalyst is designed to function at optimum efciency when the replace is burning
clean, dry, cord wood as replace fuel. A
simple visual inspection of the chimney during the wood burning process will determine
catalyst performance.
The fuel load should always be placed on
the back of the grate. Use clean dry wood,
seasoned cord wood is the best choice.
Never burn trash, plastics, gasoline, rubber,
industrial solvents, ammable liquids, naptha,
household garbage, material treated with
petroleum products, leaves, paper products,
cardboard or salt driftwood.
Refer to your INNOVATIVE HEARTH PRODUCTS Homeowner's Guide included with your
replace for proper re building technique and
ash removal procedures. These fueling guidelines must be followed in order to achieve
maximum emissions performance from the
PureFire System.
OPERATION
The proper use of a wood burning replace
equipped with the catalyst will signicantly
reduce the emissions that it produces. Simple
fuel considerations with regard to moisture
content, size, and quality of fuel will help
control the production of wood smoke and
improve the performance of the catalyst and
replace efciency. With proper care, the
catalyst will provide years of fuel savings
and lowered emissions. By following some
simple guidelines, you will ensure maximum
performance and longevity.
The smoke that is usually seen coming out
of a chimney is essentially a combination of
unburned fuel (carbon and hydrogen) and
moisture in the form of water vapor. The catalyst is a technology that provides secondary
combustion for the wood burning process.
MAINTENANCE
The PureFire System is a maintenance free
technology. Do not attempt to remove or clean
the combustor. The direct ame from the re
will clean the combustor. Only a certified
technician should remove the unit. To ensure
proper replace operation, the PureFire System should be replaced every 3 to 5 years
(see Parts on page 22).
NOTE: Chimney smoke may be visible during
the rst 8 to 10 minutes of replace operation
when the re is rst getting started and the
nal 8 to 10 minutes of operation while the re
is dissipating. Under normal operating conditions, you should see little or no smoke coming
out of the chimney. If continuous smoke is
visible, make sure only dry seasoned wood
is being burned. If visible smoke continues,
the combustor has ceased to function or
there is thermal crumbling. Call INNOVATIVE
HEARTH PRODUCTS at 1-800-655-2008 for
replacement parts.
www.Astria.US.com
126761-01A20
Page 21
PUREFIRE EMISSION CONTROL SYSTEM
Continued
PHASE 2 QUALIFIED
U.S. Environmental Protection Agency
Wood-burning Fireplace Program
Phase 2 Qualified models are cleaner and pollute less than those models that
have not met this emissions level. Exposure to smoke has been associated with
respiratory illness and other health problems. Models that have lower smoke
emissions may reduce your risk.
For more information go to www.epa.gov/burnwise
FIREPLACE
SMOKE EMISSIONS RANGE
Lower Emissions
0
Better
5.1
EPA PHASE 2 EMISSIONS LEVEL
4.4
Fireplaces with lower emissions produce less smoke when installed and operated properly.
THIS MODEL
Higher Emissions
12.0
Worse
MANUFACTURER: FMI Products, LLC
MODEL NO: GMCAT50 & VGMCAT50
PARTICLE EMISSIONS: 4.4 GRAMS/KG OF WOOD BURNED
For proper operation, catalyst must be replaced every 3 to 5 years.
* EPA has determined, based on testing by an accredited independent laboratory and a certification
of conformity by a nationally recognized certification body, that this model qualifies at the Phase 2
emissions level for U.S. EPA's Voluntary Fireplace Program.
INNOVATIVE HEARTH PRODUCTS
125574-03
U.S. Environmental Protection Agency
Wood-burning Fireplace Program
Phase 2 Qualified models are cleaner and pollute less than those models that
have not met this emissions level. Exposure to smoke has been associated with
respiratory illness and other health problems. Models that have lower smoke
emissions may reduce your risk.
FIREPLACE
SMOKE EMISSIONS RANGE
Lower Emissions
0
Better
Better
5.1
EPA PHASE 2 EMISSIONS LEVEL
4.4
Fireplaces with lower emissions produce less smoke when installed and operated properly.
MANUFACTURER: FMI Products, LLC
MODEL NAME: GMCAT42 42” Woodburning Fireplace
VGMCAT42 42” Woodburning Fireplace
PARTICLE EMISSIONS: 4.4 GRAMS/KG OF WOOD BURNED
*
EPA has determined, based on testing by an accredited independent laboratory and a certification
of conformity by a nation ally recognized certification body, that this model qualifies at the Phase 2
emissions level for U.S. EPA’s Voluntary Fireplace Program.
THIS MODEL
INNOVATIVE HEARTH PRODUCTS
Higher Emissions
12.0
Worse
Worse
For more information go to www.epa.gov/burnwise
126761-01A21
www.Astria.US.com
125574-08
Page 22
TECHNICAL SERVICE
You may have further questions about installation, operation, or troubleshooting. If so, contact INNOVATIVE HEARTH PRODUCTS at
1-800-655-2008.
REPLACEMENT PARTS
If this product is missing a part or has a broken
component, please do not return it to the store.
Call INNOVATIVE HEARTH PRODUCTS at
1-800-655-2008 to answer questions and
replace parts under warranty.
Note: Use only original replacement parts.
This will protect your warranty coverage for
parts replaced under warranty.
When calling please have your model and serial numbers of your replace ready.
You can also visit our web site at
www.Astria.US.com.
When calling or writing, please have your
model and serial numbers of your replace
ready.
Model and serial number information are in the
replace's rating plate located on the replace
smoke shelf.
www.Astria.US.com
126761-01A22
Page 23
PARTS
MODELS ORACLE CAT 42 AND ORACLE CAT 50
10
6
5
20
21
4
22
8
7
27
9
28
26
11
12
14
13
16/17
15
1
2
29
30
24
23
126761-01A23
19
3
25
www.Astria.US.com
18
Page 24
This list contains replaceable parts used in your rebox. When ordering parts, follow the
PARTS
instructions listed under Replacement Parts on page 21 of this manual.
KEY
NO.PART NO. DESCRIPTIONQTY.
1**Face Assembly••1
2**Firebox Bottom Assembly••1
3**Firebox Bottom••1
4**Firebox Surround••1
5**Outer Dome Assembly••1
6**Insulation Pan Support••1
7**Insulation Pan••1
8**Top Insulation••1
9110285-02 Fireplace Top Assembly, 42"•1
Canadian code CAN/ULC-S610-M87 and
other pertinent codes require stainless steel
chimney for the installation of this fireplace.
A Cold Air Climate Kit is also required in
Canada and is recommended for cooler
regions in the United Stated. Below, find a
list of approved stainless steel parts.
Chimney Parts List for Canada
Model No.
12-8HT12" Section Double Wall Pipe
18-8HT18" Section Double Wall Pipe
24-8HT24" Section Double Wall Pipe
36-8HT36" Section Double Wall Pipe
48-8HT48" Section Double Wall Pipe
30E-8HT30" Offset and Return
12S-8HTChimney Support
RT-8HTRound Top w/ Mesh Screen
RTT-8HT*Round Top w/ Slip Section
RLT-8HTRound Top w/ Louvers
RLTT-8HT*Round Top w/ Slip Section
ET-8HT*Square Top
ETL-8HT*Square Top w/ Slip Section
AP-8HTAnchor Plate/Collar Assembly
CAK-8Cold Air Collar Kit
*When ordered alone, this part cannot ship
via parcel delivery services.
8" Hi-Temp
Woodburning Chimney
& Mesh
& Louvers
(Masonry Fireplaces)
IMPORTANT NOTICE
A manufactured shroud which
has been approved by a national
testing agency for use with this
fireplace may be used if installed
in accordance with the instructions by its manufacturer. A
locally fabricated shroud may be
used with IHP Shroud Leg Spacer
Kit (SLK) in accordance with
instructions provided with the
shroud.
IMPORTANT NOTICE
When penetrating a ceiling
into an attic, a firestop thimble
(38FST or FST30) is required
to avoid intrusion by insulation
and recommended to negotiate a
joist.
Thimble 38FST
or FST 30
NOTICE: The firebox canopy (hood)
must not be modified or replaced with
a canopy that may be provided with
the unvented decorative room heater.
CAUTION: THE STRUCTURAL INTEGRITY OF
THE MANUFACTURED HOME FLOOR, WALL,
AND CEILING/ROOF MUST BE MAINTAINED.
WARNING: DO NOT INSTALL IN SLEEPING
ROOM OF MOBILE HOMES.
WARNING: Discontinue use of the
appliance immediately if doors
are damaged and contact a qualified installer for repair. Only doors
certified with the appliance shall
be used.
WARNING: Do not slam or strike
doors. Damage can result in a hazardous condition.
www.Astria.US.com
Firestop
126761-01A32
Page 33
NOTES
126761-01A33
www.Astria.US.com
Page 34
Innovative Hearth Products
Astria™ Brand Wood-Burning Fireplace
20 Year Limited Warranty
THE WARRANTY
Innovative Hearth Products ("IHP") 20 Year Limited Warranty warrants your Astria™ brand wood burning fireplace ("Product") to be free from defects in materials and
workmanship at the time of manufacture. The Product body, firebox and ceramic glass carry the 20 Year Limited Warranty. Ceramic glass carries the 20 Year Limited Warranty against thermal breakage only. After installation, if covered components manufactured by IHP are found to be defective in materials or workmanship during the 20
Year Limited Warranty period and while the Product remains at the site of the original installation, IHP will, at its option, repair or replace the covered components. If repair
or replacement is not commercially practical, IHP will, at its option, refund the purchase price or wholesale price of the IHP product, whichever is applicable. IHP will also
pay IHP prevailing labor rates, as determined in its sole discretion, incurred in repairing or replacing such components for up to five years. THERE ARE EXCLUSIONS AND
LIMITATIONS to this 20 Year Limited Warranty as described herein.
COVERAGE COMMENCEMENT DATE
Warranty coverage begins on the date of installation. In the case of new home construction, warranty coverage begins on the date of first occupancy of the dwelling or six
months after the sale of the Product by an independent IHP dealer/distributor, whichever occurs earlier. The warranty shall commence no later than 24 months following the
date of product shipment from IHP, regardless of the installation or occupancy date.
EXCLUSIONS AND LIMITATIONS
This 20 Year Limited Warranty applies only if the Product is installed in the United States or Canada and only if operated and maintained in accordance with the printed
instructions accompanying the Product and in compliance with all applicable installation and building codes and good trade practices.
This warranty is non-transferable and extends to the original owner only. The Product must be purchased through a listed supplier of IHP and proof of purchase must be
provided. The Product body and firebox carry the 20 Year Limited Warranty from the date of installation. Vent components, trim components, paint and applied stains are
excluded from this 20 Year Limited Warranty. The following do not carry a 20 Year Limited Warranty but are warranted as follows:
Air tubes, baffles and brick retainers – Repair or replacement for one year from the date of installation
Cast iron parts – Replacement for one year from date of installation
Electrical components – Repair or replacement for one year from the date of installation
Fireplace screens, refractory and side shields (metal or refractory) – Repair or replacement for two years from date of installation. Excludes hairline cracks.
Fuel grates –These parts are considered consumable accessories and therefore are not warranted, with the exception of defects in material or workmanship which
are covered for 90 days from the date of installation
Gaskets – Replacement for one year from date of installation
Gold & nickel plating – Replacement for two years from date of installation. Excludes tarnishing
Optional glass doors – Repair or replacement for 90 days from the date of installation
Labor coverage – Prevailing IHP labor rates apply for the warranty period of the component.
Parts not otherwise listed carry a 90 day warranty from the date of installation.
Whenever practicable, IHP will provide replacement parts, if available, for a period of 10 years from the last date of manufacture of the Product.
IHP will not be responsible for: (a) damages caused by normal wear and tear, accident, riot, fire, flood or acts of God; (b) damages caused by abuse, negligence, misuse, or
unauthorized alteration or repair of the Product affecting its stability or performance. (The Product must be subject to normal use with approved fuels listed in the Operation
Manual provided with the product. This includes burning such fireplace fuels as wood and natural or propane gas. Fuel products with abnormal burning characteristics,
including but not limited to fuel such as driftwood, coal or plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the
Product or may cause it to function improperly.); (c) damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with
the Product; (d) damages, repairs or inefficiency resulting from faulty installation or application of the Product.
Coverage of this 20 Year Limited Warranty is conditional upon use of an adequate fuel grate on factory-built fireplaces only, when applicable.
IHP is not responsible for inadequate fireplace system draft caused by air conditioning and heating systems, mechanical ventilation systems, or general construction conditions which may generate negative air pressure in the room in which the appliance is installed. Additionally IHP assumes no responsibility for smoking conditions caused by
inadequate chimney height, adjoining trees or buildings, adverse wind conditions or unusual environmental factors and conditions. Certain IHP Products are listed for use with
Security Chimneys International, Ltd. or IHP chimney systems only. Use of chimney components other than that specified in the Product manual will void the Product warranty.
This 20 Year Limited Warranty covers only parts and labor as provided herein. In no case shall IHP be responsible for materials, components or construction which are
not manufactured or supplied by IHP or for the labor necessary to install, repair or remove such materials, components or construction. Additional utility bills incurred due
to any malfunction or defect in equipment are not covered by this 20 Year Limited Warranty. All replacement or repair components will be shipped F.O.B. from the nearest
stocking IHP factory.
LIMITATION ON LIABILITY
It is expressly agreed and understood that IHP’s sole obligation and the purchaser’s exclusive remedy under this warranty, under any other warranty, expressed or implied,
or in contract, tort or otherwise, shall be limited to replacement, repair, or refund, as specified herein.
In no event shall IHP be liable for any incidental or consequential damages caused by defects in the Product, whether such damage occurs or is discovered before or after
replacement or repair, and whether such damage is caused by IHP’s negligence. IHP has not made and does not make any representation or warranty of fitness for a particular
use or purpose, and there is no implied condition of fitness for a particular use or purpose.
IHP makes no expressed warranties except as stated in this 20 Year Limited Warranty. The duration of any implied warranty is limited to the duration of this expressed warranty.
No one is authorized to change this 20 Year Limited Warranty or to create for IHP any other obligation or liability in connection with the Product. Some states and provinces
do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. The provisions of this 20 Year
Limited Warranty are in addition to and not a modification of or subtraction from any statutory warranties and other rights and remedies provided by law.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
IHP reserves the right to investigate any and all claims against this 20 Year Limited Warranty and to decide, in its sole discretion, upon the method of settlement.
To receive the benefits and advantages described in this 20 Year Limited Warranty, the appliance must be installed and repaired by a licensed contractor approved by IHP.
Contact IHP at the address provided herein to obtain a listing of approved dealers/distributors. IHP shall in no event be responsible for any warranty work done by a
contractor that is not approved without first obtaining IHP's prior written consent.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this warranty to be valid, you must contact the IHP dealer/distributor from which you purchased the product. If you cannot locate the dealer/
distributor, then you must notify IHP in writing. IHP must be notified of the claimed defect in writing within 90 days of the date of failure. Notices should be directed to the
IHP Warranty Department at 1508 Elm Hill Pike, Suite 108; Nashville, TN 37210 or visit our website at WWW.ASTRIA.US.COM.