Astria Blaze&Glow18TN, Blaze&Glow18TP, Blaze&Glow24TN, Blaze&Glow24TP Installation And Operation Instructions Manual

Page 1
Installation and Operation Instructions
P126832-01
Astria™ Unvented (Vent-Free) Gas Log Heater
P/N 126832-01 Rev. A 02/2014 Models
Blaze&Glow18TN Blaze&Glow18TP Blaze&Glow24TN Blaze&Glow24TP
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built fireplace or in a listed ventless firebox enclosure. It is design-certified for these installations in accordance with ANSI Z21.11.2. Exception: DO NOT install this appliance in a factory-built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs.
This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 6 of this manual.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Page 2
TABLE OF CONTENTS
Safety .................................................................. 2
Unpacking............................................................ 5
Product Identication ........................................... 5
Local Codes......................................................... 5
Product Features ................................................. 6
Air For Combustion and Ventilation ..................... 6
Installation ........................................................... 9
Operation ........................................................... 24
Inspecting Burners............................................. 26
Cleaning and Maintenance ................................ 27
Optional Positioning of
Thermostat Sensing Bulb .................................. 28
SAFETY
Troubleshooting ................................................. 29
Specications .................................................... 33
Blaze&Glow Log Sets ........................................ 33
Parts .................................................................. 34
Replacement Parts ............................................ 40
Service Hints ..................................................... 40
Technical Service............................................... 40
Accessories ....................................................... 40
Warranty ............................................................ 41
WARNING: Improper
installation, adjustment, alteration, service or maintenance can cause injury or property dam­age. Refer to this manual for correct installation and operational proce­dures. For assistance or additional information consult a qualified in­staller, service agency or the gas supplier.
WARNING: This ap­pliance is for installation only in a solid-fuel burning masonry or UL127 factory-
built replace or in a listed
ventless firebox enclo-
sure. It is design-certied
for these installations in accordance with ANSI Z21.11.2. Exception: DO NOT install this appliance
in a factory-built replace
that includes instructions stating it has not been test­ed or should not be used with unvented gas logs.
WARNING: This is an
unvented gas-red heat­er. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air
for Combustion and Ven­tilation section on page 6
of this manual.
This appliance may be in­stalled in an aftermarket,* permanently located, manufactured (mobile) home, where not prohib­ited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Page 3
SAFETY
Continued
WARNING: This product con­tains and/or generates chemicals known to the state of California to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op-
erate or service this replace. Improper use of this replace
can cause serious injury or death from burns, re, explo­sion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the u, with headaches, dizziness or nausea. If you have these signs, the replace may not be
working properly. Get fresh air at once! Have replace serviced. Some people are more af­fected by carbon monoxide than others. These
include pregnant women, people with heart or lung disease or anemia, those under the inu-
ence of alcohol and those at high altitudes. Natural and Propane/LP gases are odorless.
An odor-making agent is added to these gases.
The odor helps you detect a gas leak. However,
the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of
this replace.
WARNING: Any change to this heater or its controls can be dangerous.
WARNING: Do not use a blower insert, heat exchanger insert or other accessory not ap­proved for use with this heater.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner
ame patterns. Altered burner
patterns can cause sooting.
Due to high temperatures, the appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any objects on the heater.
Heater base assembly becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will remain hot for a time after shutdown. Allow surface to cool before touching.
Carefully supervise young chil­dren when they are in the room with heater.
You must operate this heater
with the replace screen and hood in place. Make sure re-
place screen and hood are in place before running heater.
The replace screen shall have
openings for introduction of combustion air.
Keep the appliance area clear and free from combustible materials, gasoline and other
ammable vapors and liquids.
Page 4
SAFETY
Continued
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/ LP supply tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup­plier’s instructions
• if you cannot reach your gas supplier,
call the re department
4. This heater shall not be installed as a vented appliance.
5. Before installing in a solid fuel burning re­place, the chimney ue and rebox must be cleaned of soot, creosote, ashes and loose paint by a qualied chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney ue may create and distribute
soot within the house. Inspect chimney
ue for damage. If damaged, repair ue and rebox before operating heater.
6. Do not burn solid-fuel in a replace in
which a vent-free room heater is installed.
7. If replace has glass doors, never operate
this heater with glass doors closed. Any glass doors shall be fully opened when the appliance is in operation. If you operate
heater with doors closed, heat buildup inside replace will cause glass to burst.
Make sure there are no obstructions
across openings of replace.
8. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance, page 29.
9. Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated, the vapors from these products may
create a white powder residue within burner box or on adjacent walls and furniture.
10. This heater needs fresh, outside air ven­tilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if enough fresh air is not available. See Air for Combustion and Ventilation,
page 6. If heater keeps shutting off, see Troubleshooting, page 31.
11. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
12. Do not use this heater to cook food or burn paper or other objects.
13. Do not use heater if any part has been ex­posed to or under water. Immediately call
a qualied service technician to inspect
the room heater and to replace any part of the control system and any gas control which has been under water.
14. Do not operate heater if any log is broken. Do not operate heater if a log is chipped (dime-sized or larger).
15. Turn heater off and let cool before servic-
ing, installing or repairing. Only a qualied service person should install, service or
repair heater.
16. Operating heater above elevations of
4,500 feet may cause pilot outage.
17. To prevent performance problems, do not
use propane/LP fuel tank of less than 100 lb. capacity (propane/LP units only).
18. Provide adequate clearances around air openings.
www.Astria.US.com
126832-01A4
Page 5
UNPACKING
CAUTION: Do not remove the data plates from the grate as­sembly. The data plates contain important warranty and safety information.
1. Remove logs and heater base assembly from cartons.
PRODUCT IDENTIFICATION
Left Side
Base Assembly
Ignitor on the side
Note: Do not pick up heater base assem-
bly by burners. This could damage heater. Always handle base assembly by grate.
2. Remove all protective packaging applied to logs and heater for shipment.
3. Check heater for any shipping damage. If heater is damaged call INNOVATIVE HEARTH PRODUCTS at 1-800-655-2008 for replacement parts before returning to dealer.
Rear Burner
Front
Figure 1 - Product Identication
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Right Side
Control Knob
State of Massachusetts: The installa­tion must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the Commonwealth of Massachusetts.
126832-01A 5
www.Astria.US.com
Page 6
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by
both realistic ames and glowing coals. This
heater is designed for vent-free operation with ue damper closed. It has been tested and ap­proved to ANSI Z21.11.2 standard for unvented heaters. State and local codes in some areas prohibit the use of vent-free heaters.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a room or space unless the required vol­ume of indoor combustion air is provided by the method de­scribed in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or
applicable local codes. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efcient than ever. New materials, increased insulation
and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in.
During heating months, home owners want
their homes as airtight as possible. While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning ap­pliances need fresh air for proper combustion and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
www.Astria.US.com
SAFETY DEVICE
This heater has a pilot with an Oxygen Deple­tion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
ELECTRONIC IGNITION SYSTEM
This heater has an electronic ignitor to light heater fuel supply.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion
and ventilation. However, in buildings of un­usually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where: a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 less with openings gasketed or sealed and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
-11
kg per pa-sec-m2) or
126832-01A6
Page 7
AIR FOR COMBUSTION AND VENTILATION
Continued
If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 8.
If your home does not meet all of the three criteria above, proceed to Determin­ing Fresh-Air Flow For Heater Location, below.
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/ NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu/hr (4.8 m3 per kw) of the aggregate
input rating of all appliances installed in that
space and an unconned space as a space
whose volume is not less than 50 cubic feet
per 1,000 Btu/hr (4.8 m3 per kw) of the ag-
gregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are
installed*, through openings not furnished with doors, are considered a part of the un­conned space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Conned or Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will install
replace plus any adjoining rooms with door­less passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20
= 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free replace __________ Btu/Hr Gas water heater* __________ Btu/Hr Gas furnace __________ Btu/Hr Vented gas heater __________ Btu/Hr Gas replace logs __________ Btu/Hr Other gas appliances* + _________ Btu/Hr Total = _________ Btu/Hr * Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Example: Gas water heater __________ Btu/Hr Vent-free replace + _________ Btu/Hr Total = _________ Btu/Hr
4.
Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_______ Btu/Hr (maximum can support) _______ Btu/Hr (actual amount used) Example: 51,200 Btu/Hr (maximum the
73,000 Btu/Hr (actual amount of
The space in the above example is a conned
space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can sup­port. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an unconned space, remove door to adjoin­ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 8.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr replace, if lower Btu/
Hr size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is an unconned space. You will need no additional
fresh air ventilation.
space can support)
Btu/Hr used)
40,000 33,000 73,000
126832-01A 7
www.Astria.US.com
Page 8
AIR FOR COMBUSTION AND VENTILATION
Outlet Air
Ventilated Attic
Outlet A
ir
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Or
Remove Door into Adjoining
Room, Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into Adjoining
Room,
Option 1
12"
12"
Continued
WARNING: If the area in which the heater may be operated does not meet the required volume for indoor combustion air, combus­tion and ventilation air shall be provided by one of the methods described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code, or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two perma­nent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size
of ventilation grills or ducts. IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo­stat-controlled power vent. Heated air entering the attic will activate the power vent.
Figure 3 - Ventilation Air from Outdoors
Figure 2 - Ventilation Air from Inside Building
www.Astria.US.com
126832-01A8
Page 9
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri­mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualied ser­vice person must install heater. Follow all local codes.
WARNING: Before installing
in a solid fuel burning replace, the chimney ue and rebox
must be cleaned of soot, creo­sote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly
heated. A dirty chimney ue may
create and distribute soot within the house. Inspect chimney and
rebox ue for damage. If dam­aged, repair ue and rebox
before operating heater.
WARNING: Seal any fresh air vents or ash clean-out doors located on oor or wall of re­place. If not, drafting may cause pilot outage or sooting. Use a heat-resistant sealant. Do not
seal chimney ue damper.
WARNING: Never install the heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture,
clothing or other ammable
objects are less than 36" from the front and 42" from top heater, For side clearances see Figure 4 page 10
• in high trafc areas
• in windy or drafty areas
CAUTION: This heater cre­ates warm air currents. These currents move heat to wall sur­faces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning u­ids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventila-
tion, page 6.
126832-01A 9
www.Astria.US.com
Page 10
INSTALLATION
Continued
CHECK GAS TYPE
Use the correct type of gas (natural or propane/ LP). If your gas supply is not the correct gas
type, do not install heater. Call dealer where
you bought heater for proper type heater.
WARNING: This appliance is equipped for either natural gas or propane/LP gas but not both. Gas type is indicated on the rat­ing plate. Field conversion is not permitted.
INSTALLATION AND CLEARANCES FOR VENT-FREE OPERATION
WARNING: Maintain the minimum clearances. If you can, provide greater clearances
from oor, ceiling and adjoining
wall.
Minimum Fireplace Clearance to
Combustible Materials
Side Wall 16", Ceiling 42", Floor 5",
Front 36"
Carefully follow these instructions. This will
ensure safe installation into a masonry, UL127-listed manufactured replace or listed vent-free rebox.
Minimum Clearances For Side Combustible Material, Side Wall and Ceiling
A. Clearances from the side of the replace
cabinet to any combustible material and wall should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and protrudes 3 1/2" from the wall. This com­bustible material must be 4" from the side
of the replace cabinet (see Figure 4).
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturer’s instructions for minimum clearances to combustible materials.
B. Clearances from the top of the replace
opening to the ceiling should not be less than 42".
Example
LOG SIZING REQUIREMENTS
Log Set
Model No.
BisonMtn18 17'' 14.5'' 26'' 20'' BisonMtn24 17'' 14.5'' 29'' 22''
BisonMtn30 21'' 14.5'' 32'' 22'' AndesMtn18 17" 13.5" 20" 14" AndesMtn24 17" 13.5" 26" 18" AndesMtn30 21'' 13.5'' 32'' 22'' AndesMtn36 21'' 13.5'' 38'' 27.5''
RedWoodM18 17'' 13.5'' 20'' 14'' RedWoodM24 17'' 13.5'' 26'' 18'' RedWoodM30 21'' 13.5'' 32'' 22''
Minimum Firebox Size
Height Depth
Front
Width
Rear* Width
www.Astria.US.com
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
126832-01A10
Page 11
INSTALLATION
Minimum Noncombustible Material
Minimum Noncombustible Material Height
Distances to Underside of Mantel
Top of Fireplace Opening
Underside of Mantel Shelf
12"
8"
(A)
18"
14"
20"
17"
22"
19"
24"
20"
All minimum distances are in inches
Log Set 24"/30"/36" Models 18" Model
2 1/2"
6"
8"
10"
Mantel Shelf
Heat Resistant Material
(A)
Continued
MINIMUM NONCOMBUSTIBLE MATERIAL CLEARANCES
If Not Using Mantel
Note: If using a mantel proceed to If Using Mantel. If not using a mantel, follow the infor­mation on this page.
You must have noncombustible material(s)
above the replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be­hind it. Noncombustible material must extend at least 8" up (for all models). If noncombus-
tible material is less than 12", you must install the replace hood accessory (24", 30" and
36" Models Only). See Figure 5 for minimum clearances.
Noncombustible
Material
Distance (A)
1
2" or more Noncombustible mate-
Between 8" and 12"
Less than 8"
Requirements for Safe
Installation
rial OK.
24", 30" or 36" Models: Install replace hood
accessory (GA6050 or GA6053 see Acces-
sories, page 45). 18"
Model: Noncombustible material OK. Noncombustible mate­rial must be extended to at least 8". See
Between 8" and 12",
above. If you cannot ex-
tend material, you must operate heater with ue
damper open.
If Using Mantel
You must have noncombustible material(s)
above the replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be­hind it. Noncombustible material must extend at least 8" up (for all models). If noncombus-
tible material is less than 12", you must install the replace hood accessory (24", 30" and 36"
Models Only). Even if noncombustible mate-
rial is more than 12", you may need the hood accessory to deect heat away from your
mantel shelf. See Figures 5 and 6 and Figure
7, page 9, for minimum clearances.
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of replace opening, a
hood is not required (see Figure 6).
Figure 5 - Heat Resistant Material (Slate,
126832-01A 11
www.Astria.US.com
Marble, Tile, etc.) Above Fireplace
Figure 6 - Minimum Mantel Clearances
Without Using Hood
Page 12
INSTALLATION
Minimum Noncombustible Material
8" Min.
12" 15" 18"
All minimum distances are in inches
Log Sets 18", 24", 30" & 36" Models
20"
2
1
/2
"
6"
8"
10"
12"
Distances to Underside of Mantel
Hood (GA6050 or GA6053)
Top of Fireplace Opening
Underside of Mantel Shelf
Mantel Shelf
14" Min.
Combustible Material
Noncombustible Material
Hearth
5" Min.
Combustible Material
Continued
Determining Minimum Mantel Clearance When Using a Hood
If minimum clearances in Figure 6, page 11, are not met, you must have a hood. When using
a hood there are still certain minimum mantel clearances required. Follow minimum clear-
ances shown in Figure 7, when using hood.
NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the minimum clear­ances shown, you must do one of the following:
• operate the logs only with the
ue damper open
• raise the mantel to an accept-
able height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on the oor level,
you must maintain the minimum distance of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14"
to the replace, you must install appliance at least 5" above the combustible ooring
(see Figure 9).
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
INSTALLING HEATER BASE ASSEMBLY
Figure 7 - Minimum Mantel Clearances
When Using Hood
www.Astria.US.com
WARNING: You must secure
this heater to replace oor. If
not, heater will move when you adjust controls. Moving heater may cause a gas leak.
CAUTION: Do not pick up heater base assembly by burn­ers. This could damage heater. Only handle base assembly by grates.
126832-01A12
Page 13
INSTALLATION
Continued
Heater Gas
WARNING: If installing in a
sunken replace, special care
is needed. You must raise the
replace oor to allow access
to heater control panel. This
will insure adequate air ow
and guard against sooting and controls being damaged. Raise replace oor with noncombus­tible material. Make sure material is secure.
IMPORTANT: Make sure the heater burners
are level. If heater is not level, heater will not work properly. For thermostat models, avoid
damage to thermostat bulb. Avoid nicks or sharp bends in thermostat bulb wire. Keep thermostat bulb in mounting bracket until
ready to mount base to oor. See Optional Positioning Of Thermostat Sensing Bulb,
page 30.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose and ttings
(provided) (if allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16” masonry drill bit
1. Apply pipe joint sealant lightly to male
threads of gas tting (provided). Con­nect approved exible gas hose to gas
regulator of heater (see Figure 10). IMPORTANT: Hold gas regulator with
wrench when connecting exible gas hose.
2. Position heater base assembly in fireplace.
3. Mark screw locations through holes in front panel of base (see Figure 11). If
installing in a brick-bottom replace, mark
screw locations in mortar joint of bricks.
4. Remove heater base from replace.
5. Drill holes at marked locations using 3/16" drill bit.
6. Attach base, through holes in front panel of base, to replace oor using masonry
screws provided in hardware package (see Figure 11).
7. Connect to gas supply. See Connecting To Gas Supply.
126832-01A 13
www.Astria.US.com
Flexible Gas Hose (if allowed by local codes)
Figure 10 - Attaching Flexible Gas Hose to
Heater Gas Regulator (Thermostatically-
Controlled Models Only)
Masonry
Screw
Figure 11 - Attaching Base to Fireplace
Floor
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 1/2" NPT (National Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualied ser­vice person must connect heater to gas supply. Follow all local codes.
CAUTION: Never connect
propane/LP replace directly
to the propane/LP supply. This heater requires an external regu­lator (not supplied). Install the external regulator between the heater and propane/LP supply.
Regulator
Page 14
INSTALLATION
Continued
WARNING: Never connect
natural gas replace to private
(non-utility) gas wells. This gas is commonly known as wellhead gas.
Installation Items Needed
Before installing heater, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas con­nector (if allowed by local codes) (not provided)
* An equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional equipment shutoff valve from your dealer.
For propane/LP units, the installer must
supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11" and 14" of water. If you do not re-
duce incoming gas pressure, heater regulator
damage could occur. Install external regulator with the vent pointing down as shown in Figure
14. Pointing the vent down protects it from
freezing rain or sleet.
CAUTION: Use only new, black iron or steel pipe. Inter­nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see
Figure 12 or Figure 13 on page 15, depending
on your model). IMPORTANT: Install equipment shutoff valve
in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special requirements for locating equipment shutoff
valve to replaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Propane/LP Supply Tank
Figure 12 - External Regulator With Vent
Pointing Down
We recommend that you install a sediment
trap in supply line as shown in Figure 13, page
15. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sedi­ment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not
installed or is installed wrong, heater may
not run properly.
External Regulator with Vent Pointing Down
www.Astria.US.com
126832-01A14
Page 15
INSTALLATION
PROPANE/LP From External Regulator (11" W.C.** to 14" W.C. Pressure) NATURAL From Gas Meter (5" W.C.** to 10.5" W.C. Pressure)
Tee Cap Pipe Joint Nipple
Sediment Trap
Figure 13 - Gas Connection
CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it
to gas piping and/or ttings.
CHECKING GAS CONNECTIONS
WARNING: Test all ga s piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.
WARNING: Never use an
open ame to check for a leak.
Apply a noncorrosive leak detec-
tion uid to all joints. Bubbles
forming show a leak. Correct all leaks at once.
Equipment Shutoff Valve With 1/8" NPT Tap*
Approved
Flexible Gas
Hose (if allowed
by local codes)
3" Minimum
Regulator
Continued
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect appliance with its appliance main gas valve (control valve) and equip­ment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equip­ment shutoff valve was connected.
3. Pressurize supply piping system by either opening propane/LP supply tank valve
Gas
for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.
4. Check all joints of gas supply piping sys­tem. Apply noncorrosive leak detection
uid to all joints. Bubbles forming show
a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve to gas supply. Check reconnected
ttings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-
ure 14, page 16).
2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.
3. Check all joints from gas meter to equip­ment shutoff valve for natural gas or pro­pane/LP supply to equipment shutoff valve
for propane/LP (see Figure 15 or 16, page
16). Apply noncorrosive leak detection uid
to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
CAUTION: Make sure exter­nal regulator has been installed between propane/LP supply and heater. See guidelines un­der Connecting to Gas Supply, page 13.
126832-01A 15
www.Astria.US.com
Page 16
INSTALLATION
Equipment Shutoff Valve
Figure 14 - Equipment Shutoff Valve
Propane/LP Supply Tank
Equipment Shutoff Valve
Open
Closed
Continued
6. Light heater (see Operation, page 26, depending on your model). Check all other internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to
Appliance, page 27.
INSTALLING LOGS
WARNING: Failure to posi­tion the parts in accordance with these diagrams or failure
to use only parts specically
approved with this heater may result in property damage or personal injury.
Thermostat Gas Valve or Control Valve Location
Figure 15 - Checking Gas Joints
(Propane/LP Only)
Equipment Shutoff Valve
Thermostat Gas Valve or Control Valve Location
Figure 16 - Checking Gas Joints (Natural
Gas Only)
PRESSURE TESTING HEATER GAS CONNECTIONS
1. Open equipment shutoff valve (see Fig­ure 14).
2. Open main gas valve located on or near gas meter for natural gas or open pro­pane/LP supply tank valve.
3. Make sure control knob of heater is in the OFF position.
4. Check all joints from equipment shutoff valve to thermostat gas valve (see Figure 15 or 16). Apply noncorrosive leak detection
uid to all joints. Bubbles forming show a
leak.
5. Correct all leaks at once.
Log Support Brackets
If installing an AndesMtn36, attach log sup­port brackets before installing logs. These brackets are provided with the Blaze&Glow24 series burner systems.
1. Install left bracket to left side of chassis us­ing 2 screws provided (see Figure 17).
2. Install right bracket to right front of chassis using 2 screws provided (see Figure 17).
Chassis
Left Log Support Bracket
Right Log Support Bracket
Right Front of Chassis
Figure 17 - Installing Log Support Brackets
www.Astria.US.com
126832-01A16
Page 17
INSTALLATION
Continued
FIBER LOG MODELS AndesMtn(18, 24, 30, 36)
Note: Your appliance may vary from model shown but log placement will be the same.
1. Place bottom log in center of the base assembly as shown in Figure 18. The
log must sit at on the black sheet metal
and behind the left metal tab as shown in Figure 18-a.
2. Rest rear log in back corner sections of base assembly as shown in Figure 18. Make sure log is completely vertical and
not leaning in toward burner where ame
will touch the log.
Ramp Log
Metal Tab
Figure 18-a - Installing Log Set
3. Position front right log against right side of grate prongs (see Figure 18).
4. Position front left log against left side of grate prongs (see Figure 18).
5. Place middle right log over front right and bottom logs as shown in Figure 19. Be sure hole in middle right log seats over pin in bottom log.
6. Place middle left log over front left and bottom logs as show in Figure 19. Be sure hole in middle left log seats over pin in front left log.
Middle Left Log
Middle Right Log
Front Left Log
Grate Prongs
Bottom Log
Base Assembly
Figure 18 - Installing Log Set
126832-01A 17
Rear Log
Front Right Log
www.Astria.US.com
Pin on Front Left Log
Figure 19 - Installing Log Set
Bottom Log
Page 18
INSTALLATION
Continued
7. For AndesMtn36, the front right and
left logs are longer and are supported with brackets on each end (see Figure
20). Place left and right small front logs under left bracket and beside right bracket.
8. For AndesMtn36, position left and right
control cover logs as shown in Figure 21. These may be placed as desired to hide
controls. Left Small Front Log
Bracket
Note: Your appliance may vary from model shown but log placement will be the same.
1. Place ber ramp-log in center on chassis as shown in Figure 22. The ber ramp-log can be identied by its shape and much lighter
weight when compared to the other logs.
2. The log must sit at on the black sheet
metal and behind the left metal tab as shown in Figure 23.
3. Place front left and right logs and rear log as shown in Figure 24.
Ramp Log
Base Assembly
Left Control Cover Log
Right Control Cover Log
Figure 20 - Installing AndesMtn36 Model
Control Cover Logs
AndesMtn(18,24,30) MODELS
AndesMtn36 MODELS
Figure 21 - Correct Log Placement
Bracket
Right Small Front Log
CONCRETE LOG MODELS RedWoodM(18, 24, 30)
Each log is marked with a number. These numbers will help you identify the log when installing (see chart on page 19). It is very important to install these logs exactly as instructed. Do not modify logs. Only use logs supplied with heater.
www.Astria.US.com
Figure 22 - Installing Log Set
Ramp Log
Metal Tab
Figure 23 - Installing Log Set
Rear Log
Front Left Log
Front Right Log
Figure 24 - Installing Logs
4. Place top left log as shown in Figure 25,
page 19. The bottom of the log is shaped
to t onto the recessed areas of the front
left log and the rear log. The recessed areas are painted yellow.
5. Place top right log as shown in Figure 25,
page 19. The bottom of the log is shaped
126832-01A18
Page 19
INSTALLATION
Continued
to t onto the recessed areas of the front
right log and the rear log. The recessed areas are painted yellow.
6. Place the small top right log as shown in Figure 26. The bottom of the log is shaped
to t onto the recessed areas of the top
right log and the front right log. The re­cessed areas are painted yellow.
Top Left Log
Front Left Log
Figure 25 - Installing Logs
Small Top Log
Top Right Log
Front Right Log
Top Right Log
CONCRETE LOG MODELS
BisonMtn (18, 24, 30)
Note: Your appliance may vary from model shown but log placement will be the same.
1. Before placing any logs on the chassis you will need to remove the Air Shield located on the left side near the rear burner as shown in Figure 27. The Air Shield is held
in place with one screw, remove the Air
Shield and place the screw back into the hole in the chassis. Place the Air Shield with you owner's manual and keep.
Screw
Air Shield
Figure 27 - Removing Air Shield
2. Place ber ramp log in center of chassis as shown in Figure 28, page 22. The ber ramp log can be identied by the shape
and much lighter weight when compared
to the other logs. The log must sit at on
the black sheet metal and behind the left metal tab as shown. Make sure the side
Front Right Log
marked ''BOTTOM'' is setting down.
Figure 26 - Installing Log
Description Qty
RedWoodM18
RedWoodM30
RedWoodM24
Front Left Log 012 001 007 1
Front Right Log 013 002 008 1
Rear Log 014 003 009 1
Top Left Log 016 005 011 1
Top Right Log 015 004 010 1
Small Top Right Log 006 006 006 1
126832-01A 19
www.Astria.US.com
Page 20
INSTALLATION
Continued
Ramp Log
Metal Tab
Figure 28 - Installing Fiber Ramp Log
3. Place front left (18" D-064, 24" D-057 & 30" D-038) and front right (18" D-065, 24" D-058
& 30" D-039) logs as shown in Figure 29.
5. The right ember bed log 24" & 30'' (D-
047) has a hole in the log that sets on
the grate nger and the other end rest on the replace oor, place log as shown in
Figure 31. The right ember bed logs for 18" (D-072) has a groove on the side that sets on the ember bed pan and the back of the log needs to rest against the front of the
base. Make sure the ame from the ember
pan does not touch the ember bed log. The back side of this log needs to rest against
the front of the base assembly, make sure the ame from the ember pan does not
touch the ember bed log.
Right Front Log
Left Front Log
Figure 29 - Installing Left/Right Front Logs
4. Place left ember bed log (18" D-073, 24"
& 30" D-048) as shown in Figure 30. The log has groove on one side that sets on the ember bed pan. The back side of this log needs to rest against the front of the base
assembly. Make sure the ame from the
ember pan does not touch the ember bed log.
Left Ember Bed Log
Right Ember Bed Log
Hole Underneath
Grate Prong
Figure 31 - Installing Right Ember Bed Log
6. The left middle log (18" D-066, 24" & 30"
D-040) has a groove on the bottom to sit on the chassis and has to sit on the tab on the back of the left front log as shown in Figure 32.
Left Middle Log
Figure 30 - Installing Left Ember Bed Log
www.Astria.US.com
Figure 32 - Installing Left Middle Log
126832-01A20
Page 21
INSTALLATION
Continued
7. The right middle log (18" D-067, 24" & 30"
D-041) has a groove on the bottom to sit on the chassis and has to sit on the tab on the back of the right front. The right middle log
should have a recess area that ts around
the ramp log as shown in Figure 33.
Right Middle Log
Figure 33 - Installing Right Middle Log
9. Rest the rear log (18" D-069, 24" & 30"
D-043) on the chassis behind the rear burner as shown in Figure 35. The bottom of the rear log will sit into the rear log sup­ports.
Rear Log
8. The rear middle log (18" D-068, 24" & 30" D-042) should t between the ramp
log and the rear burner. The left and right middle logs have recessed areas for the rear middle log to sit into (See Figure 34). There may be a small gap between the rear
middle log and the ramp log, this is normal..
Be careful not to push the rear burner out of position while installing this log.
Rear Middle Log
Figure 34 - Installing Rear Middle Log
Figure 35 - Installing Rear Log
10. Place the left top log (D-046) onto the rear log and the left middle log. Make sure to place the projection on the bottom of the left top log into the recessed areas on the rear and left middle logs (see Figure 36).
Left Top Log
Rear Log
Left Middle Log
Figure 36 - Installing Left Top Log
126832-01A 21
www.Astria.US.com
Page 22
INSTALLATION
Continued
11. Rest the middle crossover log (18" D-070,
24" & 30" D-044) onto the right middle log and the left front log (see Figure 37). Make sure to match the projection on the bottom of the crossover log with the recess area in the right middle log and the left front log.
EMBER PLACEMENT - BGE SERIES BURNER SYSTEMS
WARNING: Do not use any other ember material not sup­plied with this unit.
Middle Crossover Log
Figure 37 - Installing Middle Crossover Log
12. Place the top rear log (18" D-071, 24" &
30" D-045) onto the rear log as shown. The
rear log has a projection that will t into the
recess area on the bottom of the top rear log (see Figure 38).
Top Rear Log
Rear Log
Figure 38 - Installing Top Rear Log
WARNING: Do not operate unit without ember material correctly in place as shown in Figures 39 & 40. Do NOT place ember material anywhere else on the unit. Use only ember ma­terial supplied with unit. Exces­sive or incorrectly placed ember material may produce carbon monoxide or soot.
1. Ember Chunk Placement. The Blaze&Glow24 burner systems include three ember chunks that are designed to
t over shoulder screws on the ember pan
burner. The bottom of each ember chunk has a hole for securing the ember chunk in place when it is placed over a shoulder screw. Place the ember chunks as shown in Figure 39 on page 25 by placing the ember chunk with the number "1" on the
left, "2" in the center, and "3" on the right.
These numbers are embossed on the back of each piece for identication pur­poses. Please note that Blaze&Glow18 burner systems do not include ember chunks.
2. Two ember materials are supplied with this log set. Platinum Bright Embers give a bright glow appearing as hot coals. Follow instructions for the ember material you choose. Should embers need replac-
ing, see Parts, page 36.
Platinum Bright Ember placement. Add
embers to front, at burner. Gently remove
embers from bag. Separate pieces of ember material and place on surface of
at burner just behind horizontal ports as
shown in Figure 40.
Rock Wool placement. Place rock wool
material on front at burner in areas away
from ports as shown in Figure 41.
www.Astria.US.com
126832-01A22
Page 23
INSTALLATION
Continued
3. Add lava rock and small decorative logs around base of heater if desired. DO NOT
place rock or additional logs on front burner or on logs. Placing any material
on unit other than ember material on front
burner may result in production of carbon monoxide or soot. Use lava rock to hide wires from switch/log to control valve. Place switch/log so the switch is easy to access.
If replacement embers are needed, the replacement embers must be purchased from IHP. See page 34 for part numbers.
Ember Chunk #1
Figure 39 - Ember Chunk Placement Blaze&Glow24 Series
Ember Chunk #2
WARNING: All previously ap­plied loose material must be re­moved prior to reapplication.
Ember Chunk #3
Flat Front Burner
Ember Material
Figure 40 - Platinum Bright Embers
Rock Wool
Figure 41 - Placement of Rock Wool
(shown with Platinum Bright Embers)
126832-01A 23
www.Astria.US.com
Flat Front Burner
Page 24
OPERATION
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not fol-
low these instructions exactly,
a re or explosion may result
causing property damage, per­sonal injury or loss of life.
A. This appliance has a pilot which must
be lighted by hand. When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to
smell next to the oor because some
gas is heavier than air and will settle
on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the re department.
C. Use only your hand to push in or turn
the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a quali-
ed service technician or gas supplier.
Force or attempted repair may result in
a re or explosion.
D. Do not use this appliance if any part
has been under water. Immediately call
a qualied service technician to inspect
the appliance and to replace any part of the control system and any gas control which has been under water.
LIGHTING
INSTRUCTIONS
NOTICE: During initial operation of new heater, burning logs will give off a paper-burning smell. Orange ame will also be pres­ent. Open damper or window to vent smell. This will only last a few hours.
www.Astria.US.com
WARNING:
• If replace has glass doors,
never operate this heater with glass doors closed. If you op­erate heater with doors closed,
heat buildup inside replace
will cause glass to burst. Make sure there are no obstructions
across openings of replace.
• You must operate this heater with a fireplace screen in place. Make sure fireplace screen is closed before run­ning heater.
Note: Home owners generally prefer to oper­ate their heater with the chimney damper closed. This will put all the heat into the room. However, there may be times you will desire
the full ames of the HI heat setting but will nd the heat output excessive. You can open
the chimney damper (if you have one) fully or partially to release some of the heat.
WARNING: Damper handle will be hot if heater has been running.
1. STOP! Read the safety information.
2. Make sure equipment shutoff valve is fully open.
3. Turn control knob clockwise to the OFF position.
4. Wait ve (5) minutes to clear out any gas. Then smell for gas, including near the oor. If you smell gas, STOP! Follow B in
the safety information. If you don’t smell
gas, go to the next step.
5. Turn control knob counterclockwise
Ignitor Button
to the PILOT position. Press in
control knob for ve (5) seconds (see
Figure 42).
Control Knob
Figure 42 - Control Knob and Ignitor
Button Location
126832-01A24
Page 25
OPERATION
Continued
Note: You may be running this heater
for the rst time after hooking up to gas
supply. If so, the control knob may need to be pressed in for 30 seconds or more. This will allow air to bleed from the gas system.
6. With control knob pressed in, press and
release ignitor button. This will light pilot. The pilot is attached to the front burner. If
needed, keep pressing ignitor button until
pilot lights.
Note: If pilot does not stay lit, contact a
qualied service person or gas supplier
for repairs. Until repairs are made, light pilot with match. To light pilot with match, see Manual Lighting Procedure.
7. Keep control knob pressed in for 30 sec-
onds after lighting pilot. After 30 seconds,
release control knob.
• If control knob does not pop out when
released, contact a qualified service
person or gas supplier for repairs.
Note: If pilot goes out, repeat steps 3
through 7. This heater has a safety inter­lock system. Wait one (1) minute for sys­tem to reset before lighting pilot again.
8. Turn control knob counterclockwise to desired heating level. The burn-
ers should light. Set control knob to any heat level between HI and LO.
9. To leave pilot lit and shut off burners only,
turn control knob clockwise to the PILOT position.
TO TURN OFF GAS
TO APPLIANCE
1. Turn control knob clockwise to the OFF position.
2. Close equipment shutoff valve (see Figure
14, page 16).
THERMOSTAT CONTROL
OPERATION
The thermostat control knob can be set to any comfort level between HI and LO. The ther­mostat will gradually modulate the heat output
and ame height from higher to lower settings or pilot, in order to maintain the comfort level
you select. The ideal comfort setting will vary by household depending upon the amount of
space to be heated, the output of the central heating system, etc.
Note: Selecting the HI setting with the control knob will cause the burner to remain fully on, without modulating down in most cases.
MANUAL LIGHTING
PROCEDURE
1. Follow steps 1 through 5 under Lighting Instructions, page 26.
2. Press control knob and light pilot with match.
3. Keep control knob pressed in for 30 sec-
onds after lighting pilot. After 30 seconds,
release control knob. Now follow step 8 under Lighting Instructions, page 26.
CAUTION: Do not try to ad­just heating levels by using the equipment shutoff valve.
Ignitor Electrode
Thermocouple
Figure 43 - Pilot
126832-01A 25
Pilot Burner
www.Astria.US.com
Page 26
INSPECTING BURNERS
Check pilot ame pattern and burner ame
patterns often.
PILOT FLAME PATTERN
Figure 44 shows a correct pilot ame pattern. Figure 45 shows an incorrect pilot ame pat­tern. The incorrect pilot ame is not touching
the thermocouple. This will cause the thermo-
couple to cool. When the thermocouple cools,
the heater will shut down.
If pilot ame pattern is incorrect, as shown
in Figure 46
• turn heater off (see To Turn Off Gas to Ap-
pliance, page 27.
• see Troubleshooting, page 31
Note: The pilot ame on natural gas units will have a slight curve, but ame should be blue
and have no yellow or orange color.
Propane/LP Gas PilotNatural Gas Pilot
Thermocouple
Pilot Burner
WARNING: If incorrect
burner ame occurs, your heater
could produce increased levels of carbon monoxide.
NOTICE: Do not mistake orange
ames with yellow tipping. Dirt or other ne particles are burned
by heater, causing brief patches
of orange ame.
If burner ame pattern is incorrect, as shown
in Figure 47
• turn heater off (see To Turn Off Gas to Ap-
pliance, page 27.
Bright yellow rear
Middle burner
ame should
be blue with the ramp/blue with the ramp/log glowing orange/ red
burner ame; ame
will be blue next to burner
Small blue
ame on ember
burner with no yellow tipping
Thermocouple
Figure 44- Correct Pilot Flame Pattern
(Your pilot may vary from pilots shown)
Propane/LP Gas PilotNatural Gas Pilot
Thermocouple
Figure 45 - Incorrect Pilot Flame Pattern (Your pilot may vary from pilots shown)
Pilot Burner
Thermocouple
BURNER FLAME PATTERN
Figure 46 shows correct burner ame pat­tern. Figure 47 shows incorrect burner ame
pattern.
www.Astria.US.com
Figure 46 - Correct Burner Flame Pattern
Yellow
Yellow tipping on ember burner
Figure 47 - Incorrect Burner Flame
Dark orange rear
burner ame
Pattern
or dark orange middle burner
ame
126832-01A26
Page 27
CLEANING AND MAINTENANCE
WARNING: Turn off heater and let cool before cleaning.
Ports/Slots
Injector Holder
CAUTION: You must keep con­trol areas, burners and circulating air passageways of heater clean. Inspect these areas of heater before each use. Have heater
inspected yearly by a qualied
service person. Heater may need more frequent cleaning due to excessive lint from carpeting, pet hair, bedding material, etc.
WARNING: Failure to keep the primary air opening(s) of the burner(s) clean may result in sooting and property damage.
BURNER INJECTOR HOLDER AND PILOT AIR INLET HOLE
The primary air inlet holes allow the proper amount of air to mix with the gas. This provides
a clean burning ame. Keep these holes clear of dust, dirt, lint and pet hair. Clean these air in-
let holes prior to each heating season. Blocked air holes will create soot. We recommend that you clean the unit every three months during operation and have heater inspected yearly by
a qualied service person.
We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recommend using compressed air no greater than 30 PSI.
Your local computer store, hardware store or
home center may carry compressed air in a
can. If using compressed air in a can, please
follow the directions on the can. If you don’t
follow directions on the can, you could damage
the pilot assembly.
1. Shut off unit, including pilot. Allow unit to
cool for at least thirty minutes.
2. Inspect burner, pilot and primary air inlet
holes on injector holder for dust and dirt (see Figure 48).
3. Blow air through the ports/slots and holes in the burner.
4. Check injector holder located at the end of the burner tube again. Remove any large
particles of dust, dirt, lint or pet hair with a
126832-01A 27
www.Astria.US.com
Burner Tube
Primary Air Inlet Holes
Figure 48 - Injector Holder On Outlet
Burner Tube
soft cloth or vacuum cleaner nozzle.
5. Blow air into the primary air holes on the injector holder.
6. In case any large clumps of dust have now been pushed into the burner repeat steps 3 and 4.
Clean pilot assembly also. A yellow tip on the
pilot ame indicates dust and dirt in the pilot
assembly. There is a small pilot air inlet hole
about 2" from where the pilot ame comes out
of the pilot assembly (see Figure 49). With
the unit off, lightly blow air through the air inlet
hole. You may blow through a drinking straw if compressed air is not available.
Pilot Air Inlet Hole
Pilot Assembly
Figure 49 - Pilot Inlet Air Hole (Your pilot
may vary from pilot shown)
LOGS
• If you remove logs for cleaning, refer to
Installing Logs, page 16, to properly replace
logs.
• Replace log(s) if broken or chipped (dime-
sized or larger).
MAIN BURNER
Periodically inspect all burner ame holes with the heater running. All slotted burner ame holes should be open with yellow ame pres­ent. All round burner ame holes should be open with a small blue ame present. Some burner ame holes may become blocked by de­bris or rust, with no ame present. If so, turn off heater and let cool. Remove blockage, blocked burner ame holes will create soot.
Page 28
OPTIONAL POSITIONING OF THERMOSTAT
SENSING BULB
FOR MASONRY AND FACTORY­BUILT METAL FIREPLACE
If your log set cycles to pilot, but the room
temperature drops to a lower than ideal comfort level before the log set comes back
on, you may want to reposition the thermostat
sensing bulb. The thermostat sensing bulb is located on the
gas valve assembly. This location allows the thermostat to keep the room temperature at an ideal comfort level for most replace appli­cations. If positioning the thermostat sensing
bulb elsewhere, follow these directions.
Tools needed: 5/16" hex driver or socket
1. Locate the gas valve assembly and ther­mostat sensing bulb (see Figure 50).
(Unit Will Differ From Illustration)
Gas Valve Assembly
Thermostat Sensing Bulb
Figure 50 - Location of Gas Valve
Assembly and Thermostat Sensing Bulb
2. With 5/16” hex driver or socket, loosen
the thermostat screw. Carefully slide the thermostat sensing bulb out of the retain­ing clamp (see Figure 51).
Note: Do not remove screw. Make sure
you tighten screw after removing thermo­stat sensing bulb.
IMPORTANT: Do not force or bend ther-
mostat sensing bulb or capillary.
3. The thermostat sensing bulb may be located to the lower right front side of
replace. Place bulb in an area that will
be close to room temperature when log set is operating.
Screw
Figure 51 - Removing Thermostat
Retaining Clamp
Sensing Bulb
Capillary
(Unit Will Differ From Illustration)
Thermostat Sensing Bulb
www.Astria.US.com
126832-01A28
Page 29
TROUBLESHOOTING
WARNING: Turn off heater and let cool before servicing. Only a
qualied service person should service and repair heater.
CAUTION: Never use a wire, needle or similar object to clean
ODS/pilot. This can damage ODS/pilot unit.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
When ignitor button is
pressed, there is no spark
at ODS/pilot
When ignitor button is
pressed, there is spark at
ODS/pilot but no ignition
POSSIBLE CAUSE
1. Ignitor electrode not con­nected to ignitor cable
2. Ignitor cable pinched or wet
3. Broken ignitor cable
4. Bad ignitor
5. Ignitor electrode positioned wrong
6. Ignitor electrode broken
7. Battery not installed, battery
power low or battery not in­stalled correctly (electronic ignition models only)
1. Gas supply turned off or equipment shutoff valve closed
2. Control knob not in PILOT position
3. Control knob not pressed in while in PILOT position
4. Air in gas lines when in­stalled
5. Depleted gas supply (pro­pane/LP only)
6. ODS/pilot is clogged
7. Gas regulator setting is not correct
REMEDY
1. Reconnect ignitor cable
2. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry
3. Replace ignitor cable
4. Replace ignitor
5. Replace pilot assembly
6. Replace pilot assembly
7. Install new alkaline battery in electronic ignitor. Verify battery is installed cor­rectly
1. Turn on gas supply or open equipment shutoff valve
2. Turn control knob to PILOT position
3. Press in control knob while in PILOT position
4. Continue holding down control knob. Repeat ignit­ing operation until air is removed
5. Contact local propane/LP gas company
6. Clean ODS/pilot (see
Cleaning and Maintenance,
page 29) or replace ODS/ pilot assembly
7. Replace gas regulator
126832-01A 29
www.Astria.US.com
Page 30
OBSERVED PROBLEM
ODS/pilot lights but ame
goes out when control knob is released
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Control knob not fully pressed in
2. Control knob not pressed in long enough
3. Safety interlock system has been triggered
4. Equipment shutoff valve not fully open
5. Pilot flame not touching
thermocouple, which allows thermocouple to cool, caus­ing pilot ame to go out. This
problem could be caused by one or both of the following:
A) Low gas pressure B) Dirty or partially clogged
ODS/pilot
6. Thermocouple connection loose at control valve
7. Thermocouple damaged
8. Control valve damaged
REMEDY
1. Press in control knob fully
2. After ODS/pilot lights, keep
control knob pressed in 30 seconds
3. Wait one minute for safety interlock system to reset. Repeat ignition operation
4. Fully open equipment shut­off valve
5. A) Contact local natural or propane/LP gas company
B) Clean ODS/pilot (see
Cleaning and Maintenance,
page 29) or replace ODS/ pilot assembly
6. Hand tighten until snug,
then tighten 1/4 turn more
7. Replace pilot assembly
8. Replace control valve
One or both burners do not light after ODS/pilot is lit
Delayed ignition of one or both burners
Burner backfiring during combustion
1. Inlet gas pressure is too low
2. Burner orice(s) clogged
3. Mislocated crossover tube
1. Manifold pressure is too low
2. Burner orice(s) clogged
3. Mislocated crossover tube
1. Burner orice is clogged or
damaged
2. Damaged burner
3. Gas regulator defective
www.Astria.US.com
1. Contact local natural or propane/LP gas company
2. Clean burner(s) (see
Cleaning and Maintenance,
page 29) or replace burner
orice(s)
3. Contact qualified service person
1. Contact local natural or propane/LP gas company
2. Clean burner(s) (see
Cleaning and Maintenance,
page 29) or replace burner
orice(s)
3. Contact qualified service person
1. Clean burner (see Cleaning
and Maintenance, page 29) or replace burner orice
2. Replace damaged burner
3. Replace gas regulator
126832-01A30
Page 31
OBSERVED PROBLEM
Yellow ame in front burner
during burner combustion
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Not enough air
2. Gas regulator defective
REMEDY
1. Check burner(s) for dirt
and debris. If found, clean
burner(s) (see Cleaning and Maintenance, page 29)
2. Replace gas regulator
Slight smoke or odor during initial operation
Heater produces a whistling noise when burners are lit
White powder residue form­ing within burner box or on adjacent walls or furniture
Moisture/condensation no­ticed on windows
Heater produces a clicking/ ticking noise just after burners are lit or shut off
1. Residues from manufac­turing processes and logs curing
1. Turning control knob to HI position when burners are cold
2. Air in gas line
3. Air passageways on heater blocked
4. Dirty or partially clogged
burner orice(s)
1. When heated, vapors from furniture polish, wax, carpet cleaners, etc. may turn into
white powder residue
1. Not enough combustion/ ventilation air
1. Metal expanding while heating or contracting while cooling
1. Problem will stop after a few hours of operation
1. Turn control knob to LO position and let warm up for a minute
2. Operate burners until air is removed from line. Have gas line checked by local natural or propane/LP gas company
3. Observe minimum installa­tion clearances (see pages 9 through 11)
4. Clean burners (see Clean-
ing and Maintenance,
page 29) or replace burner
orice(s)
1. Turn heater off when us-
ing furniture polish, wax,
carpet cleaners or similar products
1. Refer to Air for Combustion and Ventilation require­ments (page 6)
1. This is normal with most heaters. If noise is exces­sive, contact qualied ser­vice person
126832-01A 31
www.Astria.US.com
Page 32
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Fol­low the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
IMPORTANT: Operating heater where impurities in air exist may create odors. Cleaning sup-
plies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc.,
create fumes. These fumes may mix with combustion air and create odors. These odors will disappear over time.
OBSERVED PROBLEM
Heater produces unwanted odors
POSSIBLE CAUSE
1. Heater burning vapors from
paint, hair spray, glues, cleaners, chemicals, new carpet, etc. (See IMPOR-
TANT statement above)
2. Low fuel supply (propane/ LP only)
3. Gas leak. See Warning
statement at top of page
REMEDY
1. Open window to venti­late room. Stop using odor causing products while heater is running
2. Rell supply tank (propane/
LP only)
3. Locate and correct all leaks (see Checking Gas Con-
nections, page 15)
Heater shuts off in use (ODS operates)
Gas odor even when control knob is in OFF position
Gas odor during combustion
Log set cycles to pilot, but
room temperature drops to a lower than ideal level before log set comes back on
1. Not enough fresh air is available
2. Low line pressure
3. ODS/pilot is partially clogged
1. Gas leak. See Warning
statement at top of page
2. Control valve or gas control defective
1. Foreign matter between control valve and burner
2. Gas leak. See Warning
statement at top of page
1. Thermostat sensing bulb needs to be repositioned
www.Astria.US.com
1. Open window and/or door for ventilation
2. Contact local natural or propane/LP gas company
3. Clean ODS/pilot (see
Cleaning and Maintenance,
page 29)
1. Locate and correct all leaks (see Checking Gas Con-
nections, page 15)
2. Replace control valve or gas control
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks (see Checking Gas Con-
nections, page 15)
1. Reposition thermostat sensing bulb (see Optional
Positioning of Thermostat Sensing Bulb, page 30)
126832-01A32
Page 33
SPECIFICATIONS
BLAZE&GLOW18TP
• Rating (Variable): 19,000/29,000 Btu/Hr
• Type Gas: Propane/LP
• Ignition: Electronic
• Manifold Pressure: 7.9" W.C.
• Inlet Gas Pressure (in. of water):
Max - 14" W.C., Min* - 11" W.C.
BLAZE&GLOW18TN
• Rating (Variable): 21,000/28,000 Btu/Hr
• Type Gas: Natural
• Ignition: Electronic
• Manifold Pressure: 3.4" W.C.
• Inlet Gas Pressure (in. of water):
Max - 10.5" W.C., Min* - 5" W.C.
*For purpose of input adjustment
BLAZE&GLOW24TP
• Rating (Variable): 23,000/39,000 Btu/Hr
• Type Gas: Propane/LP
• Ignition: Electronic
• Manifold Pressure: 7.9" W.C.
• Inlet Gas Pressure (in. of water):
Max - 14" W.C., Min* - 11" W.C.
BLAZE&GLOW24TN
• Rating (Variable): 25,000/39,000 Btu/Hr
• Type Gas: Natural
• Ignition: Electronic
• Manifold Pressure: 3.4" W.C.
• Inlet Gas Pressure (in. of water):
Max - 10.5" W.C., Min* - 5" W.C.
BLAZE & GLOW LOG SETS
Model Description
BisonMtn18 18" Bison Mountain Log Set Refractory
BisonMtn24 24" Bison Mountain Log Set Refractory
BisonMtn30 30" Bison Mountain Log Set Refractory
AndesMtn18 18" Andes Mountain Log Set Fiber
AndesMtn24 24" Andes Mountain Log Set Fiber
AndesMtn30 30" Andes Mountain Log Set Fiber
AndesMtn36 36" Andes Mountain Log Set Fiber
RedWoodM18 18" Red Wood Mountain Log Set Refractory
RedWoodM24 24" Red Wood Mountain Log Set Refractory
RedWoodM30 30" Red Wood Mountain Log Set Refractory
126832-01A 33
www.Astria.US.com
Page 34
PARTS
THERMOSTATICALLY CONTROLLED MODELS
BLAZE&GLOW18TN, BLAZE&GLOW18TP, BLAZE&GLOW24TN, BLAZE&GLOW24TP
21
12
9
6
11
13
7
1
16
17
10
23
20
30
KEY NO. PART NO. DESCRIPTION Blaze&Glow18TN Blaze&Glow18PT Blaze&Glow24TN Blaze&Glow24TP QTY.
120466-01 Flex Tube 1 100563-01 Warning Plate 1 101054-01 Lighting Instruction Plate 1 100639-12 Caution Decal 1 101137-02 Hardware Kit 1
GA6060 Lava Rock 1 125557-01 Left Ember Chunk #1 1 125557-02 Middle Ember Chunk #2 1 125557-03 Right Ember Chunk #3 1 125071-01 Rockwool Embers 1 125070-01 Platinum Embers 1
29
3
28
29
27
32
31
26
32
4
PARTS AVAILABLE NOT SHOWN
15
24
18
18
www.Astria.US.com
5
25
22
19
8
14
2
126832-01A34
Page 35
PARTS
THERMOSTATICALLY CONTROLLED MODELS
This list contains replaceable parts used in your heater. When ordering parts, follow the
instructions listed under Replacement Parts on page 45 of this manual.
KEY NO. PART NO. DESCRIPTION Blaze&Glow18TN Blaze&Glow18TP Blaze&Glow24TN Blaze&Glow24TP QTY.
1 098271-12 Cable Ignitor 1 2 098544-01 Thermobulb Clip 1 3 098867-09 Gas Regulator 1
098867-10 Gas Regulator 1
4 125491-01 Inlet Tube 1
125491-02 Inlet Tube 1
5 101004-06 Front Orice, 0.0530 1
101004-22 Front Orice, 0.0890 1 101004-04 Front Orice, 0.0750 1
6 101004-09 Rear Orice, 0.0400 1
101004-01 Rear Orice, 0.0492 1 101004-14 Rear Orice, 0.0720 1
101004-11 Rear Orice, 0.0670 1
7 120630-02 Pilot, ODS LP 1
120630-05 Pilot, ODS NG 1
8 127245-01 Gas Valve Service Kit 1
127245-02 Gas Valve Service Kit 1 127245-03 Gas Valve Service Kit 1
127245-04 Gas Valve Service Kit 1 9 ** Plate, NG Conversion 1 10 111435-01 Electronic Ignitor 1 11 112465-01 Front Ramp Burner 1
112465-02 Front Ramp Burner 1
12 113242-01 Rear Ramp Burner 1
113242-02 Rear Ramp Burner 1
13 112713-01 Pilot Bracket 1
112713-02 Pilot Bracket 1 14 ** Min. Rate Screw 1 15 125489-01 Air Deector Bracket 1
125489-02 Air Deector Bracket 1 16 125003-01 Air Shield 1 17 125019-01 Ignitor Bracket 1 18
099211-01 19 125490-01 Manual Valve Bracket 1 20 ** Assembly, Ramp Base 1 21 121005-01 Air Shield 1 22 125499-01 Log Support Bracket 1 23 120761-01 Log Support Bracket 1 24 099387-09 Pilot Tube 1 25 125491-01 Burner Tube 1
125491-02 Burner Tube 1 26 119321-01 Venturi 1 27 119795-01 Gasket 1 28 112829-02 Air Shutter 1 29 111819-10 Orice Elbow 1
111819-11 Orice Elbow 1
099056-47 Orice 0.0225 1 30 124933-01 Orice Holder Elbow 1 31 125306-01 Pan Burner 1
125306-02 Pan Burner 1 32 125301-01 Support Bracket 2
Screw, HWH AB 10-16 x 2.5 1
126832-01A 35
www.Astria.US.com
Page 36
PARTS
1
2
3
4
5
6
7
LOG MODELS AndesMtn18, AndesMtn24, AndesMtn30
This list contains replaceable parts used in your heater. When ordering parts, follow the
instructions listed under Replacement Parts on page 45 of this manual.
KEY NO.
MODEL NUMBER
DESCRIPTION QTYAndesMtn18 AndesMtn24 AndesMtn30
1 121699-05 121699-11 121699-17 Front Right Log 1 2 121699-04 121699-10 121699-16 Front Left Log 1 3 121699-02 125683-01 125683-01 Middle Right Log 1 4 121699-03 121699-09 121699-15 Middle Left Log 1 5 121699-01 121699-13 121699-13 Bottom Log (Remote) 1 6 121699-06 121699-12 121699-18 Rear Log 1 7 126080-01 126080-01 126080-01 Switch Log 1
www.Astria.US.com
126832-01A36
Page 37
PARTS
LOG MODELS AndesMtn36
This list contains replaceable parts used in your heater. When ordering parts, follow the
instructions listed under Replacement Parts on page 45 of this manual.
3
4
1
7
9
10
11
MODEL NUMBER
KEY NO.
DESCRIPTION QTYAndesMtn36
1 121699-13 Bottom Log 1 2 125683-01 Middle Right Log 1 3 121699-15 Middle Left Log 1 4 121699-20 Front Left Log 1 5 121699-21 Front Right Log 1 6 121699-22 Back Log 1 7 121699-23 Left Small Front Log 1 8 121699-24 Right Small Front Log 1 9 121699-25 Left Control Cover Log 1 10 121699-26 Right Control Cover Log 1 11 126080-01 Switch Log 1
6
2
5
8
126832-01A 37
www.Astria.US.com
Page 38
PARTS
1
2
LOG MODELS RedWoodM18, RedWoodM24, RedWoodM30
This list contains replaceable parts used in your heater. When ordering parts, follow the
instructions listed under Replacement Parts on page 45 of this manual.
7
3
4
6
5
8
KEY NO.
1 125055-13 125055-02 125055-08 Front Right Log 1 2 125055-12 125055-01 125055-07 Front Left Log 1 3 125055-15 125055-04 125055-10 Middle Right Log 1 4 125055-16 125055-05 125055-11 Middle Left Log 1 5 125056-01 125056-02 125056-02 Ramp Log 1 6 125055-14 125055-03 125055-09 Rear Log 1 7 125055-06 125055-06 125055-06 Top Log 1 8 121079-01 121079-01 121079-01 Log Switch 1
PART NUMBER
DESCRIPTION QTYRedWoodM18 RedWoodM24 RedWoodM30
www.Astria.US.com
126832-01A38
Page 39
PARTS
LOG MODELS BisonMtn18, BisonMtn24, BisonMtn30
This list contains replaceable parts used in your heater. When ordering parts, follow the
instructions listed under Replacement Parts on page 45 of this manual.
10
12
9
11
8
1
6
2
7
3
13
4
5
LOG MODELS
BisonMtn18, BisonMtn24, BisonMtn30
Cross reference log numbers.
BisonMtn18
KEY No.
1 125851-01 NONE 125852-01 NONE 125852-01 NONE Log, Ramp 1 2 125851-02 D-064 125852-02 D-057 125853-01 D-038 Log, Left Front 1 3 125851-03 D-065 125852-03 D-058 125853-02 D-039 Log, Right Front 1 4 125851-04 D-073 125852-04 D-048 125852-04 D-048 Log, Left Front Ember Bed 1 5 125851-05 D-072 125852-05 D-047 125852-05 D-047 Log, Right Front Ember Bed 1 6 125851-06 D-066 125852-06 D-040 125852-06 D-040 Log, Left Middle 1 7 125851-07 D-067 125852-07 D-041 125852-07 D-041 Log, Right Middle 1 8 125851-08 D-068 125852-08 D-042 125852-08 D-042 Log, Rear Middle 1 9 125851-09 D-069 125852-09 D-043 125852-09 D-043 Log, Rear 1 10 125851-10 D-046 125851-10 D-046 125851-10 D-046 Log, Left Top 1 11 125851-11 D-070 125852-11 D-044 125852-11 D-044 Log, Middle Crossover 1 12 125851-12 D-071 125852-12 D-045 125852-12 D-045 Log, Top Rear 1 13 121079-01 NONE 121079-01 NONE 121079-01 NONE Log, LBG-BM Switch 1
126832-01A 39
LOG ID
No.
BisonMtn24
BisonMtn30
LOG ID
No.
www.Astria.US.com
LOG ID
No. DESCRIPTION QTY
Page 40
REPLACEMENT PARTS
Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
Contact authorized dealers of this product. If
they can’t supply original replacement part(s),
call INNOVATIVE HEARTH PRODUCTS at 1-800-655-2008.
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• heater will not produce specied heat
• propane/LP gas supply may be low You may feel your gas pressure is too low. If
so, contact your local propane/LP or natural
gas supplier.
ACCESSORIES
Purchase these heater accessories from your local dealer. If they can not supply these accessories, call INNOVATIVE HEARTH PRODUCTS at 1-800-655-2008 for referral information. You can also write to the address listed on the back page of this manual.
When calling, have ready
• your name
• your address
• model and serial numbers of your heater
• how heater was malfunctioning
type of gas used (propane/LP or natural gas)
• purchase date
Usually, we will ask you to return the part to
the factory.
TECHNICAL SERVICE
You may have further questions about instal-
lation, operation or troubleshooting. If so,
contact INNOVATIVE HEARTH PRODUCTS at 1-800-655-2008. When calling please have your model and serial numbers of your heater ready.
You can also visit INNOVATIVE HEARTH PRODUCTS technical services web site at
www.IHP.US.com.
VENT-FREE FIREBOXES
Available in 32", 36" and 42" models.
FLOOR MEDIA KIT - FM100
For all models. Includes lava rock, burner
embers, and burner cinders
CONTROL COVER KIT - CC100
For all models. Includes control cover log
and 6 unique fall-away logs.
FIREPLACE HOOD
Black - GA6050 Brushed Brass - GA6053 For all models. Helps deect heat away from
mantel or wall above replace. Fits openings
28" to 48" wide.
LAVA ROCK - GA6060
For all models. Order when additional rock
is desired.
www.Astria.US.com
126832-01A40
Page 41
Innovative Hearth Products
Astria™ Brand Gas Log Set & Outdoor Gas Fire Pit
Limited Three Year Warranty
THE WARRANTY
Innovative Hearth Products Limited Three Year Warranty ("IHP") warrants your Astria™ brand Gas Log Set or Outdoor Gas Fire Pit ("Product") to be free from defects in materials and workmanship at the time of manufacture. The logs and grate carry the Limited Three Year Warranty. After installation, if covered components manufactured by IHP are found to be defective in materials or workmanship during the Limited Three Year Warranty period and while the Product remains at the site of the original instal­lation, IHP will, at its option, repair or replace the covered components. If repair or replacement is not commercially practical, IHP will, at its option, refund the purchase price or wholesale price of the IHP product, whichever is applicable. IHP will also pay IHP prevailing labor rates, as determined in its sole discretion, incurred in repairing or replacing such components. THERE ARE EXCLUSIONS AND LIMITATIONS to this Limited Three Year Warranty as described herein.
COVERAGE COMMENCEMENT DATE
Warranty coverage begins on the date of installation. In the case of new home construction, warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the Product by an independent IHP dealer, whichever occurs earlier. The warranty shall commence no later than 24 months following the date of product shipment from IHP, regardless of the installation or occupancy date.
EXCLUSIONS AND LIMITATIONS
This Limited Three Year Warranty applies only if the Product is installed in the United States or Canada and only if operated and maintained in accordance with the printed instructions accompanying the Product and in compliance with all applicable installation and building codes and good trade practices.
This warranty is non-transferable and extends to the original owner only. The Product must be purchased through a listed supplier of IHP and proof of purchase must be provided. The following do not carry the Limited Three Year Warranty but are warranted as follows:
Gas components – Repair or replacement for one year from the date of installation. Remote control – Repair or replacement for one year from the date of installation. Labor coverage – Prevailing IHP labor rates apply for the warranty period of the component.
Parts not otherwise listed carry a 90 day warranty from the date of installation.
Whenever practicable, IHP will provide replacement parts, if available, for a period of 10 years from the last date of manufacture of the product.
IHP will not be responsible for: (a) damages caused by normal wear and tear, accident, riot, fire, flood or acts of God; (b) damages caused by abuse, negligence, misuse, or unauthorized alteration or repair of the Product affecting its stability or performance (The Product must be subjected to normal use. The Product is designed to burn either natural or propane gas only. Burning conventional fuels such as wood, coal or any other solid fuel will cause damage to the Product, will produce excessive temperatures and could result in a fire hazard.); (c) damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product; (d) damages, repairs or inefficiency resulting from faulty installation or application of the Product.
This Limited Three Year Warranty covers only parts and labor as provided herein. In no case shall IHP be responsible for materials, components or construction which are not manufactured or supplied by IHP or for the labor necessary to install, repair or remove such materials, components or construction. Additional utility bills incurred due to any malfunction or defect in equipment are not covered by this warranty. All replacement or repair components will be shipped F.O.B. from the nearest stocking IHP factory.
LIMITATION ON LIABILITY
It is expressly agreed and understood that IHP’s sole obligation and the purchaser’s exclusive remedy under this warranty, under any other warranty, expressed or implied, or in contract, tort or otherwise, shall be limited to replacement, repair, or refund, as specified herein.
In no event shall IHP be liable for any incidental or consequential damages caused by defects in the Product, whether such damage occurs or is discovered before or after replacement or repair, and whether such damage is caused by IHP’s negligence. IHP has not made and does not make any representation or warranty of fitness for a particular use or purpose, and there is no implied condition of fitness for a particular use or purpose.
IHP makes no expressed warranties except as stated in this Limited Three Year Warranty. The duration of any implied warranty is limited to the duration of this expressed warranty.
No one is authorized to change this Limited Three Year Warranty or to create for IHP any other obligation or liability in connection with the Product. Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. The provisions of this Limited Three Year Warranty are in addition to and not a modification of or subtraction from any statutory warranties and other rights and remedies provided by law.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
IHP reserves the right to investigate any and all claims against this Limited Three Year Warranty and to decide, in its sole discretion, upon the method of settlement.
To receive the benefits and advantages described in this Limited Three Year Warranty, the appliance must be installed and repaired by a licensed contractor approved by IHP.
Contact IHP at the address provided herein to obtain a listing of approved dealers/distributors. IHP shall in no event be responsible for any warranty work done by a
contractor that is not approved without first obtaining IHP's prior written consent.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this warranty to be valid, you must contact the IHP dealer/distributor from which you purchased the product. If you cannot locate the dealer/ distributor, then you must notify IHP in writing. IHP must be notified of the claimed defect in writing within 90 days of the date of failure. Notices should be directed to the IHP Warranty Department at 1508 Elm Hill Pike, Suite 108; Nashville, TN 37210 or visit our website at WWW.ASTRIA.US.COM.
Printed in U.S.A. © 2013 Innovative Hearth Products LLC
P/N 900201-00, Rev. NC 12/2013
Innovative Hearth Products
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
Page 42
KEEP THIS WARRANTY
Model (
located on product or identication tag
Serial No. (
located on product or identication tag
Date Purchased __________________________
Keep receipt for warranty verication.
WARRANTY
) _____________________________
) __________________________
www.Astria.US.com
126832-01A42
Page 43
NOTES
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
126832-01A 43
www.Astria.US.com
Page 44
P126826-01
P126832-01
1508 Elm Hill Pike, Suite 108
Nashville, TN 37210
1-800-655-2008
www.IHP.US.com
126832-01 Rev. A 02/14
Loading...