Aston Global EMERALD EM1000, EMERALD EM1500, EMERALD EM2000 User Manual

EMERALD
EM1000-1500-2000
User Manual
USER’S MANUAL
1000VA/1500VA/2000VA
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Please follow all instructions carefully during installation. Read this manual thoroughly before attempting to unpack, install or operate.
CAUTION- To prevent the risk of fire or electric shock, install in a temperature and humidity
controlled indoor area, free of conductive contaminants.
CAUTION- Risk of electric shock, do not remove the cover. No user serviceable parts. Refer
servicing to qualified service personnel.
CAUTION- Risk of electric shock, hazardous live parts inside this UPS can be energized from the
battery supply even when the input AC power is disconnected.
CAUTION- Risk of electric shock, Battery Circuit is not isolated from AC input, hazardous voltage
may exist between battery terminals and ground. Test before touching.
NOTICE- The UPS is designed to be for use with computer loads only.
SETUP
1 Inspection
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The package is recyclable; save it for reuse or dispose of it properly.
Inspect accessories:
Power cable 1PCS USER MANUAL
1PCS
2 Choose an installation location
3 Connect the loads
Plug in the AC input cord to the Utility(Make sure the voltage of Utility matches with the input voltage window of the UPS) Plug the UPS into the wall outlet to charge the UPS for over 8 hours before using the UPS. Plug in the loads to output receptacles on the rear panel of the UPS. CautionDo not connect a laser printer to the outlets. These UPS outlets provide battery power to the equipment when utility voltage is outside acceptable limits.
4 Connect Modem/ Phone / Network for Surge Protection(only for
the mode with RJ-45)
Connect a single modem/phone line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect from “OUT” outlet to the computer with another phone line cable.
5 Connect
Computer Interface Port (Optional)
Connect the optional interface cable to the USB interface port on the back of the UPS. Connect to the computer. See software document for installation instruction.
6 Turn ON/OFF the UPS
Turn on the UPS: Press the UPS On/OFF Switch for approx. 3 seconds, then the Buzzer sounds twice, the UPS will be start-up. Turn off the UPS: Press the UPS On/OFF Switch for approx. 3 seconds, then the Buzzer sounds twice, the UPS will be shutdown.
7 Cold Start Function
When the UPS is off and there is no power utility, it's still possible to cold start the UPS unit to power the loads.
8 Software Download and Installation
Please follow steps below to download and install monitoring software:
1. Go to the website http://www.Ablerex.com
2. Click Emily II software icon and then choose your required OS to down load the software.
3. Follow the on-screen instructions to install the software.
4. When your computer restarts, the monitoring software Software only for the model with communication port.
FRONT PANEL EXPLANATIONS
GRs - 1000 / 1500 / 2000 - LED
FRONT PANEL(STANDARD)
Symbol
LED
Color
Description/function
GRs - 1000/1500/2000 - LCD
FRONT PANEL(OPTION))
N/A
Tack switch for Turn-on/Turn-off
Green
Lit: Line mode Dim: Abnormal input voltage and frequency in standby mode Flashing: Standby mode
Yellow
Lit: Battery mode Flashing: Battery Low
Red
Lit: System malfunction or abnormal
1.Line mode
4. Battery capacity
7.Fault
2.Battery mode
5. Load level
8.Tack switch for Turn-on/Turn-off
3.AVR mode
6.Measurement Target & Value
REAR PANEL EXPLANATIONS
1. AC input outlet
2. Fuse
3. Output receptacles
4. RS-232 or USB port (option)
5. Modem/LAN Internet Protection (option)
6. Fan (only for GRs 1500/2000)
192321982025002
REPLACING THE BATTERY
NoteOnce the battery is disconnected, the loads are not protected from power outages.
1. Use a cross-type screwdriver to remove five screws on bottom shell
and screws on backplane.If there is a RS232 port,remove the screws on the port please.
2. Take off the top cover and front panel.
3. 1:Loosen the black wire from the negative (-) terminal and red wire
from the positive (+) terminal. 2:Remove the battery cover.
4. Exchange the new battery for the UPS
5. 1. Put on the battery cover on the battery. 2. Connect the battery leads to the new battery.
Note: Small sparks at the battery connectors are normal during connection.
6. 1:Install the top cover. 2:Install the front panel.
7. Fasten the screws mentioned in step 1.
8. Dispose of the old battery properly at an appropriate recycling facility.
TROUBLE SHOOTING
Should the UPS fail to function correctly we recommend you perform the following tests before calling the service. Check step: Step 1: Is the main switch in the ON position? Step 2: Is the UPS plugged into the mains power supply? Step 3: Does the power supply fall within specified unit values? Step 4: Has the fuse gone in the mains plug? Step 5: Is the UPS overload? Step 6: Is the battery flat or defective?
Situation
Check Items
Solution
No LED display on the front panel.
Low battery.
Charge the UPS at least 6 hours.
Battery fault.
Replace the battery with the same type of battery.
The UPS is not turned on.
Press the power switch again to turn on the UPS.
Alarm continuously sounds when the Utility is normal.
The UPS is overload.
Remove some loads first. Before reconnecting equipment, please verify that the load matches the UPS capability specified in the specs.
When power fails, back up time is shorten.
The UPS is overload.
Remove some critical load.
Battery voltage is too low.
Charge the UPS at least6 hours.
Battery defect. It might be due to high temperature operation environment, or improper operation to battery.
Replace the battery with the same type of battery.
The Utility is normal, but LED is flashing.
Power cord is loose.
Reconnect the power cord properly.
GRs 1000 / 1500 / 2000 SPECIFICATIONS
Model
GRs 1000
GRs 1500
GRs 2000
Capacity
1000VA / 700W
1500VA / 1050W
2000VA / 1400W
Input
Voltage
220/230/240VAC
Voltage range
165~290Vac
Output
Voltage Regulation
220/230/240VAC +/- 10%
Transfer time
Typical 6ms
Waveform
Sine Wave
Battery
Type & Number
12V/7Ah x 2
12V/9Ah x 2
12V/9Ah x 2
Charging time
4-6 hours recover to 90% capacity
Physical
Dimension(DxWxH, mm)
393 x 165 x 198
Net Weight(kgs)
9.3
12.4
12.6
Packaging Dimension(DxWxH, mm)
450 x 238 x 301
Gross Weight(kgs)
10.3
13.4
13.6
Environment
Humidity
0-90 % RH @ 0-40 C (non-condensing)
Noise level
Less than 40 dB
Less than 45 dB
Safety
Security certificate
CE
Loading...