Non-Incendive
AST43LP     Low Pressure Transducer / Transmitter     
The AST43LP is a low pressure Class I Division 2 stainless steel pressure 
transmitter for use in hazardous areas. In addition to its rugged construction and 
the best price-to-performance ratio in the industry, the AST43LP is the solution for 
low pressure measurement  for a variety of applications.
Environmental Data 
Temperature
Operating -40 to 85°C (-40 to 185°F)
Storage  -40 to 100°C (-40 to 212°F)
Thermal Limits
Compensated Range 0 to 55°C (32 to 132°F) 
TC Zero <±1.5% of FS 
TC Span <±1.5% of FS 
Other
Shock EN 60068-2-27
Vibration EN 60068-2-6, 60068-2-64, and IEC 68-2-32
EMI/RFI Protection: Yes 
Rating:     IP-66  
Benefits                                        
Class I Div 2 Groups A, B, C, D 
High Strength Stainless Steel Construction 
No Welds or Internal O-rings 
Wide Operating Temperature 
Pressures from 0-1 to 0-15 PSI 
Low Static and Thermal Errors 
Unparalleled Price and Performance 
Compatible with Wide Variety of Liquids  
 and Gases
EMI/RFI Protection 
Applications                                            
Flare Gas      
 Water Management 
Industrial OEM Equipment 
Oil & Gas Platforms 
Pressure Instrumentation 
Process Control 
Gas Compression & Storage 
Test Stands 
Oxygen Delivery Systems 
External Tank Level 
Performance @ 25°C (77°F) 
Accuracy* < ±0.25% BFSL (< ±0.5% BFSL for 0-1 PSI)
Stability (1 year) ±0.25% FS, typical 
Over Range Protection 2X Rated Pressure
Burst Pressure 5X or 75 PSI (whichever is less)
Pressure Cycles > 100 Million
* Accuracy includes non-linearity, hysteresis & non-repeatability
Electrical Data 
Output 4-20mA 1-5VDC 1-6VDC
Excitation 10-28VDC 10-28VDC 10-28VDC
Output Impedance >10k Ohms <100 Ohms, Nominal <100 Ohms, Nominal
Current Consumption: 20mA, typical 5mA, typical 5mA, typical
Bandwidth  (-3dB): DC to 250 Hz (-3dB): DC to 1kHz (-3dB): DC to 1kHz
Output Noise:  - <2mV RMS  <2mV RMS 
Zero Offset: <±1% of FS <±1% of FS  <±1% of FS 
Span Tolerance: <±2% of FS <±1.5% of FS  <±1.5% of FS 
Output Load: 0-800 Ohms@10-28VDC 10k Ohms, Min. 10k Ohms, Min.
Reverse Polarity Protection
American Sensor Technologies • 450 Clark Dr., Mt. Olive, NJ 07828 • phone (973) 448-1901 • fax (973) 448-1905 • email: info@astsensors.com
Yes Yes Yes

Ordering Information
AST43LP A 00005 P 4 1
Series Type
Process Connection
A= 1/4” NPT Male 
C= 1/4” BSPP Male 
I= 1/4” NPT Female
Pressure Measurement
Insert 5-digit pressure code
Pressure Unit
H= Inches H2O
Outputs
3= 1-5V 
4= 4-20mA (2 wire loop powered) 
6= 1-6V
Electrical
I= DIN 43650A
L= Conduit tting, Cable 2 ft. (0.6 m) 
M= Conduit tting, Cable 4 ft. (1.2 m)
Wetted Material
1= 316L   4= Hastelloy (consult factory on availability)
P= 1/2” MNPT 
T= G1/2 Male with Flush 
Diaphragm (see options)
P= PSI
N= Conduit tting, Cable 6 ft. (1.8 m) 
P =  C o n d u i t   t t i n g ,  C a b l e  1 0  f t .  ( 3 . 0  m )                                
4 = Mini-Fast (CSA Only)
L -SS
000
Options
000= No Options 
Approval
(Left Blank)= UL ANSI/ISA 12.12.01 Class I Div 2 Non-Incendive Groups A, B, C, D (formerly UL1604)
       -SS= Add “-SS” for CSA213 Class I Div 2 Non-Incendive Groups A, B, C, D and ANSI/ISA 12.27.01 Single Seal Approval
Note: CSA approved products require case/earth ground electrical connection. 
See wiring installation sheet for further details
Pressure Ranges
0-1
+
0-2.5
0-5 00005
+
0-7.5
00001
00069
00208
Pressure Code
PSIG Measurement
+
2.5 and 7.5 PSI Sensor must be ordered in inches of H2O.
0-10 00010
0-15 00015
www.astsensors.com 
© 2013 American Sensor Technologies Inc. AST43LP 12/18/2013. 
All specications subject to change without notice.

Non-Incendive
AST43LP     Low Pressure Transducer / Transmitter     
American Sensor Technologies • 450 Clark Dr., Mt. Olive, NJ 07828 • phone (973) 448-1901 • fax (973) 448-1905 • email: info@astsensors.com
www.astsensors.com 
© 2013 American Sensor Technologies Inc. AST43LP 12/18/2013. 
All specications subject to change without notice.