ASSALOY AHGUHF00 User Manual

ACS Report Number: 10-0344.W06.11.A
Certification Exhibit
FCC ID: U4A-AHGUHF00
IC: 6982A-AHGUHF00
FCC Rule Part: 15.247
Manufacturer: Assa Abloy
Model: AH13
Manual
5015 B.U. Bowman Drive Buford, GA 30518 USA Voice: 770-831-8048 Fax: 770-831-8598
Aperio
Hub Installation &
Integration Instructions
WFMN5A 11MAR 2011
EMEA Form: AAWL-260 01/31/11
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole or in part without the express written permission of ASSA ABLOY is prohibited.
Table of Contents
CHAPTER 1: TECHNICAL SPECIFICATIONS ...............................................................................................................................3
CHAPTER 2: SYSTEM OVERVIEW .................................................................................................................................................3
Introduction .............................................................................................................................................................................3
System Description ..................................................................................................................................................3
The Aperio Programming Application ..................................................................................................................3
CHAPTER 3: INSTALL THE COMMUNICATION HUB ..............................................................................................................4
Instructions ..............................................................................................................................................................................4
AH20 Integration(Wiegand) ..............................................................................................................................................5
AH20 DIP Switch Configuration ............................................................................................................................5
AH20 DIP Switch Configuration Table ..................................................................................................................6
Connections for AH20 (J100) .................................................................................................................................6
Connections for AH20 (J103) .................................................................................................................................7
Tamper Switch (AH20) ............................................................................................................................................7
AH13/AH30 Integration (RS485) ......................................................................................................................................7
AH13/AH30 DIP Switch Configuration .................................................................................................................8
AH13/AH30 DIP Switch Configuration Table .......................................................................................................8
Connections for AH13/AH30 ..................................................................................................................................9
Select EAC Address ................................................................................................................................................................9
RS485 Bus Connection ...................................................................................................................................................... 10
Physical Hub Installation ..................................................................................................................................................11
Communication Hub Adapter Plate Insatllation .............................................................................................11
Hub LED Indication ............................................................................................................................................................. 12
FCC Statement:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful Interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is Connected.
Consult the dealer or an experienced radio/TV technician for help.”
Industry Canada:
This Class B digital apparatus meets all requirements of the Canadian Interference Causing Equipment Regulations. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Cet appareillage numérique de la classe B répond à toutes les exigences de l’interférence canadienne causant des règlements d’équipement. L’opération est sujette aux deux conditions suivantes: (1) ce dispositif peut ne pas causer l’interférence nocive, et (2) ce dispositif doit accepter n’importe quelle interférence reçue, y compris l’interférence qui peut causer l’opération peu désirée.
Warnings:
Changes or modifications to this device not expressly approved by ASSA ABLOY could void the user’s authority to operate the equipment.
“This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator and your body. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.”
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the equivalent isotropically radiated power (e.i.r.p.) is not more than that necessary for successful communication.
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole
WFMN5A • PAGE 2
or in part without the express written permission of ASSA ABLOY is prohibited.
Chapter 1: Technical Specifications
Radio standard IEEE 802.15.4
Wireless Frequency Range
y 2400 – 2483.5MHz 16 channels
(11-26)
y (11-25) US only
Receiver Sensitivity
-100dBm 20 % PER
Wireless Transmit Power 10dBm/MHz
Wireless Operating Range in office
environment
Indoors - up to 50 feet (15m)
Internal Antenna
Two cross polarized dipoles
IP Classification: IP20
Electronic Requirements
Input Voltage: 8-24 VDC
Current 250mA
External Antenna
Operating Temperature
5°C to 35°C
Humidity
95% maximum (non-condensing)
Safety and Emissions
Chapter 2: System Overview
Introduction
This manual supports installation personnel, project managers, and individuals with similar responsibilities when installing and configuring Aperio technology version 2.3.0 and later.
y One reverse polarity SMA external antenna connector.
AH20 or AH13/AH30 is certified to be used with external antenna AH-ANTENNA-1. If other external antenna should be used than AH-ANTENNA-1 from ASSA ABLOY, the antenna should be of same type (dipole) and not have larger antenna gain than 3.9dBi.
y If coaxial cable need to be connected to AH20 or AH13/
AH30 plastic SMA extender AH-COAX-1 will be required to tighten the coaxial cable SMA connector to AH20 or AH13/ AH30 SMA connector.
y FCC 47CFR Part 15 subpart B and subpart C
y IC RSS-210
y EN ETSI 301 489-17 v2.1.1
System Description
The Aperio Programming Application
When a user presents a supported credential to the lock the Aperio system is designed to send the credential wirelessly to the Communication Hub. The Communication Hub (wired through RS-485 or Wiegand) then communicates with an EAC (Electronic Access Control) system. The EAC system provides the access decision to the Communication Hub ehere access to the lock is either granted or denied.
 A PC, running on Windows
Vista, Windows XP or Windows 7 and USB2.0
 Java runtime environment
version 6 or later
 USB radio with the latest
firmware
IEEE802.15.4 (2.4GHz)
Aperio Programming
Application
Figure 1. EAC System
Lock
RS485/Wiegaurd
Aperio Communication Hub
EAC System
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole or in part without the express written permission of ASSA ABLOY is prohibited.
WFMN5A • PAGE 3
Chapter 3: Install the Communication Hub
Instructions
Placement of the Hub
Note
:
Note: It is recommended to always verify the radio link quality. To do so see WFMN4A
Aperio Programming Application
Instructions for more
information.
For a stable and reliable radio link it is recommended that the distance between the lock and the Communication Hub is limited to 15 feet (5m). However, under good conditions (free air between the units and limited radio interference from other transmitters) it is sometimes possible to increase the distance to 35-45 feet (10-15m). Under poor conditions (heavy radio interface, etc.) it may be necessary to keep the distance between the lock and the Communication Hub well below 15 feet (5m). There is no minimum distance. If suitable, several Communication Hubs can be positioned together as long as the Hub-to-Hub distance is 1 foot (.2m) or more.
Figure 2. Placement of Communication Hub
Typically, the LED on the Communication Hub cover should “point” to the lock.
 The Communication Hub should be placed on the non-secure (key or card) side of the door.
Shorter distance and “light” materials in the walls permits placement on opposite sides.
 Be aware of that metallic sheet or mesh will attenuate the radio signal. Inner ceiling is, for
example, sometimes covered with foil or metallic mesh.
 Mirrors and larger metallic objects (like cable ladders) should kept at least 1 foot (2m) away
from lock or Communication Hub.
 WiFi / WLAN routers and other radio transmitters operating in the 2.4 GHz band should be kept
at least 11-12 feet (3-5m) from the Communication Hub and lock.
 Other possible sources of interference include microwave ovens, electric motors and other
high power electrical equipment. Keep at least 8-10 feet (2.5m) distance between the Communication Hub and lock.
1’
WFMN5A • PAGE 4
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole
or in part without the express written permission of ASSA ABLOY is prohibited.
AH20 Integration (Wiegand)
The AH20 Communication Hub communicates to the EAC System through Wiegand data and dry contacts. To connect follow these steps:
1. Set configuration options on DIP switch (S101)
2. Connect the Wiegand signals and dry contact outputs to the EAC System (J100 and J103)
3. Connect to the supply voltage by wiring 8 to 24 V (positive voltage) and GND (ground).
Note
:
The Communication Hub must be powered with a voltage between 8 VDC and 24 VDC.
If communication is established, the LED will have a steady green light.
AH20 DIP Switch Configuration
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole or in part without the express written permission of ASSA ABLOY is prohibited.
DIP switches 1-9 in the “OFF” position on the Communication Hub yield a default Wiegand configuration that is compatible with most EAC systems. But better performance and increased functionality can result from a customized configuration.
DIP 1: Controls use of RED LED signal to deduce Access Space Decisions.
ON: RED LED signal input is used.
OFF: RED LED signal input is ignored.
 If a signal is available that asserts access denied decision from EAC. ENABLE DIP 1 “ON” and attach
signal to J100, RED.
 If EAC system does not have RED LED output, only GREEN or does not use LED outputs to assert access
decisions, DIP 1 should be disabled “OFF”. Use lock relay output or similar EAC output (J100 GREEN) instead.
 Local override cards should not be used in conjunction with DIP 1 disabled (“OFF”) as this
configuration may produce an access denied based on a time out.
DIP 2: Reserved for future use.
DIP 3: Controls addition of parity bits if required:
ON: Addition of parity bits ENABLED.
OFF: Addition of parity is DISABLED transmitted as received.
 When enabled, addition of one even parity bit (before) and one odd parity bit (after) is applied to the
actual credential.
 Typically parity bits are already included in the creditial. In this case when DIP 3 is disabled (“OFF”)
transmitted credential may include parity.
DIP 4: Controls byte orders of transmitted credentials.
ON: The byte order is reversed compared to what is received as input to the Hub Wiegand EAC interface component.
OFF: The byte order is left as is.
 This setting is ignored as input to the hub in the case of the credential length does not make
complete bytes
 The byte order received as input to the hub in the case of a 32 bit MIFARE UID credential is UID[3], UID[2],
UID[1], UID[0]. This means that the byte order is already reversed earlier in the chain compared to the order specified in RFID interface standard ISO 14443-3.
DIP 5: Used for “Pairing Mode”.
ON: Pairing mode active.
OFF: Normal use.
 When enabled/active the next time an unpaired lock attempts to pair, it will be paired with the hub.
For unpairing the APA tool must be used. Reboot the hub for changes to take effect.
DIP 6-9: Unused in AH-20
DIP 10: Controls use of external antenna if required.
ON: Selects use of internal antenna.
OFF: Selects use of external antenna.
WFMN5A • PAGE 5
AH20 DIP Switch Configuration Table
This section provides a quick reference to DIP switch configurations for AH20 to the EAC system at use of a Wiegand interface.
DIP SwItch Number
1 A0 Controls use of LED Red signal to deduce access decision.
2 A1 Set to OFF by default. Reserve for futer use.
3 A2 Controls addition of parity bits if required.
4 A3 Controls byte order of transmitted credentials.
5 Used in “Pairing Mode”.
6-9 A4 Not used.
10 INT/EXT Internal/External Antenna Use, ON = Internal
LabeL DeScrIPtIoN
ON => LED Red is used.
OFF => LED Red is ignored.
ON => Addition of parity bits is enabled.
OFF => Addition of parity is disabled. Credentials are transmitted as received.
ON => The byte order is reversed compared to what is received as input to the Hub Wiegand EAC interface component.
OFF => The byte order is left as is.
ON => Starts in pairing mode.
OFF => Normal use.
Connections for AH20 (J100)
Communication Hub hardware version AH20 has four Wiegand signals plus ground. The purpose and connection of these signals are described in the table below.
hub coNNector DeSIgNatIoN
DATA 1 Wiegand Data 1 signal. Output from Communication
DATA 0 Wiegand Data 0 signal. Output from Communication
RED Wiegand RED LED signal. Input to Communication Hub.
GREEN Wiegand Green LED signal. Input to Communication
GND Ground Connect to EAC System ground.
8-24 VDC 8-24 VDC
DeScrIPtIoN coNNectIoN
Connect to Wiegand Data 1 on EAC
Hub. Used to transmit credentials.
Hub. Used to transmit credentials.
Used to deduce an access decision.
Hub. Used to deduce an access decision.
system.
Connect to Wiegand Data 0 on EAC system.
Connect to Wiegand RED LED output on EAC system. Leave unconnected if DIP switch 1 is selected “OFF”.
Connect to Wiegand Green LED output on EAC system. See DIP 1 on previous page for alternate instructions.
WFMN5A • PAGE 6
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole
or in part without the express written permission of ASSA ABLOY is prohibited.
Connections for AH20 (J103)
On the AH20 four form C relays are available. The purpose of the four relays is to perform Wiegand communication with an EAC System. The relay contacts are labeled and specified as:
NCL: Normal Closed
COM: Common
NOP: Normal Open
Relay 1: DPS
Relay 2: RX
Relay 3: Battery Alarm Output
Relay 4: Tamper Alarm Output
Note: Tamper output energized by default, all other outputs are de-energized by default.
Tamper Switch
Main Terminal Block
DPS
RX
Battery
DIP Switch
Tamper
Ground Lug
Relay Terminal Block
Figure 3. AH20 Connectors
Tamper Switch (AH20)
The tamper switch will be activated if AH20 is removed from its bottom cover or plastic adapter plate. If mounting to other than the plastic adapter plate as shown in the adapter plate installation instructions it is necessary to align the tamper switch with a special tamper tower post. See instructions provided with the optional mounting box.
AH13/AH30 Integration (RS485)
The AH13/AH30 Communication Hub communicates with the EAC System through RS485. To connect follow the below steps:
1. Set configuration options on DIP switch (S101).
2. Connect the RS485 signals to the EAC System (J100).
3. Connect to the supply voltage by wiring the 8 to 24 V (positive voltage) and GND (ground) terminal.
Note
:
The Communication Hub must be powered with a voltage between 8 VDC and 24 VDC.
If communication is established, the LED will have a steady green light.
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole or in part without the express written permission of ASSA ABLOY is prohibited.
WFMN5A • PAGE 7
AH13/AH30 DIP Switch Configuration
DIP 1-DIP4: Controls RS485 addressing BIT 0-BIT 3.
ON: Address bit set.
OFF: Address bit NOT set.
 Addresses “1” to “15” are available using dip switch configuration.
 Each Communication Hub connected to the same RS485 bus must have a unique RS485 address.
 An address of “0” disables the EAC interface of the Communication Hub DO NOT use this configuration
for normal installations. It also sets the Communication Hub in constant pairing mode.
 See RS485 Addressing Reference on Page 9.
DIP 5: Not used.
DIP 6: Controls use of RS485 pull down resistor.
ON: 620 Ohm pull down connected /enabled.
OFF: 620 Ohm pull down disconnected /disabled.
DIP 7: Controls use of RS485 pull up resistor.
UP: 620 Ohm pull down connected /enabled.
DOWN: 620 Ohm pull down disconnected /disabled.
DIP 8: Controls use of termination resistor between RS485 A and RS485 B.
ON: 100 Ohm connected /enabled.
OFF: 100 Ohm disconnected /disabled.
DIP 9: Not used.
DIP 10: Controls use of external antenna if required.
ON: Selects use of internal antenna.
OFF: Selects use of external antenna.
AH13/AH30 DIP Switch Configuration Table
DIP SwItch Number
1-4 A0
5 A4 Not Used.
6 DOWN Controls use of RS485 pull down resistor.
7 UP Controls use of RS485 and pull up resistor.
8 TERM Controls use of termination resistor between RS485 A and RS485 B.
9 Not used.
10 INT/EXT Controls use of external antenna if required.
LabeL DeScrIPtIoN
Controls RS485 addressing BIT 0-BIT 3.
A1
A2
A3
ON => Address bit set.
OFF => Address bit NOT set.
See RS485 Addressing Reference on Page 9.
ON => 620 Ohm pull down connected /enabled.
OFF => 620 Ohm pull down disconnected /disabled.
ON =>620 Ohm pull up connected /enabled.
OFF => 620 Ohm pull up disconnected /disabled.
ON =>100 Ohm termination resistor connected /enabled.
OFF => 100 Ohm termination resistor disconnected /disabled.
ON =>Selects use of internal antenna.
OFF => Selects use of external antenna.
WFMN5A • PAGE 8
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole
or in part without the express written permission of ASSA ABLOY is prohibited.
Connections for AH13/AH30
A and B is the RS485 interface that should be connected to EAC system. GND is the signal ground and should be connected to EAC system GND and power supply GND.
A: RS485 Data A
B: RS485 Data B
D1: N/C
D2: N/C
RED N/C
GREEN: N/C
GND: N/C
8-24VDC
Select EAC Address
The EAC address of the Communication Hub can be set in two ways:
 By configuration from the Aperio Programming Application.
 By use of the DIP switch (See Dip1-Dip4 on Page 9).
Selecting the RS-485 address from DIP switch through the Aperio Programming Application tool: the APA tool maybe used to remotely set or override the physical dip switch address setting. When the Communication Hub is set with the APA tool the physical dip switch settings are ignored. If new firmware is loaded into the commmunication hub the address must be reset by using the APA tool or the Communication Hub defaults go back to the dip switch settings.
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole or in part without the express written permission of ASSA ABLOY is prohibited.
WFMN5A • PAGE 9
RS485 Bus Connection
The RS-485 bus consists of a twisted-pair cable with a characteristic impedance of between 90 Ohm and 120 Ohms. Maximum bus length is1000m. Depending on the EAC system, a maximum of 16 units, including the EAC system, can be connected to the same bus.
If there is more than one Communication Hub to connect, the hubs should be connected in a daisy chain, not as a star so that all RS485 A connectors are connected together and all RS485 B connectors are connected together on the RS-485 bus (Fig. 5). Both ends of the RS-485 bus must be terminated. To terminate a Communication Hub at the end of the bus, switch 8 of the DIP switch must be in the ON position. All other Communication Hubs in the chain must have switch 8 of the DIP switch set to the OFF position. Refer to the EAC documentation for proper termination of the bus on the EAC side.
Pull up and pull down-resistors should be enabled once bus. Refer to EAC documentation for use of pull up or pull down on the EAC side. If pull up and pull down from the EAC system is not used, one Communication Hub on the bus should have DIP switches 6 and 7 set to the ON position.
Two examples of connection of multiple Communication Hubs to a single RS-485 bus of an EAC system:
EAC System
Termination
Enabled
EAC System
Termination
disabled
Hub 2
A B
DIP 6 OFF DIP 7 OFF DIP 8 OFF
A
B
Hub 1
A B
DIP 6 ON DIP 7 ON DIP 8 ON
Hub 1
A B
DIP 6 OFF DIP 7 OFF DIP 8 OFF
Figure 4. Examples, Communication Hub Connections
Hub 2
A B
DIP 6 OFF DIP 7 OFF DIP 8 ON
Hub N
End of Bus
A B
DIP 6 ON DIP 7 ON DIP 8 ON
aDDreSSeS a0 a1 a2 a3
0 ON
1 ON
2 ON ON
3 ON
4 ON
5 ON ON
6 ON ON
7 ON ON ON
8 ON
9 ON ON
10 ON ON
11 ON ON ON
12 ON ON
13 ON ON ON
14 ON ON ON
WFMN5A • PAGE 10
15 ON ON ON ON
Figure 5. Address Examples
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole
or in part without the express written permission of ASSA ABLOY is prohibited.
Physical Hub Installation
To install the Communication Hub, follow the following steps:
Note
:
Complete all Wiegand and DIP switch configuration prior to installing the
Communication Hub.
Communication Hub Adapter Plate Installation
Communication Hub
plugs
1. Remove the plugs from the interior of the mounting plate.
2. Secure the Communication Hub to the box with two screws.
Note
:
The square box assembly requires a plaster ring to be secured to the box prior to
securing the mounting plate to the assembly.
3. Place the plugs in the through holes of the mounting plate.
4. Place the Communication Hub on top of the adapter plate.
5. Insert two screws in the through holes of the Communication Hub.
screws
mounting plate
screws
plaster ring
box
Switch Box Assembly
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole or in part without the express written permission of ASSA ABLOY is prohibited.
Square Box Assembly
Octagon Box Assembly
Figure 6. Communication Hub Assembly
WFMN5A • PAGE 11
Handy Box Assembly
Hub LED Indications
The Communication Hub has a single LED that supports an optical scheme with red, green and yellow. The indication scheme is described by the two figures below:
Online
Aperio Lock Offline
EAC Offline
Aperio Lock and EAC Offline
UHF Communication
Figure 7. Communication Hub Normal LED Indications
Pairing Active
Figure 8. Communication Hub Normal LED Indications
Green
Green + One Red Flash
Green + Two Red Flashes
Green + Three Red Flashes
Yellow + Off, Fast Flash
Yellow
WFMN5A • PAGE 12
Copyright © 2011, ASSA ABLOY All rights reserved. Reproduction in whole
or in part without the express written permission of ASSA ABLOY is prohibited.
Notes
ASSA ABLOY is the global leader in door opening solutions, dedicated to satisfying end user needs for security, safety and convenience
WFMN5A • 01/11
Loading...