The air conditioning system comes with the following accessories. Use all of the installation
parts and accessories to install the air conditioner. Improper installation may result in water
leakage, electrical shock and fire, or cause the equipment to fail.
NAMEFigureQuantity
Remote Controller
Receiver
Pipe Clasp
Drain pipe accessories
(sectional view)
Copper Nut
(two specification)
Remote Controller
Dry Battery AAA
1
1
1
2
OPTION
EC
O
T
U
R
M
B
O
O
DE
FA
N
1
2
Installation Owner' manual
Remote Controller Instruction
Remote Controller Instruction
1
/
/
/
1
1
1
Page 4
INSTALLATION OVERVIEW
11
Read The Safety PrecautionInstall The Indoor Unit
44
Install The Drainage Pipe
55
22
33
Install The Outdoor Unit
66
Install The Refrigerant Pipe
88
Perform The Test Run
77
Electrical Wiring
Air Evacuation
2
Page 5
INDOOR UNIT INSTALLATION
Indoor Unit Parts
Pipe Juntion
Air Outlet
Mounting Hook
Electric Control Box
³ ö · ç³ ö · ç
Drainage Pipe
Air InletFilter
Refrigerant Pipe
PRECAUTION
!!
WARNING
The indoor unit shall be firmly installed on the structure capable of bearing its weight. If the
structure is too weak, the unit may fall and cause personal injury, property loss or death
DO NOT install the indoor unit in the bathroom or laundry because too much moisture will
short circuit the indoor unit and corrode the wiring.
Install the indoor unit at a height of more than 2.5m (8') above the floor.
CAUTION
!!
Install indoor and outdoor equipment, cables and wires at least 1 m (3.2 ') from TV and
radio to prevent static electricity or image distortion. The distance can be increased
appropriately according to different equipment
If the indoor unit is installed on metal, it must be electrically grounded.
DO NOT install the unit in the following locations:
In areas with oil drilling or fracking
In coastal areas with high salt content in the air
In areas with caustic gases in the air, such as near hot springs
In areas with power fluctuations, such as factories
In enclosed spaces, such as cabinets
In kitchens that use natural gas
In areas with strong electromagnetic waves
In areas that store flammable materials or gas
In rooms with high humidity such as bathrooms or laundry rooms
3
Page 6
Indoor Unit Installation lnstructions
Select installation location
The indoor unit should be installed in a location that meets the following requirements:
There is enough room for installation and maintenance.
There is enough room for the connecting pipe and drainpipe.
The ceiling is horizontal and its structure can sustain the weight of the indoor unit.
The air inlet and outlet are not impeded.
The airflow can fill the entire room.
There is no direct radiation from heaters.
Body Dimension
1.The positioning of celling hole, indoor
unit and hanging screw bolts.
G
H
E
F
A
C
D
Air inlet size
I
Air outlet opening size
DEF
570
65
18-24K
Outline dimension
AB
920
270
635
C
J
713
2.Position size of descensional
ventilation opening.
B
Size of mounted hook
M
L
35
Air return opening size
I
H
G
179
815
JKL
260
20
Size of
mounted lug
M
350
960
30K
36-60K
1140
1200
270
300
775
865
710
800
65
80
933
968
35
40
179
204
1035
1094
260
268
45
45
1240
1240
500
500
NOTE:All the figures in this manual are for explanation prupose only. They may be
slightly different from the air conditioner you purchased. The actual unit shall prevail.
4
Page 7
Choice of air return ways
.
The air conditioner should be installed securely; otherwise poor installation may lead to
abnormal noises and vibration.
This indoor unit is fitted with downward air return, which can be change to its backward counterpart if
necessary. Please follow the steps below(2-5) to change it into the mode of air return backward(6).
1.Air return backward
3. Loose the nut and dismantle flannel plate
and filter; Loose the nut dismantel the back
over.
2. Install the flannel plate and filter at the
backside; Install the cover to the
downside.
4.Air return downward
5
Page 8
Hang Indoor Unit(For finished concrete bricks)
1 Drill 4 holes 5cm (2") deep at the ceiling hook positions in the internal ceiling. Be sure
to hold the drill at a 90 angle to the ceiling.
2 Using a hammer, insert the ceiling hooks into the pre-drilled holes. Secure the bolt
using the washers and nuts.
3 Install the four suspension bolts.
For finished concrete bricks
Install the hanging hook with expansible
New Concrete Bricks
Inlaying or embedding the screw bolts.
bolt into the concrete deep to 45~50mm
to prevent loose.
Wooden construction
(Blade shape
insertion)
(Pipe hanging and embedding
screw bolt)
(Slide insertion)
Steel bar
Embedding screw bolt
Put the square timber over the roof beam,
then install the hanging screw bolts.
Timber over the beam
Roof beam
Ceiling
Hanging Screw
Bolt
Steel roof beam structure
Install the supporting angle steel.
Hanging screw bolt
Supporting
Hanging bolts
angle steel
4 Mount the indoor unit. You will need two people to Iift and secure it. Insert suspension
bolts into the units hanging holes. Fasten them using the washers and nuts.
Below the ceiling
Hanging Bolt
Nuts(Up)
Gasket(Upside)
Installing Ear
Gasket(Downside)
Nut(Downside)
L
NOTE: L shoulId be long
enough to prevent the nuts
from coming off
RECOMMENDED DISTANCES BETWEEN THE INDOOR UNIT AND THE CEILING
The distance between the mounted indoor unit and the internal ceiling should meet
the following specifications.
100mm/3.9"
6
Page 9
Outlet Air Pipe Installation
Generally, we have two types of outlet pipe available, i.e. rectangular or round ones.
Rectangular air conduit can be directly connected to air outlet of indoor unit by rivets. For
outlet dimensions, see outline drawing of the unit.
Round air conduit should be connected to a piece of transitional air conduit before it is
connected to air outlet of indoor unit, the other end of it can be separately connected to air
conduit window or connected to air conduit window after air flow diversion, and the total length
should not be over 6m. As shown in figure below, air speeds at all air outlets should be set to
basically consistent so as to meet the room air-conditioning requirements.
Air inlet
Indoor unit
Transitional air
conduit
Outlet pipe
Air-outlet window
Return Air Pipe Installation
In case sidewise air intake is adopted, return air pipe should be fabricated and rivet-connected
to return air orifice, and the other end of it should be connected to return air window.
In case of underside air intake, purchase or fabricate a section of pleated canvas air conduit
serving as transition joint for return air orifice and return air window. in this way, it can be freely
adjusted according to height of indoor ceiling board; in addition, during operation of the unit ,
canvas air conduit may avoid vibration of ceiling board, as shown in figure below.
Unit
Rivet
Installation mode for underside air intake
Return air pipe
Canvas air conduit
Canvas air conduit
Return air pipe
Return air window
Installation mode for sidewise air intake
Rivet
Unit
Tips for installation of return air pipe and outlet pipe
To minimize energy loss occurring in transmission process and condensed water during heating
operation, return air pipe and outlet pipe should be equipped with heat-insulating layer as shown in the
Heat preserving
Air conditionerAir conditioner
Plastic pinPlastic pin
Heat preserving
wool
wool
Tin foil
Tin foil
Plastic pin capPlastic pin cap
7
Page 10
NOTE:Ensure sufficient space
for installation and repair.
(see the picture for details)
100mm
Air outlet side
00
Canvas tunnel
Return air pipe and outlet pipe should be fixed to floor precast slabs by iron stand; in
addition, all ports of the air conduit should be tightly sealed by gasket cement, and it is
advisable that the edge clearance of return air pipe should be 150mm at least.
Drain pipe for condensed water should be installed with minimum gradient of 1 , and the
drain pipe should be insulated with heat-preserving pipe casing as well.
Installation diagram for indoor unit
Unit
Suspension rod
Return air pipe
Canvas air conduit
Return air window
including filter screen
Transitional air conduit
Outlet pipe
Air-out window
NOTE:Hang the nut inside the U slot of the installation panel.To confirm
level degree with gradienter . Leaning downside toward non-draining side
is prohibited. (see below)
Level Indicator
Hanging
Screw Bolt
Hanging Ear
Must Be Fixed Tight
8
Page 11
OUTDOOR UNIT INSTALLATION
Outdoor Unit Installation Instructions
Select installation location
The outdoor unit should be installed in a location that meets the following requirements:
Keep the outdoor unit as close to the indoor unit as possible.
Make sure there is enough space for installation and maintenance.
The installation area must be dry and well ventilated.
Make sure that the location of the unit is not affected by snow, leaf deposits or other
seasonal debris. If possible, provide a awning for this unit. Make sure that the awning
does not obstruct the air flow.
There must be enough space to install connecting pipes and cables and access them
for maintenance.
The area must be free of combustible gases and chemicals.The length of pipeline
between outdoor unit and indoor unit shall not exceed the maximum allowable
pipeline length.
If possible, do not install the unit in direct sunlight.
If possible, make sure the device is away from the property of your neighbors so that
the noise from the device does not interfere with them.
Air inlet and air outlet shall not be blocked or exposed to strong wind.If the location is
exposed to strong winds (for example, near the coast), you must place the unit
against the wall to block the wind. If necessary, use a sunshade.
Install indoor and outdoor equipment, cables and wires at least 1 meter away from TV
or radio to prevent static electricity or image distortion. Depending on the radio waves,
a distance of 1 meter may not be enough to eliminate all interference.
Strong wind
Strong wind
Strong wind
CAUTION
!!
Be sure to remove any obstacles that may block air circulation.
Make sure you refer to Length Specifications to ensure there is enough room for
installation and maintenance.
9
Page 12
Body Dimensions
A
A
H
H
B
DCE
MODE
18-24K
30-42K
48K
60K
AB
845586
940
940
938605
C
347
600375
600375
410
Install Outdoor Unit
Fix the outdoor unit with anchor bolts (M10)
600mm
D
372
400
400
440
E
342
340
340
417
F
312
338
338
372
F
H
700
885
1250
1369
600mm
Bolt
4 pieces for one unit
Bolt
4 pieces for one unit
10
Page 13
NOTE: The minimum distance
between the outdoor unit and walls
described in the installation guide
does not apply to airtight rooms.
Be sure to keep the unit unobstructed
In at least two of the three directions
(Front,Left,Right).
(As shown on the right)
>30
0/1
1.8
"
>2000/78"
Outdoor unit condensed water drainage(Optional)
The condensed water and the ice formed in the outdoor
unit during heating operation can be drained away through the drain pipe
1.Fasten the drain port in the 25mm hole placed in the
part of the unit as shown in the picture.
2.Connect the drain port and the drain pipe.
Pay attention that water is drained in a suitable place.
6"
3.
>600/2
>60
>300/11.8"
0/23.6"
Drilling Hole In Wall
You must drill a hole in the wall for the refrigerant piping, and the signal cable that will
connect the indoor and outdoor units.
1. Determine the location of the wall hole according to the location of the outdoor unit.
2. Use a 65 mm (2.5 ") core drill to drill holes in the wall.
3. Place the cuff on the hole. This protects the edge of the hole and helps seal the hole
when the installation process is complete.
NOTE: When drilling the wall hole, make sure to avoid wires,
plumbing, and other sensitive components.
11
Page 14
DRAINPIPE INSTALLATION
!!
CAUTION
Insulate all piping to prevent condensation.
Do not pull on the drain strongly, as this may cause it to disconnect.
If the drain is bent or installed incorrectly, water may leak and cause the water level
switch to fail.In heating mode, the outdoor unit will drain water.
Make sure that the drain hose is placed in a suitable area to avoid water damage and
slippage due to freezen drain water.
The drainpipe is used to drain water. Improper installation may cause damage to
equipment and property.
Indoor Drainpipe Installation
Install the drainpipe as shown below.
1.Attach the mouth of the drain hose to the unit's outlet pipe.Sheath the mouth of
the hose and clip it firmly with a pipe clasp.
2.Cover the drainpipe with heat insulation to prevent condensation and leakage.
1m~1.5m
Lean Downward over 1/100
Support
Flexible Hose
Attached Heat-insulation
Material
Hose band
Heat-insulation
Material
Polyvinyl Chloride PipeField-arranged
3.Using a 65-mm (2.5")core drill, drill a hole in the wall. Make sure that the hole is
drilled at a slight downward angle, so that the outdoor end of the hole is lower
than the indoor end by about 12mm (0.5") This will ensure proper water drainage
(as shown). Place the protective wall cuff in the hole. This protects the edges of
the hole and will help seal it when you finish the installation process.
4. Pass the drain hose through the wall hole.Make sure the water drains to a safe
location where it will not cause water damage or a slipping hazard.
Wall
NOTE: When drilling the wall hole,
OutdoorIndoor
12(0.5")
Drill a hole
in the wall
make sure to avoid wires, plumbing,
and other sensitive components.
The drainpipe outlet should be at
least 50mm (1.9") above the ground.
If it touches the ground, the unit may
become blocked and malfunction.
NOTE:
When using an extended drain, use an additional protective tube to tighten the indoor
connection to prevent it from loosening..
The drain pipes shall be sloped down at least 1 / 100 to prevent water from flowing back
to the air conditioner.
In order to prevent pipe sagging, a support shall be set every 1-1.5m (40-59 ").
12
Page 15
Hight static pressure drainage pipe installation
Warning:
Must install drainpipes according to the following figure , avoiding generating condensed
water and leakage water.
a.Assemble the main body according to Figure .
b.The opening of drainpipes can be installed on the leftside or the right side . Could remove
the drainstopper and put it on the left side or the right side.
c.For the best effect, should keep pipes as short as possible. Tilt the pipes to ensure the flow
of fluid.
d.Make sure the drainpipes have admirable heat insulation.
e.It is necessary to install a trap near the opening of the drainpipe,so that when the machine is
working, the pressure in the inside of the machine is lower than atmospheric pressure. If there
isn't a elbow , the water will splash and the pipe will produce a bad smell.
f.keep straightness of drainpipes so as to remove dirt.
g.Seal the drainpipe on the other side of the machine , then wrap up the drainpipe in the
heat-barriermaterials .
h.Put water into the drain pan to test whether the water can be discharged swimmingly.
i.In humid conditions , please must use a add-on drain pan(commercially available) to cover
the whole area of the indoor unit.
Indoor unit
Heat insulation
Site Preparation
Add-on drain pan
(sold separately)
13
Drain stopper
Tilt
Trap
Heat insulation
Site Preparation
The structure of the drainpipe
should be convenient for clean.
Bottom of unit body
50
50
Unit:mm
Page 16
Refrigerant Piping Connection
SAFETY PRECAUTION
!!
WARNING
All field piping must be completed by certified technicians and must comply with local
and national regulations.
When installing the refrigeration system, ensure that air, dust, moisture or foreign
substances do not enter the refrigerant circuit. Contamination in the system may cause
poor operating capacity,high pressure in the refrigeration cycle, explosion or injury.
When the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety limit
when the refrigerant leaks. If the refrigerant leaks and the concentration exceeds
its appropriate limit, it may cause a risk of hypoxia.
If refrigerant leaks during installation, ventilate the area immediately. The leaked
refrigerant gas is toxic and flammable. After completing the installation work, make
sure that there are no refrigerant leaks.
Pipe dimension and ways of installation
Outdoor pipe dimension and ways of install (in sequence of cooling capacity
Copper Pipe for Air ConditionerPipe Material
Model
Size(mm)
Liquid side
Gas side
NOTE: Ensure that the length of the refrigerant pipe, the number of bends, and
18k-24k
f 6.35(1/4inch)
f 12.7(1/2inch)
30k-42k
f 9.52(3/8inch)
f 15.8(5/8inch)
48k-60k
f 9.52(3/8inch)
f 15.8(5/8inch)
the drop height between the indoor and outdoor units meets the requirements
The maximum length and drop height based on models. (Unit: m/ft.)
Conventional pipe, cooling capacity 24KBtu/h
Longest pipe(L)
Maximum
height drop
Conventional pipe, cooling capacity 24K- 36KBtu/h
Height drop between indoor
and outdoor unit
Longest pipe(L)
Maximum
height drop
Conventional pipe, cooling capacity 36KBtu/h
Height drop between indoor
and outdoor unit
Longest pipe (L)
Maximum
height drop
Height drop between indoor
and outdoor unit H
Allowed value
30/98.4
20/65.6
Allowed value
50/164
25/82
Allowed value
65/213
30/98.4
Outdoor Unit
Oil Return
Longest PipeL
Height Drop between
indoor and outdoor unitH
Indoor Unit
14
Page 17
Oil Traps
!!
CAUTION
1 If the indoor unit is installed higher than the outdoor unit:
If oil flows back into the outdoor unit's compressor, this might cause liquid compression or
deterioration of oil return. Oil traps in the rising gas piping can prevent this.
An oil trap should be installed every 1 0m (32.Sft) of vertical suction line riser.
Indoor unit
Gas piping
Oil trap
Outdoor unit
Liquid piping
10m/32.8ft
10m/32.8ft
2 If the outdoor unit is installed higher than the indoor unit:
It is recommended that vertical suction risers not be upsized. Proper oil return to the
compressor shouId be maintained with suction gas velocity. If velocities drop below
7.62m/s(1 500fpm (feet per minute)), oil return will be decreased. An oil trap should
be installed every 6m(20ft) of vertical suction line riser.
Outdoor unit
Gas piping
6m/20ft
15
Indoor unit
6m/20ft
Liquid piping
Page 18
Refrigerant Piping Connection lnstructions
CAUTION
!!
DO NOT install the connecting pipe until both indoor and outdoor units have been installed.
1 If the indoor unit is installed higher than the outdoor unit:
Insulate both the gas and liquid piping to prevent water leakage.
DO NOT deform pipe while cutting.Be extra carefull not to damage,dent,or deform the pipe
while cutting.This will drastically reduce the heating efficiency of the unit
Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them properly. This will
ensure efficient operation and minimize the need for future maintenance.
1.Measure the distance between the indoor and outdoor units.
2.Using a pipe cutter, cut the pipe a little longer than the measured distance.
90
Remove burrs
slant roughess
Burr
Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely
removed.
1.Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
2.Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.
Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
1.After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign
materials from entering the pipe.
2.Sheath the pipe with insulating material.
3.Place flare nuts on both ends of pipe. Make sure they are facing in the right direction,
because you can't put them on or change their direction after flaring.
Point down
Pipe
Reamer
pipe
Flare nut
16
Page 19
4.Remove PVC tape from ends of pipe when ready to perform flaring work.
5.Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the
flare form.
6.Place flaring tool onto the form.
7.Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in
accordance with the dimensions
Flare form
Pipe
Outside
Diameter
7/16"
5/8"
3/4"
7/8"
17/16"
Tightening
Torque
18-20N m
(183-204kgf.cm)
25-26N m
(255-265kgf.cm)
35-36N m
(357-367kgf.cm)
45-47N m
(459-480kgf.cm)
65-67N m
(765-867kgf.cm)
Flare dimension(A)
(unit:mm/inch)
8.4/0.338.4/0.33
13.2/0.5213.5/0.53
16.2/0.6416.5/0.65
19.2/0.7619.7/0.78
23.2/0.9123.7/0.93
90 4
A
8. Remove the flaring tool and flare form,then inspect the end of the pipe for cracks and even
flaring
NOTE:Connect the copper pipes to the indoor unit first, then connect it to the outdoor unit.
You should first connect the low-pressure pipe, then the high-pressure pipe.
1 When connecting the flare nuts, apply a thin coat of refrigeration oil to the flared ends of
the pipes.
2 Align the center of the two pipes that you will connect.
3 Tighten the flare nut as tightly as possible by hand.
4 Using a spanner, grip the nut on the unit tubing.
NOTE: Use two spanners to
connect the pipe with indoor
/outdoor pipes to avoid the
copper pipe cracking.
5 While firmly gripping the nut, use a torque wrench to tighten the flare nut according to the
torque values.
CAUTION
!!
Ensure to wrap insulation around the piping. Direct contact with the bare piping may result in
1 Ifthe indoor unit is installed higher than the outdoor unit:
burns or frostbite.
Make sure the pipe is properly connected. Over tightening may damage the bell mouth and
under tightening may lead to leakage .
17
Page 20
6 After connecting the copper pipes to the indoor unit, wrap the power cable, signal cable and
the piping together with binding tape.
NOTE:While bundling these items together, DO NOT intertwine or cross the signal cable
with any other wiring.
Drain pipe outlet should be
led to a place that can avoid
affecting the environment.
Liquid-pipe heat preservation
Liquid pipe
Drain pipe
7 Thread this pipeline through the wall and connect it to the outdoor unit.
8 Insulate all the piping, including the valves of the outdoor unit.
9 Open the stop valves of the outdoor unit to start the flow of the refrigerant between the indoor
and outdoor unit.
CAUTION
!!
Check to make sure there is no refrigerant leak after completing the installation work. If there
1 If the indoor unit is installed higher than the outdoor unit:
Heavy-current cable
Gas-pipe heat pre ser vat ion
Gas pipe
Light current cable
is a refrigerant leak, ventilate the area immediately and evacuate the system (refer to the Air
Evacuation section of this manual) .
18
Page 21
ELECTRIC WIRING
SAFETY PRECAUTION
!!
WARNING
Always disconnect the power supply before working on the unit.
All electrical wiring must be done according to local and national regulations.
The wiring must be carried out by a certified technician. Improper connection may cause
electrical failure, personal injury and fire.
This unit must use independent circuit and single outlet. Please DO NOT plug other
equipment or chargers into the same outlet. If the circuit capacity is insufficient or the
electrical system fails, it will cause electric shock, fire, unit and property loss
Connect the power cord to the terminal and secure it with the wiring clamp. Improper
connections may cause fire
Make sure all wiring is correct and the control box cover is installed correctly. Otherwise,
may cause overheating at the connection points, fire, and electrical shock.
Ensure that main supply connection is made through a switch that disconnects all poles,
with contact gap of a least 3mm (0.118").
DO NOT modify the length of the power cord or use an extension cord.
CAUTION
!!
Connect the outdoor wires before connecting the indoor wires.
1 If the indoor unit is installed higher than the outdoor unit:
Be sure to ground the equipment. The grounding wire shall be away from gas pipeline, water pipe,
lightning rod, telephone or other grounding wire. Improper grounding may cause electric shock
DO NOT connect the unit with the power source until all wiring and piping is completed.
Please make sure not to cross the wire with the signal wire, which will cause distortion and
interference.
The unit must be connected to the main outlet. Normally, the power supply must have a low output
impedance of 32 ohms.
No other equipment should be connected to the same power circuit.
NOTE:The type of fuse for controller of indoor unit is 50CT/524 rated specification is
T 5A,250VAC.Fuse for the whole unit is not supplied by the manufacturer,so the installer
must employ a suitable fuse or other over-current protective device for the power supply
circuit according to the maximum power input as required.
19
Page 22
Outdoor Unit Wiring
!!
WARNING
Please turn off the main power of the system before performing any electrical or wiring work
CAUTION
!!
Please wire in strict accordance with the wiring diagram(found inside the electrical box cover).
The refrigerant circuit can become very hot. Keep the interconnection cable away from the copper tube.
Prepare The Cable For Connection
1 You must first choose the right cable size before preparing it for connection. Be sure to use
H07RN-F cables.
2 Using wire strippers, strip the rubber jacket from both ends of signal cable to reveal about
15cm (5.9") of the wires inside.
3 Strip the insulation from the ends of the wires.
4 Using a wire crimper, crimp u-lugs on the ends of the wires.
Minimum Cross-Sectional Area of Power and Signal Cables
Rated Current of
Appliance(A)
7
7-13
13-18
18-25
25-30
North Americ
AWG
18
16
14
12
10
Rated Current of
Appliance(A)
6
6-10
10-16
16-25
25-32
Other Regions
Nominal Cross-Sectional
Area(mm )
2
0.75
1
1.5
2.5
4
Wiring Instructions
1 Remove the electric cover of the outdoor unit.
Electric control box cover
Power supply wire
Signal connecting wire
Thermal insulation Materials
Connecting pipes
2. Connect the power connection cord to the terminal board. Wiring should fit that of indoor unit.
3. Fix the power connection cord with wire clamp.
4. Confirm if the wire has been fixed properly.
5. An efficient earth connection must be ensured.
6. Recover the control box cover.
20
Page 23
Indoor Unit Wiring
Prepare The Cable For Connection
1 Using wire strippers, strip the rubber jacket from both ends of signal cable to reveal about
15cm (5.9") of the wires inside.
2 Strip the insulation from the ends of the wires.
3 Using a wire crimper, crimp u-lugs on the ends of the wires.
Wiring Instructions
1. Remove the electric cover of the outdoor unit.
2. Thread the power cable and the signal cable through the wire outlet
ring of the box
the electric control box cover
wire diagram in the back of
the electric control box cover
rubber
3.Connect the power connection cord to the terminal board. Wiring should fit that
of outdoor unit.
4.Fix the power connection cord with wire clamp.
5.Confirm if the wire has been fixed properly.
6.An efficient earth connection must be ensured.
7.Reinstall the
electric cover of the indoor unit.
8.Wrap the power cable,signal cable and the piping together with binding tape.
MODEL(Btu/h)MODEL(Btu/h)
POWER
(indoor)
POWER
(outdoor)
PHASE
VOLT
PHASE
VOLT
24K24K30K30K36K36K36K36K42K42K
1 Phase1 Phase1 Phase1 Phase1 Phase
220-240V
50Hz
1 Phase1 Phase1 Phase3 Phase3 Phase
220-240V
50Hz
220-240V
50Hz
220-240V
50Hz
220-240V
50Hz
220-240V
50Hz
220-240V
50Hz
380-415V
50Hz
220-240V
50Hz
380-415V
50Hz
A/C Power Specification
21
Page 24
AIR EVACUATION
Safety Precautions
CAUTION
!!
Use a vacuum pump with a gauge reading lower than -0.1 MPa and an air discharge capacity
above 40L/min.
The outdoor unit does not need vacuuming. DO NOT open the outdoor unit's gas and liquid
stop valves.
Ensure that the Compound Meter reads -0.1 MP a or below after 2 hours. If after three hours of
operation and the gauge reading is still above -0.1 MPa, check if there is a gas leak or water
inside the pipe. If there is no leakage, perform another evacuation for 1 or 2 hours.
DO NOT use refrigerant gas to evacuate the system.
Evacuation Instructions
Manifold valve
Hihandle
Discharged hose
Vacuum pump
NOTE:Before using manifold pressure
gauge and vacuum pump, please read
their operating instructions and be familiar
with how to use the manual correctly
Multi-function gauge pressure gauge
-76cmHg
Lohandle
Discharged hose
Low presasure valve
High pressure valve
1. Connect the hose of manifold pressure gauge to the maintenance port on the low pressure
valve of outdoor unit.
2. Connect another hose from manifold pressure gauge to vacuum pump.
3. Open the Low Pressure side of the manifold gauge.Keep the High Pressure side closed.
4. Turn on the vacuum pump to empty the gas in the system.
Run the vacuum pump for at least 15 minutes, or until the compound meter reads
5.
-
76cmhg (- 1 X105pa).
6. Close the low pressure side of the manifold pressure gauge and close the vacuum pump.
7. Wait for 5 minutes and check whether the system pressure changes.
NOTE:If there is no change in system pressure, unscrew the cap from the high pressure
valve.If there is a change in system pressure, there may be a gas leak.
22
Page 25
8. Insert a hex wrench into the high-pressure valve and open the valve by turning the wrench in
a 1 /4 counter clockwise turn. Listen for any gas coming out of the system and close the valve
after 5 seconds.
Connection pipe nut
Cap
Valve body
Valve stem
9.Observe the pressure gauge for one minute to make sure that the pressure does not change.
The pressure gauge should read slightly above atmospheric pressure
10. Remove the charge hose from the service port.
Using hexagonal wrench, fully open both the high pressure and low pressure valves.
11.
12. Tighten valve caps by hand, then tighten it using the proper tool.
CAUTION
!!
When opening valve stems, turn the hexagonal wrench until it hits against the stopper. DO NOT
1 If the indoor unit is installed higher than the outdoor unit:
try to force the valve to open further.
Additional Refrigerant Charge
CAUTION
!
Refrigerant charging must be done after wiring, vacuuming and leak testing.
Do not exceed the maximum allowed amount of refrigerant or overcharge the system. This will
damage or affect the function of the device.
Charging with mismatched refrigerant can cause an explosion or an accident. Make sure that a
suitable refrigerant is used.
The refrigerant container must be opened slowly. Always use guards when charging the system.
Do not mix refrigerant types.For R290 or R32 refrigerant models, when adding refrigerant to the
air conditioner, ensure the safety of the conditions in the area by controlling flammable materials.
Some systems require additional refrigerant charge depending on the length of the pipe. The
standard pipe length of this air conditioner is 5 meters (16 feet). The following table can be used
to calculate the additional refrigerant to be charged:
Liquid pipe diameter
Additional charge for 1m/ft pipe(R32)
Additional charge for 1m/ft pipe(R410A)
6.35(1/4")
12g/0.13oZ
9.52(3/8")
24g/0.26oZ40g/0.42oZ
15g/0.16oZ30g/0.32oZ65g/0.69oZ
¦ Õ 1/2¡ å
12.7(1/2")
23
Page 26
TEST RUN
Precaution
The test run needs to be performed after the entire system is completely installed. Before
performing the test, please confirm the following points:
a. The indoor unit and outdoor unit are installed correctly according to the instructions
b. The electrical wiring is properly connected.
c. Make sure there are no obstacles near the air conditioner. These obstacles may cause
the air conditioner to malfunction or degrade performance.
d. The refrigeration system has no leakage.
e. The drain pipe has been installed as required
CAUTION
!
Failure to perform the test run may result in unit damage,property damage or even
personal injury.
Test Run Intructions
1. Open both the liquid and gas stop valves.
2
. Turn on the main power switch and allow the unit to warm up.
3. Set the air conditioner to COOL mode.
4. For the Indoor Unit
a. Ensure the remote control and its buttons work properly.
b. Double check to see if the room temperature is being registered correctly.
. Ensure the indicators on the remote control and the remote controller receiver
c
work properly.
d. Ensure the manual buttons on the indoor unit works properly.
e. Check to see that the drainage system is unimpeded and draining smoothly.
f . Ensure there is no vibration or abnormal noise during operation.
5. For the Outdoor Unit
a. Check to see if the refrigeration system is leaking.
b. Make sure there is no vibration or abnormal noise during operation.
c. Ensure the wind, noise, and water generated by the unit do not disturb your neighbors
or pose a safety hazard.
NOTE:If the unit malfunctions or does not operate according to your expectations, please
refer to the Troubleshooting section of the Owner's Manual before calling customer service.
24
Page 27
OWNER'S MANUAL
SAFTY PRECAUTION
Read the following " PRECAUTIONS" carefully before installation.
The caution items stated here must be followed because these important contents are related
to safety. The meaning of each indication used is as below.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the
seriousness is classified by the following indications.
WARNING
!
CAUTION
!
NOTE :
1. Injury means causing harmed, burned, electrical shocked, but not serious for hospitalization.
2. Damage of property means disrepair of property, material.
Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in instructions. Please remind the
customer to keep the operating instructions for future reference.
WARNING
!
After installation, ensure there are no refrigerant leaks and that the unit is operating properly. Refrigerant is both toxic and flammable and poses a serious health and safety risk.
Install according to this installation instructions strictly. If installation is defective, it will
cause water leakage, electrical shock or fire.
Use the attached accessories parts and specified parts for installation. Otherwise, it will
cause the set to fall, water leakage, fire or electrical shock.
Install at a strong and firm location which is able to withstand the set's weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit and single outlet must be used. If electrical circuit
capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to
properties only.
When carrying out piping connection, take care not to let air or other substances other
than the specified refrigerant go into refrigeration cycle. Otherwise, it will cause lower
capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
Engage dealer or specialist for installation. If installation done by user is defective, it
will cause water leakage, electrical shock or fire.
25
Page 28
WARNING
!
The appliance disconnection must be incorporated with an all-pole disconnection device
in the fixed wiring in accordance with the wiring rules.
Any person who is involved with working on or breaking into the refrigerant circuit should
hold a current valid certificate from an industry-accredited assessment authority, which
authorises their competence to handle refrigerants safely in accordance with an industry
recognised assessment specification.
Servicing shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be carried
out under the supervision of the person competent in the use of flammable refrigerants.
The equipment shall be properly stored to prevent mechanical damage from occurring.
Keep ventilation openings clear of obstruction.
Grounding is necessary. It may cause electrical shock if grounding is not perfect.
Do not install the unit at place where leakage of flammable gas may occur. In case gas
leaks and accumulates at surrounding of the unit, it may cause fire.
NOTE: The following informations are required for the units adopt R32/R290 Refrigerant.
The appliances shall be stored in the room without continuous working ignition source
(for example: open flames, an operating gas appliance or an operating electric heater).
Do not pierce or burn the appliances.
Note that the refrigerant may be odorless.
Compliance with national gas regulations shall be observed.
Appliance shall be stored in a well-ventilated area with room size corresponding to the
specified operation area.
Appliance shall be installed, operated and stored in a room with a floor area larger than X m ,
installation of pipe-work shall be kept to a minimum X m (Please see the following form ).
2
The appliance shall not be installed in an unventilated space, if that space is smaller than Xm
(Please see the following form ).Spaces where refrigerant pipes shall be compliance with
national gas regulations.
Model
Model
(Btu/h)
(Btu/h)
24K
30K-36K
42K
Amount of refrigerant
Amount of refrigerant
to be charged(kg)
to be charged(kg)
1.25
2.2-2.4
2.8
maximum installation
maximum installation
height(m)
height(m)
2.2m
2.2m
2.2m
Minimum room
Minimum room
area(m )
area( )2m
2
4
4
5
2
2
26
Page 29
CAUTION
!!
Do not operate the air conditioner or remote control with wet hands. This may cause
electric shock.
When the wind deflector moves, do not touch the air outlet with your hands. Fingers
may be pinched or the machine may be damaged.
If the air conditioner is used with other heating equipment, please adequately ventilate
to avoid insufficient oxygen in the room
After prolonged use, please check the indoor unit for damage. If the indoor unit is aged
or damaged, it may fall or cause personal injury.
Do not expose heat-producing appliances to cold air or place them under the indoor unit.
This may cause incomplete combustion or deformation of the unit due to the heat.
Do not place items that might be affected by moisture damage under the indoor unit.
Condensation can occur at a relative humidity of 80%.
Do not check the equipment yourself. Please have it checked by an authorized dealer.
Do not use air conditioners for preservation purposes (storage of food, plants, animals,
art, etc.).
Do not touch the evaporator coil inside the indoor unit. The evaporator coil is very sharp
and may cause injury.
Do not climb or place objects on top of the outdoor unit.
Do not let children play with the air conditioner.
Note about Fluorinared Gasses
1. This air conditioner contains fluorinated gas. Refer to the relevant label of the unit
itself for specific information on the type and quantity of gas.
2. The installation, repair, maintenance and repair of the device must be carried out
by qualified technicians.
3. Unloading and recycling of air conditioner must be carried out by certified
technicians.
4. The system must be checked for leaks at least every 12 months.
5. When checking the air conditioner for leakage, it is strongly recommended that all
checks be recorded
Explanation of symbols displayed on the indoor unit or outdoor unit
(applicable to the unit adopts R32/R290 Refrigerant only):
This symbol shows that this appliance uses a flammable
WARNING
CAUTION
CAUTION
CAUTION
refrigerant. If the refrigerant is leaked and exposed to
an external ignition source, there is a risk of fire.
This symbol shows that the operation manual shouId be
read carefully.
This symbol shows that a service personnel should be
handling this equipment with reference to the installation
manual.
This symbol shows that information is available such as
the operating manual or installation manual.
27
Page 30
PARTS AND FUNCTIONS
Indoor Unit
6
5
O
PTIO
N
ECO
TURBO
M
ODE
FAN
7
Outdoor Unit
13
12
³ ö · ç³ ö · ç
1
Air Outlet
Air Outlet
2
Refrigerant Pipe Junction
Refrigerant Pipe Junction
3
Installation Hook
8
9
10
Installation Hook
4
Drainage PIpe
Drainage PIpe
Air Return
Air Return
5
Filter
Filter
6
Remote controller
Remote controller
7
8
Remote controller receiver
Remote controller receiver
9
Refrigerant connection pipe
Refrigerant connection pipe
10
Connecting cord
Connecting cord
Stop valve
Stop valve
11
12
Air Outlet grille
Air Outlet grille
13
Classical wall controller
Classical wall controller
(Optional)
(Optional)
11
Requirements
Notice that the air inlet/outlet must not be choked up. If chokeup takes place, the
air conditioner behavior may be affected, or air conditioner cannot run because of
actuation of protector.
When outside temperature is below 0 (32 ),we strongly recommend keeping
the unit plugged in at all time to ensure smmoth ongoing performance.(For outdoor
unit with auxiliary electric heater.
28
Page 31
Use the air-conditioner under the following
temperature:
MODE
COOL mode
HEAT mode
DRY mode
If the air conditioner runs for a long time in
"COOLING" or "DRY" mode at air relative
humidity higher than 80% (doors or windows
opened),dew may generate and drip near air
outlet.
Room Temperature
17 -32
(62 -90 )
0 -30
(32 -86 )
17 -32
(62 -90 )
Outdoor Temperature
-15 -50
(5 -122 )
-15 -24
(5 -76 )
0 -50
(32 -122 )
Noise pollutionOperating condition
Install the air conditioner in a place
that can bear its weight in order to
operate more quietly.
Install the outdoor unit in a place
where the air discharged and the
operation noise do not annoy your
neighbors.
Do not place any obstacles in front
of the outlet of the outdoor unit for
fear it affects operation and increases
the noise level.
Features of Protector
The protective device will trip at
following cases.
Stop the appliance and restart it at once
or change other modes during operation,
you have to wait 3 minutes before restarting.
After switching on the power circuit breaker
and then turn on the air conditioner at once,
you have to wait about 3 minute/20 seconds
(some models).
In case all operations have stopped, you need
Press "ON/OFF" button again to restart it.
Set TIMER once again if it has been canceled.
Feature of HEATING mode
Preheat
2-5 minutes are necessary to preheat the indoor heat exchanger at the beginning of
"HEATING" operation, lest cold air be discharged.
Defrost
In "HEATING" operation the appliance will defrost automatically. This procedure lasts
2 10 minutes, then returns to "HEATING" mode automatically. During defrosting, indoor
fan stop running and return to heating mode operation automatically when
defrosting has finished.
Inspection
After a long time of operation, the air
conditioner should be inspected for
the following items.
Abnormal heating of the power supply
cord and plug or even a burnt smell.
Abnormal operating noise or vibration.
Water leakage from indoor unit.
Metal cabinet electrified .
Stop using the air conditioner if above
problem happened.
It is advisable that the air conditioner
should be given a detail check-up
after using for five years even if none
of the above happen.
29
Page 32
REMOTE CONTROLLER RECEIVER
Nixie tube
Running lightTiming light
Defrosting/
preheat light
Manual Switch
warning light
Display function declaration :
LED light the state of running light
When powered-on the first time, the running light twinkles, while the nixie tube does
not lit.
When started-up normally, the running light lights on, while the nixie tube shows the
designed temperature.
When operated normally, the running light lights on, while the nixie tube shows the
designed temperature.
When closed down, both LED and nixie tube are gone out.
LED light the state of Timing light
When timing set, the timing light lights on, and the nixie tube flash shows the time
setting within 5 seconds, then shows the designed temperature.
When without time setting, the timing light gone out, while the nixie tube back to the
original state.
LED light the state of defrosting/preheat light
When in the state of defrost, oil return, cold-wind proof, the defrosting/preheat light lights
on, while the nixie tube shows the designed temperature. (One-driven-one does not show
the oil return state).
When out of the state of defrost, oil return, cold-wind proof, the defrosting/preheat light
gone out,while the nixie tube shows the designed temperature.(One-drive-one dose no t
show the oil return state).
LED light the state of warning light
When nixie tube shows E* or P*, the running lights gone out, while the warning light lights on.
t
2.Trouble display of outdoor unit
(1)During standby, the digital tube displays the numbers of indoor unit currently
connected and communicating.
(2)When the compressor operates, the digital tube displays the frequency value
of the inverter compressor;
(3)The digital tube displays dxx during defrosting;
The digital tube displays Cxx during oil return
(4)During trouble protection, the information code displayed by the digital tube.
30
Page 33
MAINTAINANCE
SAFETY PRECAUTION
!!
WARNING
Make sure all wires are properly connected. Failure to connect the wires according to
the instructions may result in electric shock or fire.
Make sure to install the drain hose according to the instructions. Otherwise, it may
cause leakage and cause personal and property damage
Please contact an authorized service technician for repair or maintenance. Incorrect
repairs and maintenance may cause water leakage, electric shock or fire.
Please replace the blown fuse with a fuse of the specified specification, otherwise it
may cause circuit damage or electrical fire.
Do not disassemble or clean the filter yourself. Disassembly and maintenance must be
performed by certified technicians.
CAUTION
!!
Always turn off your air conditioning system and disconnect the power supply before
cleaning or maintenance.
DO NOT use chemicals or chemically treated cloths to clean the unit.
DO NOT use benzene, paint thinner, polishing powder or other solvents to clean the unit.
They can cause the plastic surface to crack or deform.
DO NOT wash the unit under running water. Doing so causes an electrical hazard.
DO NOT use water hotter than 50 ( (114 ) to clean the filter. This can cause the
filter to become deformed or discolored. Clean the unit using a damp, lint-free cloth and
neutral detergent. Dry the unit with a dry,lint-free cloth.
INDOOR UNIT MAINTANANCE INSTRUCTION
NOTE:The filter prevents dust and other particles from entering the indoor unit. Dust
accumulation will reduce the efficiency of the air conditioner. For best efficiency, clean
the air filter every two weeks. If you live in a dusty area, you should clean the air filter
more frequently. If the filter is severely clogged and cannot be cleaned, replace it with
a new filter.
1.Remove the air filter.
A.
For your purchasing unit is a rear ventilated one(Fig A), please remove the filter fixed
screws (2screws) and take down the filter a way from the unit.
B.For your purchasing unit is a descensional ventilated one(Fig B), please push the filter
up slightly to let the position retainer escape away from the flange fixed holes, and take
off the filter according to the arrow direction shows in the following fig B.
2.Clean the air filter by vacuuming the surface or washing it in warm water with mild detergent.
A.If using a vacuum cleaner, the inlet side should face the vacuum.
B. If using water,the inlet side should face down and away from the water stream.
3.Rinse the filter with clean water and allow it to air-dry. DO NOT let the filter dry in direct
sunlight.
4.Reinstall the filter.
31
Page 34
AB
NOTE:For households with animals, you must wipe the grille regularly to prevent
animal hair from obstructing the airflow.
PREPARATION FOR PERIODS OF NON-USE
Maintenance after Extended Non-Use
1. Remove all obstacles in front of the ventilation holes of indoor and outdoor units.
2. Clean the air filter of the indoor unit. Reinstall the filter to its original location.
3. Turn on the main power switch 12 hours before operating the equipment.
Storing the Unit While Not In Use
1. Run the product in fan mode for 12 hours in a warm room to dry it and prevent mold.
2. Turn off the power of the device and unplug the power plug.
3. Before storing, clean the air filter according to the instructions in the previous section.
4. Remove the battery from the remote control.
!!
WARNING
If the refrigerant leaks, turn off the air conditioner and any combustible heating devices,
ventilate the room and call your dealer immediately.
Refrigerant is both toxic and flammable. DO NOT use the air conditioner until the leak is
repaired.
When the air conditioner is installed in a small room, measures must be taken to prevent
the refrigerant concentration from exceeding the safety limit in the event of refrigerant
leakage. Concentrated refrigerant causes a severe health and safety threat.
32
Page 35
TROUBLESHOOTING
CAUTION
!!
If one of the following conditions occurs, switch off the power supply immediately and
contact your dealer for further assistance
The operation light continues to flash rapidly after the unit has been restarted.
The remote control buttons do not work.
The unit continually trips fuses or circuit breakers.
A foreign object or water enters the air conditioner.
The indoor unit leaks.
Other abnormal situations.
Common Problems
The following symptoms are not a malfunction and in most situations will not require repairs.
ProblemPossible Cause
When the system is turned off or in cooling mode, there will be
abnormal noise, and when the drain pump (optional) is running,
Abnormal noises
of indoor unit
noise will also be heard.
A squeaking sound may occur after running the unit in HEAT
mode due to expansion and contraction of the units plastic parts.
Abnormal noises
of outdoor unit
Both the indoor
and outdoor units
makes noises
Unit does not turn
on when pressing
ON/ OFF button
The unit changes
from COOL mode
toFAN mode
The indoor unit
emits white mist
33
The unit will make different sounds based on its current operating
mode.
The air conditioner may sizzle during operation. This is a normal
phenomenon, which is caused by refrigerant gas flowing through
the indoor and outdoor units.
When the air conditioner is turned on, and just stopped or defrosted, a hiss may be heard. This noise is normal and is caused by
refrigerant gas stopping or turning.
The unit has a 3-minute protection feature that prevents the unit
from overloading. The unit cannot be restarted within three
minutes of being turned off.
Cooling and Heating Models: If the Operation light and PRE-DEF
(Pre-heating/ Defrost) indicators are lit up, the outdoor temperature is too cold and the unit's anti-cold wind is activated in order
to defrost the unit.
The unit changes its setting to prevent frost from forming on the unit.
Once the temperature increases, the unit will start operating again.
The set temperature has been reached, at which point the unit turns
off the compressor. The unit will resume operating when the temperature fluctu ates again.
In humid regions, a large temperature difference between the room's
air and the conditioned air can cause white mist.
Page 36
ProblemPossible Cause
Both the indoor
and outdoor units
emit white mist
Dust is emitted
from either the
indoor or outdoor
unit
When the unit restarts in HEAT mode after defrosting, white mist
may be emitted due to moisture generated from the defrosting
process.
The unit may accumulate dust during extended periods of
non-use, which I will be emitted when the unit is turned on.
This can be mitigated by covering the unit during long periods
of inactivity.
The unit emits
a bad odor
The fan of the
outtdoor unit
The unit may absorb odors from the environment (such as furniture,
cooking, cigarettes, etc.) which will be emitted during operations.
The unit filters have become moldy and should be cleaned.
During operation, the fan speed is controlled to optimize product
operation.
does not operate
Troubleshooting advices
When troubles occur, please check the following points before contacting a repair company.
ProblemPossible Cause
Power failure
The power switch is offTurn on the power
The unit is not
working
Poor cooling
performance
The fuse is burned out Replace the fuse
Remote control batteries
are dead
The unit's 3minute protection has been activated
Temperature setting may
be higher than the ambient
room temperature
The heat exchanger on the
indoor or outdoor unit is dirty
The air filter is dirty
The air inlet or outlet of either
unit is blocked
Doors and windows are open
Excessive heat is generated
by sunlight
Low refrigerant due to leak
or long-term use
Wait for the power to be restored
Replace the remote control batteries
Wait three minutes after restarting
the unit
Lower the temperature setting
Clean the affected heat exchanger
Remove the filter and clean it according
to instructions
Turn the unit off, remove the obstruction
and turn it back on
Make sure that all doors and windows are
closed while operating the unit
Close windows and curtains during periods
of high heat or bright sunshine
Check for leaks, re-seal if necessary and
top off refrigerant
Solution
34
Page 37
ProblemPossible Cause
There's too much or too little
refrigerant in the system
The unit starts
and stops
frequently
There is air, incompressible
gas or foreign material in the
refrigeration system.
System circuit is blocked
The compressor is broken
The voltage is too high or too low
Solution
Check for leaks and recharge the
system with refrigerant
Evacuate and recharge the system
with refrigerant
Determine which circuit is blocked
and replace the malfunctioning piece
of equipment
Replace the compressor
Install a manostat to regulate the voltage
Poor heating
performance
Error Code
The display content
of indoor LED
E0
E1
E2
E3
E4
E5
E6
E7
E8
E9
EC
EE
The outdoor temperature is
lower than 7 (44.5 )
Cold air is entering through
doors and windows
Low refrigerant due to leak
or long-term use
The definition of failure or protection
Indoor and outdoor Communication fault
Indoor room temperature sensor fault
Indoor coil temperature sensor fault
Outdoor coil temperature sensor fault
System unnormal
Model allocation error
Indoor DC fan motor fault
Outdoor room temperature sensor fault
Exhaust temperature sensor fault
Frequency conversion module fault
Outdoor Communication fault
Outdoor EEPROM fault
Check for leaks and recharge the
system with refrigerant
Make sure that all doors and windows
are closed during use
Check for leaks, re-seal if necessary
and top off refrigerant
35
Page 38
The display content
of indoor LED
The definition of failure or protection
EF
Ed
d3
C5
P0
P1
P2
P3
P4
P5
P6
P7
P8
P9
PA
PH
PC
H1
H2
H6
HE
Outdoor fan motor fault
Indoor EEPROM fault
Water full protection
Communication failure between indoor unit and remote controller
Inverter module protection
Voltage High/Low protection
High current protection
Outdoor fan protection /Out of step/compressor damaged/insufficient refrigerant
High exhaust temperature protection
Anti-cold protection when cooling
coil high temperature protection when cooling
Anti-heat protection when heating
outdoor temperature too high /low protection
Driver board protection
Mode conflict
Exhaust temperature sensor failure protection of outdoor unit
Coil temperature sensor failure protection of outdoor unit
High pressure switch protection
Low pressure switch protection
Insufficient of refrigerant protection
Phase sequence protection
36
Page 39
DISPOSAL GUIDELINE
This appliance contains refrigerant and other potentially hazardous materials. When
disposing of this appliance,the law requires special collection and treatment. DO NOT
dispose of this product as household waste or unsorted municipal waste.
When disposing of this appliance, you have the following options:
Dispose of the appliance at designated municipal electronic waste collection facility.
When buying a new appliance, the retailer will take back the old appliance free of
charge.
The manufacturer will also take back the old appliance free of charge.
Sell the appliance to certifid scrap metal dealers.
Disposing of this appliance in the forest or other natural surroundings endangers
your health and is bad for the environment. Hazardous substances may leak into
the ground water and enter the food chain.
37
Page 40
Information Servicing
1.Safety Checks
Before starting work on systems containing flammable refrigerants, a safety check must be carried
out to ensure that the risk of fire is minimized. Before servicing the refrigeration system, observe
the following precautions.
.
2.Work procedure
Work should be carried out in accordance with specified procedures to minimize the risk of
flammable gas leakage.
.
3.Work area
All mintenance staff and others working in the local area shall be instructed on the nature of work
being carried out. work in confined spaces shall be avoided. The area around the work space shall
be sectioned off. Ensure that the conditions within the area have been made safe by control of
flammable material.
.
4.Refrigerant leakage check
Before and during work, the area should be checked with an appropriate refrigerant detector to
ensure that technicians understand the concentration of flammable gases. The leak detection
equipment used must match the flammable refrigerant.
.
5.Fire extinguisher preparation
If the refrigeration equipment or any related parts are to be operated at high temperature,
dry powder or carbon dioxide fire extinguishers should be equipped
.
6.Keep away from ignition sources
Anyone engaged in work related to refrigeration systems containing flammable refrigerants shall not use any ignition source. Any ignition source, including smoking, shall be
keptaway from the place of installation and maintenance. Failure to do so may result in
danger to life or property damage.
7.Ventilation
Make sure the area is open or well ventilated before entering the system or carrying out any hot
work. During piping work, a certain degree of ventilation shall be maintained. Ventilation should
safely disperse the released refrigerant, preferably from the outside to the atmosphere.
.
8.Checks to the refrigeration equipment
When changing electrical components, they should be suitable for their purpose and meet the
correct specifications. The manufacturer's maintenance and service guidelines should always
be followed. If in doubt, please consult the manufacturer's technical department for assistance.
For devices using flammable refrigerants, the following checks should be performed:
The charge size is in accordance with the room size within which the refrigerant containing
parts are installed;
Ventilation machinery and vents are operating normally without obstruction;
If you use an indirect refrigeration circuit, you should check whether there is refrigerant in
the secondary circuit; the mark on the equipment is still clearly visible.
Indistinct marks and signs should be corrected;
The installation location of refrigeration pipes or components should make it not easy to be
exposed to any environment that may corrode refrigerant-containing substances, unless these
components are made of inherently anti-corrosion materials or are properly anti-corrosive.
.
38
Page 41
.9. Checks to electrical devices
The repair and maintenance of electrical components shall include preliminary safety inspection
and component inspection procedures. If there are faults that may endanger safety, do not
connect any power source to the circuit until the circuit is satisfactorily handled. If the failure
cannot be corrected immediately, but it is necessary to continue the operation, an appropriate
temporary solution should be used. This should be reported to the equipment manufacturer in
order to inform the parties
Initial safety checks shall include:
that capacitors are discharged: this shall be done in a safe manner to avoid possibility
of sparking
that there no live electrical components and wiring are exposed while charging, recovering
or purging the system;
that there is continuity of earth bonding
10. Sealed components maintenance
.
10.1 During repairs to sealed components, all electrical supplies shall be disconnected from the
equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely
necessary to have an electrical supply to equipment during servicing, then a permanently
operating form of leak detection shall be located at the most critical point to warn of a
potentially hazardous situation.
10.2 Particular attention shall be paid to the following to ensure that by working on electrical
components, the casing is not altered in such a way that the level of protection is affected.
This shall include damage to cable excessive number of connections, terminals not made
to Original specification, damage to seals, incorrect fitting of glands, etc.
Ensure that apparatus is mounted securely
Ensure that seals or sealing materials have not degraded such that they no longer serve
the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall
be in accordance with the manufacturer s specifications.
11.Safe components
Do not impose any permanent inductive or capacitive load on the circuit unless it is ensured that
it will not exceed the voltage and current allowed by the equipment in use. This machine safety
component is the only type that can be operated in the presence of flammable gases. The test in
strument should have the correct rating. Replace components only with parts specified by the
manufacturer.
.
12.Cabling mantainence
Check the cable for wear, corrosion, excessive pressure, vibration, sharp edges, or any other
adverse environmental effects. The inspection should also take into account the effects of aging
or continuous vibration such as compressors or fans.
.
13.Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for Or
detection of refrigerant leals.
For systems containing flammable refrigerants, the following leak detection methods are considered acceptable. An electronic leak detector should be used to detect flammable refrigerants, but
the sensitivity may be insufficient or may require recalibration. (The testing equipment should be
calibrated in an area free of refrigerant.) Make sure that the tester is suitable for the refrigerant.
Leak detection equipment should be set as a percentage of the refrigerant LFL, and should be
calibrated for the refrigerant used, and confirm the appropriate percentage of gas (maximum 25%).
Leak detection fluids are suitable for most refrigerants, but the use of chlorine-containing cleaning
agents should be avoided because chlorine may react with the refrigerant and corrode the copper
pipes. If a leak is suspected, all open flames should be cleared or extinguished. If it is found that
the refrigerant that needs to be brazed leaks, all the refrigerant should be recovered from the
system, or be isolated in the system part away from the leakage through the shut-off valve.
39
Page 42
15.Air evacuation
When breaking into the refrigerant circuit to make repairs of for any other purpose conventional
procedures shall be used, However, it is important that best practice is followed since flammability
is a consideration. The following procedure shall be adhered to:
remove refrigerant;
purge the circuit with inert gas;
evacuate;
purge again with inert gas;
open the circuit by cutting or brazing.
The refrigerant should be recovered in the correct recovery cylinder. OFN should be used to flush
the system to ensure the safety of the equipment. This process may need to be repeated several
times. Compressed air or oxygen cannot be used for this task.
The refrigerant should be recovered in the correct recovery cylinder. OFN should be used to flush
the system to ensure the safety of the equipment. This process may need to be repeated several
times. Compressed air or oxygen cannot be used for this task. Flushing should be achieved by
using OFN to break the vacuum in the system and continue to fill until the working pressure is
reached, then evacuate to atmosphere and finally drop to vacuum. This process should be repeated until there is no refrigerant in the system. When using the final OFN charge, the system should
be vented to atmospheric pressure for operation. If you want to braze the pipe, this operation is
very important. Ensure that the outlet of the vacuum pump does not turn off any ignition source,
and there is a ventilation device.
16. Refrigerant charging
In addition to following the normal charging procedure, the following requirements should also
be followed:
When using refrigerant charging equipment, please ensure that different refrigerants will
not be contaminated. The hose or pipeline should be as short as possible to minimize the
refrigerant content.
Refrigerant tank should be kept upright.
Before charging the refrigerant system, make sure it is grounded.
Mark the system when the charge is complete.
Be extra careful to avoid overfilling the refrigeration system.
Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak
tested on completion of charging but prior to commissioning. A follow up leak test shall be ca rried out prior to leaving the site.
.
17. About air conditioner removal
Before performing this step, please confirm that the technician is fully familiar with the equipment
and has relevant qualifications. It is recommended to safely recycle all refrigerants. Before completing the task, oil and refrigerant samples should be collected. Before the task begins, the power
must be disconnected.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically
c) Before attempting the procedure ensure that
mechanical handling equipment is available, if required, for handling refrigerant cylinders
all personal protetive equipment is available and being used correctly;
the recovery process is supervised at all times by a competent person;
recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed fromvarious
parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer s instructions.
h) Do not overfill cylinders. (No more than 80% volume liquid charge).
40
Page 43
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the
cylinders and the equipment are removed from site promptly and all isolation valves on the
equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it has
been cleaned and checked.
.
18.Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating
the equipment contains flammable refrigerant.
.
19.Refrigerant recovery
When removing refrigerant from a system, either for service or decommissioning, it isrecom-
mended good practice that all refrigerants are removed safely.
When tranferring refrigerant into cylinders ensure that only appropriate refrigerant recovery
cylinders are employed. Ensure that the correct numbers of cylinders for holding the total
system charge are available. All cylinders to be used are designated for the recovered
refrigerant and labelled for that refrigerant(i.e special cylinders for therecovery of refrigerant).
Cylinders shall be complete with pressure relief valve and associated shut-off valves in good
working Order
Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning
the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants.
In addition, a set of calibrated weighing scales shall be available
and in good working order.
Hoses shall be complete with leak-free disconnect couplings and in good condition. Before
using the recovery machine, check that it is in satisfactory working order, has beenproperly
maintained and that any associated electrical components are sealed to prevent ignition in
the event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery
cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery
units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated
to an acceptable level to make certain that flammable refrigerant does not remain within the
lubricant. The evacuation process shall be carried out prior to retruning the compressor to the
suppliers. Only electric heating to the compressor body shall be employed to accelerate this
process. When oil is drained from a system, it shall be carried out safely.
.
20.Transportation, marking and storage for units
1. Transport of equipment containing flammable refrigerants
Compliance with the transport regulations
2. Marking of equipment using signs
Compliance with local regulations
3. Disposal of equipment using flammable refrigerants
Compliance with national regulations
4. Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer s instructions.
5. Storage of packed (unsold) equipment
Storage package protection should be constructed such that mechanical damage to the
equipment inside the package will not cause a leak of the refrigerant charge.The maximum
number of pieces of equipment permitted to be stored together will be determined by local
regulations.
41
Page 44
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.