Aspen Manufacturing AFW, ABW Installation Manual

INSTALLATION GUIDE
AFW & ABW Series - Vertical Wall Mount Air Handler (Hydronic Heat)
1. Safety Instruction
`
WARNING
!
This symbol indicates a potentially hazardous situation, which if not avoided, could result in serious injury, property damage, product damage or death.
CAUTION
!
Certied technicians or those individuals
WARNING
!
and product damage or personal injury hazard may occur without such background.
WARNING
!
WARNING
!
installer’s responsibility to ensure that product is installed in strict compliance with national and local codes. Manufac­turer takes no responsibility for damage (personal, product or property) caused due to installations violating regula­tions. In absence of local/state codes, refer to National Elec­tric Code: NFPA 90A & 90B Uniform Mechanical Code.
WARNING
!
(i.e. automobile, space heater, water heater etc.) ensure that the enclosed area is properly ventilated.
meeting the requirements specied by
NATE may use this information. Property
All power sources should be disconnect­ed prior to servicing. Failure to do so may cause personal injury or property damage.
Product designed and manufactured to permit installation in accordance with lo­cal and national building codes. It is the
When this unit is installed in an enclosed area, such as a garage or utility room with any Carbon Monoxide producing devices
This symbol indicates a potentially hazardous situation, which if not avoided, may result in moderate injury or property damage.
2. Ensure These Steps are Completed to Reduce Chances of a Frozen Hydronic Coil
• Ensure the air handler motor and control board are receiving proper power input per the wiring diagram.
• Ensure the hydronic coil has access to a constant water supply as loss of water movement can lead to a frozen coil.
• Prime the water circulator pump using the purge valve per the “Start-Up” section of this installation guide.
Run the pump for ve minutes after priming to ensure no air is in the system.
• If any interruption to the water supply occurs, prime the water circulator pump again.
• Insulate the water piping in unconditioned spaces or within structures that may be unoccupied during freezing conditions.
• If the air handler does not have an internal pump and/or relies on an external boiler system for hot water, the installer may need to rewire the system to ensure that it maintains access to a constant water supply.
Only factory authorized kits and acces-
CAUTION
!
these instructions. Some localities may require a licensed installer/service personnel.
WARNING
!
WARNING
!
damages caused due to modication of the unit to operate
with alternative power sources.
sories should be used when installing or modifying this unit unless it is so noted in
Unit is not approved for outdoor installa­tions.
The unit is designed for operation with 108/120 V, single phase, 60 Hz power supply. Aspen will not be responsible for
1
3. Inspection
ü On receiving the product, visually inspect it for any major shipping related damages. Shipping damages are the carrier’s responsibility. Inspect the product labels to verify the model number and options are in accordance with your order. Manufacturer will not accept dam­age claims for incorrectly shipped product.
4. Installation Preparation
Read all the instructions in this guideline carefully while paying spe­cial attention to the WARNING and CAUTION alerts. If any of the
instructions are unclear; clarify with certied technicians. Gather all
the tools needed for successful installation of the unit prior to begin­ning the installation.
4A. Clearances
This unit is designed for zero clearance installation on three sides and adequate clearance to provide access for service in the front. A minimum of 2.5 – 3.5 feet clearance is recommended on the front end (Fig 4A-1).
4C. Condensate Drain
Drain lines from the auxiliary drain pan
CAUTION
!
The drain lines must be installed with ¼” per foot pitch to provide free drainage. A condensate trap MUST be installed on the primary drain line to ensure proper drainage of the condensate. The trap must be installed in the drain line below the bottom of the drain pan (Fig. 4C-1)
CAUTION
!
from the drain pan. Aspen will NOT be responsible for any damages resulting from failure to follow these instructions.
should NOT be connected to the primary drain line of the coil.
Fig 4C-1. Condensate Drain Trap
Since coil is upstream of the blower, all drains MUST be trapped or sealed. Failure
to do so will result in condensate overow
Fig 4A-1. Minimum Clearance for Air Handler
4B. Recess Mounting or Wall Mounting Option
These units are designed to be installed in a small room where they can be mounted above a water heater or recessed into a wall. The
unit should be installed in Vertical Upow position ONLY.
If installing the air handler into a recessed wall, the unit must leave clearance to allow the removal of the front panels. The bottom of the
unit should also rest on a sturdy platform or oor. The unit must be
level to allow condensate drainage.
These air handlers come with an offset mounting bracket that at-
taches the air handler to the wall when the unit is ush mounted to
the wall.
If the drain pan is constructed of nylon
CAUTION
!
DO NOT USE SOLVENT BASED PIPE DOPE. THIS WILL RE­DUCE THE LIFE OF THE PAN.
The drain pan has primary (red) and secondary (white) drain connec­tions. If a secondary drain line is required, it should be run separately from the primary and should terminate in a highly visible location. Condensate disposal through the secondary drain line indicates that the primary drain line is plugged and needs cleaning. If a second­ary drain line will not be provided, plug the secondary drain. Drain plugs are NOT to be reused without plumbers tape or putty. Drain
line connection should be nger tightened, then turned no more than one complete turn as needed to ensure a rm connection. DO NOT
overtighten connection or damage may occur.
or plastic; use Teon tape to connect the
drain lines to the threads in the drain pan.
2
4D. Ductwork
Duct systems should be installed in accordance with standards for air-conditioning systems, National Fire Protection Association Pam­phlet No. 90A or 90B. They should be sized in accordance with Na­tional Environmental System Contractors Association Manual K, or whichever is appli­cable.
On any job, non-am­mable exible collars
should be used for the return air and dis­charge connections to prevent transmission of vibration (Fig 4D-1). Although these units have been specially designed for quiet vi­bration-free operation, air ducts can act as soundboards, and if poor­ly installed, amplify the slightest vibration to the annoyance level.
All main supply and return air drops should be properly sized as determined by the designer of the duct system and should not nec-
essarily be the size of the duct ange openings of the unit. (The duct size should never be smaller than the ange openings of the air
handler supply and return air openings.)
These models have a bottom or front return. Discard the drain ac­cess panel in the bottom of the unit if this is a bottom return applica­tion (Fig 4D-2). In case of a front return application, the front access panel should be removed and discarded.
Fig 4D-1.
Fig 4D-4.
It is recommended that wherever supply and return air sheet metal ducts pass through unconditioned areas, they be insulated to pre­vent excessive heat loss during heating operation. When applied in conjunction with summer air conditioning, sheet metal duct routed through unconditioned areas should be insulated and have an out­side vapor barrier to prevent formation of condensation.
5. Installation
Ensure that the unit is adequately sized.
CAUTION
!
WARNING
!
to installation. If holding pressure is not present, return coil to distributor for exchange.
CAUTION
!
present) are protected from heat during brazing and instal­lation to prevent leakage. Use a core removal tool to tempo­rarily remove the core when brazing. Replace the core once brazing is completed.
The tonnage of the outdoor unit should never exceed the tonnage of this unit.
The coil was manufactured with a dry ni­trogen pre-charge. Release the pressure through the Schrader valve test port prior
Some Aspen coils may include a Schrader valve on the suction manifold. Ensure that the Schrader valve and valve core (where
Fig 4D-2.
If an accessory grill is being used, the front access panel should be removed and discarded (Fig 3D-3).
Fig 4D-3.
A lter rack is provided for a 1”X20”X20” nominal size lter (Fig 4D-
4). Inspect and clean or replace lter every month. A blocked lter can reduce air ow to the coil and hinder the performance of the
system.
Only lead free solder should be used to
CAUTION
!
WARNING
!
be extremely hot and might result in burns and other person­al injury along with equipment damage. Ensure that proper safety gear is being used prior to making connections.
ü Clean coil ns with degreasing agent or mild detergent and rinse ns clean prior to installation.
ü The refrigerant line sizes should be selected according to the rec­ommendations of the outdoor unit manufacturer.
ü Care must be taken to ensure all connection joints are burr-free and clean. Failure to do so may increase chances of a leak. It is recommended to use a pipe cutter to remove the spun closed end of the suction line.
ü To reduce air leakage, rubber grommets may be present where the lines pass through the coil case. To avoid damage, remove grom­mets prior to brazing by sliding over the lines. Use a quenching cloth or allow the lines to cool before reinstalling the grommets.
ü Use of wet rags/quenching cloth is highly recommended to prevent weld-related damages to the casing and Schrader valve (if present).
3
connect water (hydronic) coil to the hot water source.
Prior to connecting the water (hydronic) coil, make sure that the hot water supply is turned off. Water from the heater could
6. Mounting Air Handler To Wall
1. Install the air handler in a level position side to side and front to back. If this step is not followed, condensate water damage may oc-
cur. (Both ush mount and recess mount congurations.)
2. Determine where the air han­dler is to be placed on the wall. Place the hanging bracket on the wall and align the holes of the bracket with the wall studs.
Level the hanging bracket and
mark the holes to drill pilot holes for the screws.
8A. Flowrator Coils
Fig 8A-1. Flowrator assembly components
CAUTION
!
ing to the capacity of the outdoor unit.
Use Piston sizes recommended by the outdoor unit manufacturer whenever pos­sible. The piston should be sized accord-
3. Drill the pilot holes.
4. Secure the bracket with
screws sufcient to hold 4X the
weight of the air handler.
5. Position the air handler on the wall with the bracket on the air handler slightly higher than the bracket secured on the wall.
Lower the air handler so that the
brackets engage. Check the unit for level, both side to side and front to back.
WARNING
!
Failure to install the proper piston can lead to poor system performance and possible compressor damage.
I. Installation
Note: Photos are for basic illustration purposes only. Actual equip-
ment conguration may differ from that shown.
I-1. Disassemble owrator body
using two wrenches and un­screwing with a counterclockwise motion.
O-ring
I-2. Replace the Teon O-ring
(located between the halves). Discard Schrader if present.
7. Connecting Ducting
1. Secure supply air ducting to the top of the air handler. Canvas con­nectors are recommended for reducing potential noise transmission.
2. If the bottom return air opening is being used, remove the bottom panel. If a front return is being used, this pan­el will remain in place.
3. Secure the return air ducting to the air handler cabinet.
8. Metering Devices/Liquid Line Connection
Aspen coils are available with two kinds of metering devices a) ow­rator or b) TXV. The following instructions are separated into sec-
tions by metering device.
!
CAUTION
Be aware of the Teon O-ring. Be sure to
replace the O-ring to attain a proper
seal. (The Teon O-ring is located between the two halves of the owrator)
I-3. Slide the attachment nut onto the liquid line stub out.
4
I-4. Braze the stub-out portion to the liquid line and let cool.
O-ring
I-6. Tighten the nut to a torque of approximately 10-30 ft-lbs. Do NOT
overtighten the nut. Overtightening will impede the piston movement during operation.
I-5. Taking care that the white
Teon seal is still in place inside the owrater body, rmly seat the
stub and screw the attachment
nut to owrater body.
II. Piston Replacement
Note: Photos are for basic illustration purposes only. Actual equip-
ment conguration may differ from that shown.
During some installations, a piston change may be required. If so, the installer MUST change the piston. Use piston sizes recommended by the outdoor unit manufacturer. If a sizing chart is not available, use the piston size chart provided be­low to size the required piston. The size of the
Fig 8A-2
piston is stamped on the piston body (Fig 8A-2).
II-5. Pull the piston out using a small wire or pick. Verify the pis­ton size (size is typically stamped on the body of the piston - Fig 8A-2). If a different piston size is required by the outdoor unit manufacturer, replace the piston using the small wire provided with the piston kit.
II-6. Replace the piston with one of the correct size. Do not force the new piston into the body. Make sure the piston moves freely in body.
CAUTION
!
coil. Failure to ensure this orientation will cause the piston to be bypassed during operation which might damage the outdoor unit.
Pay close attention to the piston orienta­tion. The pointed end of the piston MUST go into the distributor body, towards the
Use the chart below when matching coil with an outdoor unit with a different nominal capacity than the coil.
II-1. Evacuate the system as per manufacturer guidelines and rec­ommendations
II-2. Turn the 13/16” nut once to release any residual pressure in the coil.
II-3. After ensuring that the coil is free of any residual pressure,
disassemble the owrator body
completely using two wrenches. Take great care not to distort the feeder tubes. The wrench used to clasp the nut should be turned in counter-clockwise direction to unscrew the nut.
II-7. Assemble the two halves correctly and ensure that the white
Teon O-ring is present between the two halves (See I-5). Slide the
13/16” nut onto the distributor body.
CAUTION
!
II-8. Tighten the nut to a torque of approximately 10-30 ft-lbs. Do NOT overtighten the nut. Overtightening will impede the piston movement during operation.
II-9. If present, slide the rubber grommet back to position to prevent air leakage.
Be aware of the Teon O-ring. Be sure to
replace the O-ring to attain a proper
seal. (The Teon O-ring is located between the two halves of the owrator)
8B. TXV Coils
II-4. Slide the 13/16” nut over the lineset and separate the two
halves of the owrator.
Fig 8B-1. Components of a typical TXV assembly
5
The sensing bulb and TXV body MUST be
WARNING
!
be covered using a quench cloth or wet cloth when brazing.
Pointing the brazing ame away from the valve and sensing
bulb provide partial protection only.
CAUTION
!
painted green for R22 or pink for R410A. In absence of col­or, the caps will be marked with the compatible refrigerant.
CAUTION
!
formance and possible compressor damage.
protected from overheating during braz­ing. The sensing bulb and TXV body must
Ensure that the TXV selected is compat­ible with the refrigerant used in the out­door system (R22 or R410A). TXV caps are
The valves should be sized according to the capacity of the outdoor unit. Failure to install the right valve can lead to poor per-
I. TXV Bulb Horizontal Mounting
The orientation and location of the TXV bulb has a major inuence
on the system performance.
Ensure that the TXV bulb is in direct con-
CAUTION
!
ed. Failure to do so will impair the proper functioning of the TXV valve.
It is recommended that the TXV bulb be installed parallel to the
ground (on a horizontal plane). The bulb position should be at 2 o’clock or 10 o’clock. Fig. 7B-2 shows the recommended position
for the TXV bulb installation in the horizontal plane.
tact with the suction/vapor line. Gap be­tween the bulb and tube should be avoid-
II. TXV Bulb Vertical Mounting
As recommended in Section
8B-I, the TXV sensing bulb
should be mounted in a hori­zontal plane in relation to the suction/vapor line. However, some installation congura­tions may require that the sensing bulb be mounted ver­tically. In this instance, place the bulb opposite the piping wall being hit by refrigerant and oil leaving the distributor tubes, and with capillary tubes directed upwards as shown in Fig. 8B-3.
Fig 8B-3. Recommended location
for vertical TXV bulb mount
If the TXV sensing bulb is mounted verti-
CAUTION
!
wall opposite to that being directly hit by the refrigerant and oil leaving the distributor tubes.
cally; the capillary MUST be directed up­wards. The bulb must be mounted on the
III. Field-Installed TXV Retrot
Note: Photos are for basic illustration purposes only. Actual equip-
ment conguration may differ from that shown.
When installing an expansion valve, it is not necessary to slide the coil out of the housing.
Bulb position at
2 o’clock or
10 o’clock
Fig 7B-2. Recommended location for horizontal TXV bulb mount
The TXV sensing bulb SHOULD be mounted on the suction line ap­proximately 6” from the TXV or coil housing using the metal clamp
provided. In order to obtain a good temperature reading and correct
superheat control, the TXV sensing bulb must conform to ALL of the
following criteria:
1. The sensing bulb MUST be in direct and continuous contact with the suction line.
2. The sensing bulb should be mounted horizontally on the suction line.
3. The sensing bulb MUST be mounted at the 2 o’clock or 10 o’clock position on the circumference of the suction line.
4. The sensing bulb MUST be insulated from outside air.
A properly mounted sensing bulb will prevent false readings caused by liquid refrigerant that may have formed inside the suction/vapor line. Insulation will protect the sensing bulb from false readings due to contact with warm air.
III-1. Disassemble the owrator
body using two wrenches. Un­screw the body with a counter­clockwise motion.
III-2. Remove the existing ow- rator piston using a small wire or pick.
III-3. Replace the Teon O-ring
seal in place (located between the halves).
O-ring
6
III-4. Inspect the TXV box to conrm that the valve is compatible
with the refrigerant in the system.
Male
(Inlet)
Female (Outlet)
III-5. Remove the valve from
the box and note the loca­tion of the inlet side (threaded male port) and the outlet side (female swivel nut port).
III-6. After ensuring that the
Teon O-ring seal is still in place inside the owrator body, screw
the female swivel nut onto the
owrator body.
O-ring
III-7. Slide attachment the nut onto the liquid line stub out
(See 8A, I-3)
III-8. Braze the stub-out portion to the liquid line and let cool.
WARNING
!
Do not attempt to touch brazed joints while hot. Severe burns may result.
B. Screw are nut on TXV equal-
ization tube on to the Schrader valve stem.
III-12b. In some cases, a suction line schrader port may not be present. If a Schrader port is NOT present:
A. Install a eld-supplied braze-on schrader
valve like that shown on the suction line near the intended sensing bulb mounting location. Fol­low valve manufacturer instructions and recom­mendations for installation.
B. Attach equalizer tube to valve as described in section III-12a above.
III-13. Mount the sensing bulb as described in section 8B-I or 8B-II.
When handling or manipulating the equal-
!
CAUTION
izer tube, take great care not to kink or make extreme bends in the tubing.
O-ring
III-10. Tighten all connections taking care to use proper back up.
III-11. Remove the valve identication sticker from the valve and
place it adjacent to the Aspen model number on unit name plate.
III-12a. Some Aspen coils come with a Schrader valve on the suc­tion line. If a Schrader port is present:
III-9. Remove the additional Tef­lon O-ring seal from the box and place on the shoulder just inside
the TXV inlet port. Screw the nut
attached to the stub-out portion of
the owrator body onto the inlet port of the TXV.
A. Remove the valve stem from the Schrader port mounted on the suction line.
7
9. Connecting Refrigerant Lines
1. Release nitrogen hold­ing charge by depressing the Shrader Valve at the liquid line connection on the air handler. If no gas releases from the air handler, contact distributor re­garding potential leak.
2. Cut off Shrader Valve tting at
the liquid line connection. Use a tubing cutter for this step. Clean the burr from the cut tubing to reduce the chance of future leaks. Connect the liquid line to the tubing at the indoor unit.
7. Flow nitrogen through the piping when brazing.
8. Braze both refrigerant line connections using proper brazing pro­cedures.
9. When all line connections are brazed, perform a proper system evacuation procedure per the outdoor unit manufacturer instructions.
10. Seal the penetration open­ings where the lineset piping en­ters the air handler cabinet.
10. Leak Check
1. Following outdoor unit manufacturer instructions and recommen­dations, charge the system with dry nitrogen to a maximum pressure of 150 PSIG.
3. Use a tubing cutter to remove the spun end from the suction line connection at the air han­dler. Clean the burr from the cut tubing to reduce the chance of future leaks.
4. To avoid heat damage to grommets where present, remove these prior to brazing by sliding them over the refrigerant lines and out of the way.
5. Check to determine if the evaporator coil has a Shrader
tting on the suction manifold.
If yes, remove the valve core to prevent heat damage during brazing. Replace the valve core once the piping has cooled.
2. Check all brazed and screw­on line connections by applying a soap solution to the joint. A leak will produce bubbles in the soap solution.
3. If any leaks or are discovered, relieve system pressure and repair leaks. Repeat steps 1-3.
4. With no leaks or weak connections present, evacuate the system and charge as per the outdoor unit manufacturer instructions and
specications.
11. Electrical Installation
These units are designed for single phase 120 volts, 60 Hz power supply. Wire selection and wiring must be in accordance with the Na­tional Electric Code and/or local codes. Unit terminals are designed to accommodate copper or aluminum wiring. If aluminum wiring is used, please observe special precautions relative to sizing, wire con­nections and corrosion protection.
Fig.11-1 shows the typical electrical connections required for A/C only and heat pump applications.
6. If the air handler has a TXV
metering device, remove the sensing bulb from the suction line prior to brazing to prevent heat damage from occurring. Replace the sensing bulb once the piping has cooled.
Fig 11-1.
8
Line voltage wiring should be
routed through the access holes at the top of the air handler. Proper electrical conduit con-
nection ttings should be used.
Connect the power wiring to the line side connections on the air handler. The electrical ground wire should be connected to the grounding lug. Ensure both the
eld supplied ground wire and air
handler GREEN ground wire are both secured to the grounding lug of the air handler (Fig 11B-2).
Fig 11B-2.
11A. Single Stage Cooling
Fig 11A-2.
During cooling mode operation, indoor blower wire “G” will energize a time delay relay located on the control board inside the air handler. After a short time delay period, the time delay relay will send out a 24 volt signal to the low voltage terminal on the motor. (See Schematic Fig 22-1.) Fan time delay periods are 30 seconds ON delay and 120
seconds OFF delay. The Y wire from the thermostat is not connected
at the air handler. This wire goes directly to the outdoor unit 24 volt wiring to turn on the outdoor condensing unit when a call for cooling takes place. The 24 volt common for the outdoor unit circuitry is con­nected at the air handler brown wire. (See Fig11-1.) The hydronic heater low voltage wiring terminal “W” is wired directly from the thermostat to the air handler. The indoor blower, on a call for heat, will ON delay for a period of 5 seconds. When the call for heat
has been satised, the indoor blower will have an OFF delay time
period of 60 seconds.
Operating CFM based upon each speed tap number is shown on the electrical wiring diagram of the unit. Final air volume adjustments should be made by referencing total external static pressure (Table 11B-1).
Table 11B-1.
11C. Jumper Placement
The unit ships with a micro-processor based board which controls the electrical functioning of the unit. An inspection of the controls is recommended prior to startup.
Fig.11C-2 provides a schematic of the control board present in the unit. The units ship from the factory with the aquastat jumper in the OFF position (right two pins) and the heating selector in the HW position (right two pins). If an aquastat is used in the application, the jumper should be changed to the ON position (left two pins).
Note: Terminals T and N located on the top right side of the board are not intended for eld use and should be left disconnected.
11B. Two Stage Condensing Units
If the outdoor condensing unit is a two stage model, a eld provided Y2 wire can be connected to the motor using an electrical spade con-
nector. The number 4 and 5 terminals on the motor are speed taps that will increase the blower speed for second stage cooling opera-
tion. Both the G and Y2 terminals will be energized at the same time
during a call for second stage blower speed operation. The motor will
run at the speed where the Y2 wire is connected (Fig 11B-1).
Fig 11B-1.
Fig 11C-2.
The aquastat (AQ) jumper must be in the
CAUTION
!
to the ON position without installing an aquastat, the blower will not be energized.
OFF position at all times, except for when an aquastat is used. If the jumper is moved
11D. Pump/Valve/Boiler Wiring
On units shipped from the factory with a pump installed (Fig 11D-3), the pump will be energized on a call for heat.
9
Fig 11D-3.
On units that were shipped without factory installed pumps, two
black wires should be connected to the terminals marked “BOILER”
T T (see Fig 11C-2). In applications where a boiler provides the hot water supply, these wires should be connected to the boiler control
wiring. Terminals “BOILER” T T are normally open dry contacts.
In applications where a valve is used to regulate the hot water supply,
the two black wires located on the “BOILER” T T terminals should be removed and placed on the two terminals marked “VALVE”. These
wires should be connected to a 24V valve according to local require­ments and instructions of the valve manufacturer.
On a call for heat, 24V will be sent to the eld-installed valve or pump
relay, the valve will open or pump relay will close contacts allowing the pump to run. Water will circulate through the water (hydronic) coil for 60 seconds prior to energizing the blower. After the thermostat is
satised, the blower will continue to stay energized for a minimum of
30 seconds. The additional blower run time helps maximize heating
efciency.
11E. Freeze Protection Sensor Wiring
The freeze protection sensor is connected to the “FP” and “R“ ter­minals. This sensor is normally open and will close when the sensor detects a temperature of less than 40ºF. The pump will operate and stay ON for a minimum of 30 seconds. The board has a built-in timer which circulates hot water 6 times a day for 60 seconds to prevent the hydronic coil from freezing.
Table 13-1.
Use a Magnehelic Gauge with a 1” scale and two static pressure tips to measure the static pressure during the air volume adjustment procedure (Fig. 13-1). The high port static pressure tip should be placed in the supply duct near the outlet of the air handler. The low port static pressure tip should be placed in the return air duct near
the entrance to the air handler. The factory provided air lter should
be in place inside of the air handler.
Fig. 13-1
1. Select a starting speed tap from the CFM table.
12. Condensate Drain
1. Condensate drain is located at front as shown in picture with pri­mary and secondary drain port.
2. Pipe condensate system using proper PVC ttings.
3. Ensure a minimum 2” trap is installed in the condensate
drain. Locate the trap near to
the connection opening on the air handler. See illustra­tion.
13. Air Volume Adjustment
Air volume needs to be set to the level recommended by the outdoor unit equipment manufacturer. Most systems will require around 400 CFM of indoor air for every 1 ton of system cooling capacity. The air volume must be set prior to attempting system charge.
This air handler uses a constant torque ECM motor. This motor will try to maintain proper motor torque to achieve programmed air volume levels at varying levels of external static pressure. The air volume level produced by the air handlers at varying external static pressure levels is shown in Table 12-1.
The blower motor has selectable speed taps labeled 1 thru 5 (Fig. 13-2). The speed taps are energized by 24 volts received from the time delay relay. When two stage cooling units are used, both the
rst and second stage fan speed taps will be energized at the same
time. The motor will run at the speed generated at the highest motor speed tap.
Fig. 13-2
2. Call for fan only operation at the thermostat. .
3. Read the external static pressure level on the Magnehelic gauge.
4. Make speed tap selection changes to get the air vol-
ume as close as possible to the required level. .
10
5. If the static pressure is above .5” wc, excessive turbu­lence or duct friction needs to be reduced. (Obstructions in the duct system can also cause excessive static pressure.)
16. Start-Up
Ensure that motor is pre-loaded with program from factory.
6. When proper air volume is established, move on to the charging procedure.
14. System Charging
An improperly charged system may cause
CAUTION
!
of the coil, refer to the outdoor unit manufacturer for charging techniques and amount of charge. If outdoor unit manufacturers charging instructions are unavailable; then refer to instructions below to charge the system.
1. Bring airow up to the maximum CFM possible according to Table
13-1.
2. Evacuate refrigeration system to micron level required by outdoor unit manufacturer.
3. Release system charge from outdoor unit and call for cooling.
4. Use outdoor unit equipment manufacturer specic charging charts
if available and make proper charge adjustment based upon outdoor unit instructions.
5. If outdoor unit instructions and charts are not available, use Aspen provided charts. Make certain indoor air temperature is near comfort level setpoint 75F, prior to establishing superheat and subcooling levels.
14A . Flowrator Coils
Add refrigerant until the superheat measured at the outdoor unit suc­tion/vapor line matches the superheat from the chart below.
Outdoor
Temp
°F D.B. Min Nom Max
65 30 35 40
70 26 30 34
75 21 25 29
80 17 20 23
85 12 15 18
90 8 10 12
95
100
degradation in system performance and damage the compressor. After installation
Superheat
4 5 7
The hot water (hydronic) coil and all wa-
WARNING
!
result in pump damage. Aspen will not be responsible for any property or personnel damage caused by failure to fol­low this instruction.
WARNING
!
burns. Use of proper safety gear while installing or servicing the equipment is strongly recommended as is installation of a water-tempering valve (for water temperatures of above
140ºF) to supply lower temperature water to xtures in the
house. N170L series or equivalent should be used.
WARNING
!
are no leaks in the coils, connections, and/or water piping. Failure to do so could result in water leaks and property dam­age. Aspen will not be responsible for any damage caused by failure to follow this instruction.
Connect the hydronic coil to the water heater system as shown in Fig
16-1 and 16-2. Use exible piping and insulate all pipes. Plumbing
must be in compliance with state or local codes (Code CMR248 in Massachusetts). The units for hydronic heat have different top and heater box congurations. This conguration is not suitable for elec­tric heat. DO NOT try to install hydronic heater in a unit not equipped for it. Verify connections: hot water to “in” and cold water to “out”. 7/8” ODstubs are provided for plumbing connections (Fig 16-3 and
16-4. Bleed the air ow system through the bleeder port (Fig 16-5)
or optional valve.
ter lines MUST be purged of air prior to starting the pump. Failure to do so could
Hot water owing to the coil should be in
the range of 120º - 180º F. Water at these
temperatures can cause rst-degree
Installer MUST open water lines and run system to a.) ensure pump is primed and
waterow is constant and b.) ensure there
Table 15B-1.
14B . Expansion Valve Coils
Add refrigerant until the subcooling measured at the outdoor unit liquid line matches the subcooling recommendation of the outdoor manufacturer. If chart is unavailable charge the unit to a subcooling value of 8ºF +/- 1ºF.
15. Adjustment Of Heat Anticipator
After all connections are made, start-up and checkout must be per­formed before proper evaluation of the entire system can be made. Make sure that heat anticipator is properly set as noted on thermo-
stat instructions. Load requirements can vary in each residence and
it may be necessary for the installer or homeowner to make slight ad­justments to the heat anticipator setting for longer or shorter cycles. It is recommended to change the setting no more than plus or minus
0.05 amps at a time. Greater changes can cause the unit to rapid cycle or remain on excessively. Measure anticipator circuit current with electric heaters energized and set anticipator to proper level.
Fig 16-1.
Fig 16-2.
11
OUTPUT BTUH
TEMP RISE
()
..
Fig 16-3. Water In
Fig 16-4. - Water Out
formed before proper evaluation of the entire system can be made. Make sure that heat anticipator is properly set as noted on thermo­stat instructions.
Load requirements can vary in each residence and it may be neces­sary for the installer or homeowner to make slight adjustments to the heat anticipator setting for longer or shorter cycles. It is recommend­ed to change the setting no more than plus or minus 0.05 amps at a time. Greater changes can cause the unit to rapid cycle or remain on excessively. To properly check the unit’s operation, the installer should have an electrical current measuring device (0-10 amp Am­probe, Fluke), air pressure measuring device (0-1.0 in slope gauge), and a temperature-measuring device (0-200ºF thermometer).
Install the Amprobe to measure blower current, the slope gauge to measure static air pressure at the units and the temperature device to measure unit supply and return air temperature. Before taking measurements, be sure that all registers, grilles and dampers are
open or are set to their proper positions. Be sure that clean lters are
in place. Temperature measuring device must be installed to obtain average temperature at both inlet and outlet. For outlet, measure temperature of each main trunk at a location far enough away to avoid heater radiation and read the average temperatures. Table 16-1 below shows the CFM that should be achieved at various exter­nal static pressures.
Fig 16-5.
Purging The System
1. Open air vent and allow water heater to ll with water. Close air
vent when water heater is full and all air has been purged.
2. Ignite water heater. Set thermostat on water heater to 140 de­grees.
3. Close the valve on the hot water supply from the water heater (“A”) and open the valve on the cold water return to the water heater (“B”). Then open the air vent in the fan coil. Use bucket or hose to discard water during purging process at air bleed valve. Purge air completely from line.
4. Once air is purged, close return valve (“B”) and open supply valve (“A”). Purge the coil and lines of air completely.
5. After air is purged from the system and lled with water, open the
return valve (“B”). Then close the air vent in the fan coil.
6. Apply power to the fan coil and set the room thermostat on heat. Raise the temperature setting to activate the circulating pump
7. Check the pump to ensure proper operation. The water inlet of the unit should be hot if the water temperature in the water heater has reached the set point. If water is not being circulated through the coil but the pump is running, then open the air bleed valve in the unit and purge any air left in the system.
Table 16-1. - CFM Delivered at Various External Statics
17. Electric Heat Controls
Turn on power supply. Set thermostat fan switch to on. Set the cool­ing indicator to maximum, heating to minimum. System switch may be on heat or cool. Check slope gauge measurement against appro-
priate air ow chart. Make damper, register and motor speed adjust­ments to obtain required airow.
Set thermostat fan switch to auto, system to heat and thermostat heating indicator to maximum heat. Blower should start and all heat be energized.
Check air ow using temperature rise method.
CFM
=
108
Note: BTUH output should be computed by 500 x Gallons Per Min­utes x System Temperature Change = BTUH OUTPUT.
8. Adjust the water heater thermostat so that the water temperature entering the hot water coils is 120 – 180ºF depending on the amount of heat required by the structure. This is done with the unit energized and operating long enough for all temperatures to stabilize.
After all connections are made, start-up and check-up must be per-
12
Loading...