Aspen Manufacturing AEW Installation Manual

INSTALLATION GUIDE
AEW & AAW Series - Vertical Wall Mount Air Handler (Electric Heat)
1. Safety Instruction
Potential safety hazards are alerted using the following symbols. The symbol is used in conjunction with terms that indicate the intensity of the hazard.
`
!
This symbol indicates a potentially hazardous situation, which if not avoided, could result in serious injury, property damage, product damage or death.
CAUTION
!
Certied technicians or those individuals
!
and product damage or personal injury hazard may occur without such background.
!
!
installer’s responsibility to ensure that product is installed in strict compliance with national and local codes. Manufac­turer takes no responsibility for damage (personal, product or property) caused due to installations violating regula­tions. In absence of local/state codes, refer to National Elec­tric Code: NFPA 90A & 90B Uniform Mechanical Code.
!
(i.e. automobile, space heater, water heater etc.) ensure that the enclosed area is properly ventilated.
CAUTION
!
these instructions. Some localities may require a licensed installer/service personnel.
!
!
damages caused due to modication of the unit to operate
with alternative power sources.
# 123106
meeting the requirements specied by
NATE may use this information. Property
All power sources should be disconnect­ed prior to servicing. Failure to do so may cause personal injury or property dam-
age.
Product designed and manufactured to permit installation in accordance with lo­cal and national building codes. It is the
When this unit is installed in an enclosed area, such as a garage or utility room with any Carbon Monoxide producing devices
Only factory authorized kits and acces­sories should be used when installing or modifying this unit unless it is so noted in
Unit is not approved for outdoor installa­tions.
The unit is designed for operation with 208/240 V, single phase, 60 Hz power supply. Aspen will not be responsible for
This symbol indicates a potentially hazardous situation, which if not avoided, may result in moderate injury or property damage.
2. Introduction
The AEW/AAW Series air handlers are versatile upow only models that can be recess mounted or ush mounted onto walls. These air
handlers have the following standard features:
I. Application Versatility
Front or bottom return air position. Offset hanging brackets attach to unit and wall to allow hanging inside closet.
Can be ARI matched with most brands of air conditioners or heat pumps for use with either R22 or R410a when proper metering de­vice is used.
II. Motor
AEW models: Constant torque ECM speeds and torques are con­trolled by software embedded in the motor to maintain constant torque. Motors are pre-programmed at the factory. AAW models: Dual speed PSC motor.
III. Cabinet
Sturdy, short galvanized steel cabinet with painted front panels. Cab­inet fully insulated with 1/2” faced insulation to prevent sweating and
mold growth, to encapsulate glass bers, and to provide excellent
R-value. Stick pins ensure insulation remains in place.
Units ship with disposable lter in lter rack.
IV. Modular Electric Heat Kits
Heat kits available with either circuit breakers or terminal blocks. Available in 3, 5, 8, & 10 KW. Models with electric heat include se-
quencers and temperature limit switches for safe, efcient operation. Modules are easily installed in the eld using molex plugs or can be
ordered factory-installed. Controls are accessible from the front for easy service.
Electrical connections can be made from the top or left. Disconnect does not protrude through the wall panel.
Fan time delay relay standard for increased efciency.
V. Blower
Direct drive multi-speed blowers circulate air quietly and efciently.
Motor speeds can be easily selected via motor terminals. Swing mounted blowers can be easily removed for service.
VI. Electronic Circuit Board
Electronic circuit board provides 30 sec. ON/OFF blower time delay
extracting more heat/cool from the coil
1
VII. DX Coil
High efciency ried copper tubes/enhanced aluminum ns provide maximum heat transfer. All coils immersion tested at 500 psi then nitrogen pressurized and factory sealed for maximum reliability. Coil
mounted Schrader allows pre-installation pressure testing.
Available with either check style owrater or TXV metering device. Field-installable TXVs are also available.
Galvanized metal drain pan with bottom primary and secondary drain connections or alternate right side primary. All connections 3/4” FPT. Access door allows for coil cleaning.
VIII. Warranty
Five year limited parts warranty.
3. Inspection
ü On receiving the product, visually inspect it for any major shipping related damages. Shipping damages are the carrier’s responsibility. Inspect the product labels to verify the model number and options are in accordance with your order. Manufacturer will not accept dam­age claims for incorrectly shipped product.
4. Installation Preparation
Read all the instructions in this guideline carefully while paying spe­cial attention to the WARNING and CAUTION alerts. If any of the
instructions are unclear; clarify with certied technicians. Gather all
the tools needed for successful installation of the unit prior to begin­ning the installation.
4A. Clearances
This unit is designed for zero clearance installation on three sides and adequate clearance to provide access for service in the front. A minimum of 2.5 – 3.5 feet clearance is recommended on the front end (Fig 4A-1).
4C. Condensate Drain Preparation
ü An auxiliary drain pan must be provided by the installer and placed
under the entire unit with a separate drain line that is properly sloped
and terminated in an area visible to the home owner. The auxiliary pans provide extra protection to the area under the unit should the primary and secondary drain plug up and overow. As expressed
in our product warranty; ASPEN WILL NOT BE BILLED FOR ANY STRUCTURAL DAMAGES CAUSE BY FAILURE TO FOLLOW THIS INSTALLATION REQUIREMENT. The drains from the auxil-
iary drain pan must be installed according to the local building codes.
4D. Condensate Drain
Drain lines from the auxiliary drain pan
CAUTION
!
The drain lines must be installed with ¼” per foot pitch to provide free drainage. A condensate trap MUST be installed on the primary drain line to ensure proper drainage of the condensate. The trap must be installed in the drain line below the bottom of the drain pan (Fig. 4C-1)
should NOT be connected to the primary drain line of the coil.
Fig 4A-1. Minimum Clearance for Air Handler
4B. Recess Mounting or Wall Mounting Option
These units are designed to be installed in a small room where they can be mounted above a water heater or recessed into a wall. The
unit should be installed in Vertical Upow position ONLY.
If installing the air handler into a recessed wall, the unit must leave clearance to allow the removal of the front panels. The bottom of the
unit should also rest on a sturdy platform or oor. The unit must be
level to allow condensate drainage.
These air handlers come with an offset mounting bracket that at-
taches the air handler to the wall when the unit is ush mounted to
the wall.
Fig 4C-1. Condensate Drain Trap
Since coil is upstream of the blower, all
CAUTION
!
from the drain pan. Aspen will NOT be responsible for any damages resulting from failure to follow these instructions.
CAUTION
!
DO NOT USE SOLVENT BASED PIPE DOPE. THIS WILL RE­DUCE THE LIFE OF THE PAN.
The drain pan has primary (white) and secondary (red) drain connec­tions. If a secondary drain line is required, it should be run separately from the primary and should terminate in a highly visible location. Condensate disposal through the secondary drain line indicates that
2
drains MUST be trapped or sealed. Failure
to do so will result in condensate overow
If the drain pan is constructed of nylon
or plastic; use Teon tape to connect the
drain lines to the threads in the drain pan.
# 123106
the primary drain line is plugged and needs cleaning. If a second­ary drain line will not be provided, plug the secondary drain. Drain plugs are NOT to be reused without plumbers tape or putty. Drain
line connection should be nger tightened, then turned no more than one complete turn as needed to ensure a rm connection. DO NOT
overtighten connection or damage may occur.
4E. Ductwork
Duct systems should be installed in accordance with standards for air-conditioning systems, National Fire Protection Association Pam­phlet No. 90A or 90B. They should be sized in accordance with Na­tional Environmental Sys­tem Contractors Association Manual K, or whichever is applicable.
On any job, non-ammable exible collars should be
used for the return air and discharge connections to prevent transmission of vi­bration (Fig 4E-1). Although these units have been spe­cially designed for quiet vibration-free operation, air ducts can act as sound­boards, can, if poorly in­stalled, amplify the slightest vibration to the annoyance level.
All main supply and return air drops should be properly sized as determined by the designer of the duct system and should not nec-
essarily be the size of the duct ange openings of the unit. (The duct size should never be smaller than the ange openings of the air
handler supply and return air openings.) These models have a bottom or front return. Discard the drain ac-
cess panel in the bottom of the unit if this is a bottom return applica­tion (Fig 4E-2). In case of a front return application, the front access panel should be removed and discarded.
Fig 4E-2.
If an accessory grill is being used, the front access panel should be removed and discarded (Fig 4E-3).
Fig 4E-1.
A lter rack is provided for a 1”X20”X20” (AAW/AEW18/24/30/36/31/37) or 1”X14”X18” (AAW/AEW19/20/25/26) nominal size lter (Fig 4E-4). Inspect and clean or replace iter every month. A blocked lter can reduce air ow to the coil and hinder the performance of the system.
Fig 4E-4.
It is recommended that wherever supply and return air sheet metal ducts pass through unconditioned areas, they be insulated to pre-
vent excessive heat loss during heating operation. When applied in
conjunction with summer air conditioning, sheet metal duct routed through unconditioned areas should be insulated and have an out­side vapor barrier to prevent formation of condensation.
5. Installation
Ensure that the unit is adequately sized.
CAUTION
!
!
to installation. If holding pressure is not present, return coil to distributor for exchange.
CAUTION
!
present) are protected from heat during brazing and instal­lation to prevent leakage. Use a core removal tool to tempo­rarily remove the core when brazing. Replace the core once brazing is completed.
CAUTION
!
ü Clean coil ns with degreasing agent or mild detergent and rinse ns clean prior to installation.
The tonnage of the outdoor unit should never exceed the tonnage of this unit.
The coil was manufactured with a dry ni­trogen pre-charge. Release the pressure through the Schrader valve test port prior
Some Aspen coils may include a Schrader valve on the suction manifold. Ensure that the Schrader valve and valve core (where
Insulation on the suction line MUST extend into the cabinet and continue as far as possible to eliminate condensate dripping onto the access door.
# 123106
Fig 4E-3.
ü The refrigerant line sizes should be selected according to the rec­ommendations of the outdoor unit manufacturer.
ü Care must be taken to ensure all connection joints are burr-free and clean. Failure to do so may increase chances of a leak. It is recommended to use a pipe cutter to remove the spun closed end of the suction line.
ü To reduce air leakage, rubber gommets may be present where the lines pass through the coil case. To avoid damage, remove grom­mets prior to brazing by sliding over the lines. Use a quenching cloth or allow the lines to cool before reinstalling the grommets.
ü Use of wet rags/quenching cloth is highly recommended to prevent weld-related damages to the casing and Schrader valve (if present).
3
6. Mounting Air Handler To Wall
1. Install the air handler in a level position side to side and front to back. If this step is not followed, condensate water damage may oc-
cur. (Both ush mount and recess mount congurations.)
2. Determine where the air han­dler is to be placed on the wall. Place the hanging bracket on the wall and align the holes of the
bracket with the wall studs. Level
the hanging bracket and mark the holes to drill pilot holes for the screws.
3. Drill the pilot holes.
4. Secure the bracket with
screws sufcient to hold 4X the
weight of the air handler.
5. Position the air handler on the wall with the bracket on the air handler slightly higher than the bracket secured on the wall.
Lower the air handler so that the
brackets engage. Check the unit for level, both side to side and front to back.
CAUTION
!
ing to the capacity of the outdoor unit.
!
Use Piston sizes recommended by the outdoor unit manufacturer whenever pos­sible. The piston should be sized accord-
Failure to install the proper piston can lead to poor system performance and possible compressor damage.
I. Installation
Note: Photos are for basic illustration purposes only. Actual equip-
ment conguration may differ from that shown.
I-1. Disassemble owrator body
using two wrenches and un­screwing with a counterclockwise motion.
O-ring
I-2. Replace the Teon O-ring
(located between the halves). Discard Schrader if present.
7. Connecting Ducting
1. Secure supply air ducting to the top of the air handler. Canvas con­nectors are recommended for reducing potential noise transmission.
2. If the bottom return air opening is being used, remove the bottom pan­el. If a front return is being used, this panel will remain in place.
3. Secure the return air ducting to the air handler cabinet.
8. Metering Devices/Liquid Line Connection
Aspen coils are available with two kinds of metering devices a) ow­rator or b) TXV. The following instructions are separated into sec-
tions by metering device.
8A. Flowrator Coils
CAUTION
!
I-4. Braze the stub-out portion to the liquid line and let cool.
Be aware of the Teon O-ring. Be sure to
replace the O-ring to attain a proper
seal. (The Teon O-ring is located between the two halves of the owrator)
I-3. Slide the attachment nut onto the liquid line stub out.
O-ring
I-5. Taking care that the white
Teon seal is still in place inside the owrater body, rmly seat the
stub and screw the attachment
nut to owrater body.
Fig 7A-1. Flowrator assembly components
4
# 123106
I-6. Tighten the nut to a torque of approximately 10-30 ft-lbs. Do NOT overtighten the nut. Overtightening will impede the piston movement during operation.
II. Piston Replacement
Note: Photos are for basic illustration purposes only. Actual equip-
ment conguration may differ from that shown.
During some installations, a piston change may be required. If so, the installer MUST change the piston. Use piston sizes recommended by the outdoor unit manufacturer. If a sizing chart is not available, use the piston size chart provided be­low to size the required piston. The size of the
Fig 8A-2
Use the chart below when matching coil with an outdoor unit with a different nominal capacity than the coil.
piston is stamped on the piston body (Fig 8A-2).
II-6. Replace the piston with one of the correct size. Do not force the new piston into the body. Make sure the piston moves freely in body.
CAUTION
!
coil. Failure to ensure this orientation will cause the piston to be bypassed during operation which might damage the outdoor unit.
II-7. Assemble the two halves correctly and ensure that the white
Teon O-ring is present between the two halves (See I-5). Slide the 13/16” nut onto the distributor body.
Pay close attention to the piston orienta­tion. The pointed end of the piston MUST go into the distributor body, towards the
II-1. Evacuate the system as per manufacturer guidelines and rec-
ommendations
II-2. Turn the 13/16” nut once to release any residual pressure in the
coil.
II-3. After ensuring that the coil is free of any residual pressure,
disassemble the owrator body
completely using two wrenches. Take great care not to distort the feeder tubes. The wrench used to clasp the nut should be turned in counter-clockwise direction to unscrew the nut.
II-4. Slide the 13/16” nut over
the lineset and separate the two
halves of the owrator.
CAUTION
!
II-8. Tighten the nut to a torque of approximately 10-30 ft-lbs. Do NOT overtighten the nut. Overtightening will impede the piston movement during operation.
II-9. If present, slide the rubber grommet back to position to prevent air leakage.
Be aware of the Teon O-ring. Be sure to
replace the O-ring to attain a proper
seal. (The Teon O-ring is located between the two halves of the owrator)
7B. TXV Coils
# 123106
II-5. Pull the piston out using a
small wire or pick. Verify the pis­ton size (size is typically stamped on the body of the piston - Fig 8A-2). If a different piston size is required by the outdoor unit manufacturer, replace the piston using the small wire provided with the piston kit.
Fig 8B-1. Components of a typical TXV assembly
The sensing bulb and TXV body MUST be
!
be covered using a quench cloth or wet cloth when brazing.
Pointing the brazing ame away from the valve and sensing
bulb provide partial protection only.
CAUTION
!
painted green for R22 or pink for R410A. In absence of col­or, the caps will be marked with the compatible refrigerant.
protected from overheating during braz­ing. The sensing bulb and TXV body must
Ensure that the TXV selected is compat­ible with the refrigerant used in the out­door system (R22 or R410A). TXV caps are
5
Loading...
+ 9 hidden pages